VOLT POLSKA 11000 Sinus Pro Ultra Hv Instruction Manual
- August 20, 2024
- VOLT POLSKA
Table of Contents
- 11000 Sinus Pro Ultra Hv
- Product Information
- Specifications
- Product Usage Instructions
- Safety Instructions
- Assembly and Installation
- Operation
- Maintenance
- Q: What types of batteries are recommended for use with the
- Q: Can I install the inverter myself?
- Q: What should I do if I encounter errors during
11000 Sinus Pro Ultra Hv
“`html
Product Information
Specifications
-
Product: Solar Inverter SINUS PRO ULTRA-HV 6000 ULTRA-HV
11000 -
Manufacturer: VOLT POLSKA Sp. z o.o.
-
Address: ul. Swiemirowska 3, 81-877 Sopot
-
Website: www.voltpolska.pl
-
Email: pomoc@voltpolska.pl | hurt@voltpolska.pl
-
Contact: (58) 500 85 62
Product Usage Instructions
Safety Instructions
This manual provides safety and installation guidelines as well
as information on tools and wiring. It is important to read and
understand these safety instructions before operating the solar
inverter.
Assembly and Installation
-
Read the manual carefully before starting the assembly and
installation process. -
Ensure all necessary tools are available for the
installation. -
Follow the step-by-step installation procedure outlined in the
manual. -
Connect the inverter to the appropriate power sources as per
the installation instructions.
Operation
-
After successful installation, power on the solar inverter
following the startup instructions provided. -
Monitor the inverter’s performance and ensure it is functioning
correctly. -
Refer to the troubleshooting section of the manual in case of
any issues during operation.
Maintenance
-
Do not disassemble the unit yourself; always seek assistance
from a qualified service center for maintenance or repairs. -
Regularly inspect the inverter for any signs of damage or wear
and tear. -
Follow the maintenance schedule recommended in the manual to
ensure optimal performance.
FAQ
Q: What types of batteries are recommended for use with the
solar inverter?
A: Only deep-cycle lead acid type rechargeable batteries are
recommended to reduce the risk of injury or damage.
Q: Can I install the inverter myself?
A: It is recommended that only qualified personnel install the
device with batteries to ensure proper setup and operation.
Q: What should I do if I encounter errors during
operation?
A: If errors persist after following troubleshooting steps,
contact qualified service persons for assistance and do not attempt
to repair the device yourself.
“`
PRODUCT MANUAL
SOLAR INVERTER
SINUS PRO ULTRA-HV 6000 ULTRA-HV 11000
VOLT POLSKA Sp. z o.o. ul. Swiemirowska 3 81-877 Sopot www.voltpolska.pl
pomoc@voltpolska.pl | hurt@voltpolska.pl | (58) 500 85 62
ABOUT THIS MANUAL …………………………………………………………………………………………..1
Notice…………………………………………………………………………………………………………………..1 Purpose
………………………………………………………………………………………………………………1 Scope
…………………………………………………………………………………………………………………1
SAFETY INSTRUCTIONS …………………………………………………………………………………………1 INTRODUCTION
……………………………………………………………………………………………………2
Features ………………………………………………………………………………………………………………2 Basic System Architecture
…………………………………………………………………………………………2 Product Overview
…………………………………………………………………………………………………..3 INSTALLATION
……………………………………………………………………………………………………..4 Unpacking and Inspection
………………………………………………………………………………………..4 Preparation
…………………………………………………………………………………………………………..4 Mounting the Unit
…………………………………………………………………………………………………..4 Battery Connection
…………………………………………………………………………………………………5 AC Input/ Output Connection
…………………………………………………………………………………….6 PV Connection
……………………………………………………………………………………….8 Final Assembly
………………………………………………………………………………………………………9 Communication Connection
…………………………………………………………………………………….10 Dry Contact
Signal…………………………………………………………………………………………………10 OPERATION .
……………………………………………………………………………………………………….11 Power ON/OFF
……………………………………………………………………………………………………..11 Operation and Display Panel
…………………………………………………………………………………….11 LCD Display Icons
…………………………………………………………………………………………………12 LCD Setting
…………………………………………………………………………………………………………14 Fault Reference Code
…………………………………………………………………………………………….19 Warning Indicator
…………………………………………………………………………………………………21 Operating Mode Description
…………………………………………………………………………………….22 Display Setting
……………………………………………………………………………………………………..23 SPECIFICATIONS .
………………………………………………………………………………………………23 Table 1 Line Mode Specifications
………………………………………………………………………………23 Table 2 Inverter Mode Specifications
…………………………………………………………………………..24 Table 3 Charge Mode Specifications
…………………………………………………………………………..25 Table 4 General Specifications
………………………………………………………………………………….26 TROUBLE SHOOTING
…………………………………………………………………………………………..27
ABOUT THIS MANUAL Notice The purchased products, services and features are
stipulated by the contract made between supplier and the customer. All or part
of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in
the contract, all statements, information, and recommendations in this
document are provided “AS IS” without warranties, guarantees or
representations of any kind, either express or implied. The information in
this document is subject to change without notice. Every effort has been made
in the preparation of this document to ensure accuracy of the contents, but
all statements, information, and recommendations in this document do not
constitute a warranty of any kind, express or implied.
Purpose This manual describes the assembly, installation, operation and
troubleshooting of this unit. Please read this manual carefully before
installations and operations. Keep this manual for future reference.
Scope This manual provides safety and installation guidelines as well as
information on tools and wiring.
The following cases are not within the scope of warranty 1. Out of warranty.
2. Series number was changed or lost. 3. Battery capacity was declined or
external damaged. 4. Inverter was damaged caused of transport shift,
remissness, ect external factor 5. Inverter was damaged caused of irresistible
natural disasters. 6. Not in accordance with the electrical power supply
conditions or operate environment caused damage.
SAFETY INSTRUCTIONS
WARNING: This chapter contains important safety and operating instructions.
Read and keep this manual for future reference.
1. Before using the unit, read all instructions and cautionary markings on
the unit the batteries and all appropriate sections of this manual.
2. CAUTION –To reduce risk of injury, charge only deep-cycle lead acid type
rechargeable batteries. Other types of batteries may burst, causing personal
injury and damage.
3. Do not disassemble the unit. Take it to a qualified service center when
service or repair is required. Incorrect re-assembly may result in a risk of
electric shock or fire.
4. To reduce risk of electric shock, disconnect all wirings before attempting
any maintenance or cleaning. Turning off the unit will not reduce this risk.
5. CAUTION –Only qualified personnel can install this device with battery. 6.
NEVER charge a frozen battery. 7. For optimum operation of this
inverter/charger, please follow required spec to select appropriate cable
size. It’ s
very important to correctly operate this inverter/charger. 8. Be very cautious
when working with metal tools on or around batteries. A potential risk exists
to drop a tool to
spark or short circuit batteries or other electrical parts and could cause an
explosion. 9. Please strictly follow installation procedure when you want to
disconnect AC or DC terminals. Please refer to
INSTALLATION section of this manual for the details. 10. Fuses (1 piece of
150A, 63VDC for 5.2KW and 1 piece of 200A, 63VDC for 3KW) are provided as
over-current
protection for the battery supply. 11. GROUNDING INSTRUCTIONS- This
inverter/charger should be connected to a permanent grounded wiring
system. Be sure to comply with local requirements and regulation to install
this inverter. 12. NEVER cause AC output and DC input short circuited. Do NOT
connect to the mains when DC input short circuits. 13. Warning!! Only
qualified service persons are able to service this device. If errors still
persist after following
troubleshooting table, please send this inverter/charger back to local dealer
or service center for maintenance.
1
INTRODUCTION This is a multi-function inverter/charger, combining functions of
inverter, solar charger and battery charger to offer uninterruptible power
support with portable size. Its comprehensive LCD display offers user-
configurable and easy-accessible button operation such as battery charging
current, AC/solar charger priority, and acceptable input voltage based on
different applications. Features
Pure sine wave inverter Configurable input voltage range for home appliances
and personal computers via LCD setting Configurable battery charging current
based on applications via LCD setting Configurable AC/Solar Charger priority
via LCD setting Compatible to mains voltage or generator power Auto restart
while AC is recovering Overload/ Over temperature/ short circuit protection
Smart battery charger design for optimized battery performance Cold start
function
Basic System Architecture The following illustration shows basic application
for this inverter/charger. It also includes following devices to have a
complete running system:
Generator or Utility. PV modules (option) Consult with your system integrator
for other possible system architectures depending on your requirements. This
inverter can power all kinds of appliances in home or office environment,
including motor-type appliances such as tube light, fan, refrigerator and air
conditioner.
PC
TV Air-conditioning
Load
Fridge
Washing machine
PV INPUT
PV + –
Power Grid
AC INPUT Generator
BAT INPUT BAT CHARGER
Figure 1 Hybrid Power System
Battery
2
Product Overview
97.00MM
97.00MM
78
12 16 15 9
78
12 16 15 9
AC INPUT
AC OUTPUT
COM
USB
PARALLEL CONNECTION
ON
OFF
–
11
14
13
10
6
5.2KW parallel model
AC INPUT
AC OUTPUT
COM
USB
PARALLEL CONNECTION
ON
OFF
–
11
10
6
5.2KW single model
78
9
11
10
6
16 15 12
14
13
17
NC C NO
USB WI-FI
3KW parallel model
16 15 12
17
NC C NO
USB WI-FI
3KW single model 3
1. LCD display 2. Status indicator 3. Charging indicator 4. Fault indicator 5. Function buttons 6. Power on/off switch 7. AC input 8. AC output 9. PV input 10. Battery input 11. Circuit breaker 12. RS485 communication port 13. Parallel communication port (only for parallel model) 14. Parallel switch 15. Dry contact 16. USB 17. USB WIFI
INSTALLATION Unpacking and Inspection Before installation, please inspect the
unit. Be sure that nothing inside the package is damaged. You should have
received the following items inside of package:
The unit x 1 User manual x 1 USB cable x 1
Preparation Before connecting all wirings, please take off bottom cover by
removing two screws as shown below.
3K
5.2K
Mounting the Unit Consider the following points before selecting where to
install:
Do not mount the inverter on flammable construction materials. Mount on a
solid surface. Install this inverter at eye level in order to allow the LCD
display to be read at all times. For proper air circulation to dissipate heat,
allow a clearance of approx. 200 mm to the side and approx. 300 mm above and
below the unit. The ambient temperature should be between 0o c and 55oc to
ensure optimal operation. The recommended installation position is to be
adhered to the wall vertically. Be sure to keep other objects and surfaces as
shown in the diagram to guarantee sufficient heat dissipation and to have
enough space for removing wires
300mm 300mm
200mm
SUITABLE FOR MOUNTING ON CONCRETE OROTHER NON-COMBUSTIBLE SURFACE ONLY.
4
Install the unit by screwing three screws
97.00MM
97.00MM
97.00MM
97.00MM
97.00MM
97.00MM
Battery Connection
CAUTION: For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnect device between battery and inverter. It may not be requested to have a disconnect device in
some applications, however, it’s still requested to have over-current protection installed. Please refer to typical
amperage in below table as required fuse or breaker size.
Ring terminal:
D
L
WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for battery connection. To reduce risk of injury, please use the proper recommended cable and terminal size as below.
Recommended battery cable and terminal size:
Model
Typical Amperage
Battery capacity Wire Size
5.2KW DC48V 3KW DC24V
135A 142A
200AH 100AH
24AWG 24AWG
Cable mm2 (each)
21 21
Ring Terminal
Dimensions
D(mm)
L(mm)
8.4
33.2
8.4
33.2
Torque value
5 Nm
Please follow below steps to implement battery connection: 1. Assemble battery
ring terminal based on recommended battery cable and terminal size. 2. Connect
all battery packs as units requires. It’s suggested to connect at least 200Ah
capacity battery for 5.2KW
model ; at least 100Ah capacity battery for 3KW.
Inverter 5.2KW
Inverter 3KW
12V
12V
12V
12V
5
12V
12V
3. Insert the ring terminal of battery cable flatly into battery connector of inverter and make sure the bolts are tightened with torque of 2-3 Nm. Make sure polarity at both the battery and the inverter/charger is correctly connected and ring terminals are tightly screwed to the battery terminals.
WARNING: Shock Hazard Installation must be performed with care due to high
battery voltage in series.
CAUTION!! Do not place anything between the flat part of the inverter terminal
and the ring terminal. Otherwise, overheating may occur. CAUTION!! Do not
apply anti-oxidant substance on the terminals before terminals are connected
tightly. CAUTION!!Before making the final DC connection or closing DC
breaker/disconnector, be sure positive (+) must be connected to positive (+)
and negative (-) must be connected to negative (-).
AC Input/Output Connection CAUTION!! Before connecting to AC input power source, please install a separate AC breaker between inverter and AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 30A for 3KW,40A for 5.2KW.
CAUTION!! There are two terminal blocks with “IN” and “OUT” markings. Please do NOT-misconnect input and output connectors.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for AC input connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Model 5.2KW DC48V 3KW DC24V
Gauge 8 AWG 12 AWG
Torque Value 1.4~ 1.6Nm 1.2~ 1.6Nm
6
Please follow below steps to implement AC input/output connection: 1. Before
making AC input/output connection, be sure to open DC protector or
disconnector first. 2. Remove insulation sleeve 10mm for six conductors. And
shorten phase L and neutral conductor N 3mm. 3. Insert AC input wires
according to polarities indicated on terminal block and tighten the terminal
screws. Be sure
to connect PE protective conductor ( ) first.
Ground (yellow-green) L LINE (brown or black) N Neutral (blue)
EART H
A2C3I0NLVPAUCT
N
EA RTH AC2O30ULVTAPCUT N
WARNING: Be sure to that AC power source is disconnected before attempting to
hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal
block and tighten terminal screws. Be sure to connect PE protective conductor
( )first. Ground (yellow-green) L LINE (brown or black) N Neutral (blue)
E AR T H
A2C30INLVPAUCT
N
EARTH AC23O0ULVTAPCUT N
5. Make sure the wires are securely connected. CAUTION: Important Be sure to
connect AC wires with correct polarity. If L and N wires are connected
reversely, it may cause utility short-circuited when these inverters are
worked in parallel operation.
CAUTION: Appliances such as air conditioner are required at least 2~3 minutes
to restart because it’s required to have enough time to balance refrigerant
gas inside of circuits. If a power shortage occurs and recovers in a short
time, it will cause damage to your connected appliances. To prevent this kind
of damage, please check manufacturer of air conditioner if it’s equipped with
time-delay function before installation. Otherwise, this inverter/charger will
trig overload fault and cut off output to protect your appliance but sometimes
it still causes internal damage to the air conditioner.
7
PV Connection CAUTION: Before connecting to PV modules, please install separately a DC circuit breaker between inverter and PV modules.
WARNING! All wiring must be performed by a qualified personnel. WARNING! It’s very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below.
Model
Typical Amperage
Cable Size
Torque
5.2KW DC48V
27A
3KW DC24V
18A
10AWG 12AWG
1.2 ~ 1.6 Nm
PV Module Selection: When selecting proper PV modules, please be sure to
consider below parameters: 1. Open circuit Voltage (Voc) of PV modules not
exceeds max. PV array open circuit voltage of inverter. 2. Open circuit
Voltage (Voc) of PV modules should be higher than the start-up voltage. 3.
Max. Power Voltage (Vmpp) of PV modules should be close to best Vmp of
inverter or within Vmp range to get best
performance. If one PV module can not meet this requirement, it’s necessary to
have several PV modules in series connection. Refer to below table. Note:
Vmp: panel max power point voltage. The PV charging efficiency is maximized
while PV system voltage is close to Best Vmp. Maximum PV module numbers in
Series: Vmpp of PV moduleX pcs = Best Vmp or Vmp range of Inverter PV module
numbers in Parallel: Max. charging current of inverter/Impp Total PV module
numbers=maximum PV module numbers in series*PV module numbers in parallel
Solar Charging Mode INVERTER MODEL Max. PV Array Open Circuit Voltage PV Array MPPT Voltage Range MPPT Number
3KW DC24V
450Vdc max 150~430Vdc
1
5.2KW DC48V
Recommended PV module configuration
PV Module Spec (reference) Maximum Power (Pmaxl): 425W Max. Power Voltage Vmpp(V) :38.6V Max. Power Current Impp(A) :11.02A Open Circuit Voltage Voc(V) :45.80V Short Circuit Current Isc(A) :11.81A
Total solar input power 2550W 3400W
5100W
5950W
Solar input
6 pieces in series
8 pieces in series 6pieces in series 2 strings in parallel 7pieces in series 2
strings in parallel
Q’ty of modules 6 pcs 8 pcs 12 pcs
14 pcs
8
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
10
2. Check correct polarity of connection cable from PV modules and PV input
3
connectors. Then, connect positive pole (+)of connection cable to positive pole (+) of PV input connector. Connect negative pole (-) of connection
10 3mm max
–
cable to negative pole (-) of PV input connector.
3. Make sure the wires are securely connected.
Final Assembly After connecting all wirings, please put bottom cover back by
screwing screws as shown below.
9
Communication Connection Please use supplied communication cable to connect inverter and PC. Download the software by link on the first page of this manual into computer and follow on screen instruction to install the monitoring software. For the detailed software operation, please consult the seller if you have any questions.
WARNING: It’s forbidden to use network cable as the communication cable to directly communicate
with the PC port. Otherwise, the internal components of the controller will be damaged.
WARNING: RJ45 interface is only suitable for the use of the company’s supporting products or
professional operation.
Below chart show RJ45 Pins definition
Pin
Definition
1
RS-485-B
2
RS-485-A
3
GND
4
CANH
5
CANL
6
7
8
Dry Contact Signal There is one dry contact (3A/250VAC) available on the rear panel. It could be used to deliver signal to external device when battery voltage reaches warning level.
Unit status
Condition
Power Off Power On
Unit is off and no output is powered.
output is powered from Utility
Output is powered from Battery or Solar.
Program 01 set as utility
Battery voltage
Program 01 Battery voltage<Setting value in
is set as SBU, Program 20
SUB, solar Battery voltage>Setting value in
first
Program 21 or battery charging
reaches floating stage
Dry contact port: NC C NO
NC&C
NO&C
Close
Open
Close
Open
Open
Close
Close
Open
Open
Close
Close
Open
10
OPERATION Power ON/OFF
AC INPUT
AC OUTPUT
COM
USB
PARALLEL CONNECTION
ON
OFF
–
Once the unit has been properly installed and the batteries are connected
well, simply press On/Off switch (located on the bottom of the case) to turn
on the unit.
Operation and Display Panel The operation and display panel, shown in below
chart, is on the front panel of the inverter. It includes three indicators,
four function keys and a LCD display, indicating the operating status and
input/output power information.
LED Indicator LED Indicator
Green Yellow Red
Solid On Flashing Flashing Solid On Flashing
Messages Output is powered by grid in Line mode. Output is powered by battery or PV in battery mode. Battery is charging or discharging. Fault occurs in the inverter. Warning condition occurs in the inverter.
Function Keys Function Keys MENU UP DOWN
ENTER
Description
Enter reset mode or setting mode go to previous selection. Increase the
setting data. Decrease the setting data. Enter setting mode and Confirm the
selection in setting mode go to next selection or exit the reset mode.
11
LCD Display Icons
Icon
Function description
Input Source Information and Output Information Indicates the AC information Indicates the DC information
Indicate input voltage, input frequency, PV voltage, battery voltage and charger current. Indicate output voltage, output frequency, load in VA, load in Watt and discharging current.
Configuration Program and Fault Information
Indicates the setting programs
Indicates the warning and fault codes.
Warning:
flashing with warning code.
Fault: Battery Information
lighting with fault code.
Indicates battery level by 0-24%, 25-49%, 50-74% and 75-100% in battery mode and charging status in line mode.
In AC mode, it will present battery charging status.
Status
Battery voltage <2V/cell
Constant Current 2V/cell~2.083V/cell mode/Constant Voltage mode 2.083V/cell~2.167V/cell
2.167V/cell
Batteries are fully charged.
LCD Display 4 bars will flash in turns Bottom bar will be on and the other
three bars will flash in turns. Bottom two bars will be on and the other two
bars will flash in turns. Bottom three bars will be on and the top bar will
flash.
4 bars will be on.
12
In battery mode, it will present battery capacity.
Load Percentage
Battery Voltage
<1.717V/cell
Load >50%
1.717V/cell~1.8V/cell 1.8V/cell~1.883V/cell
LCD Display
1.883 V/cell <1.817V/cell
50%> Load>20%
1.817V/cell~1.9V/cell 1.9 V/cell ~1.983V/cell
1.983 V/cell
<1.867V/cell
Load<20%
1.867V/cell~1.95V/cell 1.95V/cell~2.033V/cell
2.033 V/cell
Load Information Indicates overload.
Indicates the load level by 0-24%, 25-49%, 50-74% and 75-100%.
0%~24%
25%~49%
50%~74%
75%~100%
Mode Operation Information Indicates unit connects to the mains. Indicates
unit connects to the PV panel. Indicates load is supplied by utility power.
Indicates the solar charger circuit is working.
Indicates the DC/AC inverter circuit is working. Mute Operation
Indicates unit alarm is disabled.
13
LCD Setting After pressing and holding “ENTER” button for 2 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. And then, press “ENTER” or “MENU” button to confirm the selection and exit.
Setting Programs:
Program
Description
00
Exit setting mode
Selectable option Escape
(default)
01
Output source priority selection
14
Solar energy provides power to the loads as first priority, If solar energy is not sufficient to power all connected loads, Utility energy will supply power to the loads at the same time. The battery energy will supply power to the load only in the condition of the utility is unavailable. If the solar is unavailable, the utility will charge the battery until the battery voltage reaches the setting point in program 21.If the solar is available, but the battery voltage is lower than the setting point in program 20, the utility will charge the battery until the battery voltage reaches the setting point in program 20 to protect the battery from damage. Solar energy provides power to the loads as first priority, If solar energy is not sufficient to power all connected loads, battery energy will supply power to the loads at the same time. Utility provides power to the loads only when battery voltage drops to either low-level warning voltage or the setting point in program 20 or solar and battery is not sufficient. The battery energy will supply power to the load in the condition of the utility is unavailable or the battery voltage is higher than the setting point in program 21(when BLU is selected) or program 20(when LBU is selected). If the solar is available, but the battery voltage is lower than the setting point in program 20, the utility will charge the battery until the battery voltage reaches the setting point in program 20 to protect the battery from damage. Solar energy provides power to the loads as first priority. If battery voltage has been higher than the setting point in program 21 for 5 minutes, and the solar energy has been available for 5 minutes too, the inverter will turn to battery mode, solar and battery will provide power to the loads at the same time. When the battery voltage drops to the setting point in program 20, the inverter will turn to bypass mode, utility provides power to the load only, and the solar will charge the battery at the same time. Utility will provide power to the loads as first priority. Solar and battery energy will provide power to the loads only when utility power is not available.
Appliances (default)
If selected, acceptable AC input voltage range will be within 90-280VAC.
02
AC input voltage range
03
Output voltage
04
Output frequency
UPS GEN VDE
50HZ(default)
If selected, acceptable AC input voltage range will be within 170-280VAC.
When the user uses the device to connect the generator, select the generator
mode.
If selected, acceptable AC input voltage range will conform to VDE4105
(184VAC-253VAC)
Set the output voltage, (220VAC-240VAC) 60HZ
(default)
05
Solar supply priority
Solar energy provides power to charge battery as first priority. When the utility is available, if the battery voltage is lower than the setting point in program 21, the solar energy will never supply to the load or feed into the grid, only charge the battery. If the battery voltage is higher than the setting point in program 21, the solar energy will supply to the load or feed into the grid or recharge the battery.
Solar energy provides power to the loads as first priority. If the battery voltage is lower than the setting point in program 20, the solar energy will never supply to the load or feed into the grid, only charge the battery. If the battery voltage is higher than the setting point in program 20, the solar energy will supply to the load or feed into the grid or recharge the battery.
Overload bypass: When enabled, Bypass disable
Bypass enable(default)
06
the unit will transfer to line mode
if overload occurs in battery mode.
07
Auto restart when overload occurs
Restart disable(default) Restart enable
08
Auto restart when over temperature occurs
Restart disable(default) Restart enable
If this inverter/charger is working in Line, Standby or Fault mode, charger source can be programmed as below:
Solar first
Solar energy will charge battery as first
10
Charger source priority: To configure charger source
priority. Utility will charge battery only when solar energy is not available.
priority
Solar and Utility(default) Solar energy and utility will charge
battery at the same time.
15
Only Solar
Solar energy will be the only charger source no matter utility is available or not.
If this inverter/charger is working in Battery mode, only solar
energy can charge battery. Solar energy will charge battery if it’s
available and sufficient.
Maximum charging current:
80A (default)
To configure total charging
11
current for solar and utility
chargers.(Max. charging current
=utility charging current + solar
Setting range is from 1A to 80A for PV 80A Charge/Setting range is from 1A to 100A for PV 100A Charge. Increment of each click is 1A.
charging current)
30A (default)
Setting range is from 1A to 60A for PV
13
Maximum utility charging current
80A Charge/Setting range is from 1A to 80A for PV 100A Charge.
Increment of each click is 1A.
AGM (default)
Flooded
GEL
LEAD
14
Battery type
Lithium Ion
User-Defined
If”User-Defined” or”LI” is selected,When the lithium battery and the inverter do not communicate properly,the battery icon will flash. If”LI” is selected and the battery icon does not flash,program of 11, 17,18 will be set automatically,No need for further setting. If”User-Defined” is selected and the battery icon does not flash battery charge voltage and charge current can be set up in program 11,17 and 18. 24V model default setting: 28.2V
17
Bulk charging voltage (C.V voltage)
If “User-Defined” or”LI” is selected in program 14, this program can be set
up. Setting range is from 24.0V to 29.2V for 24Vdc model. Increment of each
click is 0.1V. 48V model default setting: 56.4V
If “User-Defined” or”LI” is selected in program 14, this program can be set
up. Setting range is from 48.0V to 58.4V for 48Vdc model. Increment of each
click is 0.1V. 24V model default setting: 27.0V
18
Floating charging voltage
If “User-Defined” or”LI” is selected in program 14, this program can be set up, Setting range is from 24.0V to 29.2V for 24Vdc model. Increment of each click is 0.1V. 48V model default setting: 54.0V
If “User-Defined” or”LI” is selected in program 14, this program can be set
up, Setting range is from 48.0V to 58.4V for 48Vdc model. Increment of each
click is 0.1V.
16
24V model default setting: 20.4V
If “User-Defined” or”LI” is selected in program 14, this program can be set up. Setting range is from 20.0V to 24.0V for 24Vdc model. Increment of each click is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what percentage of load is connected. 48V model default setting: 40.8V
19
Low DC cut-off voltage or SOC percentage
If “User-Defined” or”LI”is selected in program 14, this program can be set up.
Setting range is from 40.0V to 48.0V for 48Vdc model. Increment of each click
is 0.1V. Low DC cut-off voltage will be fixed to setting value no matter what
percentage of load is connected.
SOC 10% (default)
If”User-Defined” or”LI”is selected in program 14,and the SOC percentage method is selected in program 37 ,the low DC cut-off SOC percentage will be able to be set.Low DC cut-off SOC percentage will be fixed to setting value no matter what percentage of load is connected Setting range is from 0%-90%. Increment of each click is 1%
Available options for 24V models:
24.0V (default)
Setting range is from 22.0V to 29.0V.
Increment of each click is 0.1V.
20
Battery stop discharging voltage
when grid is available
Available options for 48V models:
48.0V (default)
Setting range is from 44.0V to 58.0V.
Increment of each click is 0.1V.
Available options for 24V models:
27.0V (default)
Setting range is from 22.0V to 29.0V.
Increment of each click is 0. 1V.
21
Battery stop charging voltage when grid is available
Available options for 48V models:
54.0V (default)
Setting range is from 44.0V to 58.0V.
Increment of each click is 0. 1V.
22
Auto turn page
23
Backlight control
(default) Backlight on
If selected, the display screen will auto turn the display page.
If selected, the display screen will stay at latest screen user finally
switches. Backlight off (default)
24
Alarm control
Alarm on (default)
Alarm off
17
Alarm on
25
Beeps while primary source is interrupted
27
Record Fault code
Alarm off (default) Record disable
click click click
Percentage
20(default)
95(default)
Increment of each click is 1%. 1%.
18
(default)
.
. .
41 If “LI” is selected in program 14, program 41 can be set. After the program
41 is set,please restart the inverter to take effect.For example,ifyou set the
program 41 to 0,the inverter can communicatewith the must lithium battery.
After pressing and holding “MENU” button for 6 seconds,the unit will enter
reset model. Press “UP” and “DOWN” button to select programs. And then, press
“ENTER” button to exit.
(default) Reset setting disable
Reset setting enable
Fault Reference Code
Fault Code
Fault Cause
01
Fan is locked when inverter is off
02
Inverter transformer over temperature
03
Battery voltage is too high
04
Battery voltage is too low
05
Output short circuited
06
Inverter output voltage is high
07
Overload time out
08
Inverter bus voltage is too high
09
Bus soft start failed
11
Main relay failed
21
Inverter output voltage sensor error
22
Inverter grid voltage sensor error
23
Inverter output current sensor error
19
LCD Indication
24
Inverter grid current sensor error
25
Inverter load current sensor error
26
Inverter grid over current error
27
Inverter radiator over temperature
31
Solar charger battery voltage class error
32
Solar charger current sensor error
33
Solar charger current is uncontrollable
41
Inverter grid voltage is low
42
Inverter grid voltage is high
43
Inverter grid under frequency
44
Inverter grid over frequency
51
Inverter over current protectionerror
52
Inverter bus voltage is too low
53
Inverter soft start failed
55
Over DC voltage in AC output
56
Battery connection is open
57
Inverter control current sensor error
58
Inverter output voltage is too low
20
Warning Indicator Warning Code Warning Event
61
Fan is locked when inverter is on.
62
Fan 2 is locked when inverter is on.
63
Battery is over-charged.
64
Low battery
67
Overload
70
Output power derating
72
Solar charger stops due to low battery
73
Solar charger stops due to high PV voltage
74
Solar charger stops due to over load
75
Solar charger over temperature
76
PV charger communication error
77
Parameter error
Icon flashing
21
Operating State Description
Operating State
Match load state Note: DC power produced from your solar array is converted by
the inverter into AC power, which is then sent to your main electrical panel
to be used by your household appliances. Any excess power generated is not
sold back to the grid, but stored in battery.
Description
PV energy is charger into the battery or convertered by the inverter to the AC
load
LCD display PV energy power is larger than inverter power
PV energy power is smaller than inverter power
Charge state Bypass state Off-Grid state
Stop mode
PV energy and grid can charge batteries.
Error are caused by inside circuit error or external reasons such as over temperature, output short circuited and so on. The inverter will provide output power from battery and PV power.
Inverter power loads from PV energy.
Inverter power loads from battery and PV energy.
Inverter power loads from battery only.
The inverter stop working if you turn off the inverter by the soft key or error has occurred in the condition of no grid.
22
Display Setting The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: battery voltage, battery current, inverter voltage, inverter current, grid voltage, grid current, load in Watt, load in VA, grid frequency, inverter frequency, PV voltage, PV charging power, PV charging output voltage, PV charging current.
Selectable information
LCD display
Battery voltage/DC discharging current
Inverter output voltage/Inverter output current Grid voltage/Grid current
Load in Watt/VA
Grid frequency/Inverter frequency
PV voltage and PV charging current PV charger output voltage and PV power
SPECIFICATIONS Table 1 Line Mode Specifications
INVERTER MODEL Input Voltage Waveform Nominal Input Voltage Low Loss Voltage
Low Loss Return Voltage
High Loss Voltage
High Loss Return Voltage
Max AC Input Voltage Nominal Input Frequency Low Loss Frequency
Low Loss Return Frequency
High Loss Frequency
High Loss Return Frequency
3KW DC24V
5.2KW DC48V
Sinusoidal (utility or generator)
230Vac
90Vac±7V(APL,GEN);170Vac±7V(UPS); 186Vac±7V(VDE)
100Vac±7V(APL,GEN);180Vac±7V(UPS); 196Vac±7V(VDE)
280Vac±7V(UPS,APL,GEN); 253Vac±7V(VDE)
270Vac±7V(UPS,APL,GEN); 250Vac±7V(VDE)
300Vac
50HZ/60HZ(Auto detection)
40HZ±1HZ(UPS,APL,GEN); 47.5HZ±0.05HZ(VDE)
42HZ±1HZ(UPS,APL,GEN); 47.5HZ±0.05HZ(VDE)
65HZ±1HZ(UPS,APL,GEN); 51.5HZ±0.05HZ(VDE)
63HZ±1HZ(APL,GEN,UPS); 50.05HZ±0.05HZ(VDE)
23
Output Short Circuit Protection Efficiency (Line Mode)
Transfer Time
Output power derating: When AC input voltage drops to 95V or 170V depending on
models, the output power will be derated.
Line mode: Circuit Breaker Battery mode: Electronic Circuits >95%(Rated R
load, battery full charged)
10ms typical (UPS,VDE) 20ms typical (APL)
50ms typical (For parallel operation)
230Vac model:
Table 2 Inverter Mode Specifications INVERTER MODEL Rated Output Power Output Voltage Waveform Output Voltage Regulation Output Frequency Peak Efficiency Overload Protection Nominal DC Input Voltage Cold Start Voltage Low DC Warning Voltage @ load < 20% @ 20% load < 50% @ load 50% Low DC Warning Return Voltage @ load < 20% @ 20% load < 50% @ load 50%
3KW DC24V
5.2KW DC48V
3000W
5200W
Pure Sine Wave
230Vac±5%
60Hz or 50Hz
90%
5s@150% load; 10s@110%~150% load
24Vdc
48Vdc
23.0Vdc
46.0Vdc
22.0Vdc 21.4Vdc 20.2Vdc
23.0Vdc 22.4Vdc 21.2Vdc
44.0Vdc 42.8Vdc 40.4Vdc
46.0Vdc 44.8Vdc 42.4Vdc
24
Low DC Cut-o ffVoltage @ load < 20% @ 20% load < 50% @ load 50% High DC Recovery Voltage High DC Cut-off Voltage
Table 3 Charge Mode Specifications
Utility Charging Mode
INVERTER MODEL
Charging Current @ Nominal Input
Voltage
Floating charging
AGM / Gel/LEAD Battery
voltage
Flooded battery
Bulk charging voltage (C.V voltage)
AGM / Gel/LEAD Battery
Flooded battery
Charging Algorithm
Solar Charging Mode INVERTER MODEL Rated Power MPPT charger solar charging current Max.PV Array Open Circuit Voltage PV Array MPPT Voltage Range Min battery voltage for PV charge Battery Voltage Accuracy PV Voltage Accuracy Charging Algorithm
21.0Vdc 20.4Vdc 19.2Vdc 29Vdc 30Vdc
42.0Vdc 40.8Vdc 38.4Vdc 58Vdc 60Vdc
3KW DC24V
5.2KW DC48V
60Amax/80Amax
27.4Vdc
54.8Vdc
27.4Vdc
54.8Vdc
28.8Vdc
57.6Vdc
28.4Vdc
56.8Vdc
3-Step(Flooded Battery, AGM/Gel/LEAD Battery), 4-Step(LI)
3KW DC24V 4000W
5.2KW DC48V 6000W
80Amax/100Amax
450Vdc max
150~430Vdc
17Vdc
34Vdc
+/-0.3%
+/-2V
3-Step(Flooded Battery, AGM/Gel/LEAD Battery), 4-Step(LI)
25
Charging algorithm for lead acid battery
Charging algorithm for Lithium battery
Joint Utility and Solar Charging INVERTER MODEL Max Charging Current Default
Charging Current
Table 4 General Specifications INVERTER MODEL Safety Certification Operating
Temperature Range Storage temperature Dimension (DWH), mm Net Weight, kg
3KW DC24V
80A/100A 60A/80A
5.2KW DC48V
3KW DC24V
5.2KW DC48V
CE
-10°C to 50°C
-15°C~ 60°C
486X322X134
468X330X119 505X309X147
8
13
14.4
26
TROUBLE SHOOTING
Problem
LCD/LED/Buzzer
Explanation / Possible cause
What to do
Unit shuts down automatically during startup process.
LCD/LEDs and buzzer will be active for 3 seconds and then complete off.
The battery voltage is too low ( < 1.91V/Cell)
1. Re-charge battery. 2. Replace battery.
1. The battery voltage is far too low. 1. Check if batteries the wiring
No response after power on.
No indication.
(<1.4V/Cell) 2. Battery polarity is connected
are connected and well. 2. Re-charge battery.
reversed. Input protector is tripped 3. Replace battery.
Input voltage is
displayed as 0 on the
LCD and green LED Mains exist but the is flashing. unit works in battery
mode.
Input protector is tripped
Check if AC breaker is tripped and AC wiring is connected well.
1. Check if AC wires are too thin and/or too long.
Green LED is flashing.
Insufficient quality of AC power (Shore or Generator)
2. Check if generator (if applied) is working well or if
input voltage range setting is
correct.(Appliance=>wide)
When the unit is
turned on, internal relay is switched on
LCD display and LEDs are flashing
Battery is disconnected.
and off repeatedly.
Check if battery wires are connected well.
Buzzer beeps continuously and red LED is on.
Fault code 07 Fault code 05
Overload error. The inverter is overload 110% and time is up.
Output short circuited.
Reduce the connected load by switching off some equipment.
Check if wiring is connected well and remove abnormal load. Check whether the
air flow of
Fault code 02
Internal temperature of inverter component is over 90oC.
Battery is over-charged.
the unit is blocked or whether the ambient temperature is too high. Return to repair center.
Fault code 03
The battery voltage is too high.
Check if spec and quantity of batteries are meet requirements.
Fault code 01
Fault code 06/58
Fault code 08/09/53/57 Fault code 51 Fault code 52 Fault code 55
Fan fault
Replace the fan.
Output abnormal (Inverter voltage below than 202Vac or is higher than 253Vac)
1. 2.
Reduce the connected load. Return to repair center
Internal components filed.
Return to repair cente
Over current or surge Bus voltage is too low Output voltage is unbalanced
Restart the unit, if the error happens again, please return to repair center.
Fault code 56
Battery is not connected well or fuse is burnt.
If the battery is connected well, please return to repair center.
27
WARRANTY CARD
DATE OF PURCHASE
SHIPPING ADDRESS
SIGNATURE / STAMP
DAMAGE DESCRIPTION
SERVICE COMMENTS
FILL IN IF NEEDEED () Cross incorrect I agree to pay the cost of inverter
repair due to: expiration of the warranty period / * warranty void Before
proceeding with the repair, service will inform by phone about the exact costs
of the repair. Please attach a copy of the purchase document (receipt or
invoice) to the complaint. The full regulations of service repairs can be
found on our website www.voltpolska.pl
Proper disposal of the product (waste electrical and electronic equipment)
The marking placed on the product or in the texts related to it indicates that
it should not be disposed of with other household waste at the end of its
useful life. To avoid harmful effects to the environment and human health from
uncontrolled disposal, please separate this product from other types of waste
and recycle responsibly to promote the reuse of material resources as a
continuing practice. For information on where and how to recycle this product
in an environmentally safe manner, residential users should contact the
retailer where they purchased the product, or their local government
authority. Business users should contact their supplier and check the terms
and conditions of their purchase contract. The product should not be disposed
of with other commercial waste.
pomoc@voltpolska.pl | hurt@voltpolska.pl | (58) 500 85 62