APPION G5Twin Refrigerant Recovery Machine User Manual
- June 13, 2024
- Appion
Table of Contents
- G5Twin Refrigerant Recovery Machine
- Warnings and Safety Information
- Getting Started
- Machine Usage
- Additional Machine Usage
- Helpful Hints
- Care and Maintenance
- Troubleshooting Guide
- Machine Specifications
- Manufacturer’s Limited Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
FOR REFRIGERANT RECOVERY
G5Twin Refrigerant Recovery Machine
www.AppionTools.com OPERATION MANUAL
⚠ DANGER
Explosion Hazard. Do NOT use with hydrocarbons. See page 4.
⚠ WARNING
TO REDUCE THE RISK OF INJURY OR PRODUCT DAMAGE, READ OPERATION MANUAL PRIOR
TO OPERATING PRODUCT.
COPYRIGHT © 2016 – APPION INC. – ALL RIGHTS RESERVED APPION™ AND G5TWIN™ ARE
TRADEMARKS OF APPION INC.
Welcome to the G5Twin
Thank you for your purchase of the Appion G5Twin Refrigerant Recovery Machine.
This machine was designed to deliver fast, reliable recovery of Class III, IV
and V refrigerants. Use of this machine for any other purpose is done at your
own risk.
Faster refrigerant recovery requires proper training, preparation, and
operation. Working with refrigerants under pressure also presents numerous
safety risks and hazards.
To safely reach the full potential of this machine, read this manual and all
safety material before use.
Warnings and Safety Information
IMPORTANT – READ THIS MANUAL BEFORE OPERATION
This Operation Manual contains important information for protecting your
safety and preventing equipment problems. Unsafe operation could lead to
serious injury or death to you or others. For best results and safe operation,
read this entire manual before operation. Keep this manual in a safe,
accessible location during operation.
OPERATOR TRAINING, CERTIFICATION AND RESPONSIBILITY
⚠ NOTICE
This machine compresses and pumps liquid and vapor refrigerants at high
pressures, which can create dangerous conditions. This equipment is for use by
technicians that are professionally trained and certified in the safe handling
of refrigerant, and safe refrigerant recovery techniques.
⚠ NOTICE
Keep away from children at all times. Do not leave unattended.
⚠ NOTICE
Never defeat the safety features of this product. Do not operate with missing,
broken, or unauthorized parts. Remove broken or altered equipment from service
immediately.
PERSONAL PROTECTIVE EQUIPMENT AND MSDS
⚠ WARNING
When working with refrigerants, always use the appropriate Personal
Protective Equipment (PPE), including eye and hand protection. Read all
Material Safety Data Sheets (MSDS) for any compounds that you are likely to
encounter during operation. Failure to do so could lead to injury or death.
HAZARD: RISK OF EXPLOSION OR FIRE
⚠ DANGER Use of this equipment may pose certain explosion and fire
hazards.
WHAT CAN HAPPEN | HOW TO PREVENT IT |
---|
It is possible for electrical components within the unit to spark. If
electrical sparks come into contact with flammable vapors, they may ignite,
causing fire or explosion.| Use only in well ventilated areas. In enclosed
areas, mechanical ventilation should provide at least four air changes per
hour.
Flammable/combustible gases and air may become unknowingly ingested through
leaks in hoses,
gaskets, connections or leaking seals, leading to compression of these gases.
Air and hydrocarbons,
if pumped to a tank, create an explosive mixture that random static
electricity could ignite.| Do not use in the vicinity of spilled or open
containers of gasoline, propane, butane, acetylene, or other flammable gases.
Do not use near open sewer lines which may be emitting sewer gases.
Flammable substances may ignite or explode when compressed in certain
situations.| Do not use this machine to pump hydrocarbons, including blends
containing butane, isobutane, or
propane. Hydrocarbons are flammable substances and may ignite or explode when
compressed in
certain situations.
Improper use of extensions cords may result in overheating or fire in the cord
or machine.| Use only 12AWG or 10AWG extension cords:
– Up to 25 Feet: 12/3 UL/CSA cord
– Up to 100 Feet: 10/3 UL/CSA cord
HAZARD: RISK TO BREATHING (ASPHYXIATION)
⚠ DANGER Air and refrigerants pumped by this machine may pose certain
breathing hazards.
WHAT CAN HAPPEN | HOW TO PREVENT IT |
---|---|
Refrigerant vapors may be harmful or toxic when inhaled. | Use only in well |
ventilated areas. In enclosed areas, mechanical ventilation should provide at
least four air changes per hour.
Compressed air from this machine may contain carbon monoxide or toxic
refrigerant vapors.| Air from this machine should never be used to supply air
for human consumption
HAZARD: RISK FROM MOVING COMPONENTS
⚠ WARNING This machine is equipped with a fan and motor rotating at high
speeds.
WHAT CAN HAPPEN | HOW TO PREVENT IT |
---|
Debris or other objects may enter the machine housing through the air vents,
causing machine
damage.| Be sure the area around the machine is free and clear of debris
before operating the machine.
Physical damage may occur to body parts, tools, or other objects if inserted
into the air vents of the
machine while it is running.| Always unplug the machine and ensure that the
fan and motor are not rotating before opening the case or inserting any object
into the machine.
Damage may occur to the machine and surrounding objects if the machine is
dropped while running.| Use caution while moving this equipment, especially
during operation.
HAZARD: RISK FROM UNATTENDED OPERATION
⚠ CAUTION Factors affecting operation may change during the recovery
process.
WHAT CAN HAPPEN | HOW TO PREVENT IT |
---|
As refrigerant recovery is a dynamic process, and often performed in open
spaces, factors affecting the operation of the unit may change.| Always remain
in attendance with the machine while it is operating.
Remain observant to changes in environment, refrigerant pressure and
refrigerant temperature.
HAZARD: RISK FROM NOISE
⚠ CAUTION Moving components, high airflow, and pumping refrigerant can
all cause noise.
WHAT CAN HAPPEN | HOW TO PREVENT IT |
---|
Under some conditions and duration of use, noise from the unit may contribute to hearing loss.| Always wear certified safety equipment, including ANSI or equivalent hearing protection.
Refrigerant Storage Container Safety
⚠ WARNING
Use only DOT CFR 49 or UL-approved storage containers for recovered
refrigerant.
WHAT CAN HAPPEN | HOW TO PREVENT IT |
---|
Refrigerant storage containers may vent or explode when the working pressure
of the container is exceeded.| Refrigerant storage containers are designed
with different working pressures. Verify that the rating of the storage
cylinder is appropriate for the refrigerant being recovered.
For R-410a, 4BA400 and 4BW400 are appropriate ratings for refrigerant storage
containers.
“80% Shut Off Switches,” also known as Tank Overfill Sensors and Overfill
Protection devices, may fail to prevent overfilling of the storage cylinder,
leading to venting or explosion.
These sensors only cut power to the recovery machine, and do not stop the flow
of refrigerant,
which may continue due to a siphon, or due to temperature-induced migration.|
Do not rely on these switches to prevent overfilling.
Only a refrigerant scale can provide an active and accurate measurement of the
amount of refrigerant in the storage container. Do not rely on these switches
to stop the flow of refrigerant into the container. Only the valves on the
recovery machine and on the cylinder can stop the flow of refrigerant into the
container.
Refrigerant expands when heated (Diagram 1), and storage containers may vent
or explode when filled over 80% capacity.| A refrigerant scale must be used to
monitor the amount of refrigerant in the storage container.
Be sure to close the valves on the storage container when it has reached 80%
capacity.
Diagram 1
Overfilled storage containers may explode due to liquid refrigerant expanding
when heated.
Transportation of refrigerant storage cylinders more than 80% full is a DOT
violation.
Getting Started
⚠ CAUTION
Always use a grounded outlet that meets minimum voltage supply requirements
for industrial equipment. Do not use with portable power generators.
⚠ CAUTION
Always open valves slowly for safety, and to check for leaks.
⚠ CAUTION
The G5Twin is equipped with a 550psi (38.6 kg/cm²) pressure shut off switch to
protect the machine from damage. This does not prevent overfilling of the
storage container. (See Page 6)
ACCESSORY EQUIPMENT
Additional equipment may be used to connect the G5Twin to the system you are
recovering refrigerant from.
Verify operational details and safety information from the manufacturers of
other equipment before use.
-
⚠ CAUTION A leaking hose may cause venting of refrigerant, and may introduce atmospheric air or other contaminants into the recovered refrigerant. Examine the gaskets on each hose to ensure they are intact, checking for any damage or wear that may lead to leaks.
-
Use the shortest length of 3/8”-diameter hoses possible on every connection. IMPORTANT: Do not use “quick disconnect” or “auto-shutoff” hoses for refrigerant recovery, as this can bring the recovery to a halt.
-
Use Valve Core Removal Tools with a ball valve (such as Appion MegaFlow VCT) to remove all “Schrader”type access valve cores from the System access fittings. This prevents restrictions that would otherwise limit the performance of the G5Twin and/or cause overheating of the recovery cylinder. See Page 15 for more information.
-
The recovery cylinder should have extra capacity beyond the amount you intend to recover. For maximum recovery speeds, use a recovery cylinder that is already evacuated (500 microns or better).
Note: new recovery cylinders may not be sufficiently evacuated – always verify before use. -
Check your refrigerant scale with a known weight to ensure that is operating correctly. A malfunctioning scale may not alert you to the amount of refrigerant in the storage container.
-
Examine your external manifold gauges for proper valve operation and calibration of the gauges. Contact the manifold gauge manufacturer for instructions in this process.
-
Use a new inline filter dryer as shown when pumping dirty refrigerant. Replace the filter dryer after each use. If the filter has exceeded its capacity, this may affect the performance of the machine.
-
Use a sight glass to verify liquid flow. This can also be useful for troubleshooting purposes. Make sure that the sight glass is in good condition and does not leak.
CHECKING YOUR RECOVERY EQUIPMENT
Before connecting or operating the G5Twin, verify that the G5Twin will be able
to operate properly:
- Check that the debris screen at the inlet fitting is clean before starting every job. This screen prevents damage to the machine that may get past the inline filter. When pumping dirty/used refrigerant, this screen may quickly clog and slow the process when used without an inline filter.
- Verify the power source provides adequate voltage at the machine while it is running (within 10% of the rated power). When using an extension cord, follow the sizing guidelines on Page 4.
Review the information for Care and Maintenance on Page 17 regularly to ensure optimal performance.
Machine Usage
PREPARING FOR OPERATION
Every recovery procedure starts with the same five basics:
- Remove any access valve cores from the AC/R System access fittings with a Valve Core Removal Tool;
- Remove any core depressors from the hose fittings. Do not use “quick disconnect” or “auto-shutoff” hose connections for refrigerant recovery, as this can bring the recovery to a halt. Use only ball valves for low-loss.
- Use the shortest length of 3/8”-diameter hoses possible on every connection. Even with 1/4” fittings, the larger hose diameter can deliver better performance during recovery.
- Purge the hoses of non-condensables as you connect the hoses, as needed, using best practices to minimize any refrigerant release (aka “de minimis”). Excess non-condensables can cause tank overheating, and may contaminate recovered refrigerant.
- Connect the G5Twin to a grounded power source for the proper voltage of the machine (115v/230v). If using an extension cord, follow the cord sizing guidelines on Page 4.
✪ For additional refrigerant recovery tips, see pages 14-17.
⚠ CAUTION
To reduce the risk of injury or product damage, read this entire operating
manual, with particular emphasis on the Safety and Preparation sections (Page
4-8), prior to operating the G5Twin.
STANDARD RECOVERY PROCEDURE
-
Setup the G5Twin as shown in Diagram 4 (below). Make sure that all connections are tight.
A. Connect the AC/R System Liquid Port to the Manifold high side.
B. Connect the AC/R System Vapor Port to the Manifold low side.
C. Connect the Manifold Center port to the G5Twin input port.
D. Connect the G5Twin output port to the Vapor Port on the Recovery Cylinder.
Diagram 4
Recover into the Vapor Port of the Recovery Cylinder for faster recovery.
OPTIONAL: To improve tank cooling, start with the recovery cylinder upside down, and flip the tank right-side up near the end of the vapor recovery. -
Close both valves on the Manifold Gauge Set.
-
Open both valves on the G5Twin, open the Valve Core Removal Tool ball valves at the system (if equipped), and open the Recovery Cylinder Vapor Port.
Make sure to completely open the Recovery Cylinder valve to prevent “output restrictions” (See Tip #1). -
Turn on the G5Twin. The compressor and fan should start.
-
Slowly open the Manifold High Side (liquid) valve.
Removing liquid first will keep recovery time to a minimum, and improve cooling properties of the recovery cylinder.
NOTE: Overheating or slow recovery speeds may be caused by “input restrictions” (See Tip #2). -
When all the liquid has been removed, completely open the Manifold Low Side (vapor) valve. Both sides should now be fully open to maximize vapor flow.
-
Continue to run the G5Twin until the EPA-required vacuum is achieved.
-
Close both valves on the Manifold Gauge set.
-
Turn off the G5Twin, then close the output valve on the G5Twin.
-
Close the G5Twin input valve, close the valves on the Recovery Cylinder, and disconnect the hoses.
⚠ CAUTION
To reduce the risk of injury or product damage, read this entire operating
manual, with particular emphasis on the Safety and Preparation sections (Page
4-8), prior to operating the G5Twin.
HIGH-SPEED DIRECT LIQUID PROCEDURE
This recovery method allows for the fastest possible “direct liquid” recovery
speeds. To maximize recovery rates, be sure to follow all of the Preparing for
Operation information on Page 8.
-
Setup the G5Twin as shown in Diagram 5 (below). Make sure that all connections are tight.
A. Connect the AC/R System Liquid Port to the G5Twin input port.
B. Connect the G5Twin output port to the Liquid Port on the Recovery Cylinder.
C. Connect the Cylinder Vapor Port to the AC/R System Vapor Port.
D. Connect a Compound Pressure Gauge to the AC/R System Vapor Port using a T-fitting or a side-port on a valve core removal tool.
Diagram 5
This recovery method allows for the fastest possible “direct liquid” recovery speeds, although the “vapor” phase of recovery may take a little longer. -
Close the Valve Core Removal Tool (VCRT) ball valves at both of the AC/R System Liquid and Vapor ports.
-
Open both valves on the G5Twin, and open both valves on the Recovery Cylinder.
Make sure to completely open the Recovery Cylinder valves to prevent “output restrictions” (See Tip #1). -
Turn on the G5Twin. The compressor and fan should start.
-
Begin liquid recovery by opening both of the VCRT ball valves at the AC/R System access ports.
-
When all the liquid has been removed: close the Recovery Cylinder Vapor Valve.
-
Continue to run the G5Twin until the EPA-required vacuum is achieved.
-
Close both of the VCRT ball valves.
-
Turn off the G5Twin, then close the valves on the G5Twin.
-
Close the valves on the Recovery Cylinder and disconnect the hoses.
⚠ CAUTION
To reduce the risk of injury or product damage, read this entire operating
manual, with particular emphasis on the Safety and Preparation sections (Page
4-8), prior to operating the G5Twin.
STANDARD RECOVERY WITH INLINE COOLING
This ALTERNATIVE procedure allows the user to switch between the Standard
Recovery Procedure and the High-Speed Direct Liquid Procedure during recovery,
leading to reduced temperatures and back-pressure from the recovery cylinder.
This can be particularly useful with R410A and/or high ambient conditions.
-
Setup the G5Twin as shown in Diagram 6 (below). Make sure that all connections are tight.
A. Connect the AC/R System Liquid Port to the Manifold high side.
B. Connect the AC/R System Vapor Port to the Manifold low side.
C. Connect the Manifold Center port to the G5Twin input port.
D. Connect the G5Twin output port to the Liquid Port on the Recovery Cylinder.
E. Connect the Cylinder Vapor Port to the AC/R System Vapor Port, using a T-fitting or a side-port on a valve core removal tool.
Diagram 6
This method allows the user to switch between Standard Recovery and High-Speed Direct Liquid, which can cool the recovery cylinder as needed. -
Close both valves on the Manifold Gauge Set. Open both valves on the G5Twin, open both valves on the Recovery Cylinder, and open the VCRT ball valves at the AC/R System access ports (if equipped).
Make sure to completely open the Recovery Cylinder valves to prevent “output restrictions” (See Tip #1). -
Turn on the G5Twin. The compressor and fan should start.
-
Begin liquid recovery by opening the Manifold High Side (liquid).
-
When all the liquid has been removed: close the Recovery Cylinder Vapor Valve, open the Manifold Low Side (vapor) valve, and the hose ball valve at the system vapor port (if equipped).
-
Continue to run the G5Twin until the EPA-required vacuum is achieved.
-
Close both valves on the Manifold Gauge set.
-
Turn off the G5Twin, then close the valves on the G5Twin.
-
Close the valves on the Recovery Cylinder and VCRT ball valves (if equipped), and disconnect the hoses.
⚠ CAUTION
To reduce the risk of injury or product damage, read this entire operating
manual, with particular emphasis on the Safety and Preparation sections (Page
4-8), prior to operating the G5Twin.
PUSH/PULL RECOVERY PROCEDURE
The Push/Pull method induces a siphon from the system directly into the
recovery cylinder using the G5Twin.
This method is useful for recovering large amounts of liquid from a system.
This will only work on large systems where the liquid can be accessed easily.
Do not attempt this on systems that contain less than 15 lbs.
of liquid refrigerant (unless there is a receiver tank), or it may not work
correctly.
⚠ CAUTION
Once the siphon starts, it can continue to fill the tank even when the machine
has been powered off. To avoid overfilling, you must close all valves on the
tank and system when finished.
-
Setup the G5Twin as shown in Diagram 7 (below). Make sure that all connections are tight.
A. Connect the AC/R System Vapor Port to the G5Twin output port.
B. Connect the AC/R System Liquid Port to the Recovery Cylinder Liquid port.
C. Connect the G5Twin input port to the Recovery Cylinder Vapor port.
Diagram 7
The Push/Pull recovery method induces a siphon to move large amounts of liquid directly from the system to the recovery cylinder. -
Slowly open both valves on the G5Twin.
-
Turn on the G5Twin. The compressor and fan should start.
-
Slowly open the valves on the tank and system. The liquid should now begin to be pulled out of the system. You can monitor the progress with an inline sight glass.
Make sure to completely open the Recovery Cylinder valves to prevent “output restrictions” (See Tip #1). -
When all the liquid has been siphoned off, turn off the G5Twin and close all the valves.
-
You can now proceed to remove the remaining refrigerant vapor using the Standard Recovery Procedure (Page 9).
Additional Machine Usage
PURGING NON-CONDENSABLES FROM RECOVERY CYLINDERS
In the event that the Recovery Cylinder pressure is higher than expected, or
if the recovery process seems slower than usual, use an external gauge (not
the gauge on the G5Twin) and a Refrigerant Pressure/Temperature chart to check
for the presence of noncondensable gases in the cylinder.
You can bleed/purge non-condensables into another cylinder following this
procedure:
- The Recovery Cylinder must remain undisturbed for at least 24 hours for the non-condensables to rise to the top of the cylinder.
- Through a Manifold Gauge Set, connect the Recovery Cylinder Vapor Port to the Vapor Port of a second recovery cylinder.
- Consult a Refrigerant Pressure/Temperature chart, and check the temperature of the Recovery Cylinder to determine what the pressure should be.
- While the pressure is higher than the pressure on the chart, slowly open the Vapor Port to bleed off excess pressure until it is about 5 psi (0.35 Kg/cm²) above the pressure listed on the chart.
- Close the valves and let the cylinder stand still for 10 minutes. Repeat if necessary.
CHANGING BETWEEN REFRIGERANT TYPES
Appion refrigerant recovery machines are unique in that there is no
refrigerant directly introduced into the compressor crankcase. This allows the
G5Twin to easily and efficiently clear out refrigerant at the end of the
recovery process. However, as with all recovery machines, trace refrigerant
vapors may remain and should be cleared out when switching between different
types of refrigerant.
When you are changing between refrigerant types, any refrigerant remaining in
the recovery machine should be drawn into a deeply evacuated recovery cylinder
before switching. Then, to prevent any crosscontamination, it is recommended
that a vacuum pump be connected to the output port of the G5Twin (keep the
Input Valve closed and the Output Valve open), and run the vacuum pump to
completely evacuate the machine of any trace refrigerant vapors.
STORING THE MACHINE BETWEEN USES
When storing the machine between recovery jobs, trace refrigerant vapors can
continue to wear on the internal components of the machine. If the machine is
fully sealed (closed valves or port covers), storing the machine in a hot
truck can cause the trace vapors to expand and wear on the components further.
To minimize wear during storage, leave both valves on the G5Twin open. You can
use port caps/covers to protect the machine from dirt, but make sure they do
not have an airtight seal.
Helpful Hints
PLAN AHEAD
In just a few years, refrigerant recovery has come a long way. At first
glance, it’s simply the process of taking refrigerant out of a system and
putting it into a storage tank. However, this simple process can rapidly
become difficult and time consuming if a few things are overlooked. What
follows are some notes and guidelines that we have learned over the years that
can help you save time and make the job easier.
The first thing you need to do is determine the quantity and type of
refrigerant that is being used in the system you are working on. Use a tank
that is DOT approved for the high pressures that are present with R410a. If
the system is a burnout, you will need to use a special tank marked as
containing burnout and other unidentified gases and you must use extra
filtration before recovery. This extra filtration is to protect your equipment
from corrosion caused by acids that may be present.
If the gas in the system is fairly clean or new, then you should use a clean,
new tank. If the refrigerant is going to be reclaimed, or you are going to put
the refrigerant back into the system when you are done servicing it, then you
should use a tank with the same type of refrigerant in it. One note of
caution: If you use many different gases and you only own a single tank,
you’re asking for trouble with the Environmental Protection Agency (EPA). You
should own at least one tank for every type of refrigerant that you will
service, and a spare tank for unknown gases and burned out systems.
TIP #1 Output Restrictions: Loud Recovery & High Pressure Shutoff
It is a common belief that recovering liquid refrigerant will always be
“noisy.” However, the “hammering” or “knocking” sound associated with
recovering liquid can often be caused by output restrictions, which is any
flow restriction between the recovery machine and the interior of the recovery
cylinder. If the G5Twin is excessively noisy during liquid recovery, check
for, and remove, any output restrictions.
Another common symptom of output restrictions is the recovery machine
intermittently shutting off on high pressure, but resets on its own after the
output pressure quickly drops in a short time. If the G5Twin shuts off on high
pressure but the output pressure quickly drops, check for, and remove, any
output restrictions.
Prolonged pumping against output restrictions not only slows the recovery
process, but the increased load can accelerate the wear of your recovery
equipment. This wear can be seen with damaged output gauges, electrical
component failure, and slower performance on the bench test (see Page 18).
Remove Output Restrictions to Maximize Recovery Performance:
To improve recovery performance, and prolong the life of your equipment, take
the time to remove these typical output restrictions before you start:
- Remove core depressors from all of the hose fittings (they block up to 50% of the flow) – See Tip #4
- DO NOT USE refrigerant charging hoses with “quick disconnect” or “auto-shutoff” fittings
- Make sure that the recovery cylinder valve is completely opened
- Discard of used/worn hoses with deteriorating inner linings
TIP #2 Input Restrictions: Slow Recovery & Hot Recovery Cylinders
For the fastest recovery speeds, it is necessary to pump out the liquid first.
Using the Direct Connection procedures in this manual, on a typical system,
you should expect the “liquid recovery” stage to move the bulk of the entire
system charge as liquid – this means it should go very quickly for most of the
recovery process (in most larger systems, this could be over 90% of the
refrigerant charge).
However, if you observe hot recovery cylinders, or very slow recovery after only moving a few pounds of refrigerant, then you likely have input restrictions. You may further confirm input restrictions by checking for frost or condensation at each hose/port connection between the AC/R System and the recovery machine (e.g., the system access port, or the inlet fitting to the recovery machine). Input restrictions can cause liquid refrigerant to get trapped behind the restriction, causing recovery to be slower than the expected vapor rate (see Diagram 8), and unexpectedly adding heat to the recovery cylinder.
Diagram 8
What Happens With Input Restrictions:
Input restrictions will greatly slow down refrigerant recovery by preventing
the full “liquid flow” from reaching the recovery machine. The pressure drop
caused by the recovery machine triggers a liquid-to-vapor expansion at the
point of restriction, which drops the temperature of the liquid refrigerant at
the restriction. As the point of restriction continues to get colder, the
vapor pressure drops, slowing the vapor flow.
Pretty soon, the recovery machine is only receiving a reduced flow of vapor
that is now picking up ambient heat and adding it to the heat of compression.
All of this heat is sent along to the recovery cylinder, quickly raising the
recovery cylinder temperature.
Efforts to cool a cylinder are more effective when there is liquid
refrigerant, as the liquid aids in transferring heat through the cylinder
walls to the “bucket of ice” or cooled airflow. However, if contents of the
tank are mostly vapor, efforts to cool the tank (e.g., airflow, ice) could be
less effective than expected.
Remove Input Restrictions to Maximize Recovery Performance:
For the fastest recovery times, take the time to address these typical input
restrictions before you start:
- Remove core depressors from all of the hose fittings (they block up to 50% of the flow) – See Tip #4
- DO NOT USE refrigerant charging hoses with “quick disconnect” or “auto-shutoff” fittings
- Remove “Schrader”-type access valves using a Valve Core Removal Tool – See Tip #4
- Discard of used/worn hoses with deteriorating inner linings
With a full flow of liquid refrigerant, the G5Twin will quickly fill the recovery cylinder with cool liquid. Once the liquid recovery is complete, the remaining vapor will be pumped into a cooler tank, resulting in lower final temperatures and faster overall recovery speeds.
TIP #3 External Cooling Accessories Between Recovery Unit & Cylinder
Recovering large amounts of vapor (especially on a hot day) can increase the
temperature of a recovery cylinder, and the resulting increased back-pressure
can further slow the vapor recovery process. In situations like these, cooling
the recovery cylinder and/or using an External Cooling Accessory (ECA) in a
bucket of ice water can cool off the tank and speed up the recovery process.
For maximum recovery speeds, pre-cool the recovery cylinder (and/or the ECA)
by placing it in a bucket of ice water at least 30 minutes prior to beginning
the recovery process. The longer the cylinder is cooled, the better.
Diagram 9
How to Make an External Cooling Accessory:
Making an ECA uses the same tools as you would use when installing an AC/R
system. You will need 10 feet of 5/16” (OD) copper tubing, and two (2) 1/4” FL
Service Valves. Connect the service valves to each end of the copper tubing
with solder using industry practices. Then, coil the tubing around a pipe or
round object of at least 3” inches in diameter, and maintaining about 1/2”
spacing between each coil. Leave about 1 foot of the copper tubing straight,
and bend it upwards, so that both service ports are pointing in the same
direction, and both extend above the “coiled area,” as in Diagram 9. Prior to
using the ECA, verify pressure and vacuum tightness using the same methods as
on an AC/R system.
Diagram 10
How to Use an External Cooling Accessory:
The ECA is about 50% submerged in water before adding ice. Add ice on top,
until the ECA is submerged below the ice level by at least 3 inches. This will
help keep the ice water cooled as the heated vapor travels through the ECA.
Connect the ECA and hoses equipped with ball valves as shown in Diagram 10.
Submerge the ECA in a bucket of ice water (as described above). Close the ball
valve on Hose “C”, and open the ball valves on Hose “A” and Hose “B”, as shown
in Diagram 10. Proceed with the Standard Recovery Procedure as described on
Page 9, starting from Step 2, and continuing through Step 9 (substitute the
Recovery Cylinder Liquid Port in Step 3).
Diagram 11
WARNING: After recovery is complete, the ECA and Hoses A, B and C will
contain high pressure refrigerant.
To recover the residual refrigerant from the ECA:
- Close the G5Twin output valve, Recovery Cylinder liquid valve, and the ball valve at the end of Hose “A”.
- Disconnect the hoses from the G5Twin input/output.
- Connect the hoses as shown in Diagram 11.
- Open the G5Twin output valve, Recovery Cylinder vapor valve, and all 3 ball valves.
- Repeat Steps 7-10 from Page 9 to finish the recovery.
TIP #4 Remove Restrictions at the Valves, Fittings & Hoses
AC/R Systems are generally not designed specifically for the recovery process,
and this is reflected in the wide use of 1/4” access valves with
“Schrader”-type valve cores. These valve cores block about 90% of the flow
through the access port, and require the use of core depressors in the hose
fittings, which in turn block about 50% of the flow. When left in during the
recovery process, both of these items can significantly restrict the flow of
refrigerant, making the recovery process take up to six times longer to
complete.
Use a Valve Core Removal Tool to remove these valve cores while leaving the system seal intact, as shown in Diagram 12. These tools are available from your local wholesale distributor. Core depressors in the ends of the hoses should be removed as well. See Page 20 for ordering info.
Use ball valves and open-ended hoses. Another common restriction is found in
charging hoses that have “Quick Disconnect, Low Loss” fittings. These fittings
use a restrictive internal check valve to limit venting when disconnecting the
hose from the system. While these may be useful in charging setups, they
restrict the flow of refrigerant, and are not ideal for use in refrigerant
recovery.
Use the shortest length of 3/8” hose for fast recovery. The length and
diameter of the hose can also impact the recovery speed. Even when recovering
through 1/4” fittings, the larger diameter hose will allow for greater vapor
flow, and greatly reduce the time needed for the recovery process. See Page 20
for ordering info.
Imagine trying to drink water through a 1/4-in., 3-ft. long straw. Now pinch
the end closed a little bit, and you get an idea of the kind of work your
recovery machine is trying to accomplish. Using larger hoses without any
restrictions will make it easier on your machine and allow you to finish the
job much quicker.
TIP #5 Extension Cords and Low Voltage
Recovery machines will work best when the voltage at the machine (while it is
running) is about 100-105% of the rated power (115v-122v or 230v-240v). A
lower voltage can cause difficulty in starting against high pressures. If you
have low voltage source power, you may need to relieve the back pressure on
the unit to allow it to start.
Check that the voltage coming from the source outlet is adequate. Please note
that the circuit could have many other items on it e.g. light fixtures,
appliances, or other motors. Also, recovery equipment is used primarily in the
hot summer months when supply voltage can be at the lowest point of the year
due to the demand from A/CR equipment operating at peak conditions. These
factors may cause a lower voltage and reduced performance.
Likewise, long and thin extension cords starve the motor of necessary voltage
and can cause very dangerous overheating of the motor and extension cord. A
hot, sunny rooftop can also reduce the ampacity of the extension cord. Refer
to the extension cord sizing guidelines on Page 4.
Care and Maintenance
INLINE FILTER DRYERS
Use a new inline filter dryer on the input side of the G5Twin when pumping
dirty refrigerant. Refrigerant acts like a solvent and can collect dirt and
debris when it is pumped out of a system. Failure to use an inline filter
dryer can cause damage to the compressor, and will void the warranty on your
machine.
While specifications may vary, most Size 032 filters will not be effective for
more than 50 lbs. (22.6 Kg) of refrigerant. Also, once refrigerant has been
introduced into the inline filter, it may continue to wear down, and may not
have the same effective capacity if used across multiple jobs. Change the
inline filter dryer regularly, and consult the filter manufacturer for
expected capacity. See Page 20 for ordering info.
SCREEN CLEANING AND REPLACEMENT
The G5Twin is equipped with a debris screen inside the input fitting. This is
the last line of defense for the recovery machine against any debris that
might make it past an inline filter. For best results it is recommended to
clean it before each use. If it becomes worn, replace it immediately.
- Unscrew Filter Cap from Input Port.
- Remove screen from Filter Cap.
- Clean screen and Filter Cap thoroughly. If thescreen is worn or damaged, replace it.
- Check the O-ring that seals the Filter Cap to the Input Port. If it is dry, apply a drop of refrigeration oil. If it is damaged, replace it.
- Place clean screen into Filter Cap and screw itback onto the Input port.
PLANNED MAINTENANCE
You can use any standard refrigeration oil (mineral is ideal) to scavenge out
dirt and debris, and recondition the seals. Run the machine with no hoses
connected and both valves open. Using a 1/4” port cap, fill it with
refrigeration oil and hold it up against the input port, allowing the G5Twin
to suck it in. Place a towel below the output port to catch any oil spray.
This is very helpful after recovery of burnout systems, and as regular
maintenance depending on the frequency of use.
1-MINUTE BENCH TEST
The following test can be performed to verify that the G5Twin is operating
normally:
- Disconnect any hoses from the machine.
- With the input valve open and the output valve closed (Diagram 14), turn the machine on.
3. Time how long it takes for the unit to pressure up and cut off. The unit should pressure up and cut off at approximately 550 psi (38.6 Kg/cm²) in under 1 minute. Otherwise, the unit may be in need of maintenance or repair.
Troubleshooting Guide
⚠ WARNING
Read all safety information found in this manual and in the Material Safety
Data Sheets (MSDS) for any refrigerants used with this machine prior to
performing any service on this machine.
SYMPTOM: Machine will not start, no sound when power switch turned ‘On’
CAUSE | SOLUTION |
---|---|
Power cord not plugged in, or no power in outlet | Check power cord, try |
different outlet
Machine in High Pressure Shutoff| See symptom below
Motor in Thermal Overload| Allow motor to cool down
SYMPTOM: Machine tries to start, makes humming/buzzing sound
CAUSE | SOLUTION |
---|---|
Low voltage at source outlet | Try different power source outlet |
Voltage drop in extension cord | See Extension Cord sizing guidelines on Page 4 |
Too much back pressure on compressor | Try starting the machine with the Input |
Valve closed to reduce back pressure on compressor
SYMPTOM: Machine pumps into high pressure shut off
CAUSE | SOLUTION |
---|---|
Valve on machine or recovery cylinder not fully opened | Check that both valves |
on machine are fully open (pointing upward);
Check that the valve on the recovery cylinder is fully opened
Restriction in output hose
– See Tip # 1 on Page 14| Check hoses for any blockage;
Remove any core depressors
SYMPTOM: Pumps liquid slowly
CAUSE | SOLUTION |
---|
Flow restrictions on input side of machine
– See Tip # 2 on Page 15| Use 3/8” hoses;
Remove “Schrader” valve cores and core depressors
Input Valve on machine not fully open| Check that the blue Input Valve on
machine is fully open (pointing upward)
Trapped liquid in system
– See Tip # 2 on Page 15| Cycle system compressor for a few seconds to move
trapped liquid to another area;
Check for condensation on system, and apply heat as needed;
Check for condensation at hose fittings, and apply heat as needed
Machine Specifications
MODEL # G5TWIN SPECIFICATIONS
USA Dimensions & Power:
LENGTH | 13.75 in |
---|---|
HEIGHT | 10.3 in |
WIDTH | 9.4 in |
WEIGHT | 24 lbs |
POWER | 115 VAC, 60 Hz, 10 Amps |
International Dimensions & Power:
LENGTH | 349 mm |
---|---|
HEIGHT | 262 mm |
WIDTH | 239 mm |
WEIGHT | 11 kgs |
POWER | 230 VAC, 50/60 Hz, 5 Amps |
G5Twin UL Certified Test Results
Per ARI 740-98 – as of March 2016
| PUSH PULL RATE| DIRECT LIQUID RATE| VAPOR
RATE| FINAL RECOVERY VACUUM| REFRIGERANT LOSS,
WEIGHT %| RESIDUAL TRAPPED REFRIGERANT| HIGH TEMP VAPOR
RECOVERY RATE 104F (40C)
---|---|---|---|---|---|---|---
| kg/min| lb/min| kg/min| lb/min| kg/min|
lb/min| kPa| inHg| | | kg/min| lb/min
R134a| 7.20| 15.87| 4.60| 10.14| 0.21| 0.46| 50.53| 15.00| <3| 0|
n/a| n/a
R22| 7.54| 16.62| 4.70| 10.36| 0.28| 0.62| 50.53| 15.00| <3| 0| 0.28|
0.62
R407C| 7.99| 17.61| 5.41| 11.93| 0.25| 0.55| 50.53| 15.00| <3| 0| n/a|
n/a
R410A| 9.30| 20.50| 7.80| 17.20| 0.25| 0.55| 50.53| 15.00| <3| 0| n/a|
n/a
- Uses high speed direct liquid mode; 8.16lb (3.7kg) with standard recovery.
With external cooling accessory (see Page 16); R22 is 0.60lb (0.27kg) with standard recovery; R134a is 0.44 lbs (0.20 kgs) with standard recovery.
REPAIR KIT ORDERING INFORMATION**
PART NO. | DESCRIPTION (CONTENTS) |
---|---|
KTF612 | Inlet Filter Fitting (1/4” Flare Fitting, 4-Pack of Inlet Filter |
Screens, o-ring)
KTGA00| 2-Pack of 0-700 PSI Gauges
KTG515| Piston Seal Kit (seals, seal o-rings, slide rings)
KTG520| Compressor Repair Kit (valve plates, valves, springs, seals, seal
o-rings, slide rings)
KTG535| Front Ball Valve Seal Replacement Kit (input/output seals, o-rings)
RELATED ACCESSORY ORDERING INFORMATION
PART NO. | DESCRIPTION (CONTENTS) |
---|---|
KTF032 | Filter Dryer Kit (Size 032 filter, 6” adapter hose) |
MGAVCR | MegaFlow Valve Core Removal Tool – 5/16in. |
MGAVCT | MegaFlow Valve Core Removal Tool – 1/4in. |
MH380006AAY | MegaFlow 3/8 in. Hose – 6 ft. (1/4FL to 1/4FL) Yellow |
MH380003AAY | MegaFlow 3/8 in. Hose – 3 ft. (1/4FL to 1/4FL) Yellow |
# | PART NO. | DESCRIPTION |
---|---|---|
1 | AY0050 | Front Panel Assembly |
2 | PL7601S | Front Panel Only w/Labels |
3 | WR9000 | Power Cord – 115v US |
3 | WR9230 | Power Cord – 230v EU |
4 | PL7011 | Output Knob – Red |
5 | PL7010 | Input Knob – Blue |
6 | KTGA00 | 0-700 PSI Gauge (2-Pack) |
6 | KTGA61 | PSI & Kg/cm2 Gauge (2-Pack) |
7 | EL5120 | Power Switch |
8 | CT1760L | Left Side Condenser |
9 | LB1235 | Front Panel Label (Top) |
10 | KTF612 | Inlet Filter Fitting |
11 | EL5030 | High Pressure Switch |
12 | LB1205 | G5Twin Side Label |
13 | AY0221 | Case Side Panel (each) |
14 | EL5017 | Motor Start Relay – 115v |
14 | EL5027 | Motor Start Relay – 230v |
15 | PL7000 | Case Handle |
16 | AY0036 | Fan Gearbox Assembly w/ Blade |
17 | PL7602 | Case Back Panel |
18 | PL7625 | Motor Support Bracket (each) |
19 | LB1201 | G5Twin Warning Label – 115v |
19 | LB1262 | G5Twin Warning Label – 230v |
20 | EL5000 | Motor – 115v |
20 | EL5230 | Motor – 230v |
21 | EL5028 | Motor Start Capacitor – 115v |
21 | EL5034 | Motor Start Capacitor – 230v |
22* | CA1603 | Cylinder (each) |
23 | CT1760R | Right Side Condenser |
24 | AY0020 | Manifold Assembly |
* Note: Contact Appion for compressor ordering info – See Page 20 for
repair kits
Appion reserves the right to make changes to product and specifications
without notice.
ELECTRICAL DIAGRAM REFRIGERANT FLOW DIAGRAM
Manufacturer’s Limited Warranty
Appion Inc. (hereinafter Appion) warrants that this equipment will, under
normal and anticipated use, be free from defects in materials and workmanship
for a period of one (1) year from the date of purchase by Purchaser from an
Appion-authorized distributor.
Appion shall be liable to repair or replace the applicable parts during this
period, so long that:
The User of this equipment notifies Appion of the discovery of an alleged
defect during the warranty period;
Purchaser obtains return authorization from Appion during the warranty period
(see Page 19 of this Manual);
Purchaser returns the equipment during the warranty period with all
transportation charges prepaid by purchaser;
Appion’s examination of the equipment confirms a defect that is not caused by
Purchaser or its agents;
The equipment has not been modified by Purchaser or its agents; AND The
defective part(s) are otherwise covered by this limited warranty.
Purchaser may attempt to repair or replace defective parts without risk of
voiding this warranty, so long that:
Purchaser follows all instructions and guidance provided by Appion to perform
such repair AND Purchaser utilizes only parts obtained from or authorized by
Appion in such repair;
Notwithstanding anything contained in this limited warranty to the contrary,
this limited warranty shall become null and void upon the use of any improper
chemicals, or in the event that modifications or improper service or
installation is performed on the equipment.
This limited warranty is applicable only to the first Purchaser when purchased
through an authorized wholesale distributor, and no subsequent purchasers of
the equipment from Purchaser shall be entitled to any warranty whatsoever from
Manufacturer, express or implied.
The obligation of Appion under this limited warranty is limited to the repair
or supply of parts, excluding consumables such as oil, grease, and plastic
parts. Parts shall be new or nearly new. Appion assumes no liability for
failure in performing its obligations thereunder if failure results, directly
or indirectly, from any cause beyond its control, including but not limited to
acts of God, acts of government, floods, fires, shortages of materials,
strikes and other labor difficulties or delays, or failures of transportation
facilities.
This warranty constitutes the sole and exclusive warranty of manufacturer with
respect to the equipment. There are no other warranties, express or implied,
and Appion specifically disclaims all other warranties, express or implied,
including (without limitation) any and all warranties as to the suitability or
merchantability or fitness for any particular purpose of the equipment
hereunder. The exclusive remedy of Purchaser against Appion for any breach of
the foregoing limited warranty shall be to seek replacement of the affected
parts. In no event will Appion’s liability in connection with the equipment
which is found to be defective exceed the amounts paid by Purchaser to Appion
hereunder for such equipment which is specifically found to be defective.
These limitations apply to all causes of action in the aggregate, both at law
and in equity, and including without limitation, breach of contract, breach of
warranty, manufacturer negligence, infringement, strict liability,
misrepresentation and other torts and contractual claims. Except for the
exclusive remedy provided above for Appion’s breach of this limited warranty,
Purchaser, for itself and its successors and assigns, hereby waives and
releases Appion from any and all other claims or causes of action they have
against Appion on account of or associated with the equipment purchased
hereunder or for Appion breach of this limited warranty.
In no event shall Appion be liable for any indirect, special, incidental,
consequential or punitive damages, such as, but not limited to, loss of
anticipated profits, lost savings, lost revenues, fines, or other economic
loss in connection with or arising out of the existence, furnishing,
functioning or use of any item of equipment provided under this agreement,
even if Appion has been advised of the possibility of such damages and/or such
damages are reasonable and/or foreseeable. Further, Purchaser, for itself and
its successors and assigns, waives and releases any rights they may have to
bring an action arising or resulting from this agreement, regardless of its
form, more than fifteen (15) months after purchase of the affected equipment
by Purchaser from an Appion- authorized distributor. Some states do not allow
the exclusion or limitation of incidental or consequential damages, so the
above limitation or exclusion may not apply to you.
The provisions of this warranty shall supersede any contrary provisions
contained in this agreement, any document supplied by Appion to Purchaser or
by Purchaser to Appion, or any other agreement, written or oral, between
Purchaser and Manufacturer, notwithstanding the fact that the provisions
contained in this warranty directly conflict with other terms or provisions of
this agreement or such other documents, or that such other documents or
agreements were provided, delivered, made or executed subsequent to this
agreement unless such agreements are in writing, specifically refer to this
agreement, and specifically provide that they are amending this and are signed
by the President of Appion.
This warranty gives you specific legal rights, and you may also have other
rights which vary in certain states or provinces.
If any term herein is declared invalid or unenforceable, the validity of the
remaining terms shall not be affected thereby.
Appion Inc.