Danfoss AK PC 551 Module Controller
Specifications
- Model: AK-PC 551
- Cable Length Options: 1.5m (080G0075), 3.0m (080G0076)
- Supply Voltage: 230 V a.c. 20 VA or 24 V a.c. / d.c. 17 VA
Product Usage Instructions
Supply Voltage
The supply voltage can be either 24 V or 110-230 V. Check the label on the
controller for the specific voltage requirement.
Modbus Installation
Ensure correct installation of the data communication cable for Modbus. Refer
to literature No. RC8AC for proper installation guidelines and bus
termination.
Digital Outputs (DO)
The device has 8 digital outputs labeled DO1 to DO8. DO5 and DO6 are solid-
state relays. Ensure proper power supply to drive alarm relays and prevent
dropouts during alarms.
Analogue Outputs (AO)
There are 2 analogue outputs, AO3 and AO4, which should be used with frequency
converters or EC motors. Connect 24 V on N and L separately, avoid earth
faults, and pay attention to polarity.
Analogue Inputs (AI)
The device features 4 analogue inputs, AI1 to AI4, with factory settings for
different parameters. Configure the inputs based on your specific
requirements.
Digital Switch Inputs (DI)
There are 8 digital switch inputs labeled DI1 to DI8. Configure these inputs
for shutdown or interruption functions as needed.
FAQ
Q: How should electric noise be managed?
A: Keep signal cables separate from high-voltage electric cables, use
separate cable trays, maintain a distance of at least 10 cm between cables,
and avoid using cables longer than 3 m at the DI input.
Q: How can the compressor capacity be controlled?
A: The compressor capacity can be controlled using the signal to operate
unloading valves connected to DO5 or DO6, distributing the capacity
accordingly.
Identification
Kit
-
080G0282 = 080G0321 + 080G0294 + 080G0075 (230 V)
-
080G0288 = 080G0326 + 080G0294 + 080G0075 (24 V)
-
IP 20
-
-20 – 60°C
-
(0 – 140°F)
RH max. 90% non condensing
Principle
Connection
Connection, lower level
DO | DO1 | DO2 | DO3 | DO4 | DO5 | DO6 | DO7 | DO8 | Σ 1-8 |
---|---|---|---|---|---|---|---|---|---|
I Max. | 10 A | 10 A | 6 A | 6 A | 0.5 A | 0.5 A | 6 A | 6 A | 32 A |
(3,5) | (3,5) | (4) | (4) | min. 50 mA | min. 50 mA | (4) | (4) | ||
Ioff < 1.5 mA | Ioff < 1.5 mA | ||||||||
U | All 24 V or all 230 V a.c. |
Supply Voltage.
The supply voltage is either 24 V or 110-230 V. See the label on the reverse side of the controller.
÷ = Plugs normally not used
However, if connecting to an external display, a jumper must be inserted
between the connections “H” and “R”.
Modbus
It is important that the installation of the data communication cable be done
correctly. Cf. separate literature No. RC8AC.
Remember termination at the bus termination.
DO – Digital outputs, 8 pcs. DO1 – DO8
DO5 and DO6 are solid-state relays.
The relays are de-rated to the specified values.
If an alarm relay is defined, it will be driven under normal operation and it
will drop in the event of alarms and insufficient power to the controller.
Connection, upper level
Warning
The supply voltage of AI may not share the signal with other controllers.
Electric noise
Signal cables for sensors, DI inputs, data communication and display must be
kept separate from high voltage (230 V) electric cables:
- Use separate cable trays
- Keep a distance between high voltage and signal cables of at least 10 cm
- Cables longer than 3 m at the DI input should be avoided
AO – Analogue output, 2 pcs. AO3 – AO4
- Must be used when using a frequency converter or EC motors.
- Connect 24 V on N and L (separate supply). Avoid earth fault current. Use double-insulated transformer. The secondary side must not be earthed.
- Obtain 0-10 volts from terminals N and AO3, respectively N and AO4. PAY ATTENTION TO THE POLARITY of N.
AI – Analogue inputs, 4 pcs. AI1 – AI4
Pressure transmitters
- Ratiometric: 10-90% of supply, AKS 32R
- Signal: 1-5 V, AKS 32
- Power: 0-20 mA / 4-20 mA, AKS 33 (supply = 12 V)
Temperature sensor
- Pt 1000 ohm, AKS 11 or AKS 21.
- NTC 86K ohm @ 25°C, from digital scroll.
Factory settings
- AI1=PoA, AI2=PoB, AI3=Pc, AI4=Outdoor temperature SC3.
- DI – Digital switch inputs, 8 pcs. DI1 – DI8
- The connection may be a shut-down or interruption function.
- Select what is to be activated during configuration.
÷ = Plugs normally not used
AI – Analogue inputs, 4 pcs. AI5 – AI8
Pressure transmitters
- Ratiometric: 10-90% of supply, AKS 32R
- Signal: 1-5 V, AKS 32
Temperature sensor
- Pt 1000 ohm, AKS 11 or AKS 21.
- NTC 86K ohm @ 25°C, from digital scroll
External display
Dimensions
The capacity from the digital scroll compressor
The capacity is divided into period times as “PWM period time”. 100% capacity is delivered when cooling takes place for the whole period.
An off time is required by the capacity control valve within the period and an
on time is also permitted. There is “no cooling” when the valve is on.
The controller itself calculates the capacity needed and will then vary it
according to the cut-in time of the capacity control valve.
A limit is introduced if low capacity is needed so that the cooling does not
go below 10%. This is because the compressor can cool itself. This value can
be increased if necessary.
Copeland Stream compressor
The signal can also be used to control one stream compressor with one
unloading valve (4 cylinders version).
The compressor capacity is distributed by up to 50% for one relay and the
remaining 50-100% for the unloader. The unloader is connected to DO5 or DO6.
Bitzer CRII
The pulse signal can also be used to control one of the CRII with 2 unloaders
(4 cylinders version).
Compressor capacity can be controlled from 10 to 100% depending on the
pulsation of the unloaders. The unloader is connected to DO5 or DO6.
Unloader 2 follows unloader 1 but is offset a ½ period.