Specifications

  • Product: Color and Wattage Selectable LED Panel Fixture with Emergency Backup
  • Performance Summary:
    • Size: 2×2 or 2×4
    • Wattage: 25W, 30W, 40W, 50W
    • CCT (Correlated Color Temperature): 3500K, 4000K, 5000K
    • CRI (Color Rendering Index): 80
    • Dimming: 0-10V
    • Voltage: 120-277V
    • Emergency Operation: Yes
    • Recharge Time: 90 minutes
    • Emergency Output Lumens: 1000 to 1500
    • Replaces: 2 or 3 Lamp Fluorescent
  • DLC #: PLTM521511 for 40W, 5000K | PLTM532511 for 50W, 5000K
  • DLC Level: 5.1 Standard

Product Usage Instructions

Selectable Table
Choose the desired wattage and CCT from the selectable table based on your requirements.

Dimensions

  • 2×2 Dimensions:
  • Length: 23.7″
  • Height: 1.5″
  • Width: 23.74″
  • Weight: 6.88 lbs
  • 2×4 Dimensions:
  • Length: 47.8″
  • Height: 1.5″
  • Width: 23.74″
  • Weight: 10.32 lbs

Frequently Asked Questions (FAQ)

  • Q: How do I select the wattage and color temperature for the LED panel fixture?
    A: Refer to the Selectable Table to choose the desired wattage and CCT settings.

  • Q: What is the emergency backup feature in the LED panel fixture?
    A: The fixture comes with built-in emergency backup to provide light during power failures for up to 90 minutes.

  • Q: What is the DLC Level mentioned in the specifications?
    A: The DLC Level is 5.1 Standard, indicating the product meets specific energy efficiency and performance criteria.

COLOR AND WATTAGE SELECTABLE LED PANEL FIXTURE WITH EMERGENCY BACKUP

DESCRIPTION
Create a modern look in your space by installing these color and wattage selectable LED panels. These fixtures come with a built-in emergency backup, ensuring you have light in the event of a power failure.

FEATURES

  • Efficiently replaces up to a 3 lamp fluorescent fixture
  • Built-in emergency backup operates fixtures for at least 90 minutes in the event of a power failure; recharges in 24 hours
  • Red test switch located on the frame
  • 0-10V dimming
  • Light output varies depending on wattage and color temperature selected; see Selectable Table for full breakdown
  • Wattage and color temperature is selectable via switches on the driver box; see installation instruction for more information

LISTINGS

  • UL rated for damp locations
  • IC Rated
  • FCC
  • DesignLights Consortium® 5.1 Standard – meets the requirements for the highest DLC qualification for efficacy and lumen maintenance

PERFORMANCE• CRI: 80

  • CCT: 3500K, 4000K, and 5000K
  • LED L70 Life Hours @ 70°C: >100,000 hours

EMERGENCY OPERATION

  • Operation: 90 minutes
  • Charging Time: 24 Hours
  • Input Voltage: 100-277V
  • Output Power: 8W
  • Output Lumens: 1000 to 1500

THERMAL
-4°F to 122°F (-20°C to 50°C) operating temperature

ELECTRICAL

  • THD: <20%
  • Power Factor: >0.9
  • Input Voltage: 120-277V
  • Dimmable power supply (0-10V)
  • Surge Protection: 2kV

INSTALLATION

  • Designed for recessed installation in a T-grid ceiling; see installation instructions for more information

CONSTRUCTION

  • Stamped sheet metal housing with white powder coat finish
  • Frosted PS lens protects LEDs while evenly distributing light
project name type

catalog number
comments| voltage
approved by| date

PLT-90350-Color-and-Wattage-Selectable-LED-Panel-with-Emergency-Backup-
\(1\) PLT-90350-Color-
and-Wattage-Selectable-LED-Panel-with-Emergency-Backup-
\(2\)

WARRANTY

5-year limited warranty;
see pltsolutions.com for warranty details

APPLICATIONS

  • Conference Rooms
  • Retail
  • Offices
  • Hospitality
  • Healthcare
  • Schools
  • Reception Areas
  • Corridors
  • Foyer

PERFORMANCE SUMMARY

Item #| Size| Watts| CCT| CRI| Dimming| Voltage| Emergency Operation| Recharge Time| Emergency Output Lumens| Replaces| Default Settings| DLC #| DLC

Level

---|---|---|---|---|---|---|---|---|---|---|---|---|---

PLT-90350

|

2×2

| 25/

30/

40

| 3500K/

4000K/

5000K

|

80

|

0-10V

|

120-277V

|

90 minutes

|

24 Hours

|

1000 to 1500

|

2 or 3 Lamp

Fluorescent

|

40W,

5000K

|

PLTM521511

|

5.1

Standard

PLT-90351

|

2×4

| 30/

40/

50

| 3500K/

4000K/

5000K

|

80

|

0-10V

|

120-277V

|

90 minutes

|

24 Hours

|

1000 to 1500

|

3 Lamp

Fluorescent

|

50W,

5000K

|

PLTM532511

|

5.1

Standard

SELECTABLE TABLE

Item # Wattage CCT Lumens Efficacy

__

__

__

__

__

__

__

PLT-90350

| __

__

25

| 3500K| 3208| 128
4000K| 3386| 135
5000K| 3253| 130
__

__

30

| 3500K| 3862| 128
4000K| 4124| 137
5000K| 3818| 130
__

__

55

| 3500K| 4832| 120
4000K| 5222| 130
5000K| 4882| 122
__

__

__

__

__

__

__

PLT-90351

| __

__

30

| 3500K| 3943| 131
4000K| 4029| 134
5000K| 3938| 131
__

__

40

| 3500K| 4930| 123
4000K| 5230| 130
5000K| 5055| 126
__

__

50

| 3500K| 5793| 115
4000K| 6194| 123
5000K| 5935| 118

DIMENSIONS

2X2 DIMENSIONS

  • Length: 23.7″
  • Height: 1.5″
  • Width: 23.74″
  • Weight: 6.88 lbs

2X4 DIMENSIONS

  • Length: 47.8″
  • Height: 1.5″
  • Width: 23.74″
  • Weight: 10.32 lbs

PLT-90350-Color-and-Wattage-Selectable-LED-Panel-with-Emergency-Backup-
\(4\)

PHOTOMETRICS

2X2

PLT-90350-Color-and-Wattage-Selectable-LED-Panel-with-Emergency-Backup-
\(5\)

2X4

PLT-90350-Color-and-Wattage-Selectable-LED-Panel-with-Emergency-Backup-
\(6\)

972-535-0926 | PLTSOLUTIONS.COM | ver 013024

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals