Appion AV760 Digital Vacuum Gauge Instruction Manual

August 13, 2024
Appion

Appion AV760 Digital Vacuum Gauge

Introduction

TO REDUCE THE RISK OF INJURY OR PRODUCT DAMAGE, READ OPERATION MANUAL PRIOR TO OPERATING PRODUCT.

PATENT INFO AT APPIONTOOLS.COM – ©2024 APPION INC. ALL RIGHTS RESERVED

AC/R system operating efficiency depends on proper evacuation. Proper evacuation depends on a reliable vacuum gauge capable of monitoring the entire evacuation process.
The AV760 accurately displays measurements from atmosphere (760,000 microns) all the way to deep vacuum (10 microns), so you can be sure your system is clean, dry, and tight.

Safety

  • Do not connect to systems under pressure.

  • Do not use leaky or damaged batteries.

  • Use only specified batteries and cleaning agents.

  • Battery operating temperatures may vary by manufacturer.
    The batteries supplied with this unit are for storage and operating between 32°F – 104°F (0°- 40°C)

  • Dispose of batteries in accordance with any applicable local laws and regulations.

  • Do not dispose of the product or battery in a fire or heat above 100°C.

Do not insert any objects into the sensor ports of the sensor housing.
Doing so may permanently damage the sensors.

Display

  1. Battery Indicator
  2. Auto Power Off
  3. Bluetooth® Indicator
  4. Measurement
  5. Units

General Functions

Button Configuration

  1. Quick PRESS a button for the “Press” function.
  2. HOLD a button for 2 seconds for the “Hold” function.
  3. Quick press BOTH buttons for the “Both” function.

Using The AV760

CAUTION : Do NOT connect the AV760 to systems under high pressure. While the AV760 is designed to withstand accidental exposure to positive pressures, continued exposure may cause permanent damage.

  1. Using the 45° Swivel Vacuum Connector (included), connect the AV760 to an available service port furthest from the vacuum pump.
  2. Hand-tighten the connections to ensure a tight connection. Never tool tighten a knurled fitting.
  3. Press the Power button to turn on the AV760. A countdown will display while the AV760 starts up and performs self testing.
  4. Press and hold the units button for 2 seconds to cycle the displayed units (optional).

Tip : Connect to the side access port on a vacuum-rated Valve Core Removal Tool with the Vacuum Connector. Make sure the depressor side is attached to the Valve Core Removal Tool.
Tip : Make sure the AV760 is vertical, with the fitting pointed downward. This will help minimize contamination from any oil that may be pulled out of the system during evacuation.
Tip : Add the use of a secondary Valve Core Removal Tool or a Core Control Tool to isolate the gauge prior to introducing positive pressure.

Appion Central™ Bluetooth Operation

Note : Bluetooth communication requires a compatible device running the Appion Central™ App. Development of the Appion Central™ App is ongoing, and any information presented in this manual about the Appion Central™ App may not be up to date. Please visit AppionTools.com or your device’s App Store for the latest Appion Central™ App and additional information.

  1. With the AV760 powered on, press and hold the Bluetooth button until the Bluetooth symbol appears on the AV760 screen.
  2. In the Appion Central™ App, navigate to “My Devices” and connect to the AV760 as shown.
  3. If the connection is lost due to exceeding the Bluetooth range, or due to loss of power, repeat Step 1, then “Reconnect” the AV760 through the Appion Central ™ App interface.

Note : Bluetooth range may vary due to obstructions or interference. The Appion Central™ App will indicate when communication is lost.
Note : The AV760 will continue to operate normally even if Bluetooth communication is lost.

Appion Central™ App

Scan to download app and access user guide.


General Maintenance & Care

The AV760 is a precision instrument that must be maintained to ensure proper function. The knurled fitting can be removed to enable easy inspection of the sensor housing components if you suspect the AV760 sensors are dirty and no longer reading correctly.

  1. Remove the knurled fitting with o-ring and the oil catch filter from the sensor housing.
    Do NOT remove the protective screen covering the sensors.

  2. Inspect the knurled fitting and o-ring for damage or excessive wear. Replace the o-ring if damage is suspected. If the knurled fitting is damaged, contact Appion directly.

  3. Inspect the fitting tip for debris buildup and ensure the ball check valve within the knurled fitting moves freely and is clear of obstructions by shaking the fitting and l listening for a rattling noise. If the fitting tip has debris buildup or the ball check valve is not moving freely, use quick-dry electronics cleaner to clean the fitting.

  4. Inspect the oil catch filter for oil by blotting it on a clean paper towel. If any oil remnants appear, discard the oil catch filter and replace with a new one.

  5. Apply a small amount of vacuum grease to the knurled fitting o-ring and hand-tighten the fitting onto the s sensor housing. NEVER tool-tighten a knurled fitting.

  6. Connect the AV760 to a vacuum pump. Then, run the pump until the gauge display reads 100 microns or less.

  7. If necessary, perform an isolation test to ensure the fittings and sensor housing are not leaking.

Advanced Cleaning

Please follow the General Maintenance and Care procedures outlined previously BEFORE attempting the advanced cleaning procedures.

Do not touch or insert any objects into the sensor ports. Doing so may permanently damage the sensors.

  1. Remove the knurled fitting with o-ring, then the oil catch filter from the sensor housing.
  2. Pour quick dry electronics cleaner into the sensor housing. Cover the sensor housing to trap the cleaner inside. Next, gently shake the gauge for 5-10 seconds.
  3. Dump the remaining cleaner from the sensor housing and let the gauge sit right-side-up for 15 minutes.
  4. Apply a small amount of vacuum grease to the o-ring on the knurled fitting. Then, reinstall a new oil catch filter and hand-tighten the knurled fitting onto the sensor housing. Never tool tighten a knurled fitting.
  5. Connect the AV760 to a vacuum pump, and run the pump until the gauge reads 100 microns or less.
  6. If necessary, perform an isolation test to ensure the fitting and sensor housing are not leaking.

AV760 Cleaning Video

Scan to view video

Specifications

Range:
760,000 microns to 1 micron

Accuracy:
±5% of reading + 10 microns (1 to 5k)
±5% of reading (5k to AM)

High Resolution:
1 micron (1 to 142,999)
50 micron (15,000 to ATM)

Low Resolution:
1 micron (1 to 14,999)
50 micron (2k to 5k), 250 (5k to 15k)
1k (15 to ATM)

Units:
microns, mTorr, kPa, psia, mBar, in/Hg

Power:
(3) AA Batteries

Battery Life:
120 Hours
*Continuous usage with Bluetooth off

Weight:
6.9 oz. (196 g) *without batteries

Gauge Dimensions:
4.65 x 2.75 x 1.2 in. (118 x 70 x 30 mm)

Fitting:
1/4 in. Male Flare

Maximum Overpressure:
400 psi

Operating Temperature:
0° to 140° F (-17.8° to 60° C)

Regulatory Information

This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:

  1. This device may not cause harmful interference
  2. This device must accept any interference received, including the interference that may cause undesired operation.

Federal Communication Commission Interference Statement

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which may be determined by turning the equipment off and on, the user is encouraged to try to connect the interference by one of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

FCC Radiation Exposure Statement

This equipment complies with FCC RF radiation exposure limits set forth for an uncontrolled environment. This transmitter must not be co-located or operating in conjunction with any other antenna or transmitter.

FCC Caution

To assure continued compliance, any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.

Industry Canada Radio Equipment

This device complies with Industry Canada license exempt RSS-247 standard. Operation is subject to the following two conditions:
(1) this device may not cause interference, and (2) this device must accept any interference that may cause undesired operation of the device.

Warranty Information

Appion Inc. (Hereinafter Appion) warrants that this equipment will, under normal and anticipated use, be free from defects in materials and workmanship for a period of one (i) year from the date of purchase by Purchaser from an Appion-authorized distributor.
The complete Manufacturer’s Limited Warranty is available online at AppionTools.com.
All warranty services must receive Appion Factory Authorization and an RGA number prior to any action. Contact your local Appion authorized distributor to obtain the RGA number and shipping instructions. To help us provide the best service, be sure to have the following information available:

  • Serial number of the equipment
  • Purchase date of the defective unit
  • A detailed description of the problem

Appion offers technical troubleshooting customer support for the lifetime of every product. Regardless of your warranty status, you can always contact us for assistance. Our website includes additional technical information that can help you experience the fullest potential of our products, making your job quicker and easier.

Scan for Product Registration

QR Code Index

Appion Central™ App Download

AV760 Cleaning Video

Product Registration

All AV760 Videos

Customer Support

Appion Inc.
2800 South Tejon St.
Englewood, CO 80ii0 USA
Tel: i-303-937-1580
Fax: i-303-937-1599
AppionTools.com
Sales@AppionTools.com
Support@AppionTools.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals