Danfoss Types EVR 32 Solenoid Valve

Danfoss-Types-EVR-32-Solenoid-Valve-product

Specifications:

  • Product Name: Danfoss Solenoid Valve Types EVR 32, EVR 40
  • Refrigerants: R22/R407C, R404A/R507, R410A, R134a, R407A, R23
  • Max. Working Pressure: 400 psig (28 bar pe)
  • Max. Test Pressure: 650 psig (45 bar pe)
  • Ambient Temperature: Refer to manual for details
  • Coil Specifications: 24 V, 60 Hz, 14 Watt

Product Usage Instructions

Installation:

Follow the installation guide provided in the manual for mounting positions and connecting junction boxes.

Wiring:

Ensure wiring and fusing comply with local and national codes. Never switch on power when the coil is dismounted from the valve.

Transformer Selection:

Refer to the manual for transformer selection based on voltage and frequency requirements.

Tightening Torques:

Refer to the manual for specific tightening torques for different components.

FAQ

  • Q: Can I use refrigerants other than the ones listed?
    • A: For other refrigerants, please contact Danfoss for guidance on compatibility.
  • Q: What should I do if the coil is dismounted from the valve?
    • A: Never switch on power to the coil when it is dismounted to avoid damage and potential risks of injuries and burns.

Specification

Refrigerants:

  • R22/R407C, R404A/R507,
  • R410A, R134a, R407A, R23.
  • For other refrigerants, please contact Danfoss.
  • Max. working pressure: 400 psig (28 bar pe)
  • Max. test pressure: 650 psig (45 bar pe)
  • Refrigerant temperature: Min. -40 °F (-40 °C)
    • Max. 220 °F (105 °C)
  • Ambient temperature: Min. -40 °F (-40 °C)
    • Max. 122 °F (50 °C)
  • Ambient temperature: Min. -40 °F (-40 °C)
    • Max. 122 °F (50 °C)

Refrigerant temperature:

  • Min. -40 °F (-40 °C)
  • Max. 220 °F (105 °C)

Valve and coil

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(1\)

Caution

Wiring and fusing (when used) must comply with prevailing local and national wiring codes and ordinances.

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(2\)

Warning

Never switch on power to the coil when the coil is dismounted from the valve. Otherwise the coil may be damaged and there is risk of injuries and burns

Mounting position

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(4\)

Soldering of copper connections

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(5\)

Transformer selection

Coil

| Inrush| Holding
---|---|---
[Volt- Amp]| [W]| [Volt- Amp]
208 – 240 V| 50 Hz| 49| 14| 28
230 V| 50 Hz| 49| 17| 28
110 V| 50 – 60 Hz| 49| 16| 28
120 V| 60 Hz| 49| 15| 28
24 V| 50 – 60 Hz| 49| 14| 28

Tightening torques

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(3\)

Valve and coil construction

Danfoss-Types-EVR-32-Solenoid-Valve-fig
\(6\)

Cut-away

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(7\)

Mounting of piston

Danfoss-Types-EVR-32-Solenoid-Valve-fig \(8\)

Mounting of omega springDanfoss-Types-EVR-32-Solenoid-Valve-fig
\(9\)

Documents / Resources

| Danfoss Types EVR 32 Solenoid Valve [pdf] Installation Guide
Types EVR 32, Types EVR 32 Solenoid Valve, Solenoid Valve, Valve
---|---