HARVIA CX30C-U1, CX30C-U3 Xenio Combi Instruction Manual
- August 16, 2024
- HARVIA
Table of Contents
HARVIA XENIO COMBI
CX30C-U1/CX30C-U3
Instructions for Installation and
Use of Control Unit
ETL LISTED
CONFORMS TO UL STD 875
CERTIFIED TO
CANICSA STD E60335-2-53-05
CX30C-U1, CX30C-U3 Xenio Combi
These instructions for installation and use are intended for owners of saunas,
heaters and control units, persons in charge of managing saunas, heaters and
control units, and for electricians responsible for installing heaters and
control units. Once the control unit is installed, these instructions of
installation and use are handed over to the owner of the sauna, heater and
control unit, or to the person in charge of maintaining them. Congratulations
on making an excellent choice and choosing a Harvia control unit!
HARVIA XENIO CONTROL UNIT (CX30C-U1 / CX30C-U3)
Control unit’s purpose of use: The control unit is meant for controlling the
functions of an electric sauna heater and steamer, or a Combi heater, which is
their combined version. It is not to be used for any other purpose.
HARVIA XENIO
1.1. General
The Harvia Xenio control unit consists of a control panel, a power unit, a
temperature sensor and a humidity sensor. See Figure 1.
The control unit regulates the temperature and humidity in the sauna room
based on information given by the sensors. The temperature sensor and the
overheat protector are located in the sensor box. The temperature is sensed by
an NTC thermistor, and there is a resettable overheat protector (see section
3.5.).
The control unit can be used to delay the start of the heater and/or steamer
(timer delay). See Figure 3d.
1.2. Technical Data Control panel:
- Temperature adjustment range 104–194 ºF (40–90 °C).
- Humidity adjustment range: 20–80 rH
- Timer delay time adjustment range 0–12 h.
- Lighting control, max. power 100 W, 120 V 1 Ph
- Fan control, max. power 100 W, 120 V 1 Ph
- Dimensions: 3.4” x 1.0” x 4.4” (85 mm x 24 mm x 110 mm)
Power unit:
- Supply voltage
CX30C-U1: 240 V 1 Ph
CX30C-U3: 208 V 3 Ph
Max. load
CX30C-U1: 12,7 kW (Two supply wires. See
Figure 6b.) /240V 1 Ph
CX30C-U3: 10.8 kW/208V 3 Ph
Dimensions: 14.3” x 2.9” x 10.5”
(364 mm x 73 mm x 267 mm)
Sensor:
- The temperature sensor WX232 is equipped with a resettable overheat protector and a temperaturesensing NTC thermistor (22 kΩ/T=77ºF (25 °C)).
- The humidity sensor WX325 measures temperature and relative humidity.
- Dimensions: 2.0” x 2.9” x 1.1” (51 mm x73 mm x 27 mm)
- Weight 175 g with wire, ca 13’ (4 m)
1.3. Troubleshooting
If an error occurs, the power to the heater will be cut off and the control
panel will show an error message ”E (number)”, which helps troubleshooting the
cause of the error. Table 1.
Note! The overheat protector can be reset by user.
All other maintenance must be done by licensed professional maintenance
personnel. Control unit should not be opened by unlicensed personnel.
If the heater does not heat properly, check heater grade from settings menu.
See figure 3b.
| Description| Remedy/Solution
---|---|---
E1| Temperature sensor’s measuring circuit
broken.| Check the red and yellow wires to the temperature sensor and their
connections (see Figures 6a and 6b) for faulties.
E2| Temperature sensor’s measuring circuit
short-circuited.| Check the red and yellow wires to the temperature sensor and
their connections (see Figures 6a and 6b) for faulties.
E3| Overheat protector’s measuring circuit
broken.| Press the overheat protector’s reset button (see section 3.5.). Check
the blue and white wires to the temperature sensor and their connections (see
Figures 6a and 6b) for faulties.
E6| Humidity sensor’s temperature measuring
component failure.| Check the brown and blue wires to the humidity sensor and
their connections (see figures 6a and 6b) for faulties. Replace the sensor.
E7| Humidity sensor’s humidity measuring
component failure.| Check the brown and blue wires to the humidity sensor and
their connections (see figures 6a and 6b) for faulties. Replace the sensor.
E8| Humidity sensor’s humidity measuring circuit
broken.| Check the brown and blue wires to the humidity sensor and their
connections (see figures 6a and 6b) for faulties.
E9| Connection failure in the system.| Switch the power off from the main
switch (figure 1). Check the data cable, sensor cable/s and their connections.
Switch the power on.
| Water level low or steamer’s overheat
protector engaged. Water level warning light
blinks.| Add water (manual filling models) or check the water supply
(automatic filling models). Check the steamer’s overheat protector. See the
steamer’s or Combi heater’s manual for more instructions and safety
information.
Table 1. Error messages. Note! The overheat protector can be reset by user. All other maintenance must be done by licensed professional maintenance personnel. No user-serviceable parts inside.
STATUS MESSAGES
SAFE| Safety switch circuit is open| Remove the object from atop the safety
switch
---|---|---
rESt| Pause time active| –
rc on| Remote control activated| –
INSTRUCTIONS FOR USE
2.1. Using the Heater and the Steamer
WARNING! Before switching the heater on always check that there isn’t
anything on top of the heater or inside the given safety distance.
IMPORTANT ! Before switching the heater on for the first time, choose the
right heater grade from the settings menu (SET 3). See figure 3a. See the
right heater grade from the heater’s type label, under “control unit grade
settings”.
The right heater grade must be chosen to pair the control unit and the heater.
Right heater grade optimizes heater and ensures the best possible sauna
experience.
2.1.1. Heater and/or Steamer On
Heater and steamer are switched on and off independently (only with the Harvia
Xenio CX30C-U1 model).
| Start the heater by pressing the I/O button on the control panel.
---|---
| Start the steamer by pressing the steamer I/O button on the control panel.
When the heater and/or steamer starts, the display will show previously set
values for five seconds.
The shown values (temperature/humidity/on-time) differ depending on which
devices are started.
When the desired temperature and/or humidity has been reached in the sauna
room, the heating elements are automatically turned off. To maintain the
desired temperature and/or humidity, the control unit will automatically turn
the heating elements on and off in periods.
If the heater efficiency is suitable and the sauna has been built correctly,
the sauna takes no more than an hour to warm up.
2.1.2. Heater and/or Steamer Off
The heater and/or steamer turn off and the control unit switches to standby-
mode when
- the I/O button is pressed
- the on-time has elapsed or
- an error occurs.
If the water container runs empty, the steamer will be turned off, the water
level warning light will blink and the display will show the text “OFF”.
If the water level sensor develops a failure, the steamer’s overheat protector
will engage, the water level warning light will blink and the display will
show the text “OFF”.
NOTE! It is essential to check that the control unit has cut off power
from the heater after the on-time has elapsed, the dehumidification has ended
or the heater has been switched off manually.
2.1.3. Changing the Settings
The settings menu structure and changing the settings is shown in figure 3.
The programmed temperature and humidity values and all values of additional
settings are stored in memory and will also apply when the devices are
switched on next time.
Note! The humidity value determines the maximum temperature in the sauna. The
sum of temperature and humidity values can be 140 at maximum (temperature 60
°C + humidity 80 rH).
This is due to safety reasons.
If the steamer is activated and you try to set the temperature too high, the
humidity value will blink in the display.
2.2. Using Accessories
Lighting and ventilation can be started and shut down separately from their
own operating buttons.
2.2.1. Lighting
The lighting in the sauna room can be set up so that it can be controlled from
the control panel. (Max 100 W.)
Switch the lights on/off by pressing the button on the control panel.
2.2.2. Ventilation
If there is a fan installed in the sauna room, it can be connected to the
control unit and be controlled from the control panel.
Start/stop the fan by pressing the button on the control panel.
2.2.3. Safety switch
Safety switch refers to e.g. Harvia SFE, a safety device installed above or
integrated to the heater, preventing the heater from heating should any object
(e.g. towel, piece of clothing) drop or be placed on top of the heater and
cause a fire hazard.
The switch is connected to the control unit according to their manuals. See
also figures 6a and 6b in this manual.
2.2.4 Remote switch
To remotely control the heater’s power input, the control unit can be equipped
with an on/off remote switch (e.g. building automation). For more information,
see section 2.3.
2.3. Remote control
According to the product standard IEC/EN 60335 -2-53 regulating electrical
sauna heaters, a control unit can be used to remotely control the heater once
the heater is equipped with a safety switch.
Using with a safety switch: the heater can be turned on remotely, if the
safety switch circuit is closed. If the circuit is open, ”SAFE” is displayed
and the heater will not start.
Pause time: These features are limited by a pause time that prevents the
heater from turning on if it has been less than 6 hours since the heater was
last turned off. Trying to remotely turn the heater on during the pause time
period (6 hours), text ”rESt” is displayed. The heater can be remotely started
after the pause time has elapsed and ”rc” is displayed.
Memory for power failures: the control unit resumes operation, if the remote
switch has remained in ON position.
Preset time: if the control unit is on preset delay time, it cannot be
controlled with a remote switch.
After the preset delay has passed and the heater is turned on, it can be
turned off with a remote switch.
2.4. Control panel lock
| Press and hold the heater and light buttons for three seconds.
---|---
| CL- is shown on the display. Panel lock can be activated only in standby
mode.
Panel lock also prevents remote start.
|
Basic mode (heater and steamer on) The top row shows the sauna room
temperature. The bottom row shows the humidity level (or remaining on-time, if
the steamer is not activated).
| Press the MENU button to open the settings menu.
| Sauna room temperature (shown if the heater is activated)
The display shows the sauna room temperature setting. Temperature indicator
light blinks.
• Change the setting to the desired temperature with the – and + buttons.
• The sum of temperature and humidity can be 140 at maximum (see chapter
2.1.3.)
| Press the MENU button to access the next setting.
| Sauna room humidity level (shown if the steamer is activated)
The display shows the sauna room humidity setting. Humidity indicator light
blinks.
• Change the setting to the desired humidity with the – and + buttons.
• The sum of temperature and humidity can be 140 at maximum (see chapter
2.1.3.)
| Press the MENU button to access the next setting.
| Remaining on-time
Press the – and + buttons to adjust the remaining on-time.
Example: the heater will be on for 40 minutes.
| Set the timer delay in remaining on time mode:
• Press the + button to set the on time to maximum (1:00).
• Press the + button to enter the timer delay mode. The temperature indicator
light switches off.
Timer delay symbol blinks on the screen.
• Select the desired delay time using the – and + buttons. The time changes in
10 minute steps. Press and hold the button to make the time change faster. The
adjustment range is from 10 minutes to 12 hours. Example: the heater will
start after 10 minutes.
| Press the MENU button to exit.
|
Basic mode (timer delay running, heater and steamer off)
The decrease of remaining delay time is shown until zero appears, after which
the activated devices (heater and/or steamer) are switched on. The bottom row
shows the remaining delay time.
Figure 3. Settings menu structure
ADDITIONAL SETTINGS
| Control unit standby
---|---
| Open the settings menu by simultaneously pressing the locations of the
buttons –, MENU and +. Press for 5 seconds.
The buttons do not glow when the control unit is in standby mode.
| See
sections 2.2.3. and 2.3. for further information.
Setting the remote use and safety switch Set the remote use (rc) ON/OFF with –
and + buttons.
Confirm the selection with the MENU button.
Set the safety switch (SAFE) ON/OFF with – and + buttons.
Confirm the selection with the MENU button.
When the cries ON, choose is the remote use for steamer (CTRL Heat) or steamer
and heater (CTRL CO).
Confirm the selection with the MENU button.
When cries ON the menu will show setting for pause time (rest).
Enable or disable the pause time feature with buttons + and -. Pause time must
be enabled, if the control unit is remotely started by an automated schedule
(e.g. a weekly timer).
| Press the menu button till SET2 appears in
the screen. Change the temperature unit
with the – and + buttons. The options are
Fahrenheit (FAHR)* and Celsius (CELS).
| Press the MENU button to accept the set.
Press the MENU button again and the next
set will appear or the control unit switches
to standby mode.
Figure 3a. Settings menu structure, additional settings
| Heater grade
Heater grade can be changed with the and + buttons. See the right grade from
the heater’s type label, under “control unit grade settings”.
---|---
| Press the MENU button to accept the set. Press the MENU button again and the
next set will appear.
| Sauna dehumidifying interval The sauna dehumidifying interval turns the fan
on (If installed / accessory) and dries out the sauna room to keep it in a
good condition. The sauna dehumidifying interval can be turned ON or OFF*).
The interval will begin when the devices are switched off from the I/O buttons
or when the set on-time runs out. The lenght of the
interval is 45 minutes. When the time runs out, the fan turns off
automatically. The
interval can also be stopped manually at any time by pressing the I/O button.
| Press the MENU button to accept the set. Press the MENU button again and the
next set will appear or the control unit switches to standby mode.
Figure 3b. Settings menu structure, additional settings
INSTRUCTIONS FOR INSTALLATION
The electrical connections of the control unit may only be made by a licensed
professional electrician and in accordance with the current regulations.
When the installation of the control unit is complete, the person in charge of
the installation must pass on to the user the Instructions for Installation
and Use that come with the control unit and must give the user the necessary
training for using the heater and the control unit.
- Thread the data cable through the hole in the back cover.
- Fasten the back cover to a wall with screws.
- Push the data cable to the connector.
- Press the front cover into the back cover.
3.1. Installing the Control Panel
The control panel is splashproof and has a low operating voltage. The panel
can be installed in the dressing room, or in the living quarters. If the panel
is installed in the sauna room, it must be at least 1,5 ft (50 cm) away from
the heater and at a maximum height of one metre from the floor. Figure 4.
Conductor tubing (ø 1”3/16, 30 mm) inside the wall structure allows you to
thread the data cable hidden within the wall – otherwise the installation will
have to be on the wall surface. We recommend you to install the control panel
embedded in to the wall and far away from possible splashes.
3.2. Installing the Power Unit
Install the power unit to a wall outside the sauna room, in a dry place with
an ambient temperature more than 32 ºF (0 ºC). See Figure 5 for instructions
on how to open the power unit cover and how to fix the unit to the wall.
Note! Do not embed the control unit into the wall, since this may cause
excessive heating of the internal components of the unit and lead to damage.
See Figure 5.
3.2.1. Electrical Connections
The heater and control unit may only be connected to the electrical network in
accordance with the current regulations by a licensed professional
electrician.
Figures 6a and 6b shows the electrical connections of the power units. For
more detailed installation instructions see The Instructions for Installation
and Use of the selected heater model.
3.2.2. Instructions for Installation
The power unit of CX30C-U1 and CX30C-U3 is controlled by control panel
Xenio.
- Control panel is connected to power unit via data cable.
- Only one control panel can be connected to the power unit.
Temperature sensor:
- WX232 is needed to operate CX30C-U1 and CX30C-U3. See section 3.3. for correct temperature sensor placement.
Humidity sensor:
-
WX325 is needed to operate CX30C-U1 and CX30C-U3. See section 3.4. for correct humidity sensor placement.
Two relay outputs (120 V 1Ph): -
For driving a fan (max. 100 W) and lighting (max. 100 W).
Breakers on the electronics card (if a breaker has blown, see section 3.2.3.):
- F1 = 2,5 A
- F2 = 40 mA
Breakers on the factory wirings (if a breaker has blown, see section 3.2.3.):
- F3 = 10 A
Technical specifications:
- Max. length of data cable: 80’ (25 m)
- Max. heater power raitings (Table 2)
| CX30C-U1 240 V 1Ph| CX30C-U3 208 V 3Ph
---|---|---
Max power / (kW)| Min wire size/(AWG)| Max power / (kW)| Min wire size(AWG)
1 Group| n/a| n/a| 10,8| 10
2 Group| 12,7| 10| n/a| n/a
Table 2. Max. heater power ratings.
3.2.3. Power Unit Breaker Faults
Replace a blown breaker by a new one with the same resistance. The placement
of the breakers in the power unit is shown in Figures 6a and 6b.
- If the breaker F2 for the electronic unit has blown, there is likely a fault in the power unit and it might need to be replaced. Service is required.
- If the breaker F1 has blown, there is a problem with lighting or fan. Check the wiring and functioning of lighting and fan.
- If the breaker F3 has blown, there is a problem with the heater’s overheat protector circuit. In the heater, check the safety contactor circuit, overheat protector and their wiring.
NOTE! Only a qualified licensed electrician should replace the electronic card or breaker of the control unit, by following the necessary precautions!
3.3. Installing the Temperature Sensor
Floor-mounted heaters (see Figure 7)
-
The temperature sensor is mounted on the wall above the heater, along the vertical centre line running parallel to the sides of the heater, at a distance of 3 15/16” (100 mm) from the ceiling.
Wall-mounted heaters (see Figure 8) -
The temperature sensor is wall-mounted above the heater, along the vertical centre line running parallel to the sides of the heater, at a distance of 3 15/16” (100 mm) from the ceiling.
NOTE! If the temperature sensor comes with the heater, you MUST install it as shown in the manual of the heater. The wire of the sensor can be extended with similar type of wire. Not exceeding 80’ (25m).
Do not install the temperature sensor closer than 3’-3 3/8” (1000 mm) to an air vent. The air flow near an air vent cools down the sensor, which gives inaccurate temperature readings to the control unit. As a result, the heater might overheat. See Figure 9.
3.4. Installing the Humidity Sensor
Fasten the humidity sensor on the wall as far from the heater as possible and
at a distance of 20–28’’ (500–700 mm) from the ceiling. See figures 7 and 8.
3.5. Resetting the Overheat Protector
The sensor box contains a temperature sensor and an overheat protector. An NTC
thermistor senses the temperature, and the resettable overheat protector cuts
off the heater power in a case of malfunction, after which the protector can
be reset. See Figure 10.
Note! The reason for the going off must be determined before the button
is pressed.
SPARE PARTS
Use only parts approved by the manufacturer!
1 | Control panel | WX387 |
---|---|---|
2 | Data cable 5 m | WX311 |
3 | Data cable extension 10 m (accessory) | WX313 |
4 | Temperature sensor | WX232 |
5 | Humidity sensor | WX325 |
6 | Circuit board | WX357 |
7 | Contactor 30 A (CX30C-U1, CX30C-U3) | ZSK-778 |
MAINTENANCE INSTRUCTIONS
- All service operations must be done by professional licensed maintenance personnel. Control unit should NOT be opened by unlicensed personel.
- Wipe dust and dirt from the power unit and the control panel with a damp cloth. DO NOT use running water!
- Prevent any water to go inside the power unit at anytime.
- The control panel is splashproof.
GUARANTEE
The manufacturer gives a one year guarantee for this control unit. The
guarantee starts from the date of purchase and includes all the parts of the
control unit.
The guarantee covers faults from the manufacture and material only. The
guarantee includes a supply of spare parts by the manufacturer or importer
after the faulty parts have been returned. Replacing any parts in the control
unit does not extend the original guarantee period of one year.
The guarantee does not cover defects caused by normal wear and tear, defects
caused by improper installation, poor maintenance or failure to follow the
manufacturer’s instructions for installation, use and care, or alterations
made to the product.
The guarantee is void if the control unit is used improperly. The guarantee
does not cover delivery costs of the faulty part or repair costs on the field.
If the control unit is returned to the manufacturer or importer within five
years from the date of purchase, the importer will provide free repair work,
but may charge for spare parts if the oneyear guarantee has expired.
The guarantee is void if installation and wiring has not been carried out by
licensed electrician or authorized and licensed service representative.
Please not that the installers signature is needed below.
The guarantee is void if the information below is not filled out and returned
to the manufacturer or importer within 15 days of purchase. The guarantee
applies only to the first installation of the product and to the original
purchaser.
Harvia control unit model……………..
Model number…………….
Date of purchase………….
Original purchaser…………………..
Address………………..
Purchased from……………..
Date of electrical installation……………..
Signature of the installer…………..
License number…………………….
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>