Encelium Phase Cut Dimming Module Installation Guide
- September 4, 2024
- ENCELIUM
Table of Contents
Phase Cut Dimming Module
“`html
Specifications
-
Product Name: Phase-Cut Dimming Module (PCDM)
-
Compatibility: Incandescent/Halogen lamps, ELV LED lamps or LED
drivers -
Incompatible Load Types: ELV/MLV transformers, MLV LED
drivers -
Maximum Dimmed Line Length: 15.2 m (50 ft)
-
Absolute Maximum Load Ratings:
- 120 VAC: 450 W, 3.8A maximum
- 277 VAC: 900 W, 3.3A maximum
Product Usage Instructions
Installation
The Phase-Cut Dimming Module (PCDM) should be installed
following these steps:
-
Mount the PCDM on top of a standard square 119.1 mm (4.6875
inches) junction box. -
Ensure proper wiring connections as per the provided
diagram. -
Connect the PCDM to the GreenBus network for automatic
addressing. -
Ensure installation is in dry, indoor locations only.
Load Compatibility
The PCDM is compatible with incandescent/Halogen lamps and ELV
LED lamps or LED drivers. It is not compatible with ELV/MLV
transformers or MLV LED drivers.
Wire Length Consideration
Ensure that the combined length of the dimmed line (Red) from
the PCDM to the load does not exceed 15.2 m (50 ft). For specialty
applications like chandeliers, consider wiring within the luminaire
within the same limit to prevent stress on PCDM components.
Electrical Connections
Follow these wiring connections for the PCDM:
- WHITE–Neutral
- RED–Relay Output & DIM Control
- BLACK–Line In
- GREEN–Ground
Frequently Asked Questions (FAQ)
Q: What are the compatible load types for the PCDM?
A: The PCDM is compatible with incandescent/Halogen lamps and
ELV LED lamps or LED drivers.
Q: What is the maximum dimmed line length supported by the
PCDM?
A: The maximum dimmed line length from the PCDM to the load
should not exceed 15.2 m (50 ft).
Q: How should I handle electrical connections for the
PCDM?
A: Follow the wiring instructions provided, ensuring proper
connections for control and power wires.
“`
PCDM
INSTALLATION INSTRUCTIONS
PRODUCT SAFETY
When using electrical equipment, basic safety precautions should always be
followed, including the following:
READ THESE INSTRUCTIONS BEFORE USING THIS PRODUCT.
Do not let power supply cords touch hot surfaces.
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not
readily be subjected to tampering by unauthorized personnel.
The use of accessory equipment is not recommended by Encelium as it may cause
an unsafe condition.
Do not use this equipment for other than the intended use.
SAVE THESE INSTRUCTIONS.
GETTING STARTED
Overview
The Phase-Cut Dimming Module (PCDM) provides an interface between the phase-
cut dimmable (forward- and reverse-phase) luminaires and the Encelium X
Lighting Control System. The PCDM is automatically addressed as soon as it is
connected to the GreenBus network. Individually addressable, the PCDM enables
each group or zone of fixtures to be independently controlled and configured
to best meet the needs of the facility.
PCDM
INSTALLATION INSTRUCTIONS
WIRED SYSTEM OVERVIEW
GreenBus technology makes wiring fast and error-free, since it’s intuitive to
install. With Encelium X, you can control DALI devices exclusively or a
mixture of GreenBus and DALI.
Sensor
PCDM
Sensor
PCDM
Wired Manager — GreenBus
SSU
Luminaire
User Interface
User Interface
Wire Key
Ethernet GreenBus Dimming
INSTALLATION
The mechanical construction allows for simple installation of the PCDM on top
of a standard square 119.1 mm (4.6875 inches) junction box.
AC Line
Input to PDCM
Line Neutral Ground
BLACK WHITE GREEN
GreenBus Ports
In/Out
Dimmed AC Line
Output to Load Luminaire
RED WHITE GREEN
Dimmed Line Neutral Ground
Juncon Box
Notes: The PCDM is to be installed in dry, indoor locations ONLY.
Compatible Load Types The PCDM is compatible with incandescent/Halogen lamps
and ELV LED lamps or LED drivers. It is not compatible with ELV/MLV
transformers or MLV LED drivers. The below parts are identified as
incompatible loads.
Manufacturer Luminii Luminance
Item Number PSD Series L7510-1 A19
Part Number/Description Class 2 Dimmable LED Light Bulb
2
PCDM Installation Instructions | Installationsanleitung | Instructions d’installation | Instrucciones de Instalación
PCDM
INSTALLATION INSTRUCTIONS
Wire Length Consideration
The maximum combined length of the dimmed line (Red) from the PCDM to the load
must be less than 15.2 m (50 ft).
For specialty applications such as chandelier, the wiring within the luminaire
to the load must be accounted within the 15.2 m (50 ft) limit. Exceeding this
limit can cause stress to the PCDM components and lead to failure.
15.2 m (50 ft )
AC Line Dimmer Luminaires
GreenBus Ports In/Out
Notes: 15.2 m (50 ft) maximum distance from PCDM to the last luminaire
Absolute maximum load ratings: 120 VAC: 450 W, 3.8A maximum | 277 VAC: 900 W,
3.3A maximum
Due to the internal relay, power feed to module may be live even if lights are
off. Turn off power at circuit breaker or fuse before installing or servicing
module. Observe lockout procedures.
ELECTRICAL CONNECTIONS PCDM Wiring
Control & Power Wires
WHITE–Neutral RED–Relay Output & DIM Control BLACK–Line In
GREEN–Ground
GreenBus Ports In/Out
PCDM Installation Instructions | Installationsanleitung | Instructions d’installation | Instrucciones de Instalación
3
PCDM
INSTALLATION INSTRUCTIONS
GreenBus
GreenBus is a low-cost, high reliability communication means to report
information back to the Encelium X and Encelium Edge Lighting Control Systems.
The GreenBus wiring can originate at the Wired Manager and propagates in a
daisy-chain from module to module (or other compatible equipment). When
tethering the GreenBus wiring can also originate from a GB port on a Wireless
Area Lighting Control Module (WALC) or a Wireless Control Module (WCM).
The GreenBus wires must be used with proprietary connectors supplied. Insert
the connectors to the PCDM GB ports.
GreenBus must be laid out as per supplied system layout drawing. If changes
are required, determine an optimum wiring path utilizing the supplied cables,
based on the position of the devices
7 mm (0.27 inch)
Insert Connectors
Insert Wires
To remove the wires, use a flat head screwdriver to release the wires from the
terminal blocks.
Insert flat head screwdriver into release tab
Notes: Relay Contact; recommended relay switching capacity 120 VAC, 450 W or
277 VAC, 900 W maximum.
If the devices are connected with a method other than daisy-chain, this must
be indicated to an Encelium Representative for approval before wiring.
GreenBus uses proprietary connectors and jacks for ease of installation only.
GreenBus is a proprietary standard. Connect to Encelium Lighting Control
System only. Do not connect to other circuits.
© Copyright 2024 Legrand All Rights Reserved. © Copyright 2024 Legrand Alle
Rechte vorbehalten © Copyright 2024 Tous droits réservés Legrand. © Copyright
2024 Legrand Todos los derechos reservados..
080466r1 02/24