Honeywell UV2400U6000 AirBRIGHT 6 Ultraviolet Air Purifier with Carbon Installation Guide

July 30, 2024
Honeywell

Honeywell UV2400U6000 AirBRIGHT 6 Ultraviolet Air Purifier with Carbon

Product Specifications

  • Model: UV2400U6000
  • Power Module: 24 VAC (Expanded range ballast: 20V-32V), 50/60Hz, 1.4A
  • Mounting Plate Dimensions: 6-3/4H x 6-3/4W
  • Electrical Weight: 3 lbs
  • UV-C Lamp Life : 18,000 hours
  • Ozone: UL 2998 validated no ozone

Installation Instructions

Before Installing this Product

  • Read these instructions carefully; failure to follow them could damage the product and cause a hazardous situation.
  • The installer must be a trained, experienced service technician.

WARNING: UV Light Hazard.
Harmful to bare skin and eyes. Can cause temporary or permanent loss of vision. Never look at lamps while illuminated.

  • To prevent exposure to ultraviolet light, disconnect power to the ultraviolet air treatment system before servicing any part of the heating/air conditioning system.
  • View illumination only through lamp handle or sight glass.
  • Do not attempt to bypass the duct mount switch.
  • Do not attempt to open the housing; the unit is sealed to prevent ultraviolet light exposure.

CAUTION : Personal Injury Hazard. The HVAC power supply can cause electrical shock.

  • Disconnect the HVAC power supply before installing, cleaning, or replacing ultraviolet lamp(s).
  • Breakable Glass Hazard. Can cause personal injury.
  • Be careful when inserting lamp(s) into the lamp base.
  • Wear protective gloves when handling lamp(s).
  • Personal Injury Hazard. The power supply can cause electrical shock.
  • Disconnect the power supply before cleaning or replacing the ultraviolet lamp(s).
  • Do not open the base unit or lamp handle; there are no user-serviceable components inside.
  • UV Lamp Burn Hazard. Harmful to bare skin. Can cause severe burns.
  • Disconnect power 15 minutes before removing the ultraviolet lamp(s).

Included Inside Box

  • Carbon air purifier system
  • 24 VAC power supply
  • Core
  • UV-C lamp
  • 40VA transformer
  • Mounting plate
  • Mounting hardware
  • Installation instructions
  • Sight glass
  • UV warning stickers

Specifications

Honeywell-UV2400U6000-AirBRIGHT-6-Ultraviolet-Air-Purifier-with-Carbon-
FIG-1

  • Model UV2400U6000
  • Power Module: 6-3/4”H x 6-3/4”W
  • Mounting Plate : 7” H x 7” W
  • Electrical 24 VAC (Expanded range ballast: 20V-32V), 50/60Hz, 1.4A. 3000V surge protection.
  • Weight: 3 lbs.
  • UV-C Lamp 18,000 hour life. Water resistant.
  • Ozone UL 2998 validated no ozone

UV Installation Notes

  • We recommend the AirBRIGHT 6 UV Air Purifier be installed on the supply side duct 3-5 inches above the A-coil.
  • The germicidal UV light should be positioned to shine on surfaces that are prone to mold growth like the A-coil.
  • Add the included stickers bearing the ULTRAVIOLET RADIATION hazard symbol on any doors/access panels which would allow direct UV light to shine through if opened while UV is powered. Make sure these doors/panels remain closed while the UV is powered.
  • UV-C BARRIERS bearing the ULTRAVIOLET RADIATION hazard symbol should not be removed.
  • Do not operate UV-C LAMPS outside of the appliance.

Wiring And Transformer Installation Notes
This device requires a constant 24 VAC power source. It is recommended that the device be powered by a dedicated, non-cycling, 40VA transformer. Cycling this UV light will void the lamp’s warranty and lessen the effective lifetime of the lamp. If powering from an existing transformer is already integrated into a furnace, air handler, or other appliance, an upgrade may be required to the original equipment transformer. Ensure there is adequate volt-ampere (VA) capacity on the transformer to support an additional 1.4A draw from this product.

  1. Verify the available volt amperes before connecting the UV fixture to the 24 VAC circuit. Energize all 24 VAC components powered by the transformer so they reach their maximum amp load.
  2. After obtaining the available volt-amperes, determine if the transformer can accommodate an additional 1.4 amp load.
  3. Beware that inadequate transformers may initially seem to power up the circuit only to then overheat as a result of an overdrawing system.
  4. After installing the UV fixture, energize all 24VAC components at their full amp draw, including the UV fixture, and ensure that all systems are operational and that fuses remain intact.

Metal Ductwork Installation

  • Locate a suitable area of the duct for installation. Minimum 7” area.
  • If needed, cut away insulation to expose the metal duct.
  • Mark the location for the 5” opening using the included mounting plate as a template.
  • Cut opening for the device.
  • Remove the backing from the mounting plate gasket, center the mounting plate over the opening, and press onto the duct. The adhesive gasket will hold the mounting plate in place.
  • Secure the mounting plate using self-tapping screws.
  • Insert the device into othe opening and secure it with knurled nuts.
  • Connect to proper power and test operation. The operation indicator light on the face of the device should be on.

Fiberglass Ductwork Note
For fiberglass ductwork installations use 3” toggle bolts to attach the mounting plate.

Maintenance/UV Lamp Indicator
For optimal performance, replace the carbon core each year and the UV-C lamp every year after the initial two-year period.

The operation indicator on the face of the device is for UV Lamp operation only. If the unit has power and the indicator does not glow, the UV lamp should be replaced.

WARNING : Electric Shock Hazard.

  • Can cause injury or death.
  • Electrical wiring of the unit to the HVAC system should be done by a licensed HVAC technician or electrical installer

Changing the Core or UV-C Lamp

  • Disconnect the device from power.
  • Removed the knurled nuts securing the device and removed the device from the core.
  • Remove the screws securing the core.
  • Remove the core from the device and dispose of it properly. Note: If only changing the UV-C lamp, detach the lamp from the device and dispose of it properly.
  • Secure the new core or new UV-C lamp to the device.
  • Reverse the previous steps to return the device to operation.

WARNING: UV Light Hazard. Can cause serious eye and skin damage.
Harmful to bare skin and eyes. Can cause temporary or permanent loss of vision. Never look at lamps while illuminated.

Mercury Notice

  • This device contains mercury in the sealed ultraviolet lamp(s). Do not place your used lamp(s) in the trash.
  • Dispose of it properly.

Broken Lamp Cleanup and Disposal

  • Do not use a household vacuum. Sweep debris (phosphor/glass) into a plastic bag and dispose of it properly.
  • Contact your local waste management authority for instructions regarding recycling and the proper disposal of old lamps (s

Replacement Parts

  • UV2400U6000 – AirBRIGHT 6 Ultraviolet Air Purifier with Carbon
  • UV2400XLAM6 – Replacement Lamp
  • UV2400XCRB6 – Replacement Carbon

Limited Warranty

Resideo warrants this product to be free from defects in workmanship or materials, under normal use and service. The warranty period on the power module is seven (7) years from the date of first purchase by the original purchaser. The warranty on the bulb is two (2) years from the date of first purchase by the original purchaser. The warranty is not intended to cover parts replaced as part of the normal maintenance schedule. If at any time during the warranty period, the product is determined to be defective due to workmanship or materials, Resideo shall repair or replace it (at Resideo’s option).

If the product is defective,

  1. return it, with a bill of sale or other dated proof of purchase, to the place from which you purchased it; or
  2. call Resideo Customer Care at 1-800-468-1502. Customer Care will determine whether the product should be returned to the following address: Resideo Return Goods, 1985 Douglas Dr. N., Golden Valley, MN 55422, or whether a replacement product can be sent to you.

This warranty does not cover removal or reinstallation costs. This warranty shall not apply if it is shown by Resideo that the defect was caused by damage
which occurred while the product was in the possession of a consumer.

Resideo’s sole responsibility shall be to repair or replace the product within the terms stated above. RESIDEO SHALL NOT BE LIABLE FOR ANY LOSS OR DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS PRODUCT. Some states do not allow the exclusion or limitation of incidental or consequential damages, so this limitation may not apply to you.

THIS WARRANTY IS THE ONLY EXPRESS WARRANTY RESIDEO MAKES ON THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES,
INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IS HEREBY LIMITED TO THE DURATION OF THIS
WARRANTY. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.

This warranty gives you specific legal rights, and you may have other rights which vary from state to state. If you have any questions concerning this
warranty, please write Resideo Customer Care, 1985 Douglas Dr, Golden Valley, MN 55422, or call 1-800-468-1502.

www.resideo.com

© 2024 Resideo Technologies, Inc. All rights reserved.
The Honeywell Home trademark is used under license from Honeywell International, Inc.
This product is manufactured by Resideo Technologies, Inc. and its affiliates.

FAQ

  • Q: How often should I replace the UV-C lamp?
    • A: The UV-C lamp should be replaced every year after the initial two-year period for optimal performance.
  • Q: Can I install this product without professional help?
    • A: No, installation of this product should be done by a trained and experienced service technician to avoid hazards and ensure proper functioning.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Honeywell User Manuals

Related Manuals