Appion AV760 Digital Vacuum Gauge Instruction Manual
- August 13, 2024
- Appion
Table of Contents
- Introduction
- Safety
- Display
- General Functions
- Using The AV760
- Appion Central™ Bluetooth Operation
- Appion Central™ App
- General Maintenance & Care
- Advanced Cleaning
- Specifications
- Regulatory Information
- Warranty Information
- QR Code Index
- Customer Support
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Appion AV760 Digital Vacuum Gauge
Introduction
TO REDUCE THE RISK OF INJURY OR PRODUCT DAMAGE, READ OPERATION MANUAL PRIOR TO OPERATING PRODUCT.
PATENT INFO AT APPIONTOOLS.COM – ©2024 APPION INC. ALL RIGHTS RESERVED
AC/R system operating efficiency depends on proper evacuation. Proper
evacuation depends on a reliable vacuum gauge capable of monitoring the entire
evacuation process.
The AV760 accurately displays measurements from atmosphere (760,000 microns)
all the way to deep vacuum (10 microns), so you can be sure your system is
clean, dry, and tight.
Safety
-
Do not connect to systems under pressure.
-
Do not use leaky or damaged batteries.
-
Use only specified batteries and cleaning agents.
-
Battery operating temperatures may vary by manufacturer.
The batteries supplied with this unit are for storage and operating between 32°F – 104°F (0°- 40°C) -
Dispose of batteries in accordance with any applicable local laws and regulations.
-
Do not dispose of the product or battery in a fire or heat above 100°C.
Do not insert any objects into the sensor ports of the sensor housing.
Doing so may permanently damage the sensors.
Display
- Battery Indicator
- Auto Power Off
- Bluetooth® Indicator
- Measurement
- Units
General Functions
Button Configuration
- Quick PRESS a button for the “Press” function.
- HOLD a button for 2 seconds for the “Hold” function.
- Quick press BOTH buttons for the “Both” function.
Using The AV760
CAUTION : Do NOT connect the AV760 to systems under high pressure. While the AV760 is designed to withstand accidental exposure to positive pressures, continued exposure may cause permanent damage.
- Using the 45° Swivel Vacuum Connector (included), connect the AV760 to an available service port furthest from the vacuum pump.
- Hand-tighten the connections to ensure a tight connection. Never tool tighten a knurled fitting.
- Press the Power button to turn on the AV760. A countdown will display while the AV760 starts up and performs self testing.
- Press and hold the units button for 2 seconds to cycle the displayed units (optional).
Tip : Connect to the side access port on a vacuum-rated Valve Core
Removal Tool with the Vacuum Connector. Make sure the depressor side is
attached to the Valve Core Removal Tool.
Tip : Make sure the AV760 is vertical, with the fitting pointed downward.
This will help minimize contamination from any oil that may be pulled out of
the system during evacuation.
Tip : Add the use of a secondary Valve Core Removal Tool or a Core
Control Tool to isolate the gauge prior to introducing positive pressure.
Appion Central™ Bluetooth Operation
Note : Bluetooth communication requires a compatible device running the Appion Central™ App. Development of the Appion Central™ App is ongoing, and any information presented in this manual about the Appion Central™ App may not be up to date. Please visit AppionTools.com or your device’s App Store for the latest Appion Central™ App and additional information.
- With the AV760 powered on, press and hold the Bluetooth button until the Bluetooth symbol appears on the AV760 screen.
- In the Appion Central™ App, navigate to “My Devices” and connect to the AV760 as shown.
- If the connection is lost due to exceeding the Bluetooth range, or due to loss of power, repeat Step 1, then “Reconnect” the AV760 through the Appion Central ™ App interface.
Note : Bluetooth range may vary due to obstructions or interference. The
Appion Central™ App will indicate when communication is lost.
Note : The AV760 will continue to operate normally even if Bluetooth
communication is lost.
Appion Central™ App
Scan to download app and access user guide.
General Maintenance & Care
The AV760 is a precision instrument that must be maintained to ensure proper function. The knurled fitting can be removed to enable easy inspection of the sensor housing components if you suspect the AV760 sensors are dirty and no longer reading correctly.
-
Remove the knurled fitting with o-ring and the oil catch filter from the sensor housing.
Do NOT remove the protective screen covering the sensors. -
Inspect the knurled fitting and o-ring for damage or excessive wear. Replace the o-ring if damage is suspected. If the knurled fitting is damaged, contact Appion directly.
-
Inspect the fitting tip for debris buildup and ensure the ball check valve within the knurled fitting moves freely and is clear of obstructions by shaking the fitting and l listening for a rattling noise. If the fitting tip has debris buildup or the ball check valve is not moving freely, use quick-dry electronics cleaner to clean the fitting.
-
Inspect the oil catch filter for oil by blotting it on a clean paper towel. If any oil remnants appear, discard the oil catch filter and replace with a new one.
-
Apply a small amount of vacuum grease to the knurled fitting o-ring and hand-tighten the fitting onto the s sensor housing. NEVER tool-tighten a knurled fitting.
-
Connect the AV760 to a vacuum pump. Then, run the pump until the gauge display reads 100 microns or less.
-
If necessary, perform an isolation test to ensure the fittings and sensor housing are not leaking.
Advanced Cleaning
Please follow the General Maintenance and Care procedures outlined previously BEFORE attempting the advanced cleaning procedures.
Do not touch or insert any objects into the sensor ports. Doing so may permanently damage the sensors.
- Remove the knurled fitting with o-ring, then the oil catch filter from the sensor housing.
- Pour quick dry electronics cleaner into the sensor housing. Cover the sensor housing to trap the cleaner inside. Next, gently shake the gauge for 5-10 seconds.
- Dump the remaining cleaner from the sensor housing and let the gauge sit right-side-up for 15 minutes.
- Apply a small amount of vacuum grease to the o-ring on the knurled fitting. Then, reinstall a new oil catch filter and hand-tighten the knurled fitting onto the sensor housing. Never tool tighten a knurled fitting.
- Connect the AV760 to a vacuum pump, and run the pump until the gauge reads 100 microns or less.
- If necessary, perform an isolation test to ensure the fitting and sensor housing are not leaking.
AV760 Cleaning Video
Scan to view video
Specifications
Range:
760,000 microns to 1 micron
Accuracy:
±5% of reading + 10 microns (1 to 5k)
±5% of reading (5k to AM)
High Resolution:
1 micron (1 to 142,999)
50 micron (15,000 to ATM)
Low Resolution:
1 micron (1 to 14,999)
50 micron (2k to 5k), 250 (5k to 15k)
1k (15 to ATM)
Units:
microns, mTorr, kPa, psia, mBar, in/Hg
Power:
(3) AA Batteries
Battery Life:
120 Hours
*Continuous usage with Bluetooth off
Weight:
6.9 oz. (196 g) *without batteries
Gauge Dimensions:
4.65 x 2.75 x 1.2 in. (118 x 70 x 30 mm)
Fitting:
1/4 in. Male Flare
Maximum Overpressure:
400 psi
Operating Temperature:
0° to 140° F (-17.8° to 60° C)
Regulatory Information
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
- This device may not cause harmful interference
- This device must accept any interference received, including the interference that may cause undesired operation.
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class
B digital device, pursuant to Part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a
residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment
does cause harmful interference to radio or television reception, which may be
determined by turning the equipment off and on, the user is encouraged to try
to connect the interference by one of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Radiation Exposure Statement
This equipment complies with FCC RF radiation exposure limits set forth for an uncontrolled environment. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.
FCC Caution
To assure continued compliance, any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.
Industry Canada Radio Equipment
This device complies with Industry Canada license exempt RSS-247 standard.
Operation is subject to the following two conditions:
(1) this device may not cause interference, and (2) this device must accept
any interference that may cause undesired operation of the device.
Warranty Information
Appion Inc. (Hereinafter Appion) warrants that this equipment will, under
normal and anticipated use, be free from defects in materials and workmanship
for a period of one (i) year from the date of purchase by Purchaser from an
Appion-authorized distributor.
The complete Manufacturer’s Limited Warranty is available online at
AppionTools.com.
All warranty services must receive Appion Factory Authorization and an RGA
number prior to any action. Contact your local Appion authorized distributor
to obtain the RGA number and shipping instructions. To help us provide the
best service, be sure to have the following information available:
- Serial number of the equipment
- Purchase date of the defective unit
- A detailed description of the problem
Appion offers technical troubleshooting customer support for the lifetime of every product. Regardless of your warranty status, you can always contact us for assistance. Our website includes additional technical information that can help you experience the fullest potential of our products, making your job quicker and easier.
Scan for Product Registration
QR Code Index
Appion Central™ App Download
AV760 Cleaning Video
Product Registration
All AV760 Videos
Customer Support
Appion Inc.
2800 South Tejon St.
Englewood, CO 80ii0 USA
Tel: i-303-937-1580
Fax: i-303-937-1599
AppionTools.com
Sales@AppionTools.com
Support@AppionTools.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>