BLAUBERG EKH 100 Duct Electrical Heater User Manual
- September 3, 2024
- BLAUBERG
Table of Contents
DUCT ELECTRICAL HEATER
EKH 100 EKH 250 EKH 400×200 EKH 700×400
EKH 125 EKH 315 EKH 500×250 EKH 800×500
EKH 150 EKH 500×300 EKH 900×500
EKH 160 EKH 600×300 EKH 1000×500
EKH 200 EKH 600×350
USER’S MANUAL
www.blaubergventilatoren.de EKH
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the EKH unit and all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
SAFETY REQUIREMENTS
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the fan from power supply prior to any connection, servicing and
repair operations.
Only qualified electricians with a work permit for electrical units up to
1000 V are allowed for installation and The present user’s manual should be
carefully read before beginning works.
Check the unit for any visible damages of the casing before starting
installation. The casing internals must be free of any foreign objects.
While mounting the unit, avoid compression of the casing!
Misuse of the unit and any unauthorized modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it.
The information in this user’s manual was correct at the time of the
document’s preparation. The Company reserves the right to modify the technical
characteristics, design, or configuration of its products at any time in order
to incorporate the latest technological developments.
Do not touch the unit with wet or damp hands.
Do not touch the unit when barefoot.
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Cleaning and user maintenance shall not be done by children without
supervision.
Children shall not play with the appliance.
CAUTION: In order to avoid a safety hazard due to inadvertent resetting of the thermal cutout, this unit must not be supplied through an external switching device, such as a timer, or connected to a circuit that is regularly switched on and off by the utility.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
Duct heaters are designed for heating of intake fresh air transported through
the ventilating system.
The unit is a component part and is not designed for independent operation.
The heater is designed for extended periods of continuous operation without
disconnection from the power mains.
Transported air must not contain any flammable or explosive mixtures,
evaporation of chemicals, sticky substances, fibrous materials, coarse dust,
soot and oil particles or environments favourable for the formation of
hazardous substances (toxic substances, dust, pathogenic germs).
DELIVERY SET
Name
|
Number
---|---
Heater|
1
User’s manual|
1
DESIGNATION KEY
-
Heater power [kW]
-
Nominal duct dimensions
Connected air duct diameter – for round ducts [mm] Flange size (WxH) – for rectangular ducts [cm] -
Heater name
EKH – Duct electrical heater
Designation example:
EKH 315-9.0-3 – three-phase heater with branch pipe diameter 315 mm, power 9
kW.
EKH 40×20-4.5 heater for a rectangular duct 400×200 mm, power 4,5 kW.
The basic heater overall dimensions must correspond to the ones provided in
the tables «Overall and connecting dimensions».
The basic heater parameters and thermal dynamic characteristics are shown in
the tables «Main technical parameters».
TECHNICAL DATA
The unit is designed for indoor application at ambient temperature from -30 °C
up to +50 °C and relative humidity up to 80 %.
The heater is rated as a class I electric appliance.
Ingress protection rating against access to hazardous parts and water ingress
is IP40.
The heater design is constantly improved, so some models may slightly differ
from the ones depicted herein.
OVERALL AND CONNECTING DIMENSIONS OF HEATERS FOR ROUND DUCTS
Heater model
| Dimensions [mm]
---|---
D| L| B| F| C|
A
EKH 100-0.6
| 99| 306| 226| 207| 40| 94
EKH 100-0.8| 99| 306| 226| 207| 40|
94
EKH 100-1.2
| 99| 306| 226| 207| 40| 94
EKH 100-1.6| 99| 306| 226| 207| 40|
94
EKH 100-1.8-1
| 99| 376| 296| 207| 40| 94
EKH 125-0.6| 124| 306| 226| 230| 40|
103
EKH 125-0.8-1
| 124| 306| 226| 230| 40| 103
EKH 125-1.2| 124| 306| 226| 230| 40|
103
EKH 125-1.6
| 124| 306| 226| 230| 40| 103
EKH 125-2.4| 124| 376| 296| 230| 40|
103
EKH 150-1.2
| 149| 306| 226| 255| 40| 120
EKH 150-1.7| 149| 306| 226| 255| 40|
120
EKH 150-2.0
| 149| 306| 226| 255| 40| 120
EKH 150-2.4| 149| 306| 226| 255| 40|
120
EKH 150-3.4
| 149| 306| 226| 255| 40| 120
EKH 150-3.6| 149| 376| 296| 255| 40|
120
EKH 150-5.1
| 149| 376| 296| 255| 40| 120
EKH 150-6.0| 149| 376| 296| 255| 40|
120
EKH 160-1.2
| 159| 306| 226| 267| 40| 120
EKH 160-1.7| 159| 306| 226| 267| 40|
120
EKH 160-2.0
| 159| 306| 226| 267| 40| 120
EKH 160-2.4| 159| 306| 226| 267| 40|
120
EKH 160-3.4
| 159| 306| 226| 267| 40| 120
EKH 160-3.6| 159| 376| 296| 267| 40|
120
EKH 160-5.1
| 159| 376| 296| 267| 40| 120
EKH 160-6.0| 159| 376| 296| 267| 40|
120
EKH 200-1.2
| 199| 294| 214| 302| 40| 150
EKH 200-1.7| 199| 294| 214| 302| 40|
150
EKH 200-2.0
| 199| 294| 214| 302| 40| 150
EKH 200-2.4| 199| 294| 214| 302| 40|
150
EKH 200-3.4
| 199| 294| 214| 302| 40| 150
EKH 200-3.6| 199| 376| 296| 302| 40|
150
EKH 200-5.1
| 199| 376| 296| 302| 40| 150
EKH 200-6.0| 199| 376| 296| 302| 40|
150
EKH 250-1.2
| 249| 306| 226| 356| 40| 150
EKH 250-2.0| 249| 306| 226| 356| 40|
150
EKH 250-2.4
| 249| 306| 226| 356| 40| 150
EKH 250-3.0| 249| 306| 226| 356| 40|
150
EKH 250-3.6
| 249| 376| 296| 356| 40| 150
EKH 250-6.0| 249| 376| 296| 356| 40|
150
EKH 250-9.0
| 249| 376| 296| 356| 40| 150
EKH 315-1.2| 313| 294| 214| 425| 40|
150
EKH 315-2.0
| 313| 294| 214| 425| 40| 150
EKH 315-2.4| 313| 294| 214| 425| 40|
150
EKH 315-3.6
| 313| 376| 296| 425| 40| 150
EKH 315-6.0| 313| 376| 296| 425| 40|
150
EKH 315-9.0
| 313| 376| 296| 425| 40|
150
MAIN TECHNICAL PARAMETERS OF HEATERS FOR ROUND DUCTS
Heater model
| Power [kW]| Number of phases| Voltage [V]| Number of
electric heating elements x power [kW]| Current [A]| Minimum air
flow [m³/h]| Weight [kg]
---|---|---|---|---|---|---|---
EKH 100-0.6| 0.6| 1| 230| 1×0.6| 2.6| 60|
1.3
EKH 100-0.8
| 0.8| 1| 230| 1×0.8| 3.5| 80| 1.3
EKH 100-1.2| 1.2| 1| 230| 2×0.6| 5.2| 90|
1.5
EKH 100-1.6
| 1.6| 1| 230| 2×0.8| 7.0| 120| 1.5
EKH 100-1.8| 1.8| 1| 230| 3×0.6| 7.8| 130|
1.7
EKH 125-0.6
| 0.6| 1| 230| 1×0.6| 2.6| 60| 1.4
EKH 125-0.8| 0.8| 1| 230| 1×0.8| 3.5| 80|
1.4
EKH 125-1.2
| 1.2| 1| 230| 2×0.6| 5.2| 90| 1.7
EKH 125-1.6| 1.6| 1| 230| 2×0.8| 7.0| 120|
1.7
EKH 125-2.4
| 2.4| 1| 230| 3×0.8| 7.8| 150| 1.9
EKH 150-1.2| 1.2| 1| 230| 1×1.2| 5.2| 120|
2.0
EKH 150-1.7
| 1.7| 1| 230| 1×1.7| 7.4| 130| 2.0
EKH 150-2.0| 2.0| 1| 230| 1×2.0| 8.7| 140|
2.0
EKH 150-2.4
| 2.4| 1| 230| 2×1.2| 10.4| 150| 2.4
EKH 150-3.4| 3.4| 1| 230| 2×1.7| 14.7| 220|
2.4
EKH 150-3.6
| 3.6| 3| 400| 3×1.2| 5.2| 265| 2.8
EKH 150-5.1| 5.1| 3| 400| 3×1.7| 7.4| 320|
2.8
EKH 150-6.0
| 6.0| 3| 400| 3×2.0| 8.7| 360| 2.8
EKH 160-1.2| 1.2| 1| 230| 1×1.2 | 5.2 | 150|
2.1
EKH 160-1.7
| 1.7| 1| 230| 1×1.7| 7.4| 160| 2.1
EKH 160-2.0| 2.0| 1| 230| 1×2.0| 8.7| 170|
2.1
EKH 160-2.4
| 2.4| 1| 230| 2×1.2| 10.4| 180| 2.5
EKH 160-3.4| 3.4| 1| 230| 2×1.7| 14.8| 250|
2.5
EKH 160-3.6
| 3.6| 3| 400| 3×1.2| 5.2| 265| 3.0
EKH 160-5.1| 5.1| 3| 400| 3×1.7| 7.4| 375|
3.0
EKH 160-6.0
| 6.0| 3| 400| 3×2.0| 8.7| 440| 3.0
EKH 200-1.2| 1.2| 1| 230| 1×1.2| 5.2| 150|
2.5
EKH 200-1.7
| 1.7| 1| 230| 1×1.7| 7.4| 160| 2.5
EKH 200-2.0| 2.0| 1| 230| 1×2.0| 8.7| 170|
2.5
EKH 200-2.4
| 2.4| 1| 230| 2×1.2| 10.4| 180| 3.0
EKH 200-3.4| 3.4| 1| 230| 2×1.7| 14.8| 250|
3.0
EKH 200-3.6
| 3.6| 3| 400| 3×1.2| 5.2| 265| 3.5
EKH 200-5.1| 5.1| 3| 400| 3×1.7| 7.4| 375|
3.5
EKH 200-6.0
| 6.0| 3| 400| 3×2.0| 8.7| 440| 3.5
EKH 250-1.2| 1.2| 1| 230| 1×1.2| 5.2| 180|
3.2
EKH 250-2.0
| 2.0| 1| 230| 1×2.0| 8.7| 200| 3.2
EKH 250-2.4| 2.4| 1| 230| 2×1.2| 10.4| 265|
3.7
EKH 250-3.0
| 3.0| 1| 230| 1×3.0| 13.0| 375| 3.2
EKH 250-3.6| 3.6| 3| 400| 3×1.2| 5.2| 375|
4.6
EKH 250-6.0
| 6.0| 3| 400| 3×2.0| 8.7| 440| 4.6
EKH 250-9.0| 9.0| 3| 400| 3×3.0| 13.0| 660|
4.6
EKH 315-1.2
| 1.2| 1| 230| 1×1.2| 5.2| 180| 4.0
EKH 315-2.0| 2.0| 1| 230| 1×2.0| 8.7| 200|
4.0
EKH 315-2.4
| 2.4| 1| 230| 2×1.2| 10.4| 265| 4.8
EKH 315-3.6| 3.6| 3| 400| 3×1.2| 5.2| 375|
5.6
EKH 315-6.0
| 6.0| 3| 400| 3×2.0| 8.7| 440| 5.6
EKH 315-9.0| 9.0| 3| 400| 3×3.0| 13.0| 660|
5.6
OVERALL AND CONNECTING DIMENSIONS OF HEATERS FOR RECTANGULAR DUCTS
Heater model
| Dimensions [mm]
---|---
A| B| C| D| E| F|
H
EKH 40×20-4.5
| 540| 240| 420| 220| 400| 200| 200
EKH 40х20-6| 540| 240| 420| 220| 400| 200|
200
EKH 40х20-7.5
| 540| 240| 420| 220| 400| 200| 200
EKH 40х20-9| 540| 240| 420| 220| 400| 200|
200
EKH 40х20-10.5
| 540| 240| 420| 220| 400| 200| 200
EKH 40х20-12| 540| 240| 420| 220| 400| 200|
200
EKH 40х20-15
| 540| 240| 420| 220| 400| 200| 200
EKH 50х25-6| 640| 290| 520| 270| 500| 250|
200
EKH 50х25-7.5
| 640| 290| 520| 270| 500| 250| 200
EKH 50х25-9| 640| 290| 520| 270| 500| 250|
200
EKH 50х25-10.5
| 640| 290| 520| 270| 500| 250| 200
EKH 50х25-12| 640| 290| 520| 270| 500| 250|
200
EKH 50х25-15
| 640| 290| 520| 270| 500| 250| 200
EKH 50х25-18| 640| 290| 520| 270| 500| 250|
200
EKH 50х25-21
| 640| 290| 520| 270| 500| 250| 200
EKH 50×30-6| 640| 340| 520| 320| 500| 250|
200
EKH 50×30-7.5
| 640| 340| 520| 320| 500| 300| 200
EKH 50×30-9| 640| 340| 520| 320| 500| 300|
200
EKH 50×30-10.5
| 640| 340| 520| 320| 500| 300| 200
EKH 50×30-12| 640| 340| 520| 320| 500| 300|
200
EKH 50×30-15
| 640| 340| 520| 320| 500| 300| 200
EKH 50×30-18| 640| 340| 520| 320| 500| 300|
200
EKH 50×30-21
| 640| 340| 520| 320| 500| 300| 200
EKH 60×30-9| 740| 340| 620| 320| 600| 300|
200
EKH 60×30-12
| 740| 340| 620| 320| 600| 300| 200
EKH 60×30-15| 740| 340| 620| 320| 600| 300|
200
EKH 60×30-18
| 740| 340| 620| 320| 600| 300| 200
EKH 60×30-21| 740| 340| 620| 320| 600| 300|
200
EKH 60×30-24
| 740| 340| 620| 320| 600| 300| 200
EKH 60×35-9| 740| 390| 620| 370| 600| 350|
200
EKH 60×35-12
| 740| 390| 620| 370| 600| 350| 200
EKH 60×35-15| 740| 390| 620| 370| 600| 350|
200
EKH 60×35-18
| 740| 390| 620| 370| 600| 350| 200
EKH 60×35-21| 740| 390| 620| 370| 600| 350|
200
EKH 60×35-24
| 740| 390| 620| 370| 600| 350| 200
EKH 70×40-18| 840| 440| 720| 420| 700| 400|
390
EKH 70×40-27
| 840| 440| 720| 420| 700| 400| 510
EKH 70×40-36| 840| 440| 720| 420| 700| 400|
750
EKH 80×50-27
| 940| 540| 820| 520| 800| 500| 390
EKH 80×50-36| 940| 540| 820| 520| 800| 500|
510
EKH 80×50-54
| 940| 540| 820| 520| 800| 500| 750
EKH 90×50-45| 1040| 540| 920| 520| 900| 500|
750
EKH 90×50-54
| 1040| 540| 920| 520| 900| 500| 750
EKH 100×50-45| 1140| 540| 1020| 520| 1000| 500|
750
EKH 100×50-54
| 1140| 540| 1020| 520| 1000| 500|
750
MAIN TECHNICAL PARAMETERS OF HEATERS FOR RECTANGULAR DUCTS
Heater model
| Power [kW]| Number of phases| Voltage [V]| Number of
electric heating elements x power [kW]| Current [A]| Minimum air
flow [m3/h]| Weight [kg]
---|---|---|---|---|---|---|---
EKH 40×20-4.5| 4.5| 3| 400| 3×1.5| 6.5| 330|
6.5
EKH 40х20-6
| 6.0| 3| 400| 3×2.0| 8.7| 440| 6.5
EKH 40х20-7.5| 7.5| 3| 400| 3×2.5| 10.9| 550|
6.5
EKH 40х20-9
| 9.0| 3| 400| 3×3.0| 13.0| 660| 6.5
EKH 40х20-10.5| 10.5| 3| 400| 3×3.5| 15.2| 770|
6.5
EKH 40х20-12
| 12.0| 3| 400| 3×4.0| 17.4| 880| 6.5
EKH 40х20-15| 15.0| 3| 400| 3×5.0| 21.7| 1100|
6.5
EKH 50х25-6
| 6.0| 3| 400| 3×2.0| 8.7| 440| 7.65
EKH 50х25-7.5| 7.5| 3| 400| 3×2.5| 10.9| 550|
7.65
EKH 50х25-9
| 9.0| 3| 400| 3×3.0| 13.0| 660| 7.65
EKH 50х25-10.5| 10.5| 3| 400| 3×3.5| 15.2| 770|
7.65
EKH 50х25-12
| 12.0| 3| 400| 3×4.0| 17.4| 880| 7.65
EKH 50х25-15| 15.0| 3| 400| 3×5.0| 21.7| 1100|
7.65
EKH 50х25-18
| 18.0| 3| 400| 3×6.0| 26.0| 1320| 7.65
EKH 50х25-21| 21.0| 3| 400| 3×7.0| 30.0| 1540|
7.65
EKH 50×30-6
| 6.0| 3| 400| 3×2.0| 8.7| 440| 8.2
EKH 50×30-7.5| 7.5| 3| 400| 3×2.5| 10.9| 550|
8.2
EKH 50×30-9
| 9.0| 3| 400| 3×3.0| 13.0| 660| 8.2
EKH 50×30-10.5| 10.5| 3| 400| 3×3.5| 15.2| 770|
8.2
EKH 50×30-12
| 12.0| 3| 400| 3×4.0| 17.4| 880| 8.2
EKH 50×30-15| 15.0| 3| 400| 3×5.0| 21.7| 1100|
8.2
EKH 50×30-18
| 18.0| 3| 400| 3×6.0| 26.0| 1320| 8.2
EKH 50×30-21| 21.0| 3| 400| 3×7.0| 30.0| 1540|
8.2
EKH 60×30-9
| 9.0| 3| 400| 3×3.0| 13.0| 660| 9.4
EKH 60×30-12| 12.0| 3| 400| 3×4.0| 17.4| 880|
9.4
EKH 60×30-15
| 15.0| 3| 400| 3×5.0| 21.7| 1100| 9.4
EKH 60×30-18| 18.0| 3| 400| 3×6.0| 26.0| 1320|
9.4
EKH 60×30-21
| 21.0| 3| 400| 3×7.0| 30.0| 1540| 9.4
EKH 60×30-24| 24.0| 3| 400| 3×8.0| 34.7| 1760|
9.4
EKH 60×35-9
| 9.0| 3| 400| 3×3.0| 13.0| 660| 9.75
EKH 60×35-12| 12.0| 3| 400| 3×4.0| 17.4| 880|
9.75
EKH 60×35-15
| 15.0| 3| 400| 3×5.0| 21.7| 1100| 9.75
EKH 60×35-18| 18.0| 3| 400| 3×6.0| 26.0| 1320|
9.75
EKH 60×35-21
| 21.0| 3| 400| 3×7.0| 30.0| 1540| 9.75
EKH 60×35-24| 24.0| 3| 400| 3×8.0| 34.7| 1760|
9.75
EKH 70×40-18
| 18.0| 3| 400| 6×3.0| 26.0| 1320| 14
EKH 70×40-27| 27.0| 3| 400| 9×3.0| 39.0| 1980|
18.5
EKH 70×40-36
| 36.0| 3| 400| 12×3.0| 52.0| 2640| 25
EKH 80×50-27| 27.0| 3| 400| 9×3.0| 39.0| 1980|
19
EKH 80×50-36
| 36.0| 3| 400| 12×3.0| 52.0| 2640| 23.5
EKH 80×50-54| 54.0| 3| 400| 18×3.0| 78.0| 3960|
30
EKH 90×50-45
| 45.0| 3| 400| 15×3.0| 65.0| 3300| 31
EKH 90×50-54| 54.0| 3| 400| 18×3.0| 78.0| 3960|
33.5
EKH 100×50-45
| 45.0| 3| 400| 15×3.0| 65.0| 3300| 33
EKH 100×50-54| 54.0| 3| 400| 18×3.0| 78.0| 3960|
36
The allowable power supply voltage deviations from the rated voltage shown in the tables above is +10 %.
DESIGN AND OPERATING PRINCIPLE
The heaters (see the figure below) consist of a casing with a rigidly fixed
connecting box that is with the removable cover.
The tight seals are located at the external side of the connection box for
routing of supply, control and ground cables.
The heating elements are located inside the casing.
The casing, the connection box and the heater cover are made of galvanized
steel.
The connection box incorporates:
– terminal block for connection of external supply and control circuits of the
heater;
– screw ground terminal;
– hermal switches (automatic and manual).
The heaters are equipped with two overheating sensors – thermal switches:
– with automatic reset and temperature threshold value 50 °C;
– with manual reset and temperature threshold value 90 °C.
Thermal switch with manual reset is equipped with a button for manual restart. The label RESTART is near the button.
The electric heater wiring diagram is shown at the internal wall of the connecting box.
EKH HEATER FOR ROUND DUCTS
- Connection box
- Removable cover
- Electric lead-ins
- Electrical heating elements
- Casing
EKH HEATER FOR RECTANGULAR DUCTS
- Removable cover
- Cable glands
- Casing
- Electrical heating elements
- Electrical terminal box
MOUNTING AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT
Disconnect the unit from power supply prior to any connection, servicing and
repair operations.
Prior to the heater installation check the heater for the integrity and
reliability of the heating element fixation. The heater shall be installed in
the air duct with the same diameter (dimensions).
The working position of the heater must ensure unimpeded access to the connection box and the RESET thermoswitch manual reset button.
The heater must be securely fastened in place. The mounting location must enable quick access to the heater and provide ample space for technical maintenance operations.
The duct heaters are designed for min. air flow speed 1,5 m/s and max. exhaust air temperature 40 °C.
The rectangular heaters are to install in such a way that the arrow on the casing indicates the air flow direction.
The minimum clearance between the heater and other ventilation system components should at least double the connection size (for the heaters with round air ducts) or double the diagonal cut (for the heaters with rectangular air ducts).
Do not insulate the heaters against heat! No inflammable, explosive or fire-
hazardous materials are allowed within 150 mm of the heater casing and within
500 mm of the heater air inlet and outlet. Air ducts and fans must be equipped
with a grille or similar protective device preventing free access to the
electric heating elements.
The supply voltage must be fed via an automatic circuit breaker with a minimum
gap of 3 mm between the open contacts on all poles. The circuit breaker must
be integrated into the stationary wiring in accordance with the applicable
electrical wiring regulations.
The air filter shall be installed upstream of the heater to protect it from
dust and dirt. The distance between the filter and the heater shall be long
enough as the close filter location to the heater is not allowed due to fire
safety reasons.
Pre-commissioning precautions:
- The unit must be safely grounded in compliance with the «Regulations for Electrical Installation» (i.e. the clamp must be connected to the protective ground wire);
- Power to the electrical heater is supplied only when the fan is running;
- Electric heater power cut-off is allowed only when the fan is running, the time span between the heater power cut-off and the fan turn-off shall be at least 30 seconds;
- The minimum air flow through the heater must comply with the value stated in the technical specification.
To ensure proper and safe operation the heater should be equipped with an automatic control system capable of comprehensive control and protection – in particular:
- automatic control of power and air heating temperature control;
- monitoring the filter condition using the pressure differential sensor feedback;
- powering off the heater in the event of the supply fan shutdown or air flow velocity drop as well as upon actuation of the built-in overheating protection thermostats;
- ventilation system shutdown after complete cooling of heating elements.
In the course of operation, the triggering of thermoswitches with automatic
reset may occur.
The thermoswitches may be triggered by an unexpected power failure or an
incompatibility between the chosen heater and the air flow rate. The
thermoswitches are to interrupt the power supply until the heater cools down
to the room temperature.
The thermoswitch with manual reset may be triggered in the heater supplied
with power if the air flow is absent (emergency operation) or the air flow
rates are too low (below the minimum nominal rate).
In case of triggering of the thermoswitch with manual reset:
- interrupt the power supply to the heater;
- rectify the fault in the ventilation system;
- remove the cover from the connection box and press the RESET button to restore the switch to the original position.
CONNECTING ROUND AIR DUCTS TO THE HEATER
The heater is designed for internal installation into air ducts in the horizontal or vertical position. In a horizontal position the connection box must face upwards. Permitted deviation up to 90 °C. The heater must not be mounted with the connection box suspended downwards (risk of condensate leaking and short circuit of power grid).
CONNECTING RECTANGULAR AIR DUCTS TO THE HEATER
CONNECTION TO POWER MAINS
POWER OFF THE POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT.
THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S
LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
The heaters have to be connected to the single-phase AC mains with voltage of
230 V/ 50 Hz or three-phase AC mains with voltage of 400 V/ 50 Hz dependent on
the heater model.
The electric connections must be performed with insulated, durable and heat-
resistant conductors (cables, wires) with a matching cross section.
The external lead-in (230 V/50 Hz or 400 V/50 Hz) must be equipped with an
automatic circuit breaker built into the stationary wiring to interrupt all
the network phases in case of a short circuit or an overload.
The location of the QF external switch must ensure free access for quick
shutdown of the unit. The protection trip current must be consistent with the
maximum current consumption of the unit (see the tables of main technical
parameters).
The cross section selection must account for the maximum permissible wire heating which depends on the wire type, its insulation, length and installation method (i.e. overhead, in pipes or inside walls).
Wiring diagram types are determined by quantity of the heating elements, supply voltage characteristics, number of phases.
Wiring diagram designation key:
S1, S2 – thermal switches
En – electrical heating elements
X1 – terminal block
X2 – ground clamp
WIRING DIAGRAM OF THE HEATER WITH ONE ELECTRICAL HEATING ELEMENT AND SINGLE-PHASE POWER SUPPLY
WIRING DIAGRAM OF THE HEATER WITH TWO ELECTRICAL HEATING ELEMENTS AND SINGLE-PHASE POWER SUPPLY
WIRING DIAGRAM OF THE HEATER WITH THREE ELECTRICAL HEATING ELEMENTS AND SINGLE-PHASE POWER SUPPLY
WIRING DIAGRAM OF THE HEATER WITH THREE ELECTRICAL HEATING ELEMENTS AND THREE-PHASE POWER SUPPLY
WIRING DIAGRAM OF THE HEATER WITH SIX ELECTRICAL HEATING ELEMENTS AND THREE- PHASE POWER SUPPLY, STAR CONNECTION AND THERMAL PROTECTION CONTACTS LEADED OUTSIDE
A
| L1
---|---
B|
L2
C
|
L3
WIRING DIAGRAM OF THE HEATER WITH SIX ELECTRICAL HEATING ELEMENTS, THREE- PHASE POWER SUPPLY, DELTA CONNECTION AND THERMAL PROTECTION CONTACTS LEADED OUTSIDE
A
| L1
---|---
B|
L2
C
|
L3
WIRING DIAGRAM OF THE HEATER WITH ONE ELECTRICAL HEATING ELEMENT, SINGLE- PHASE POWER SUPPLY AND TIME-DELAY RELAY
WIRING DIAGRAM OF THE RECTANGULAR HEATER WITH THREE ELECTRICAL HEATING ELEMENTS, THREE-PHASE POWER SUPPLY, STAR CONNECTION AND TIME-DELAY RELAY
S – ON\OFF switch
KT – time-delay relay
M – fan
KM – magnetic starter
Q – automatic circuit breaker
WIRING DIAGRAM OF THE RECTANGULAR HEATER WITH THREE ELECTRICAL HEATING ELEMENTS, THREE-PHASE POWER SUPPLY, DELTA CONNECTION AND TIME-DELAY RELAY
WIRING DIAGRAM OF THE RECTANGULAR HEATER WITH THREE ELECTRICAL HEATING ELEMENTS, THREE-PHASE POWER SUPPLY, STAR CONNECTION AND TIME-DELAY RELAY
S – ON\OFF switch
KT – time-delay relay
M – fan
KM – magnetic starter
Q – automatic circuit breaker
Operation principle of the electric heater with control circuits is as
follows:
As the ON/OFF switch S turns ON, the KM magnetic starter coil is
charged through the closed contacts of the thermal switches. Consequently
electric power is supplied to the heating elements through the closed contacts
of the thermal switches and magnetic starter. Should at least one of the
thermal switches turn on the power circuit of the magnetic starter KM and
of the heating element gets broken thus preventing the heater overheating. The
diagram shows the fan connection example with the time-delay relay KT. The
motor M is turned off before the heater is turned off to ensure the
electric heating elements cooling.
The automatic circuit breaker Q is designed for overload protection of the
electrical circuits.
Wiring diagram types are determined by quantity of the heating elements,
supply voltage characteristics, number of phases.
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM POWER MAINS BEFORE REMOVING THE
PROTECTION.
The heaters shall be operated and maintained by duly qualified experts.
Check the following conditions during the unit maintenance:
- Inspection of screw connections as well as rivet and welded joints;
- Inspection of tightening of ground screw clamps and electric connections;
- Inspection of the wire terminal connections;
- Cleaning of the electric heating elements of dust and dirt. Cleaning with any kinds of solvents and/or flammable substances is forbidden.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 °C to +40 °C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility. We hereby declare that the
product complies with the provisions of Electromagnetic Compatibility (EMC)
Directive 2014/30/EU of the European Parliament and of the Council, Low
Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the
Council and CE-marking Council Directive 93/68/EEC. This certificate is issued
following test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE STAMP
CERTIFICATE OF ACCEPTANCE
Unit Type|
Duct electrical heater
---|---
Model|
Serial Number|
Manufacture Date|
Quality Inspector’s Stamp|
SELLER INFORMATION
Seller| |
Seller’s Stamp
---|---|---
Address|
Phone Number|
E-mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The _____ unit is installed pursuant to the requirements stated in the present user’s manual.|
Installation Stamp
---|---
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed in accordance with the provisions of all the
applicable local and national construction, electrical and technical codes and
standards. The unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type|
Duct electrical heater
|
Seller’s Stamp
---|---|---
Model|
Serial Number|
Manufacture Date|
Purchase Date|
Warranty Period|
Seller|
www.blaubergventilatoren.de
B09EN-10