FUMECARE FC-20 Benchtop Fume Cupboard Instruction Manual
- August 15, 2024
- FUMECARE
Table of Contents
FC-20 Benchtop Fume Cupboard
“`html
Product Specifications:
- Product Name: FUME CDCARE BENCHTOP FUME CUPBOARD
- Version: 2.0
- Quality Standard: nqa 9001
- Brand: VXAS
- Warranty: 1 year from date of purchase
Installation:
-
Step 1) Position Enclosure: Place enclosure on
your bench top or in the desired location. Feed cables through
pass-through ports. -
Step 2) Install Head Unit: Position head unit
on top of the enclosure with open access panel facing front. -
Step 3) Optional Electronic Sensor
Installation: Secure sensor to the right hand side
enclosure wall. Handle with care. -
Step 4) Mains Power: Connect Mains Power lead
to the head unit fused inlet, but do not plug into mains socket
yet.
Operation and Maintenance:
-
Step 5) Filter Selection: Refer to filter
chart datasheet to choose correct filter type for operator
protection. -
Step 6) Filter Installation: Insert new filter
with black gasket facing downwards. Slide into head using wheels
and guide runners. Lock in position with wing nuts. -
Step 7) Filter Installation Continued: Ensure
filter is located against rear stop before securing with wing nuts.
Refit front panel door using provided filter key.
FAQ:
Q: What should I do if the sensor is damaged during
installation?
A: If the sensor is damaged during
installation, please contact the manufacturer or authorized
personnel for assistance. Handling the sensor with care is crucial
to prevent damage.
“`
FUME CDCARE
BENCHTOP FUME CUPBOARD MANUAL
(Version 2.0)
FumeCare Ltd., Suite 8, Jubilee House, Altcar Road, Formby, Merseyside, L37 8DL United Kingdom Tei·. +44 (0)1704 833093 Fax: +44 (0)1704 831133 Website: www.fumecare.com Email: office@fumecare.com Company Registration No. 06954287 VAT No, 838 346110 BS EN
nqa 9001
VXAS
OPERATION AND MAINTENANCE MANUAL
WARRANTY & INDEMNITY
The manufacturer warrants this product for one year from date of purchase. We
will repair without charge, or replace at our discretion, any defects due to
faulty material or workmanship. This warranty does not apply to filters,
accessories or damage caused by improper use, or damage caused by improper
repair. WARNING: The manufacturer and their appointed agents and distributors
wili only consider themselves responsible for the safety, reliability and
performance of the installation if:
Modification, relocation or repairs are carried out by authorized persons The
electrical installations comply with state and national regulations The
equipment is used in compliance with there operating instructions The
equipment is maintained on a regular basis and is used in compliance with
these operation instructions.
INSTALLATION
Step 7) Position Enclosure
Place enclosure on your bench top or in the desired location. The enclosure is
supplied with an open base and is shipped fully assembled. At this stage it is
advised to feed any cables you require through the pass-through ports on the
back panel of the enclosure.
Step 2) Instal Head Unit
Position the head unit on top of the enclosure with the open access panel
facing towards the front. Locate up against the rear rail. Care must be taken
not to damage the seal on the top of the enclosure.
Step 3) Optional Electronic Sensor Installation
Carefully unpack the sensor and remove the red protective tape from the
sensor. Then secure it to the right hand side enclosure wall using the nut and
bolt supplied, ensuring the sensor aligns to slot in the side panel. N.B. Make
sure unit is turned off. When handling the sensor, handle with great care as
it is a very sensitive and can easily be damaged.
Step 4) Mains Power
Connect the Mains Power lead to the head unit fused inlet, but DO NOT plugin
to the mains socket until step 9 is complete
OPERATION AND MAINTENANCE MANUAL
Step 5) Filter Selection
Important Notice: Correct filter selection is vital to ensure operator protection.
Main Filters are required in each Fume Cupboard. Backup/Safety Filters are optional. Prefilters come supplied.
Quantities to order: 1 Filter (10, and 15).
2 Filters (20, 25 and 30)
To look up which filter type is suitable for your application, please refer to the filter chart datasheet supplied.
Filter Type Safety Filter No. Main Filter No.
FCS-OOI
FOR FCS-013
FCM-OOI FCM-013
ACI FCS-OI 5
FCS-018
FCM-015 FCM-018
MIL
SUL
n/a
FCS-016
FCM-III FCM-016
FCS-012
CYN FCS-017
ACR FCS-002
FCM-012 FCM-OI 7 FCM-002
ACM FCS-003 FCM-003
HEPA FCS-030 FCM-030
Custom* FCS-110 FCM-IIO
Step 6) Filter Installation
Use the Filter Key supplied to open the security locks on the front panel of
the head unit. Once the front panel has been removed, locate filter clamp wing
nuts and remove. If you are replacing a filter, lift the front handle of the
filter (to break the seal) and slide the filter out of the unit into a waste
bag. N.B. Make sure unit is turned offand use Personal Protective Equipment
for this step. Also ensure that you dispose of the filter in accordance to
current health & saftey regulations and policies.
Step 7) Filter Installation Continued
To insert the new filter, ensure that the black gasket is facing downwards and
care must be taken not to damage this important seal. Then slide the filter in
to the head using the wheels and guide runners. Ensure that the filter is
located against the rear stop before locking in to position by tightening the
two wing nuts until the filter is secure. then refit the front panel door,
using the filter key provided.
FILTER
Step 8) Prefilter Installation
The prefilters are released by rotating the cam which is on the under side of
the filter module. underneath the head unit. Once released the old prefilter
can be removed from the tray and sealed in a bag for safe disposal. The new
filter can then be placed on the tray which can then be placed back in its
position, ensuring the cams are locked back in position. N.B. Use Personal
Protective Equipment for this step
Step 9) Optional Safety-filter Installation
Unscrew and remove the outlet cover which is located on the top of the main
head unit. If you are replacing a filter, lift out the old filter and place
into a waste bag for safe disposal. The new filter is simply located in to the
recess. The outlet cover is then replaced, ensuring that all screws are
tightened evenly to create a good seal. N.B. Make sure unit is turned off and
use Persona/ Protective Equipment for this step
FILTER & COVER
OPERATION AND MAINTENANCE MANUAL
FILTER SELECTION CHART
1m portant Notice: Correct filter selection is vital to ensure operator
protection. When ordering, please supply details of what containments are to
be filtered and in what volumes. To look up which filter type is suitable for
your application, please refer to the chart below:
Filter Name
GP (General Purpose)
Containment Suitability
ACIDS
Acetic, Acetic anhydride, Acrylic, Butyric, Caprylic, Carbolic, Formic,
Lactic, Osmium tetroxide, Palmitic, Phenol, Proprionic, Valeric
ALCOHOLS Ethyl, Amyl, Buryl, Cyclohexanol, Isopropyl, Methyl (methanol),
Propyl
ALIPHATIC HYDROCARBONS Acerylene, Iso-butane, Burylene, Butadiene,
Cyclohexane, N-decane, Ethane, Ethylene, N-heptane, Heprylene, Hexane,
Hexylene, Methane, N-nonanc, N-ocrylene, Pentane, Propane, Propylene
ALDEHYDES & KETONES Acetone, Acrolein, Benzaldehyde, Butyraldehyde,
Caproaldehyde, Cyclohexanol, Diethyl ketone, Mesitryl oxide, Methyl butyl
ketone, Valeraldehyde, Valeric aldehyde
ETHERS Amyl, Buryl, Celosolve, Dioxan, Ethylene oxide, Isopropyl, Propyl
ESTERS Buryl acetuate, Cellosolve acetate, Ethyl acetate, Ethyl acrylate,
Ethyl formate, Isopropyl acetate, Methyl acetate, Methyl acylate, Methyl
methacrylate
HALOGENS Bromine, Butyl chloride, Carbon tetrachioride,Chlorine,
Chlorobenzene, Chlorobutadiene, Chloroform, Chloro pierin, Chloro
nitropropane, Dibromoethane, Dichlorobenzene, Dichlorodifluoro methane,
Dichlorodifluoroethane, Dichloro ethyl ether, Dichloromethane,
Dichloromonofluoromethane, Dichloropropane, Dichlorotetrafluoroethane, Ethyl
bromlde, Ethyl chloride, Ethylene dichloride, Fluorotrichloromethane, Freon
(BP-20 C), Iodine, Iodoform, Methyl bromide, Methyl chloride, Methyl
chloroform, Methylene chloride, Monochlorobenzene, Paradichlorobenzene, Propyl
chloride, Tetrachloroethane, Tetrachloroethylene, Vinyl
chloride
AROMATIC HYDROCARBONS Benzene, Napthalene, Ninhydrin, Sryene Monomer,Toluene,
Toluidine, Xylene
SULPHUR COMPOUNDS Carbon disulphide, Dimethyl sulphate, Tetrahydrothiapene
NITROGEN COMPOUNDS Acetonitrile, Aniline, Diethyl aniline, Indole, Nicotine,
Nitrobenzene, Nitroethane, Nitroglycerine, Nitromethane, Nitrotoluene, Urea,
Uric acid
MISCELLANEOUS Cyanoacrylate, Adhesives, Carbon monoxide, Carbon dioxide*,
Deodorisers, Detergents, Ozone, Perfumes, Petrol, Resins
FOR (Aldehyde) ACI (Acid)
ETH (Ether) MIL (Military) SUL (Sulphur) AMM (Ammonia)
CYN (Cyanide) ACR (radioactive) ACM (Mercury) HEPA (Particulates) Custom
Acetaldehyde, Formaldehyde, Glutaraldehyde ALDEHYDES & KETONES Dipropyl
ketone, Methyl ethyl ketone HALOGENS Hydrogen bromide, Hydrogen chloride,
Hydrogen iodide SULPHUR COMPOUNDS Sulphur dioxide, Sulphur trioxide, Sulphuric
acid NITROGEN COMPOUNDS Nitric acid fumes, Nitrogen dioxide
Dieth (ethyl), Methyl Phosgene Ethyl mercaptan, Hydrogen sulphate, Mercaptans
– high MW Ammonia, Amines, Diethyl amine, Dimethyl amine, Ethyl amine,
Pyridine Hydrogen cyanide
Low level radioactive iodine and methyl iodine
Mercury
Particulate removal down to .31-1 State carbons required (maximum of 3). e.g.
For General Purpose and Formalin state: AST*-110 GP-FOR
Although Filtration units are contaminantsare produced,
suitable for most laboratory applications, it should be noted that they are such as acid digestion or evaporation of solvents to dryness. Nor are tney
not recommended for use advised where very highly
where extremely toxic substances
large are in
quantities use, or
of
unknown reactions are carried out.
- poorly adsorbed by all filters and therefore should only be used in small quantities. Their exhaust concentration will however be considerably Icwer than the input concentration due to retardation of the filter matrix (chromatography effect).
OPERATION AND MAINTENANCE MANUAL
CONTROLS
Sample Port
There is a manual sample port on the top left of the head unit. This is used
for testing the condition of the filter for saturation. The port is to be used
with a Gastec or Dräger test kit.
Standard Control Panel
The standard microprocessor controller monitors the airflow of the cabinet.
Audio and visual alarms alert the operator whenever any operating conditions
become unsafe.
Power On / Off Press the switch down to turn the unit on. A green indicator
lamp will indicate that power is connected to the unit.
CAL Calibration is described in details in the subsequent technical section of
this manual.
ALARM MUTE The audio alarm becomes activated after 5 minutes of the cabinet
being switched on. If the alarm does sound, the mute button can be pressed to
momentarily silence the alarm.
LOW AIRFLOW ALARM 0.40
Optional BFC200 Enhanced Controls
Green light will indicate proper filtration of the carbon filter. A Red light and audio alarm indicate main carbon filter is saturated and should be replaced.
Audio
Mute
Optional BFC250 Electronic Monitoring
The optional microprocessor controller monitors all cabinet safety parameters including
0.50
airflow, containment, and filter condition. Audio and visual alarms alert the operator whenever any operating conditions become unsafe.
power On,’01f
FILTER 0K
11611 r
Power On / Off Press the switch down to turn the unit on. A green indicator lamp will indicate that power is connected to the unit.
Fan (VAV Controlled) The Fan button turns the Fan on/off. The arrows allow the speed to be manually adjusted.
CAL Calibration is described in details in the subsequent technical section of this manual.
LIGHT Turns the main enclosure light On/Off.
ALARM MUTE The audio alarm becomes activated after 5 minutes of the cabinet
being switched on. If the alarm does sound, the mute button can be pressed to
momentarily silence the alarm.
MENU OPTION Press the Menu button for 5 seconds to reveal the following on-
screen options:Airflow Units, Filter ID, Alarm Reminder, Run Time (Reset),
Data. On-Screen instructions are then displayed.
OPERATION AND MAINTENANCE MANUAL
SAFE OPERATION & MONITORING
To start the unit, switch the power switch on. Please allow 5 minutes for the
airflow indicator to stabilize (on electronic model). Check the airflow and
filter saturation on a regular basis. The cabinet is designed to run
effectively with the lower front flap in the closed position. A heat source
(such as a Bunsen burner) should not be placed too close (< 150mm) to the side
or back panels. It is not recommended that an open flame or heat source be
positioned closer than 300mm from the bottom of the filter face. It is NOT
recommended that large quantities of solvents or acids should be boiled off in
any ductless fume cupboard. High concentrations of fumes entering the main
filter may temporarily reduce the filtration efficiency. For this reason any
major spillage within the fume cupboard should be cleared up immediately,
preferably using spillage absorption granules, rather than tissue paper which
may aggravate the evaporation of toxic fumes from the spillage area. Following
a major spillage, the main filters must be changed, as the heat of wetting may
reduce filter efficiency. After stabilization, the old filters can normally be
re-used, provided saturation has not been reached. a The electrical equipment
in the cabinet including light fittings and control equipment are in the head
unit on the clean side of the filter. The equipment should not be used in a
flammable room atmosphere. The purpose of monitoring is to detect when the
pre-filters or main filters cease to operate effectively. If the pre-filters
are blocked, the airflow will be reduced at the fume cupboard aperture. If the
main filters are saturated, they will cease to remove the fumes effectively.
The units are fitted with a low airflow alarm. Details for testing and
calibration are in the Appendix. You should carry out a manual check of filter
saturation once every three months, as described below. If an odour is
noticed, it is sensible to check the fume hood main filter. However, it must
be remembered that the sense of smell is very sensitive for some chemicals
(i.e. ammonia or hydrogen sulphide) and a slight smell does not mean that the
exhaust levels of chemical have approached the maximum acceptable
concentration. Manual monitoring should be carried out at least yearly to
check the integral systems on the unit. An anemometer should be used to check
the airflow (face velocity) at the working aperture, with the lower panel
down. Any suitable anemometer may be used, including hot wire, propeller or
vane anemometer. A minimum of five readings should be taken across the working
aperture. Note the result in a record book kept for this purpose. We advise
changing the pre-filter ifthe average airflow drops below 0.35m/sec. A visual
alarm will show when the airflow falls below 0.3m/sec The pre-filters will
normally need to be changed more frequently than the main filters. A blocked
HEPA filter (when fitted) is also indicated by reduced airflow which is not
restored after a pre-filter change.
ENVIRONMENTAL
Indoor use only Altitude up to 2000 meters Temperature 1 OOC to 400C
Maximum relative humidity 80% for temperatures up to 31 oc, decreasing
linearly to 50% at 400C. Main power supply voltage fluctuations not to exceed
± 10% of nominal.
OPERATION AND MAINTENANCE MANUAL
TECHNICAL
Specification
Cat No. Main Filter Weight (12kg) Safety Filter* Weight (5kg)
Prefilter** (qty) Airflow (m3/hr) Dimensions (WxDxH), mm Working Base Area, mm
Noise (dBA) Face Velocity (m3/sec) Electrical Supply Switches
Monitoring Lighting (watts) Fan Construction
FCIO FCI 0-01 1 x 12kg 1 x 5kg
1
246 750x700x1210 700×650
FC15 FC15-01 1 x12kg 1 x5kg
246 1 ooox700x1210 950×650
FC20 FC20-01 2x12kg 2x5kg
2
500 1250x700x1210 1200×650
FC25 FC25-01 2x12kg 2 x 5kg
2
500 1500x700x1210 1450×650
FC30 FC30-01 2x 12kg 2x5kg
2
500 1750x700x1210 1700×650
Single Phase, 230v, 50Hz Mains ON/OFF Low Airflow Indicator 2 x 15 watts Low Noise Centrifugal Epoxy coated mild steel frame and head unit. Clear Acrylic Panels. Hinged front screen. Unit supplied in 2 easy to assemble sections.
*Safety/Backup Filters are optional **Prefilters come supplied as standard with all units. Efficiencies superior to 99.6%
Manual Filter Saturation Detection
Select a suitable test chemical and matching sampling tube (Gastec or Dräger).
Examples include alcohols, toluene, trichloroethylene, or any suitable
chemical in routine use in the fume hood, provided it is well adsorbed and is
not dangerously toxic. Place 6 ml’s of chemical in a beaker on a hotplate.
Adjust the hotplate to boil off the chemical in about two minutes. This gives
a concentration of about 100 – 200 ppm to challenge the filter. Use 3 ml’s of
chemical for Model 10. For testing ACI filters (acid adsorbing), or multi-
filters with acid adsorbing layers, use sulphur dioxide gas (S02) at 2 bubbles
per second through water Using the sample tube, sample the outlet air stream
from the unit, following the instructions given with the Gastec tube (one pump
stroke for trichloroethylene, eight pump strokes for sulphur dioxide for
example). The reading should be below the TLV.
If a significant level of chemical is noted in the exhaust air, the main
filter should be changed.
ACCESSORIES
Optional accessories for this range of Fume Cupboards are listed below.
Accessory
FCIO
Box Section Support Stand. Ideal for wheelchair access. Lockable Casters. FCIO-B-Stand
Enclosed Support Stand with Storage facility.
FCI O-E-Stand
Electronic Filter Saturation Alarm. Electronic Airflow Alarm Electronic Monitoring System.
EFSA-200 EAA-AUTO EMS-250
Pack of 6 Prefilters*
STM-PRF
Tap (Cold Water), Outlet & Drip Cup**
SA-TODC
Double Switch Socket Outlet
SA-DSSO
Gas Tap**
SA-Gas
FC15 FCI 5-B-Stand FC15-E-Stand
FC20 FC20-B-Stand FC20-E-Stand
FC25 FC25-B-Stand FC25-E-Stand
FC30 FC30-B-Stand FC30-E-Stand
Prefilters are designed to remove particles from the air-stream before going through the Main Filter. They are required on all Fume Filtration Units, One prefilter comes supplied with this unit. *Where Gas or Water Taps are ordered then a separate installation fee will be incurred. Please supply an installation address to receive an installation quotation.
OPERATION AND MAINTENANCE MANUAL
FAULT FINDING
Electrical components are mounted behind the control panel. Access to the
electrical components is gained by removing the panel on top of the head,
undoing the retaining screws to gain access. Unit will not operate:-
Check that unit is plugged in and switched on Check fuse in mains supply.
Check fuses in electrical input socket.
Fan does not operate:Change speed controller is in the ON position. Fan Motors
are fitted with a thermal cut-out device, which will operate if the motor
temperature rise exceeds 95 degrees Overheating may be caused by filter
blockage. Low airflow alarm will activate.
MAINTENANCE
Regular maintenance will reduce the possibility of hazard to the operator and
prolong the life of the fume cupboard. Before attempting any inspection or
replacement of electrical components in the head assembly, always isolate the
fume hood from the main power supply. Items in the cabinet may be contaminated
depending on your application. Use Personal Protective Equipment (PPE).
The units are fitted with a low airflow alarm. With this model you should test
the alarm at least once a year. The filter condition should be monitored
regularly, i.e. every 3 months or more frequently if required.
Cleaning and Inspection
You should carry out the following procedures at six monthly intervals: Remove
the spillage tray (if feasible) and wash in dilute detergent solution. Wash
the interior surface of the cupboard with dilute detergent solution. Inspect
the cupboard frame and panels for mechanical damage. Inspect the hinged door
for corrosion and correct adjustment of friction hinges (when fitted). Check
all filters and alarms
The following checks should be made every 12 months: a Check the condition of
services to the hood, including water supply, drip cup, waste drain (where
fitted), gas supply (where fitted) and
electric cable and plug. The electrical wiring and insulation should be
inspected by a qualified electrician. Check all filters (and replace if
necessary) and check all alarms
Testing & Calibration
OPERATION AND MAINTENANCE MANUAL
Testing The Low Airflow Alarm
Ensure that new pre-filters are installed. Switch on the unit and the
indicator will display the airflow. Switch off unit. Block the pre-filters.
Switch on. An alarm will sound when the airflow display drops below 0.3m/s. If
a malfunction is indicated by steps 1 or 2, then a calibration procedure may
be required. Details are provided below.
Calibration Procedure
Power up unit. To set nominal run point, press and hold the mute key for 4
sec’s, when an audio beep is observed release the mute switch The Led display
will flash Using a calibrated anemometer set the airfow to the desired
velocity Using the up and down arrows set the display to read that reading
Press the mute switch once to store calibration point ( Led will stop flashing
) To set an alarm point, press and hold the mute switch then press and hold
the up arrow key for 4 seconds after audio beep release both switches Set the
display using the up and down arrows to the desired alarm point, in 0.05 m/s
increments Press the mute switch once to store the alarm point To display in
FPM remove LKI, to display in m/s fit LKI
The filter saturation is pre-set on the BFC200 and as such there is no
calibration required.
Calibration of BFC250 Requires the use of a calibrated anometer.
Hold in “CAL” whilst applying mains power to the cabinet. Release the “CAL”
button when two beeps are observed. After a second audio beep is observed the
message “SET FAN SPEED” will show on the LCD display. Allow the system to run
for a minimum of 15 minutes to stabilize and allow the gas sensor to reach its
running temperature. Using a calibrated hand held anomometer set the average
face velocity to the required setting 0.5m/sec by using the AV keys. u When
the required velocity has been set and allowed to stabilize press the “CAL”
button and the display will show airflow in m/sec. (0.00) Use the fan AV to
set the display to read the same as the measured VELOCITY (0.50) When the
desired reading has been achieved press the “CAL” button again to store the
setting. The system will now return to the main display screen. To enter the
main menu hold the menu option switch for more than 4 seconds and a sub-menu
will appear. AIRFLOW UNITS, SET FILTER D, ALARM SET TIME, ELAPSED TIME, VIEW
SYSTEM DATA, EXIT To view or change any of the parameters above select and
follow the on screen instructions The LCD back light contrast can be adjusted
by turning VRI on the display PCB
OPERATION AND MAINTENANCE MANUAL
INSTALLING & CHANGING OF FILTERS
A CAUTION BIOHAZARD- DIRTY FILTERS MAY BE CONTAMINATED
There is a risk that the internal parts of the hood may be contaminated with
whatever substance or particulates the filter is intended to remove. Extreme
caution is therefore urged before opening the filter housing for servicing.
Appropriate protection equipment should be used. Used filters should be placed
in impermeable bags for disposal in accordance with local regulations.
Electrostatic Filtrete Pre-filter
Pre-filter should be inspected regularly. It would be one of the first things
to inspect if the low air flow alarm sounds. A good indication is the colour,
pre-filter is generally white. Grey and dark discoloration is an indication
that it may soon become clogged. As the frame is lowered the pre-filter will
be released. The contaminated pre-filter should be disposed of as directed in
your contaminated waste removal procedure. The new pre-filter can be replaced
by holding it on the support frame while returning it to the closed position
and rotating the red cams.
Main Carbon/HEPA filter
Filters should be replaced when the concentration level of contaminants begin
to rise and before they reach their respective Threshold Limit Value. (TLV)
Monitoring and regular servicing will aid in the early detection of filter
failure. Use the Filter Key supplied to open the security locks on the front
panel of the head unit. Once the front panel has been removed, locate and
rotate the two red handles. If you are replacing a filter, lift the front
handle of the filter (to break the seal) and slide the filter out of the unit
into a waste bag. To insert the new filter, ensure that the black gasket is
facing downwards and care must be taken not to damage this important seal.
Then slide the filter in to the head using the wheels and guide runners.
Ensure that the filter is located against the rear stop before locking in to
position by rotating the red handles back in to the downward position. You can
then refit the front panel door, using the filter key provided.
The replacement filter should be fitted with care to avoid the gasket becoming
damaged which could result in creating gaps and possible fume escape routes.
Optional Back-up safety filter
Unscrew and remove the outlet cover which is located on the top of the main
head unit. If you are replacing a filter, lift out the old filter and place
into a waste bag for safe disposal. The new filter is simply located in to the
recess. The outlet cover is then replaced, ensuring that all screws are
tightened evenly to create a good seal.
BLUE LIVE BLACK NEUTRAL BROWN CAPACITOR GREEN EARTH
CAPACITOR
CENTRIFUGALFAN
PRESSURE SWITCH
POWER INLET 220V 50hZ
LIGHT UNIT
FINISH: MATERIAL:
000012
HOUR COUNTER-(OPTIONAL) LOW AIRFLOW
ON/OFF
NAME
DATE
TITLE:
BASIC WIRING DRG
DWG. No. BFC5-ELEC-01UK
Drawn
JH 26/05/2002
Checked
REV
DO NOT SCALE
SHEET 1 OF 1
11
LIGHT UNIT FINISH: MATERIAL:
BLUE LIVE BLACK NEUTRAL BROWN CAPACITOR GREEN EARTH
CAPACITOR
5,
POWER INLET 220V 50hZ
CENTRIFUGAL FAN
DISPLAY PCB
OO
0.55
AIRFLOW SENSOR
POWER SUPPLY
O
PL2
PLI
o
z
z
ON/OFF z
z
z
TITLE:
BASIC WIRING DRG
NAME
DATE
CLIENT:
Fumecare limited
DWG. No. FC-ELEC-OIUK
DO NOT
z
Drawn
JH
20/02/2012
SCALE
Checked
REV
SHEET 1 OF 1
MEMBRANE PANEL
CAPACITOR
BROWN CAPACITOR BLACK NEUTRAL .BLUE LIVE
FAN 1 CENTRIFUGALFAN
POWER INLET 220V 50hZ
TRANSFORMER
FINISH: MATERIAL:
DISPLAY PCB
J9
AIRFLOW SENSOR
GAS SENSOR
MAINS IN
FAN SUPPLY
ON/OFF
TITLE:
ELECTRONIC WIRING DRG
DWG. No. BFC-ELECTRONIC-ELEC-OIUK
Drawn
NAME
DATE
·JH 26/05/2002
DO NOT SCALE
Checked
REV
SHEET 1 OF 1
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>