ADICOS HOTSPOT-Ex IR Heat Detector Instruction Manual
- August 26, 2024
- ADICOS
Table of Contents
**ADICOS HOTSPOT-Ex IR Heat Detector Instruction Manual
**
Abstract
The Advanced Discovery System (ADICOS®) is used for early detection of fires in industrial environments. It is comprised of various, separate detector units. By parameterizing and arranging the detectors appropriately, the system fulfills a predefined detection goal. The ADICOS system ensures reliable early detection of embers and smoldering fires even in adverse environments.
The detectors of the HOTSPOT product series are equipped with thermal imaging sensors and use infrared measurement technology and intelligent signal analysis to detect all types of smoldering fires and open fires, even in the incipient stage. The fast response speed of 100 milliseconds enables the monitoring of conveyor belts or other conveyor systems, e.g. on moving embers.
ADICOS HOTSPOT-Ex detectors are designed for operation within explosive atmospheres up to ATEX zone 20.
About this Manual
Objective
This manual describes the special requirements on installation, wiring, commissioning, and operation of ADICOS HOTSPOT-Ex detectors for explosive atmospheres up to ATEX zone 20. They are exclusively addressed to knowledgeable specialist personnel (–› Chap. 2, Safety instructions).
Explanation of Symbols
This manual features a continuous structure for best possible comprehension. The following labels are used.
Warning signs
The following types of notes are used through this manual.
-
DANGER!
This combination of symbol and signal word indicates an immediately dangerous situation that will lead to death or severe injuries if not avoided. -
WARNING!
This combination of symbol and signal word indicates a possibly dangerous situation that could lead to death or severe injuries if not avoided. -
Explosion protection
This information type signals measures that must be implemented for maintaining the Explosion protection. -
Tips and recommendations
Helpful tips and recommendations as well as information to ensure efficient and uninterrupted use.
Storing the Manual
Store this manual easily reachable and in direct vicinity of the detector system to enable use as needed.
Safety Instructions
ADICOS HOTSPOT-Ex detectors for explosive atmospheres up to ATEX zone 20 ensure operational safety assuming proper installation, commissioning, operation, and maintenance. For this purpose, it is absolutely required to completely read, understand, and follow this manual and the safety information contained.
WARNING!
Personal injury and property damage! Incorrect installation and operating errors can cause death, serious injury and damage to industrial equipment.
Read the entire manual and follow the instructions!
Explosion protection
When using ADICOS detectors in potentially explosive atmospheres, follow the
specifications of the ATEX operating directive.
Intended Use
ADICOS HOTSPOT-Ex are designated for the detection of fire scenarios in explosive atmospheres of ATEX zone 20, 21 and 22. In this context, the operating parameters described in Chap. 9, »Technical Data« must be met. Any deviating use requires prior consultation with the manufacturer.
Compliance with this manual as well as all applicable country-specific provisions is also part of the intended use.
Standards and Regulations
The safety and accident prevention regulations applicable for the specific application must be observed during detector installation, commissioning, maintenance, and test. The following standards and directives in their current version are of particular importance when handling potentially explosive atmospheres:
Standards and Regulations | Description |
---|---|
EN IEC 60079-0:2018/ AC: 2020-02 | Explosive atmospheres – Part 0: Equipment – |
General requirements
EN 60079-31:2014| Explosive atmospheres – Part 31: Equipment dust ignition
protection by enclosure „t“
EN 60529| Degrees of protection provided by enclosures (IP Code)
2014/34/EU| ATEX product directive (about equipment and protective systems
intended for use in potentially explosive atmospheres)
1999/92/EG| ATEX operating directive (on safety and health protection of
workers potentially at risk from explosive atmospheres)
Personnel Qualification
Any work on ADICOS HOTSPOT-Ex may only be performed by qualified personnel. Persons, who can perform work on electrical systems and recognize possible dangers based on their professional education, knowledge, and experience as well as knowledge of the applicable provisions, are considered qualified personnel.
WARNING!
Personal injury and property damage! Improperly performed work on and with the device can lead to malfunctions.
Installation, startup, parameterization and maintenance may be performed only by authorized and properly trained personnel.
Handling Electrical Voltage
DANGER!
Risk of explosion by electrical voltage in potentially explosive atmospheres!
The electronics of ADICOS HOTSPOT-Ex detectors requires an electrical voltage
that can trigger an explosion in potentially explosive atmospheres.
- Do not open enclosure!
- De-energize the entire detector system and secure against unintentionally reactivation for all wiring work!
Modifications
WARNING!
Property damage or detector failure by any form of unauthorized modification!
Any form of unauthorized modification or extension can lead to a failure of the detector system. The warranty claim expires.
Never make unauthorized modifications on your own authority.
Accessories and Spare Parts
WARNING!
Property damage due to short circuit or failure of the detector system The use of parts other than the manufacturer’s original spare parts and original accessories may result in property damage due to short circuits.
- Only use original spare parts and original accessories!
- Original spare parts and accessories may only be installed by trained specialist personnel.
- Qualified personnel are persons as described in Chap. 2.3.
Structure
Overview
No. | Description |
---|---|
① | Enclosure |
② | Display elements |
③ | Purge air adapter IR-Sensor |
④ | IR-Sensor |
⑤ | Purge air adapter camera |
⑥ | Explosion Proof cable gland |
⑦ | Camera |
Cable Assignment
12-pin cable OELFLEX 415CP
Wire | Signal | Limit value contact |
---|---|---|
1 | Operating voltage |
DC 21.6 … 40 V non-polarised
2
3| M-Bus
max. 40 V non-polarised
4
5| Relay output X6 e| Alarm NO1
6| Relay output X6 a| Alarm NO1
7| Relay output X7 a| Fault NC
8| Relay output X7 e| Fault NC
1
with series resistor
Option analog signal
Wire | Signal | Analog signal |
---|---|---|
9 | Analog current | 4 … 20 mA |
10 | Analog current | 4 … 20 mA |
11 | ||
12 |
Option Fire panel interface
Wire | Siemens FDnet | Bosch LSNi |
---|---|---|
9 | FDnet-A (-) | LSN b1 in |
10 | FDnet (+) | LSN a in |
11 | FDnet-B (-) | LSN b2 out |
12 | FDnet (+) | LSN a out |
Option pre-alarm
Wire | Auxiliary relay |
---|---|
9 | – |
10 | – |
11 | Common |
12 | Normally open |
Installation
Mounting on Mounting Plate
WARNING!
Risk of explosion in hazardous areas due to electrical voltage.
ADICOS HOTSPOT-Ex detectors must be mounted with closed enclosure.
- Do not open enclosure!
- Use ADICOS mounting plate!
Mounting on Mounting Bracket
WARNING!
Risk of explosion in hazardous areas due to electrical voltage.
ADICOS HOTSPOT-Ex detectors must be mounted with closed enclosure.
- Do not open enclosure!
- Use ADICOS mounting foot!
Wiring
Wiring according to chapter 3.2.
DANGER!
Risk of explosion in hazardous areas due to electrical voltage.
The electronics of the ADICOS HOTSPOT-Ex detectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres.
- Do not open enclosure!
- De-energize the entire detector system and secure against unintentionally reactivation for all wiring work!
- In the case of wiring within potentially explosive atmospheres, only use explosion-proof junction boxes with respective approval!
- Do not bend connection cable! Observe minimum bending radius! (–› Chap. 9, Technical Data)
Commissioning
DANGER!
Risk of explosion in hazardous areas due to electrical voltage.
The electronics of the ADICOS HOTSPOT-Ex detectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres.
- Prior to switching on, check that all detectors are properly mounted and wired!
Operation
DANGER!
Risk of explosion in hazardous areas due to electrical voltage. The electronics of the ADICOS HOTSPOT-Ex detectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres.
- Never open the enclosure or loosen the cable gland during operation!
Maintenance
DANGER!
Risk of explosion in hazardous areas due to electrical voltage.
The electronics of the ADICOS HOTSPOT-Ex detectors requires an electrical voltage that can trigger an explosion in potentially explosive atmospheres.
- Do not open enclosure!
- De-energize the entire detector system and secure against unintentionally reactivation for all wiring work!
- Replace the closed detector including connection cable only!
Disposal
Return the device to the manufacturer when it reaches the end of its serviceable life. The manufacturer will ensure that the components are disposed of properly, in an environmentally friendly manner.
Technical data
General
Model| | ADICOS HOTSPOT-Ex
Item No.| | 410-2001-235 | 410-2001-236
Enclosure dimensions| mm| 128 x 100 x 90 (Length x Width x Depth) (Length:
cable gland included)
Weight
(incl. 10 meter cable)
| kg| 2.3
Degree of protection| | IP 65
Enclosure| | Aluminum die casting, powder-coated
Electrical properties
Voltage range| V| DC 21.6 … 40
Max. Power consumption (excl. heating)| VA| 2
Max. Power consumption: (incl. heating)| VA| 10
M-Bus-Voltage (Signal)| V/mA| max. 40 V non-polarized / max. 30 mA
Thermal data
Ambient t ≤ 95 (nicht kon- densierend) emperature| °C| –10 … + 50
Relative humidity| %| ≤ 95 (non-condensing)
Optional communication modules (input parameters)
BMZ-Modul Siemens FDnet| | DC 33 V; max. 10 mA
ADICOS
Coupling module 4-20 mA
| | DC 35 V; max. 20 mA
BMZ-Modul Bosch LSN| | DC 36 V; max. 20 mA
Pre-alarm relay module| | DC 40 V; max. 10 mA
DC 24 V; max. 20 mA
Sensor data
Resolution| Pixel| 32 x 31
Capture angle| °| 53 x 52 | 93 x 92
Reaction time| s| < 1
Temporal resolution| s| 0.1 or 1 (depending on configuration)
Information regarding explosion protection Certified according to ATEX
and IECEx
Explosion protection class BVS 15 ATEX E102| | II 1D Ex ta IIIC T110°C Da
II 2D Ex tb IIIC T80°C Db
Explosion protection class IECEx BVS 15.0089| | Ex ta IIIC T110°C Da
Ex tb IIIC T80°C Db
Ex tc IIIC T80°C Dc
Device group (ATEX)| | II, category 1D/2D
Other
Bending radius cable| mm| > 91.5
ID Plate
Model| Device model| SERIAL| Serial number (variable)| YR| Year of production
(variable)
---|---|---|---|---|---
ART. No| Article number (variable)| TEMP| Ambient temperature| IP| Degree of
protection
COM No.| Communication number (variabel)| VDC/VA| Voltage range / maximum pow-
er consumption (heating incl.)| Is| Internal fusing (Short-circuit current)
CE marking| Information on explosion protection
Appendix
ADICOS Mounting Plate
ADICOS Mounting Bracket
Read User Manual Online (PDF format)