AO Smith VF Series Vertical Water Heater User Manual
- August 15, 2024
- AO Smith
Table of Contents
AO Smith VF Series Vertical Water Heater
Specifications
- Model: VFS-SER Rev A
- Models: 500 – 2000
- Up To 4:1 Turndown
- Features: Setup/Return, Save/Clear, Run/Stop
Safety Warning
WARNING: This product must only be used by a qualified heating installer or service technician. Failure to comply with instructions could result in personal injury, death, or property damage.
Installation
Read all instructions provided in the manual and the VF Series Installation and Operation Manual before installing the product. Perform installation steps in the given order.
Maintenance
Perform maintenance and annual startup procedures as outlined in the manual (Pages 16-24).
Troubleshooting
Before Troubleshooting: Check the Control Module Fuses (Page 25). Refer to the Troubleshooting Charts provided in the manual for issues like No Display, Noisy System, Fault Messages, etc.
FAQs
Q: Who should use this product?
A: This product should only be used by qualified heating installers or
service technicians.
Q: What should I do in case of a hazardous situation?
A: Follow the safety warnings provided in the manual to avoid any risks
of personal injury or property damage.
Hazard definitions
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product.
DANGER
DANGER indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
NOTICE
NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
2
Service Manual
Please read before proceeding
WARNING
Installer Read all instructions, including this manual and the VF Series
Installation and Operation Manual, before installing. Perform steps in the
order given.
User This manual is for use only by a qualified heating installer/service
technician. Refer to the VF Series Installation and Operation Manual for your
reference.
Have this appliance serviced/inspected by a qualified service technician at
least annually.
Failure to comply with the above could result in severe personal injury, death
or substantial property damage.
NOTICE
When calling or writing about the appliance Please have the appliance model
and serial number from the appliance’s rating plate.
Consider piping and installation when determining appliance location (see the
VF Series Installation and Operation Manual).
Any claims for damage or shortage in shipment must be filed immediately
against the transportation company by the consignee.
When servicing appliance
· To avoid electric shock, disconnect electrical supply before performing
maintenance.
· To avoid severe burns, allow appliance to cool before performing
maintenance.
Appliance operation
· Do not block flow of combustion or ventilation air to the appliance.
· Should overheating occur or gas supply fail to shut off, do not turn off or
disconnect electrical supply to circulator. Instead, shut off the gas supply
at a location external to the appliance.
· Do not use this appliance if any part has been under water. The possible
damage to a flooded appliance can be extensive and present numerous safety
hazards. Any appliance that has been under water must be replaced.
Appliance water
· Thoroughly flush the system (without appliance connected) to remove
sediment. The high-efficiency heat exchanger can be damaged by build-up or
corrosion due to sediment.
· Do not use petroleum-based cleaning or sealing compounds in the appliance
system. Gaskets and seals in the system may be damaged. This can result in
substantial property damage.
· Do not use “homemade cures” or “appliance patent medicines”. Serious damage to the appliance, personnel, and/or property may result.
Service Manual
What is in this manual?
Service
Maintenance
The VF Series display · Display panel readout, buttons and their functions
Control module inputs · Control module inputs and options
Control module outputs · Control module outputs and options
General · How the appliance operates · How the control module operates ·
Access modes — user and installer · Sequence of operation — Domestic Hot Water
(DHW)/space heating
Control panel menu access · Accessing programming mode and locating menus
Control panel parameter access · Accessing and changing parameters from the
display panel
Service and maintenance schedules · Address reported problems · Inspect appliance area and appliance interior · Clean condensate system · Check all piping for leaks · Flue vent system and air piping · Check water system · Check expansion tank · Check control settings · Check igniter · Check all appliance wiring · Check flue gas passageways · Flame inspection · Inspect and clean burner · General maintenance · Checking manifold gas pressure · Combustion analysis procedure · Gas valve adjustment procedure · Cleaning heat exchanger · Review with owner
Troubleshooting
Quic k st a rt inform a t ion — pa ra m e t e r t a ble · An index of
available adjustments and readouts, where to
access them and where to find detailed information.
VF Series operation · A: General · B: Data Logging · C: Functions · D: DHW
Settings · E: Control Modes · F: Building Management System (BMS) · G:
Circulation Pump · H: Service Notification
· Troubleshooting table – No display · Checking temperature sensors · Troubleshooting table – Noisy system · Troubleshooting table -Fault messages displayed on Operator Interface
Service
The VF Series display
SETUP/RETURN
Service Manual
SAVE/CLEAR RUN/STOP
BACK
FORWARD
5
1 Service
Control inputs
(FIELD SUPPLIED)
(FACTORY SUPPLIED) ON/OFF / 0-10V (FIELD SUPPLIED) (FIELD SUPPLIED)
Service Manual
6
1 Se rvic e (continued)
Control outputs
Service Manual
(FIELD SUPPLIED) (IF EQUIPPED)
7
Service Manual
1 Service
General Operation
How the appliance operates
Access modes
The water heater uses a copper-finned tube heat exchanger to transfer heat from the flue products to the water. An electronic control module monitors various inputs to initiate a call for heat. The blower provides both primary and secondary air to the burner and forces the flue products out of the combustion chamber and into the vent system. The control module regulates the blower speed to control the firing rate of the appliance. The modulating gas valve monitors the amount of combustion air being pulled into the blower and regulates the amount of gas supplied, which then mixes with the combustion air and is supplied to the burner.
User
The user can adjust the tank setpoint using the (+) and (-) buttons at any
time during normal operation. By entering the USER code (0101), the user can
also change temperature units, time and date, and night setback settings. In
user mode, the following parameters can be viewed but not changed: heater
model number; software version; total operating hours, total cycles and last
10 faults.
Installer
How the control module operates
The VF Series control module receives input from appliance sensors. The
control module activates and controls the blower and gas valve to regulate
heat input and switches the DHW pump on and off as needed. The user/installer
programs the module to meet system needs by adjusting control parameters.
These parameters set operating temperatures and heater operating modes.
Appliance operation can be based on heater return water temperature, tank
temperature, tank temperature thermostat, and/or remote enable switch.
Sequence of operation
Most parameters are available only to the installer, accessible only by
entering the installer access code (2525).
Saving parameters To save parameters and exit programming:
Press the SAVE/CLEAR button, then the SETUP/RETURN button 3 times.
To keep parameter settings only for a current operating cycle:
Press the SETUP/RETURN button 3 times after making all desired parameter
changes.
Table 1A shows control module normal sequences of operation for DHW operation.
To enter a parameter and continue programming:
Press the SETUP/RETURN button 1 time to return to the parameter listings;
press again to return to the menu listings. Remember to press the SAVE/CLEAR
button when finished programming in order to save the changes made.
8
1 Se rvic e (continued)
Sequence of operation
Service Manual
Table 1A_Sequence of Operation – Space Heating and DHW
OPERATION
DISPLAY
1. The manual reset high limit must be closed before any HTR: Standby
action will take place.
OUT: 123.8F(129)
2. Upon a call for heat the control turns on the DHW pump. The HTR: Standby flow switch and low water cutoff (if equipped) must close. OUT: 123.8F(129)
3. · The gas pressure switch(es) (if equipped) must close.
· The contacts for the louvers close. The louver proving,
blocked drain switch, and auto reset high limit inputs must close.
HTR:
Standby
· If the air pressure switch is open, the prepurge cycle then OUT: 123.8F(129)
begins by starting the combustion blower. Once started,
the air pressure switch must close.
4. After prepurge, the blower slows down and the hot surface HTR: PREPURGE
igniter (HSI) is energized.
OUT: 123.9F(129)
5. Once the HSI is hot, the trial for ignition begins with the HTR: IGNITION
opening of the gas valve.
OUT: 123.9F(129)
6. If the control does not sense flame, it will lock out.
HTR: POSTPURGE, LOCKOUT OUT: 123.9F(129)
7. If the control senses flame, it will fire the burner to maintain HTR: DHW
20% RATE the setpoint. The firing rate will modulate as required to hold OUT:
124.8F(129)
the tank temperature at the setpoint.
8. Once the call for heat is satisfied, the control will turn
off the burner. The blower will remain on for the postpurge HTR: POSTPURGE
cycle. The DHW pump will continue to run for its pump OUT: 127.4F(129)
delay time, then turn off.
9. Pump off.
HTR: Standby OUT: 124.7F(129)
9
1 Service
Display panel menu access
Table 1B_Use this procedure to access menus from the display panel
Service Manual
SAVE/ CLEAR SETUP/ RETURN
(+)
FORWARD
(+)
FORWARD
(+)
FORWARD
(+)
SAVE/ CLEAR
(-) (-) (-) (-)
SAVE/CLEAR
2 000
2 000 2500 2500 2520
2520
2525
he FORWARD and BACK buttons
(+)
(-)
SAVE/CLEAR
10
1 Se rvic e (continued)
Display panel parameter access
Service Manual
Table 1C_This is a typical example of accessing a parameter, shown for pump delay parameter
(-)
(-)
(-)
(-)
SAVE/ CLEAR SAVE/ CLEAR
(+) (-)
SAVE/ CLEAR SETUP/ RETURN SETUP/ RETURN
y
y 30 sec
y 45 sec
y
The DHW Pump Delay menu item is shown The DHW Pump Delay setting is shown
The new setting is saved and the menu item is shown
a DHW
11
Service Manual
1 Service
Parameter table
Table 1D_This table lists control module parameters and where to access them
GENERAL
Menu
SUB ITEM
1 Reset Last 10 Errors
C
2 Service Mode Delay
13
No
No
Yes
Yes
13
No
No
Yes
Yes
FUNCTIONS
DHW SETTINGS
CONTROL MODES
1 Tank Setpoint
D
2 Tank Offset
3 Tank Differential
1 Enable Input
E
2 0-10V Building Management Input
1 Voltage at Minimum
2 Voltage at Maximum
F
3 Minimum Power
4 Maximum Power
14
Yes
Yes
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
14
No
No
Yes
Yes
BMS
CIRCULATION
PUMPS
G
1 DHW Pump Delay
15
No
No
Yes
Yes
SERVICE NOTIFICATION
1 Service Notification in Months
2 Service Notification Running Hours
H
3 Service Notification Cycles
4 Reset Service Notification Counter
5 Accept PPlug
15
No
No
Yes
Yes
15
No
No
Yes
Yes
15
No
No
Yes
Yes
15
No
No
Yes
Yes
15
No
No
Yes
Yes
12
Service Manual
1 Se rvic e (continued)
View able and changeable control parameters
NOTICE A: General
Before changing parameters, note the settings so that the unit can be returned to its original operating parameters.
Heater model
The control will display “VWH500 – 2000” as the model number because the same
control is used on several models. This will be displayed when parameter A1
has been accessed. This parameter is not changeable.
User code
The User Code allows the user to access and change a limited number of control
parameters. The access code can be changed by the user or the installer to a
code of their choosing. To change the code, parameter A2 must be accessed. The
default code is 0101. The code can be changed one digit at a time by using the
arrow keys on the display.
Date and time
The control uses an internal clock for the night setback feature and for logging of events. For these features to work correctly, the clock must be set when the unit is first installed or any time the unit has been powered off for more than 30 days. To set the clock, parameter A3 must be accessed. The date and time are displayed as “YY:MM:DD W hh:mm”. YY = year, MM = month, DD = date, W = day (1 = Monday, 2 = Tuesday, etc.), hh = hour (24 hour time; 2:00 PM = 14:00), mm = minutes.
NOTICE
The internal clock does not adjust for Daylight Savings Time and therefore, will require a manual adjustment.
Software version
The software version allows the user to view the software version in use by the control. This software controls the operation of the unit. When a new software version becomes available, the existing control can be replaced with a new control to update the software.
Temperature units
The control can be configured to display temperature in either °C or °F. This
parameter can be changed by the user or the installer by accessing parameter
A5. The default is °F.
Night setback temperature
Once the internal clock has been set correctly, the night setback feature can
be used to program a lower water temperature setpoint for the tank. This
parameter can be changed by the user or the installer by accessing parameter
A6. The temperature range for this parameter is 32°F (0°C) to 261°F (127°C).
If set higher than the tank setpoint (parameter D1) the tank setpoint will be
used. The feature is turned off with a setting of 32.0°F (0°C). The default
value is 32.0°F (0°C).
Night setback times
If parameter A6 is set to anything other than 32.0°F (0°C), the night setback
feature becomes active. This will require start and stop times to be
programmed for the days that reduced temperatures are required. These times
can be changed by the user or the installer by accessing parameter A7. Each
day of the week (Monday through Sunday) will have an on and off time.
Example: Monday ON: 22:30, Tuesday OFF: 6:45. If you wish to skip a day and
have no night setback, leave the on and off times the same. The default times
for each day will be 08:00 (OFF) and 18:00 (ON).
B: Data logging
Hours running DHW
The hours running DHW parameter shows the total number of hours the unit has
been in the DHW firing position. This parameter can be viewed by the user and
the installer by accessing parameter B1.
Ignition attempts
The ignition attempts parameter shows the total number of times the unit has
attempted to fire. This parameter can be viewed by the user and the installer
by accessing parameter B2.
Show last 10 errors
The control will log the 10 most current errors with the date and time the
error occurred. This parameter can be viewed by the user and the installer by
accessing parameter B3.
C: Functions
Reset last 10 errors
The reset last 10 errors parameter allows the error counter to be reset to 0.
This parameter can only be cleared by the installer by accessing parameter C1.
Once accessed, press the SAVE/CLEAR button to clear the counter.
Service mode delay
By pressing the hidden button on the front of the display for five (5)
seconds, the control will be placed in Service Mode. This will override all
other heat demands. The Service Mode allows the installer to set the unit to
any desired firing rate for the purpose of combustion analysis. The delay sets
the length of time the unit will stay in the Service Mode if no keys have been
pressed before going back to its original state. This parameter can only be
changed by the installer by accessing parameter C2. The time range of this
parameter is 0 to 40 minutes. The default value is 20 minutes.
13
Service Manual
1 Service
D: DHW settings
F: Building Management System (BMS)
Tank setpoint
When a temperature sensor is installed in the tank, the tank setpoint sets the
target temperature of the water in the tank. The user or installer can adjust
this setpoint by accessing parameter D1. The temperature range of this
parameter is 60°F (15°C) to 190°F (88°C). The default value is 120°F (49°C).
Tank offset
The tank offset is the number of degrees the tank temperature must go above
the tank setpoint before the water heater will turn off. The installer can
adjust this setpoint by accessing parameter D2. The temperature range of this
parameter is 0° to 10°F (5°C). The default value is 4°F (2°C).
Tank differential
The tank differential is the number of degrees the tank temperature must go
below the tank setpoint before the heater will start to heat the tank. The
installer can adjust this setpoint by accessing parameter D3 The temperature
range of this parameter is 0° to 40°F (22°C). The default value is 6°F (3°C).
E: Control modes
Enable input
The tank thermostat input can be used in two different ways. When a tank
aquastat is used, this input can start a heat demand when the aquastat closes.
When a tank sensor is used, this input can be used to enable/disable the water
heater using an external contact. This setting can be used by the installer by
accessing parameter E1. To use this input with an aquastat, set this parameter
to “Aquastat”. To use this input with a remote enable contact, set this
parameter to “Remote Enable”. The default setting is “Aquastat”.
0-10V building management input (BMS)
Voltage at minimum
This setting determines the voltage at which the external signal begins to
increase either the modulation or the setpoint. Below this voltage, the
modulation or setpoint will be at their minimum values. This parameter can be
adjusted by the installer by accessing parameter F1. The range for this
parameter is 0V – (F2 – 0.1V). The default value is 2V.
Voltage at maximum
This setting determines the voltage at which the external signal forces the
modulation to its maximum value. This parameter, along with the previous
parameter, determines how much the modulation changes as the BMS input voltage
changes. The modulation will change in proportion to the change in voltage
between the minimum and maximum voltage settings. This parameter may be
adjusted by the installer by accessing parameter F2. The range for this
parameter is (F1 + 0.1V) 10V. The default setting is 10V.
Minimum power
This setting determines the modulation of the unit when the BMS input voltage
is at or below the Voltage at Minimum setting. This parameter is active only
when the BMS type is set to Power. This parameter can be as low as 25%. This
parameter may be adjusted by the installer by accessing parameter F3. The
range for this parameter is 0 – 100%. The default value is 20%.
Maximum power
This setting determines the modulation of the unit when the BMS input voltage
is at or above the Voltage at Maximum setting. This parameter is only active
when the BMS type is set to Power. This parameter can be adjusted by the
installer by accessing parameter F4. The range for this parameter is 0 100%.
The default value is 100%.
When the building management input is enabled, the control modulates the unit based on the voltage on the 0-10V input on the connection board. The 0-10V input controls the modulation of the unit(s). This setting is adjustable by the installer by accessing parameter E2. The default value is Inactive. See menu Section F to adjust the parameters that control the BMS operation.
14
Service Manual
1 Se rvic e (continued)
G: Circulation pumps
Accept PPlug
DHW pump delay
The DHW pump delay parameter sets the length of time the DHW pump (if
connected) will run after a DHW demand has been satisfied. This parameter is
adjustable by the installer by accessing parameter G1. The time range for this
parameter is 1 second to 40 minutes. The default time is 30 seconds.
H: Service Notification
After replacing a control board, the new control will require the installer to verify the model in which it is installed. As soon as the power is turned on, the screen will display “Wrong ID Plg”. Look behind the control panel at the connector plugged into X5 on the control board. Note the number written on the connector. Access parameter H5. That number should appear after the word “Setting:” on the bottom line. If this number matches the number on the connector, press the SAVE/CLEAR button.
Service notification in months
When the control determines that a scheduled service is due based on days of installation, the display will alternate the standard display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing parameter H1. The time range for this parameter is 0 months to 36 months. The default time is 12 months.
Service notification running hours
When the control determines that a scheduled service is due based on the hours of actual operation, the display will alternate the standard display text with the message SERVICE DUE every 5 seconds. This parameter is adjustable by the installer by accessing parameter H2. The time range for this parameter is 0 hours to 100,000 hours. The default time is 10,000 hours.
Service notification cycles
When the control determines that a scheduled service is due based on the
number of cycles, the display will alternate the standard display text with
the message SERVICE DUE every 5 seconds. This parameter is adjustable by the
installer by accessing parameter H3. The range for this parameter is 0 cycles
to 100,000 cycles. The default is 10,000 cycles.
Reset service notification counter
Once servicing has been completed, the service notification counter should be reset. This parameter can be reset by the installer by accessing parameter H4. Once accessed, press the SAVE/CLEAR button to reset the service notification counter.
15
Maintenance
Maintenance and annual startup
Service Manual
ANNUAL START-UP
Table 2A_Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
General:
· Address reported problems
· Inspect interior; clean and vacuum if necessary;
· Inspect condensate system and flush with fresh water
· Check for leaks (water, gas, flue, condensate)
· Examine venting system
· Check system water pressure/system piping/expansion tank
· Check control settings
· Check igniter
· Check wiring and connections
· Check flue gas passageways
· Flame inspection (stable, uniform)
· Inspect and clean the burner
· Check manifold gas pressure
· Perform start-up checkout and performance verification per Section 7 in the
VF Series Installation and Operation Manual.
If combustion or performance indicate need:
· Clean heat exchanger
· Remove and clean burner using compressed air only
· Clean the blower wheel
Ow ner maintenance
Daily
· Check appliance area
· Check pressure/temperature gauge
Monthly
· Check vent piping · Check air piping · Check relief valve · Check condensate drain system
Every 6 months
· Test low water cutoff (if used)
· Reset button (low water cutoff)
· Check appliance piping (gas and water) for leaks
· Operate relief valve
16
Service Manual
2 M a int e na nc e (continued)
WARNING
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perform the service and maintenance could result in damage to the
appliance or system. Failure to follow the directions in this manual and component literature could result in
severe personal injury, death, or substantial property damage.
WARNING The appliance should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the appliance designated in Table 2A and explained on the following pages must be performed to assure maximum appliance efficiency and reliability. Failure to service and maintain the appliance and system could result in equipment failure.
WARNING
Electrical shock hazard Turn off power to the appliance before any service operation on the appliance except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock,
causing severe personal injury or death.
Address reported problems
Figure 2-1_Condensate Trap
1. Inspect any problems reported by the owner and correct before proceeding.
Inspect appliance area
1. Verify that appliance area is free of any combustible materials, gasoline and other flammable vapors and liquids.
Inspect appliance interior
1. Remove the outer access panels and inspect the interior of the appliance.
2. Vacuum any sediment from inside the appliance and components. Remove any
obstructions.
Clean condensate system
1. Inspect the condensate drain line, condensate PVC fittings, Che c k a ll piping for le a k s
and condensate trap.
1. Inspect all water and gas piping and verify to be leak free.
Flush condensate trap with water
1. Remove the four (4) screws securing the top cover to the condensate trap
and remove the cover (reference FIG. 2-1).
2. Locate the plastic ball inside the float tube. Verify there is nothing
under the ball causing it to not seat properly.
2. Look for signs of leaking lines and correct any problems found.
3. Check gas line using the procedure found in Section 3 – Gas Connections of
the VF Series Installation and Operation Manual.
3. If necessary, flush with fresh water until the water begins to pour out of the drain.
4. Replace the top cover on the condensate trap.
5. Replace the four (4) screws removed in Step 1.
17
Service Manual
2 Maintenance
Flue vent system and air piping
1. Check for gastight seal at every connection, seam of air piping, and vent
piping periodically inspected by a qualified service agency.
WARNING Venting system must be sealed gastight to prevent flue gas spillage
and carbon monoxide emissions, which will result in severe personal injury or
death.
Check w ater system
1. Verify all system components are correctly installed and operational.
2. Watch the system pressure as the unit heats up (during testing) to ensure
pressure does not rise too high. Excessive pressure rise indicates expansion
tank sizing or performance problem.
3. Inspect automatic air vents and air separators. Remove air vent caps and
briefly press push valve to flush vent. Replace caps. Make sure vents do not
leak. Replace any leaking vents.
Check expansion tank
1. Expansion tanks provide space for water to move in and out as the heating
system water expands due to temperature increase or contracts as the water
cools. Tanks may be open, closed, diaphragm or bladder type. See Section 4 –
Water Connections of the VF Series Installation and Operation Manual for
suggested best location of expansion tanks and air eliminators.
Check relief valve
1. Inspect the relief valve and lift the lever to verify flow. Before
operating any relief valve, ensure that it is piped with its discharge in a
safe area to avoid severe scald potential. Read Section 4 – Water Connections
of the VF Series Installation and Operation Manual before proceeding further.
WARNING
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency not by the owner. Failure to re-inspect the relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage.
WARNING
Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to
ensure that waterways are clear. Certain
naturally occurring mineral deposits may
adhere to the valve, rendering it inoperative.
When manually operating the lever, water
will discharge and precautions must be taken
to avoid contact with hot water and to avoid
water damage. Before operating lever, check
to see that a discharge line is connected to
this valve directing the flow of hot water
from the valve to a proper place of disposal.
Otherwise severe personal injury may result.
If no water flows, valve is inoperative. Shut
down the appliance until a new relief valve
has been installed.
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
18
Service Manual
2 M a int e na nc e (continued)
Inspect/replace hot surface igniter
Pe rform st a rt -up a nd c he c k s
1. Turn off main electrical power to the appliance.
1. Start appliance and perform checks and tests specified
2. Turn off main manual gas shutoff to the appliance.
in Section 7 – Start-up of the VF Series Installation and Operation Manual.
3. Carefully pull back the insulation flaps to expose the burner
mounting flange.
2. Verify cold fill pressure is correct and that operating
pressure does not go too high.
4. Locate the hot surface igniter. Disconnect the two power
leads to the hot surface igniter.
Check burner flame
5. Loosen and remove the two wing nuts that mount the igniter.
6. Lift the igniter vertically out of the burner mounting flange. Use care,
do not hit or break the silicon carbide igniter. Do
Visually check main burner flames at each start-up after long shutdown periods or at least every six months. A burner viewport is located on the burner mounting flange.
not contaminate the igniter by handling with oily or dirty hands.
WARNING The area around the burner viewport is hot and direct contact could result in burns.
7. Check the replacement igniter for cracks or damage before
installing.
Figure 2-2_Flame Pattern Illustration
8. Ensure that the fiber gasket used to seal the base of the
igniter to the burner flange is reinstalled to seal the base of
the replacement igniter.
9. Carefully insert the igniter into the mounting point on the burner flange and position on the mounting studs.
10. Reinstall the two wing nuts and tighten by hand only. Over tightening the wing nuts may break the ceramic mounting flange.
11. Ensure that the igniter gasket is properly installed and seals the point of contact between the igniter and burner mounting flange.
12. Reconnect the power leads to the igniter.
13. Replace the insulation blanket flaps.
14. Turn on main gas supply and main power.
15. Test fire the appliance to ensure proper operation.
Check all w iring
1. Inspect all wiring, making sure wires are in good condition and securely
attached.
Normal Flame: A normal flame at 100% of burner input is blue, with slight yellow tips, a well defined flame and no flame lifting.
Check control settings
Yellow Tip: Yellow tipping can be caused by blockage or partial obstruction of air flow to the burner.
1. Set the control module display to Parameter Mode and check all settings.
See Section 1 of this manual. Adjust settings if necessary. See Section 1 of
this manual for adjustment procedures.
2. Check settings of external limit controls (if any) and adjust if
necessary.
Yellow Flames: Yellow flames can be caused by blockage of primary air flow to
the burner or excessive gas input. This condition MUST be corrected
immediately.
Lifting Flames: Lifting flames can be caused by over firing the burner,
excessive primary air or high draft.
If improper flame is observed, examine the venting system, ensure proper gas supply and adequate supply of combustion and ventilation air.
19
Service Manual
2 Maintenance
Check flue gas passagew ays
Access to the burner will require the following steps:
Any sign of soot around the inner jacket, outer jacket, flue 1. Turn off main electrical power to the appliance.
pipe connections, burner or in the areas between the fins on 2. Turn off main manual gas shutoff to the appliance. the copper heat exchanger indicates a need for cleaning. The
following cleaning procedure must only be performed by a 3. Remove the front outer control panel covers. Slide out the
qualified serviceman or installer. Proper service is required to
inner control panel to increase service clearances and
maintain safe operation. Properly installed and adjusted units
carefully remove the multi-pin wiring connectors on the
seldom need flue cleaning.
back of the control panel. Remove the screws along the
front and rear edge of the top outer jacket panel to remove
CAUTION
All gaskets/sealants on disassembled components or jacket panels must be replaced
top. Remove the control panel to allow access to the components in the top of the appliance.
with new gaskets/sealants on reassembly.
Gasket and sealant kits are available from 4. Remove the sensing tubes from the low air pressure switch
your distributor.
to the combustion air blower.
CAUTION
When a Category IV vent system is disconnected for any reason, the flue must
Disconnect the wiring connections on the top of the combustion air blower.
be reassembled and resealed according to the 6. Remove the six (6) hex head bolts attaching the gas/air
vent manufacturer’s instructions.
venturi to the inlet of the combustion air blower.
Inspect and clean burner
The burner should be removed for inspection and cleaned on an annual basis. An
appliance installed in a dust or dirt contaminated environment may require
cleaning of the burner on a 3 to 6 month schedule or more often, based on
severity of the contamination. The fan assisted combustion process may force
airborne dust and dirt contaminants, contained in the combustion air, into the
burner. With sustained operation, non-combustible contaminants may reduce
burner port area, reduce burner input or cause non-warrantable damage to the
burner.
Use extreme care when operating an appliance for temporary heat during new
construction. Airborne contaminants such as dust, dirt, concrete dust or
drywall dust can be drawn into the burner with the combustion air and block
the burner port area. An external combustion air filter is provided with the
appliance. This filter helps ensure clean air is used for the combustion
process. Check this filter every month and replace when it becomes dirty. The
burner of an appliance used for temporary heat without a combustion air filter
installed will probably require a thorough cleaning before the unit is placed
into normal service.
7. Remove the four (4) nuts holding the combustion air blower to the top of
the burner and remove the combustion air blower assembly.
8. Use care when removing the combustion air blower assembly to prevent
damage to the venturi and burner gaskets.
9. Disconnect the power wires to the hot surface igniter.
10. Remove the hot surface igniter. The hot surface igniter is fragile. Use
care to prevent impact damage to the silicone carbide igniter surface when
removing the igniter.
11. Remove the eight (8) nuts holding the burner to the heat exchanger.
12. The burner can now be lifted vertically out of the heat exchanger
chamber.
13. Use care when removing the burner to prevent damage to the woven burner
port surface or gaskets on removal.
14. Remove any visible dust or dirt blockage from the surface of the burner
with a vacuum. Compressed air may also be blown across the burner surface to
clean the “pores” of the woven burner port material.
15. Reassemble in reverse order.
20
Service Manual
2 M a int e na nc e (continued)
Checking manifold gas pressure
The gas manifold pressure tap is located on the venturi connection of the gas
manifold assembly (FIG. 2-3). The manifold gas pressure tap can be accessed by
removing the upper left access panel on the front of the appliance.
Figure 2-3_Gas Train Assembly
Follow the steps below when checking manifold gas pressure:
1. Turn the appliance power switch to the “OFF” position.
2. Turn the latch counterclockwise and open the upper door.
3. Remove the screws along the front and rear edge of the top outer jacket
panel. Disconnect the ventilation fan’s 2-pin connector hanging from the top
panel cover inside the unit. Remove the top outer jacket panel.
4. Loosen the set screw on the venturi connection of the gas manifold
assembly one full turn from inside the pressure tap to read manifold gas
pressure. Place the tubing of the manometer over the tap once the set screw is
loosened.
5. Turn the appliance power switch to the “ON” position.
6. Place the appliance into the active position by pressing the SAVE/CLEAR
button on the display board (see page 5) until HTR:Standby appears in the
display window.
7. Locate the pinhole button below the SAVE/CLEAR button (see page 5). Press
the button once and hold for five (5) seconds to place the appliance into
Service Mode. In Service Mode the appliance will fire and operate at 100% of
rate.
8. As the appliance comes on and fires, record the inches of water column of
displacement on both sides of the manometer. The sum of these two readings
will be the gas manifold pressure. Reference Table 2B – Gas Manifold Pressure
Chart for the proper measurement.
9. This is a reference pressure only and is not field adjustable. An
appliance supplied with the required minimum gas supply pressure will operate
at the correct manifold gas pressure.
Table 2B_Gas Manifold Pressure Chart
Model No.
Natural Gas Water Column
(w.c.)
LP Gas Water Column
(w.c.)
500
-6.7 to -7.2
-7.9 to -8.4
750
-3.0 to -3.5
-4.0 to -4.5
1000
– 6.1 to -6.6
-8.4 to 8.9
1500
-3.9 to -4.6
-2.1 to -2.6
2000
-3.9 to -4.6
-2.1 to -2.6
10. Once the gas manifold pressure has been checked, press the SAVE/CLEAR button on the display board to take the appliance out of Service Mode. The appliance will go to shutdown and the display will show HTR:OFF.
11. Turn the appliance power switch to the “OFF” position.
12. Remove the manometer and related fitting(s) from the connection tap and replace the 1/8″ hex plug (on F9 models only).
13. Replace the top jacket panel and reconnect the ventilation fan’s 2-pin connector hanging from the top panel cover.
14. Replace the upper left access panel.
15. Turn the appliance power switch to the “ON” position.
16. Press the SAVE/CLEAR button on the display board until HTR:Standby appears in the display window.
21
Service Manual
2 Maintenance
Combustion analysis procedure
1. Turn the appliance power switch to the “OFF” position.
8. If the combustion is not within the specified range, reference the Troubleshooting Chart below for possible causes and corrective actions.
2. Remove the flue temperature sensor from the flue pipe. Note: Combustion measurements will be made at this Table 2D_Combustion Troubleshooting Chart
point.
3. Turn the appliance power switch to the “ON” position.
Possible Cause
Corrective Action
4. Place the appliance into the active position by pressing the SAVE/CLEAR
button on the display board (see page 5) until HTR:Standby appears in the
display window.
5. Locate the pinhole button below the SAVE/CLEAR button. Press the button
once and hold for 5 seconds to place the appliance into Service Mode. In
Service Mode the appliance will fire and operate at 100% of rate.
–
Vent / Air Intake Length or Obstruction
Refer to Section 2 – Venting in the VF Series Installation and Operation Manual for the proper venting and air intake methods.
– Check for obstructions in the vent / air intake terminals.
6. Insert the probe from a combustion analyzer into the hole left by the
removal of the flue temperature sensor.
7. Compare the combustion measurement to the values listed in Table 2C.
Gas Supply Pressure
– Refer to Section 3 – Gas Connections in the VF Series Installation and Operation Manual for the proper gas supply for the VF Series.
Table 2C_Combustion Measurements
Model No.
500 – 1300 1500 2000
Natural Gas CO2 (%)
8.2 to 8.7 8.6 to 9.1 7.6 to 8.2
LP Gas CO2 (%)
9.0 to 9.5 9.6 to 10.1 8.6 to 9.2
Dirty / Burner
Damaged
–
Refer to page 20 of this manual for burner removal and cleaning procedures.
Replace burner if necessary.
– Refer to page 23 of this manual Gas Valve Adjustment for the gas valve
adjustment
procedure.
9. Once the combustion analysis is complete, press the SAVE/CLEAR button on
the display board to take the appliance out of Service Mode. The appliance
will go to shutdown and the display will show HTR:OFF.
10. Turn the appliance power switch to the “OFF” position.
11. Replace the flue temperature sensor into the flue pipe.
12. Turn the appliance power switch to the “ON” position.
13. Press the SAVE/CLEAR button on the display board until HTR:Standby
appears in the display window.
WARNING
You must replace the flue temperature sensor to prevent flue gas spillage into the
room. Failure to comply could result in
severe personal injury, death, or substantial
property damage.
22
Service Manual
2 M a int e na nc e (continued)
Gas valve adjustment procedure
1. Turn the appliance power switch to the “OFF” position.
2. Remove the screws along the front and rear edge of the top outer jacket
panel. Disconnect the ventilation fan’s 2-pin connector hanging from the top
panel cover inside the unit. Remove the top outer jacket panel.
3. Follow the Combustion Analysis Procedure on page 22 of this manual to
measure combustion.
4. With the appliance operating in the Service Mode, locate the throttle
adjustment screw on the gas valve (see FIG. 2-4) . Using an Allen wrench turn
the throttle adjustment screw a 1/4 turn counterclockwise to increase CO2
levels and a 1/4 turn clockwise to decrease CO2 levels.
5. After one adjustment of the valve, measure the combustion.
6. If the combustion is still not within the specified range, repeat the
procedure. This procedure SHOULD NOT be performed more than four (4) times. If
after four (4) adjustments the combustion is still not within the specified
range, revisit the possible causes in Table 2D on page 22 of this manual.
7. Once the combustion analysis is complete, press the SAVE/CLEAR button on
the display board to take the appliance out of Service Mode. The appliance
will go to shutdown and the display will show HTR:OFF.
8. Turn the appliance power switch to the “OFF” position.
9. Replace the flue temperature sensor into the flue pipe.
10. Replace the top jacket panel and reconnect the 2-pin connector hanging
from the top panel cover.
11. Replace the upper left access panel.
12. Turn the appliance power switch to the “ON” position.
13. Press the SAVE/CLEAR button on the display board until HTR:Standby
appears in the display window.
Figure 2-4_Throttle Adjustment Screw
WARNING
Overfire and underfire hazards! Possible fire, explosion, overheating,
and component failure. Do not attempt
to adjust firing rate of the water heater.
The firing rate must be adjusted only by
factory trained personnel.
23
Service Manual
2 Maintenance
Inspect and clean the heat exchanger
1. Turn off all power to the appliance.
2. Turn off main gas to appliance.
3. Remove the front outer jacket panel.
4. Remove the inner jacket panel (see FIG. 2-5).
5. Check the heat exchanger surface for soot. If soot is present, the heat exchanger must be cleaned and the problem corrected.
6. Remove the burner as described in the Inspect and Clean Burner section of this manual.
7. Check the “V” baffles on the heat exchanger. Remove and clean if necessary.
8. Remove soot from the heat exchanger with a stiff bristle brush. Use a vacuum to remove loose soot from surfaces and inner chamber.
9. The heat exchanger can be removed by disconnecting all water piping to the
heat exchanger, removing the screws holding the heat exchanger to the top of
the inner jacket and sliding the heat exchanger towards the front of the
appliance. Once the heat exchanger is removed, a garden hose can be used to
wash the tubes to ensure that all soot is removed from the heat exchanger
surfaces. Note: Do not wet the insulation blankets on the inside of the outer
jacket panels.
10. Ensure that any soot present on the burner is removed. See Inspect and
Clean Burner section.
Figure 2-5_Location of the Heat Exchanger Inside Jacket
Review w ith ow ner
11. Carefully reinstall the heat exchanger and “V” baffles if 1. Review the VF Series Installation and Operation Manual
removed from the appliance.
with the owner.
12. Reinstall the inner jacket panel, burner, manifolds, 2. Emphasize the need to perform the maintenance schedule
wires, and hoses. Use new gasket material to ensure a
specified in this manual.
proper air seal.
13. Reassemble all gas and water piping. Test for gas leaks.
3. Remind the owner of the need to call a licensed contractor should the appliance or system exhibit any unusual behavior.
CAUTION
Upon completion of any testing on the gas system, leak test all gas connections with a soap and water solution while main burners are operating. Do not spray soap and water solution on the control module housing. The use of an excessive amount of soap and water solution can damage the control. Immediately repair any leak found in the gas train or related components. Do not operate an appliance with a leak in the gas train, valves, or related piping.
4. Remind the owner to follow the proper shutdown procedure and to schedule
an annual start-up at the beginning of the next heating season.
Oiled bearing circulators
Inspect the pump every six (6) months and oil as necessary. Use SAE 30 non-
detergent oil or lubricant specified by the pump manufacturer.
14. Reassemble outer jacket panels. 15. Cycle unit and check for proper operation.
24
Service Manual
3 Troubleshooting
WARNING
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the appliance before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.
Check control module fuses
NOTICE
ALWAYS check control module fuses before replacing control module or any major components (blower, etc.). If one of these fuses is blown, it can prevent the control module or other components from operating.
1. Turn OFF the power to the appliance at the external line
WARNING
Never jumper (bypass) any device except for momentary testing as outlined in the
switch.
Troubleshooting chart. Severe personal 2. Remove front access cover.
injury, death, or substantial property damage can result.
Inspect fuses F1, F2, F3, F5, and F6, see FIG. 3-1 below.
Before troubleshooting:
Figure 3-1_Control Module Fuses
1. Have the following items: a. Voltmeter that can check 120 VAC, 24 VAC, and
12 VDC. b. Continuity checker. c. Contact thermometer.
2. Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to appliance.
3. Make sure either the tank thermostat or tank sensor is calling for heat.
If the enable input is set to remote enable (see page 14), the tank thermostat
input must be closed and the tank temperature sensor must be below the DHW
setpoint minus the tank differential. Check for 24 VAC between the tank
thermostat connections and ground.
4. Make sure all external limit controls are installed and operating.
Check the follow ing:
4. The appliance is shipped with three (3) spare fuses in a
1. Wire connectors to control module are securely plugged in
plastic bag attached to the control panel.
at the module and originating control.
5. If necessary, replace open fuse (F1 and F6 are 1.6 amps, F3
2. Gas pressures:
is 3.15 amps, F2 and F5 are 5 amps).
Refer to Section 3 – Gas Connections of the VF Series Installation and Operation Manual for detailed information concerning the gas supply.
Note: Fuses F1 – F6 are all slow blow fuses.
WARNING Do not jumper fuse or replace with any fuse except as specified.
Failure to comply could result in severe personal injury, death, or
substantial property damage.
6. Install front access cover after fuse inspection.
7. Restore power to the appliance at the external line switch and verify water heater operation (Section 7 – Start-up in the VF Series Installation and Operation Manual) after completing water heater service.
25
3 Troubleshooting
Table 3A Troubleshooting Chart – No Display
FAULT
CAUSE
– No 120 VAC supplied to unit.
N o Displa y – Bad wiring connection. – Blown fuse. – Bad display board.
Service Manual
CORRECTIVE ACTION
· Check external line switch, fuse, or breaker. · Check position of ON/OFF
switch. Turn switch to the
ON position. · Check 120 VAC through the ON/OFF switch. No
voltage through switch, replace switch. · Check wiring harness connection
between the display
board and the main control board. Connect the harness at both points. ·
Replace fuse F6 on the main control board, see FIG. 3-1 on page 25 of this
manual. · Replace board.
– Bad main control board.
· Replace main control board.
– Main control board temperature setpoint · Review temperature setting. satisfied.
No Burner Operation
– Remote enable switch open. – Unit locked out on fault.
Unit Does Not Modulate
Above 50%
– Controlled by BMS.
· Review tank thermostat setting.
· Consult display for specific fault. Refer to fault descriptions on pages 29
– 35 of this manual for corrective actions.
· Check BMS parameter settings.
26
Service Manual
3 T rouble shoot ing (continued)
Checking temperature sensors
The appliance temperature sensors (inlet water, outlet water, system water,
tank water, flue, and outdoor air) are all resistance type devices. The
following tables show the correct values for the sensors at various
temperatures. Use an ohmmeter to read the resistance of the sensor at a known
temperature. If the resistance of the sensor does not closely match its
corresponding table, replace the sensor.
Table 3B Inlet/Outlet Resistance vs. Temperature
Temperature (°F)
50 68 86 104 122 140
Resistance
18,780 12,263 8,194 5,592 3,893 2,760
Temperature (°F)
158 176 194 212
Resistance
1,990 1,458 1,084 817
Table 3C Flue Temperature Sensor Resistance vs. Temperature
Temperature (°F)
68 77 86 104 122 140
Resistance
125,500 100,000 80,220 52,590 35,270 24,160
Temperature (°F)
158 176 194 212 230 248
Resistance
16,870 12,000 8,674 6,369 4,744 3,581
Table 3D Tank Sensor Resistance vs. Temperature
Temperature (°F)
32 50 68 86 104 122 140
Resistance
32,650 19,900 12,490 8,057 5,327 3,603 2,488
Temperature (°F) 158 176 194 212
Resistance 1,752 1,258 918 680
27
3 Troubleshooting
Table 3E Troubleshooting Chart – Noisy System
FAULT
CAUSE
– Gas supply problem.
Service Manual
CORRECTIVE ACTION
· Refer to Section 3 – Gas Connections of the VF Series Installation and
Operation Manual for detailed information concerning the gas supply.
– Gas/air mixture problem.
Noisy Operation
– Dirty/damaged burner.
· Refer to the Checking Manifold Gas Pressure and Combustion Analysis
Procedure on pages 21 and 22 of this manual for the proper settings. Verify
that the vent/air intake lengths do not exceed the maximum listed in the
Venting section of the VF Series Installation and Operation Manual.
· Refer to page 20 in this manual for the burner removal and inspection
procedure. Clean or replace the burner as necessary.
– Low water flow through the heat exchanger.
· Refer to Section 4 – Water Connections of the VF Series Installation and Operation Manual for minimum flow rates. Verify that the appliance is piped in a primary/secondary fashion and that the appliance and system pump are running on a call for heat.
– Air in the piping system.
· Properly purge all air from the piping system.
– Low system water pressure.
· Verify system pressure is a minimum of 12 PSI.
No Pump Operation
– Faulty pump. – Internal fault on control board.
· Replace pump.
· Replace main control board. Note: Make sure the pump horse power (hp) does
not exceed 1 hp.
– System pressure exceeds relief valve · Lower the system pressure below the rating of
setting.
the supplied relief valve.
Relief Valve Opening
– Improperly sized expansion tank. – Outlet water temperature in excess of 210°.
· Install properly sized expansion tank. · Check setpoint of temperature control.
· Check temperature rise across heat exchanger. Refer to the temperature rise chart in Section 4 – Water Connections of the VF Series Installation and Operation Manual.
28
3 T rouble shoot ing (continued)
Service Manual
Table 3F Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
· Reset the pressure switches.
Gas Pressure SW (Will require a manual reset once the condition has been corrected.)
Either the optional manual reset low gas pressure switch or the optional manual reset high gas pressure switch tripped.
· Measure the supply gas pressure to determine cause of failure. Refer to Section 3 – Gas Connections of the VF Series Installation and Operation Manual for detailed information concerning the gas supply.
· Correct the supply gas pressure if necessary.
Flow Sw itch/ LWCO
(Lockout will reset automatically after 5 minutes or may be reset immediately
once condition has been corrected. Press the SAVE/CLEAR button on the display
to reset.)
Either the flow switch or the optional low water cutoff is not making.
· Check pump operation on a call for heat.
· Check for closed valves or obstructions in the water piping.
· Verify system is full of water and all air has been purged from the system.
Blocked Drain SW (Lockout will reset automatically after 5 minutes or may be
reset immediately once condition has been corrected. Press the
SAVE/CLEAR button on the display to reset)
The blocked drain switch has detected excessive condensate build up inside the unit.
· Check condensate tube from unit to floor drain for proper installation and
obstructions.
· Inspect condensate trap for blockage. Clean if necessary.
· Check for loose wiring connection at wire harness plug.
· Bad blocked drain switch. Replace switch.
Flame Sequence (Will require a manual reset once the condition has been corrected. Press the SAVE/CLEAR button on the display to reset.)
The flame detector circuit is seeing a flame signal while no flame is present.
· Check supply voltage for proper polarity. · Check external wiring for voltage feedback. · Check the internal wiring for bad connections. · Replace main control board.
29
3 Troubleshooting
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
· Inspect igniter and associated wiring for damage and connection. Reference page 20 of this manual for removal and cleaning procedure. Replace if necessary.
· Check for proper electrical grounding of unit.
· Check incoming supply gas pressure. Refer to Section 3 – Gas Connections in the VF Series Installation and Operation Manual for detailed information concerning the gas supply.
No Flame Ign (Will require a manual reset. Press the SAVE/ CLEAR button on the
display to reset.)
The unit has failed to prove main burner flame upon ignition.
· Verify that the tube from the gas valve to the air inlet is connected and is
not damaged.
· Verify that the vent/air intake pipes are correctly installed and that there
are no obstructions.
· Inspect the burner. Reference page 20 of this manual for removal and
cleaning procedures. Replace if necessary.
· Refer to the Checking Manifold Gas Pressure and Combustion Analysis Procedure on pages 21 and 22 of this manual for the proper settings.
· Check for 120 VAC to the gas valve during the ignition attempt. If no voltage is present, check the wiring between the gas valve and the main control board.
· Replace the wiring or the main control board as necessary.
HSI Current Low
(Will require a manual reset once the condition has been corrected. Press
Amp draw of the hot surface igniter did not meet the minimum requirement of 2.6 amps.
the SAVE/CLEAR button
on the display to reset.)
· Measure the amp draw of the hot surface igniter during the trial for
ignition stage. If less than 2.6 amps replace the hot surface igniter.
· If more than 2.6 amps replace the control module.
Flame CKT Error
The main control board has detected an internal fault.
· Replace the main control board.
30
3 T rouble shoot ing (continued)
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
The unit was running and lost the flame signal.
· Inspect igniter and associated wiring for damage and connection. Reference page 20 of this manual for removal and cleaning procedure. Replace if necessary.
· Check for proper electrical grounding of unit.
No Flame Running (Will require a manual reset once the condition has been corrected. Press the SAVE/CLEAR button on the display to reset.)
· Check incoming supply gas pressure. Refer to Section 3 – Gas Connections of
the VF Series Installation and Operation Manual for detailed information
concerning the gas supply.
· Verify that the tube from the gas valve to the air inlet is connected and is
not damaged.
· Verify that the vent/air intake pipes are installed correctly and there are
no obstructions.
· Refer to the Checking Manifold Gas Pressure and Combustion Analysis
Procedure on pages 21 and 22 of this manual for the proper settings.
· Inspect the burner. Reference page 20 of this manual for removal and cleaning procedures. Replace if necessary.
· Replace the main control board.
Auto Reset High Limit
The outlet water temperature has exceeded the · Verify that the system is full of water and that all air
fixed setting of the automatic reset high limit.
has been properly purged from the system.
· Verify that the appliance is piped properly into the heating system. Refer to Section 4 – Water Connections of the VF Series Installation and Operation Manual for the proper piping methods for the VF Series.
· Check 120 VAC to DHW pump motor on a call for heat. If voltage is not present, check wiring back to the main control board. Replace the main control board if necessary.
· If 120 VAC is present on a call for heat and the pump is not operating, replace the pump.
· If the system pump is a variable speed pump, ensure that the system flow is not less than the flow.
· Check temperature setting of the main control board.
· Check resistance of water sensors and compare to Table 3B on page 27 of this manual. Replace sensor if necessary.
· Replace high limit.
31
3 Troubleshooting
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
· Verify setting of adjustable high limit.
· Verify that the system is full of water and that all air has been properly purged from the system.
Manual Reset High Limit
(Will require a manual reset once condition has been corrected. The outlet
water temperature has exceeded
Press the SAVE/CLEAR the setting of the adjustable high limit. button on the
display to
reset.)
· Verify that the appliance is piped properly into the system. Refer to
Section 4 – Water Connections of the VF Series Installation and Operation
Manual for proper piping methods for the VF Series.
· Check 120 VAC to the pump motor on a call for heat. If voltage is not
present, check wiring leading to the main control board. Replace the main
control board if necessary.
· If 120 VAC is present on a call for heat and the pump is not operating,
replace the pump.
· If the system pump is a variable speed pump, ensure the system flow is not
less than the flow.
· Check temperature setting of the main control board.
· Check resistance of water sensors and compare to the tables on page 27 of this manual. Replace the sensor if necessary.
· Replace high limit.
Inlet Low
· Raise temperature setpoint above 130°.
The inlet water temperature did not exceed 130° within 15 minutes of ignition.
· Install a 3-way valve per the piping diagram in Section 4 – Water Connections of the VF Series Installation and Operation Manual.
· Replace the main control board.
The actual fan RPM is 30% lower than what is being called for.
Fan Low OR
Fan Speed Low (Will require a manual
reset once condition has been corrected. Press the SAVE/CLEAR button on the
display to
reset.)
· Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section
2 – Venting of the VF Series Installation and Operation Manual for proper
lengths.
· Check for obstruction or blockage in the vent/air intake pipes or at
terminations.
· Check wiring connections at the fan and at the main control board.
· Replace the fan.
· Replace the main control board.
Blown fuse.
· Replace fuse F3 on the main control board, see page 25 of this manual.
32
3 T rouble shoot ing (continued)
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Fan High OR
Fan Speed High (Will require a manual reset once the condition has been
corrected. Press the SAVE/CLEAR button on the display to reset.)
The actual fan RPM is 30% higher than what is being called for.
· Vent/air intake lengths exceed the maximum allowed lengths. Refer to Section
2 – Venting of the VF Series Installation and Operation Manual for proper
lengths.
· Check for obstruction or blockage in the vent/air intake pipes or at
terminations.
· Check wiring connections at the fan and at the main control board.
· Replace the fan.
· Replace the main control board.
Flue Open OR
Flue Shorted
The flue sensor wiring has been disconnected, grounded, or the flue sensor has been removed from the flue.
· Check the sensor and associated wiring. replace sensor or wiring if damaged.
· Reinstall sensor in flue outlet.
Repair or
Sensor Open (Will require a manual reset once the condition has been corrected. Press the SAVE/CLEAR button on the display to reset.)
Either the inlet water or outlet water temperature sensor has been disconnected.
· Check the sensors and their associated wiring. Repair or replace the sensor
or wiring if damaged.
· Measure the resistance of the sensors and compare the resistance to the
tables on page 27 of this manual.
· Replace the sensor if necessary.
Sensor Shorted (Will require a manual reset once the condition has been corrected. Press the SAVE/CLEAR button on the display to reset.)
Either the inlet water or outlet water temperature sensor has been shorted.
· Check the sensors and their associated wiring. Repair or replace the sensor
or wiring if damaged.
· Measure the resistance of the sensors and compare the resistance to the
tables on page 27 of this manual.
· Replace the sensor if necessary.
Louver Proving (Lockout will reset automatically after 5 minutes or may be
reset immediately once condition has been corrected. Press the
SAVE/CLEAR button on the display to reset.)
An optional remote proving switch is not making.
· Check function of remote devices.
· Check for loose or misplaced jumper if proving switch is not installed.
Tank Open
Tank sensor not connected.
· Repair or replace the sensor wiring if damaged. · Replace the sensor if necessary.
APS Open (Lockout will reset automatically after 5 minutes or may be reset immediately once condition has been corrected. Press the SAVE/CLEAR button on the display to reset.)
The air pressure switch did not make within 1 minute after the combustion air blower has been energized.
· Check air filter. Clean or replace as necessary.
· Vent/air intake lengths exceed the maximum allowed lengths.
· Check for blockage or obstruction in vent/air inlet pipe or at terminations.
· Verify combustion air blower is operating. Replace if necessary.
33
3 Troubleshooting
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
APS Closed (Lockout will reset automatically after 5 minutes or may be reset immediately once condition has been corrected. Press the SAVE/CLEAR button on the display to reset.)
The control sensed that the air pressure switch was closed before the combustion air blower was energized.
· Check for jumper on air pressure switch.
· Check for an unusually high negative draft in the vent stack.
Wrong ID Plug
· Verify that ID plug is connected properly to connector X5 on the control module.
Control module ID plug does not match parameter H5.
· Verify that the wiring in the ID plug is not cut or damaged and that the
wiring connectors are seated properly in the plug.
· Verify that the number on the ID plug matches the number in parameter L5. If
not, replace the control module.
· When replacing control modules, verify that the number in parameter L5 matches the number on the ID plug. If so, press the SAVE/CLEAR button on the display. If not, replace the control module.
· Inspect the heat exchanger. Reference page 20 of this manual for the procedure on how to clean the flue side of the heat exchanger.
The stack temperature has exceeded the set parameters for the water heater.
· Inspect the flue sensor and associated wiring. Measure the resistance of the flue sensor and compare to Table 3C on page 27 of this manual. Replace the sensor if necessary.
T e m p O/Shoot (Lockout will reset automatically after 5 minutes or may be
reset immediately once condition has been corrected. Press the SAVE/CLEAR
button on
the display to reset.)
The temperature rise across the heat exchanger has exceeded the set parameters for the appliance.
· Verify that the vent/air intake pipes are properly installed and that there
are no obstructions.
· Replace the main control board.
· Verify that the system is full of water and that all air has been properly
purged from the system.
· Verify that the appliance is piped properly into the heating system. Refer
to Section 4 – Water Connections of the VF Series Installation and Operation
Manual for the proper piping methods.
· Check for 120 VAC to the pump motor on a call for heat. If voltage is not
present, check the wiring leading to the main control board. Replace the main
control board if necessary.
· If 120 VAC is present on a call for heat and the pump is not operating, replace the pump.
34
3 T rouble shoot ing (continued)
Service Manual
Table 3F (continued from previous page) Troubleshooting Chart – Fault Messages Displayed on Operator Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
T e m p O/Shoot (continued) (Lockout will reset automatically after
5 minutes or may be reset immediately once
condition has been corrected. Press the SAVE/CLEAR button on the display to
reset.)
Outlet water temperature has exceeded the maximum outlet water temperature.
· Verify that the system is full of water and that all air has been properly
purged from the system.
· Verify that the appliance is piped properly into the system. Refer to
Section 4 – Water Connections of the VF Series Installation and Operation
Manual for the proper piping methods.
· Check 120 VAC to the pump motor on a call for heat. If voltage is not
present, check wiring leading to the main control board. Replace the main
control board if necessary.
· If 120 VAC is present on a call for heat and the pump is not operating,
replace pump.
· Replace the main control board.
Rem Ctrl Flt
External control is cycling too often.
· Check setpoint of the external control.
· Check the wiring between the external control and the unit.
· Replace the control.
· Establish a heating load to remove heat from the system.
· Verify that the system is full of water and that all air has been properly purged from the system.
Service Blk
While the unit is in Service Mode, the outlet temperature has exceeded 185°F (85°C).
· Verify that the appliance is piped properly into the system. Refer to
Section 4 – Water Connections of the VF Series Installation and Operation
Manual for the proper piping methods.
· Check 120 VAC to the pump motor on a call for heat. If voltage is not
present, check the wiring leading to the main control board. Replace the main
control board if necessary.
· If 120 VAC is present on a call for heat and the pump is not operating, replace the pump.
· Check 120 VAC supply to the transformer.
Low Voltage
· Check wiring connections at the low voltage terminal 120 VAC input to the
main control board has strip. dropped below 80 VAC.
· Check the wire size/length to remote devices.
· Replace the main control board.
Watch Dog Error
The main control board has detected an internal fault.
· Replace the main control board.
Write EEProm
The main control board has detected an internal fault.
· Replace the main control board.
Program EEProm
The main control board has detected an internal fault.
· Replace the main control board.
CRC Parameters
The main control board has detected an internal fault.
· Replace the main control board.
No Error Stored
The main control board has detected an internal fault.
· Replace the main control board.
35
Revision Notes: Revision A (ECO C12846) initial release.
VFS-SER Rev A 06/13
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>