ACCUREX 481488 Auto Cleaning Hood
Installation, Operation, and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate, or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and all applicable local and national building and fire codes. Personnel should be aware of general safety precautions. SMACNA guidelines should be followed for hanging and supporting the hood. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near a unit. Lock and tag the
disconnect switch or breaker to prevent accidental power-up.
NOTE
Follow all local electrical, plumbing, and safety codes, as well as the
National Electrical Code (NEC) and the latest edition of the National Fire
Protection Agency Standard for Ventilation Control and Fire Protection of
Commercial Cooking Operations, (NFPA 96). Follow the Canadian Electrical Code
(CEC) and ULC-S650 if installing this product in Canada.
Receiving
Upon receiving the product, check to ensure all items are accounted for by
referencing the delivery receipt or packing list. Inspect each crate or carton
for shipping damage before accepting delivery. Alert the carrier of any damage
detected. The customer will make a notation of damage (or shortage of items)
on the delivery receipt and all copies of the bill of lading which is
countersigned by the delivering carrier. If damaged, immediately contact your
Accurex Representative. Any physical damage to the unit after acceptance is
not the responsibility of Accurex, LLC.
Unpacking
Verify that all required parts and the correct quantity of each item have been
received. If any items are missing, report shortages to your local
representative to arrange for obtaining missing parts. Sometimes it is not
possible for all items in the unit to be shipped together due to the
availability of transportation and truck space. Confirmation of shipment(s)
must be limited to only items on the bill of lading. Filters are shipped on a
separate skid in their original packaging. Do not remove factory packaging or
install filters until just before commissioning. Remove all other
shipping/packing materials.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the
skid when a forklift is used. The location of brackets varies by model and
size. Handle in such a manner as to keep from scratching or denting. A damaged
finish may reduce the ability of the unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be
installed and operated immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user assumes responsibility for
the unit and accessories while in storage. The manufacturer will not be
responsible for damage during storage. The ideal environment for storage of
the hood and accessories is indoors, above grade in a clean, dry atmosphere
that is sealed from the elements. While in storage, inspect equipment
routinely. If any moisture, dirt, or other accumulations are found on the hood
or any of the parts, the source should be located and eliminated.
Removing from Storage
As equipment is removed from storage to be installed in its final location, it
should be protected and maintained as outlined in the Handling section above.
Auto Scrubber Hood Function
Accurex’s Auto Scrubber hoods are designed for three primary functions:
- Capture and contain the effluent produced by the cooking process.
- Remove grease and other contaminants from the airstream with either one or multiple stages of mechanical filters.
- Wash the filters and other surfaces within the exhaust plenum to remove contaminants
NOTE
The wash sequence of the hood is not designed for fire suppression and will
not engage in the event of a fire.
NOTE
For information on the complete wash cycle, please refer to the Wash Sequence
of Operation, pages 21 and 22.
System Components
Hood
The hood is shipped from the factory pre-piped and ready to install. All wash
components within the hood are complete and ready for connection to hot water,
sanitary sewer drain, and electrical sources. If the Auto Scrubber Control
Panel is mounted on the hood, wiring from the control panel to the hood
lights, valves and sensors is completed by Accurex. All field plumbing and
wiring must conform to plumbing and electrical codes.
Auto Scrubber Control Panel (ASCP)
The control cabinet contains the water and electrical components, including
the Programmable Logic Controller (PLC), that controls the wash sequencing and
operations. The control cabinet also includes the detergent reservoir,
detergent pump, and other water piping.
NOTE
Filters are shipped loose with the hood and installed in the field. To
install the filters, perform the sequence of steps outlined on page 25 in
reverse.
Backflow Preventer
A backflow preventer will be shipped loose with the ASCP and will need to be
installed in-line with the hot water supply to the ASCP to prevent detergent
from back-feeding into the building water supply. Plumbing instructions begin
on page 13.
User Interface
The user interface will be either a keypad with LCD screen or touch screen. It
can be mounted on the Auto Scrubber control cabinet, hood or shipped loose for
remote mounting. It will provide a WASH button (WASH ON/OFF with touch
screen), and a means of turning on/off hood fans and lights, if applicable. It
also includes system alarm notifications to alert of any faults on the system,
such as a low detergent alarm.
NOTE
For detailed information on the Auto Scrubber Control Panel (ASCP), please
refer to the Accurex website, www.accurex.com
Hood Weights
Hood Weights
Hood Width
inches (cm)
| Length
4 feet
lbs. (kg)
| 8 feet
lbs. (kg)
| 12 feet
lbs. (kg)
| 16 feet
lbs. (kg)
48
(121.92)
| 244
(110.7)
| 398
(135.2)
| 553
(250.8)
| 707
(320.7)
51
(129.54)
| 250
(113.4)
| 404
(183.3)
| 559
(253.6)
| 713
(323.4)
54
(137.16)
| 256
(116.1)
| 410
(186.0)
| 565
(256.3)
| 719
(326.1)
57
(144.78)
| 262
(118.8)
| 416
(188.7)
| 571
(259.0)
| 725
(328.9)
60
(152.40)
| 268
(121.6)
| 422
(191.4)
| 577
(261.7)
| 731
(331.6)
63
(160.02)
| 274
(124.3)
| 428
(194.1)
| 583
(264.4)
| 737
(334.3)
66
(167.64)
| 280
(127.0)
| 434
(196.9)
| 594
(269.4)
| 743
(337.0)
69
(175.26)
| 286
(129.7)
| 440
(199.6)
| 600
(272.2)
| 749
(339.7)
72
(182.88)
| 292
(132.4)
| 446
(202.3)
| 606
(274.9)
| 755
(342.5)
CAUTION
To ensure proper structural support, all hanger brackets must be used for
hanging the hood.
Supply Plenum Weights and Dimensions
External Supply Plenum Type | Weight | Width | Height | Length per section |
---|---|---|---|---|
lbs/ft | kg/m | in. | mm | in. |
Air Curtain Supply (ASP)
| Refer to Air Curtain Supply Plenum Weight Table| Refer Air Curtain Supply Plenum Weight Table| ****
10 to 24
| ****
254.0 to 609.6
| ****
10
| ****
254.0
| ****
3 to 16
| ****
.91 to 4.88
Split Air Curtain Supply (Split ASP)| 15.5| 23.07| 24| 609.6| 10| 254.0| 3 to
16| .91 to 4.88
Back Supply (BSP)| 35.0| 52.09| 6| 152.4| Variable| Variable| 3 to 16| .91 to
4.88
Horizontal Supply (HSP)| 14.0| 20.83| 12| 304.8| 18| 457.2| 3 to 16| .91 to
4.88
Variable Supply (VSP)| 16.0| 23.81| 12| 304.8| 18| 457.2| 3 to 16| .91 to 4.88
Weight| Air Curtain Supply Plenum Width (inches)
---|---
10| 11| 12| 13| 14| 15| 16| 17| 18| 19| 20| 21| 22| 23| 24
lbs/ft| 8.3| 8.6| 8.9| 9.2| 9.5| 9.8| 10.1| 10.4| 10.7| 11.1| 11.3| 11.6|
11.9| 12.2| 12.5
kg/m| 12.35| 12.80| 13.24| 13.69| 14.14| 14.58| 15.03| 15.48| 15.92| 16.52|
16.82| 17.26| 17.71| 18.16| 18.60
Prior to Installation
Prior to installation, check with the Authorities Having Jurisdiction (AHJ)
on clearance requirements to structures surrounding the hood and other
equipment. Verify there is enough space to safely lift the hood up into its
operating position and enough clearance around the hood for components like
fire system connections, hood lights, hood control components, plumbing
connections, etc. Consider access for servicing the equipment and the
different components when locating the hood. The UL label located on the end
panel on the inside of the hood will provide pertinent information regarding
the hood installation. Information includes:
- Allowable cooking surface temperatures of the cooking equipment
- Front and side overhang requirements
- Minimum exhaust airflow requirements
- Hood lights load information and restrictions
- Filter information
- Fire damper fusible link replacement information, if applicable
Unpacking
Carefully remove the top of the crate and set aside all accessories in the
crate such as backsplash panels, control packages, and boxes with loose parts.
When removing the hood from the crate, place protective material on the floor
next to the crate to avoid damaging the hood. Lift the hood only by utilizing
the hanger brackets. Make sure the hood weight is evenly distributed. Slowly
lift the hood out of the crate and place on the protective material.
NOTE
If using straps, the straps should not interfere with plumbing on the top
of the hood in an effort to prevent internal piping damage which could cause
future leaks.
Hood Installation Overview
It is recommended that the protective plastic sheeting remain on the hood until fully installed to better protect the product from scratching and marking. Once removed, use stainless steel polish, such as BlueAway or equivalent, to clean the hood and/or remove marks or discoloration. Be sure to wipe with the grain and not against it.
-
If the hood is provided with filler panels, shipped loose, install them now. See page 7, Filler Panel Installation. Filler panels may be integral to the hood, which requires no additional installation.
-
If the hood is equipped with Clearance Reduction Methods, refer to pages 7 and 8 for special considerations with hanging the hood.
-
If the hood is provided with hood/duct sensors or thermostats that were shipped loose, install them now. See the Installation and Operations guide provided with the control panel.
-
If the hood was provided with either exhaust collars or supply collars that have shipped loose, it is recommended that the exhaust and supply openings are cut and collars are attached now, prior to hanging the hood. See Installing Duct Collars on page 8.
-
If the hood is provided with a back supply plenum (BSP) install it now. See page 9, Installing the Back Supply Plenum.
-
If possible, connect (weld) exhaust duct to the hood while on the floor, unless it prohibits the hood from being raised into place. For information on ductwork, see page 9, Ductwork.
-
At this point, drill holes in the building structural support system or utilize uni-strut to match up with the hanger bracket holes. Then slowly and evenly raise the hood into position and insert 1/2-inch
(12.7 mm) diameter threaded rod (provided by others) between the hanger brackets and structure. The hood hanging height requirements are given on the UL label. Typical canopy hood hanging height will be 80 inches (198.12 cm) off the finished floor.
NOTE
If the hood is supplied with ceiling enclosure panels, the height of the enclosures will typically be the distance from the ceiling to the top of the hood. Use this dimension to find the hood’s hanging height off of the floor.For questions regarding the supporting structure and its integrity, either the contractor or structural engineer needs to be consulted.
NOTE
All hanger brackets MUST be used and the hood must be properly supported while lifting to prevent damage or distortion to the hood.
NOTE
Ensure the hood is hung evenly to prevent drainage problems. Provide adequate support so that the hood does not move in a manner that is unacceptable to the Authorities Having Jurisdiction (AHJ).
WARNING
When mounting the hood or any components against the hood, never puncture or drill into the canopy unless otherwise instructed in this manual. Doing so will void the hood listing and warranty. -
If the hood was provided in sections with the continuous capture option, once each hood section is hung, install this option now. See page 9, Continuous Capture Plenum Hoods.
-
If the hood was provided with any front or side external supply plenums (other than the back supply plenum), install these now. See page 10, Installing Front/Side External Supply Plenums.
-
Install the remainder of both the exhaust and supply ductwork. For further guidelines see page 9, Ductwork.
-
If the hood is provided with any backsplash/sidesplash panels, install them now. See page 11, Installing Backsplash Panels.
-
If the hood is provided with any end skirts, install them now. See page 12, Installing End Skirts.
-
This is a Type I hood and it requires a fire suppression system. Once the hood(s) and ductwork are fully installed, appliance(s) are in place and walls are complete, the fire system should be completed.
If the hood is provided with a full factory-coordinated fire suppression system installation, the certified fire system installer should be contacted at this time to complete the final hookups, testing, and system certification based upon the manufacturer’s specification and local fire codes. If the hood is equipped with pre-piping only, and/or does not include fire suppression, it is the responsibility of a certified fire system installer to install, test, and certify the system based upon the manufacturer’s specifications and local fire codes. -
The Auto Scrubber Control Panel (ASCP), if shipped loose, will need to be installed at this time. Once mounted, plumbing and electrical wiring will need to be completed by the jobsite plumber and electrician. Typical site wiring responsibilities include wiring hood temperature sensors, hood lights, hood sequencing valves, fire suppression micro-switches, and fans (if applicable) to the control panel. Hood plumbing details are given on page 13-14, and hood electrical wiring details are provided on page 15-17.
-
If the hood is provided with enclosure panels, install them now. See page 18, Installing Enclosure Panels.
-
Install the rest of the hood accessories provided. This may include grease filters or condensate hood baffles, grease cups, light bulbs (provided by others unless LED tube style), light globes, and trim strips.
Filler Panel Installation
- Uncrate the hood and lay it on the floor with protective material between the hood and the floor.
- Bolt the filler panels together with 5/16 in. bolts provided in the hardware package.
- Position the filler panels to the hood back, and tackweld them into place.
- To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Clearance Reduction Methods
Clearance reduction methods have been evaluated and tested and are listed by UL (Underwriters Laboratory). The method of test was derived from the UL 710 test standard. The hood may be installed with zero clearance to combustible materials if constructed in the following manner.
- One inch (2.54 cm) thick layer of insulation of Owens Corning® Type 475, Johns Manville Type 475, IIG® MinWool-1200® Flexible Batt, or Knauf Insulation Type EI 475.
- Insulation must be held securely in place. Pins that are welded or secured with an adhesive may be used.
- A backsplash panel must be attached to the wall (insulated or uninsulated).
To comply with the UL Listing, the cooking appliances must be as follows:
-
Maximum surface temperature is 700°F (371°C)
-
Appliances are located at least 3 in. (7.62 cm) from the rear wall
-
Appliances are at least 40 in. (101.6 cm) below the bottom front edge of the hood
The hood may be installed with 3 in. (7.62 cm) clearance to limited combustible materials per NFPA 96 if constructed in one of the following methods: -
3 in. (7.62 cm) rear uninsulated stand-off
-
3 in. (7.62 cm) top enclosure panel system
-
3 in. (7.62 cm) end uninsulated stand-off
Top Clearance Reduction Options
One inch (2.54 cm) layer of insulation installed on top of the hood (optional)
meets zero-inch requirements for clearance to combustible surfaces as outlined
under the clearance reduction methods.
Three inches (7.62 cm) of uninsulated airspace installed on top of the hood (optional) meets NFPA 96 requirements for clearance to limited combustible surfaces.
Back and Front Clearance Reduction Options
One inch (2.54 cm) layer of insulation in 1 in. (2.54 cm) back stand-off meets
zero-inch requirements for clearance to combustible surfaces as outlined under
the clearance reduction methods. Three inches (7.62 cm) uninsulated back
stand-off meets NFPA 96 requirements for clearance to limited combustible
surfaces. One inch (2.54 cm) layer of insulation factory-installed on the
front of the hood (optional) meets zero-inch requirements for clearance to
combustible surfaces.
End Clearance Reduction Options
One inch (2.54 cm) layer of insulation factory-installed on the end of the
hood (optional) meets zero-inch requirements for clearance to combustible
surfaces under the clearance reduction methods. Three inches (7.62 cm) of
uninsulated airspace is installed on end of hood (optional). Meets NFPA 96
requirements for clearance to limited combustible surfaces.
Installing Duct Collars
Exhaust Duct Collars
-
The exhaust duct connection needs to be located within 48 in. (121.92 cm) from the center of the hood length to the center of the duct connection and within the shaded area as shown.
Top View of the Hood
NOTE
An 8x8x4-inch enclosure and sequencing solenoid valves will be mounted on top of the Auto Scrubber hood near the right or left-hand side. Avoid interference with these items by keeping the exhaust collars 20 inches from the end of the hood where these components are mounted.
-
The exhaust duct connection is to be a continuous liquid-tight weld. Utilizing the 1” (rectangular collars) or 1/2” (round collars) flange, weld with a non-ferrous filler wire, such as silicon bronze or stainless steel filler wire. Protect all stainless steel areas from weld splatter.
Supply Duct Collars to the Plenum
Place the duct collar(s) over the opening, fastening with tack-welds at 1 to 2
in. (2.54 to 5.08 cm) intervals, or sheet metal screws at 3 to 6 in. (7.62 to
15.24 cm) intervals.
Installing the Back Supply Plenum
Install the Supply Duct Collar
- Find the center of the back supply plenum.
- If the back supply plenum is to have one opening, cut the opening such that it is centered at L /2 from the plenum end. (Fig. 1)
- If the back supply plenum is to have two openings, cut openings such that they are centered at L /4 from each end of the plenum. (Fig. 2)
- Place the duct collar(s) over the opening(s), fastening with screws or tack‑welds every 4 to 6 in. (10.16 to 15.24 cm). (Fig. 3) Hang the Plenum
- Hang the back supply plenum from the ceiling. The back supply plenum needs to be mounted 31.25 in. (79.375 cm) above the finished floor. This is measured from the lowest rear edge of the back supply plenum to the finished floor. (Fig. 4) Hang using a threaded rod placed through the hanger brackets.
- Fasten the back supply to the wall, going through the lower back supply wall.
- These fasteners are to help maintain the location of the back supply and are not intended to hold the weight of the back supply unit.
- The fasteners should not interfere with the removable air diffusers.
Ductwork
- Exhaust – As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust duct systems must be constructed in the following manner:
- Materials: Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm (0.054 in.) (No. 16 MSG) in thickness, or stainless steel not less than 1.09 mm (0.043 in.) (No. 18 MSG) in thickness.
- Installation: All seams, joints, penetrations, and duct-to hood collar connections shall have a liquid‑tight external weld. If you have an automatic fire damper, please refer to that manual for installation instructions now.
- Supply – Supply ductwork (where applicable) should be connected to the hood in a manner approved by the local code authorities.
NOTE
For hoods with fire dampers in the exhaust and supply duct collars, an access
panel for cleaning and inspection shall be provided in the duct. This panel
shall be as close to the hood as possible but should not exceed 18 in. (45.72
cm). For proper installation of duct collars when they are shipped unattached.
Continuous Capture Plenum Hoods
- Remove the support angles provided for support during shipping on the open-end panels. Install and level both hoods.
- After leveling, secure the hoods together by tack welding and/or bolting the angles that are located at the top of the hoods along their width (Fig. 5).
- Next, fasten the hoods together at its inside plenum profile using u-clips and bolts (Fig. 6). Caulk this joint with NSF-approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
Installing Front/Side External Supply Plenums
Using Uni-strut
The uni-strut (supplied by others) supporting the hood may be cantilevered over the end of the hood. Utilizing the external supply plenum’s hanger brackets, securely fasten to the uni-strut.
Air Curtain Supply (ASP) Horizontal Supply Plenum (HSP) Variable Supply Plenum (VSP) Mounted with uni-strut and threaded rod When using uni-strut (supplied by others), it must be bolted to the hood and external supply plenum hanger brackets.
NOTE
The uni-strut needs to be the full length of the hood and the external supply
plenum.
Using Hanger Brackets and Threaded Rod
-
Insert 1/2 in. (12.7 mm) diameter threaded rod (by others) into hanger brackets on the external supply plenum top. Raise and hang the external supply plenum from adequate roof or ceiling supports.
NOTE
Ensure the external supply plenum is installed flush with the hood front and is plumb and level by adjusting the threaded rod(s). There should be no gap between the bottom of the external supply plenum and the hood after installation and adjustments are completed. -
The external supply plenum should be resting lightly against the hood. The hood is only used to position the plenum; it is not intended to support the plenum. All hanger brackets on the external supply plenum must be used and the plenum must be properly supported while lifting to prevent damage or distortion. The external supply plenum must be level to operate properly.
NOTE
After hanging, secure the external supply plenum to the hood (or to another external supply plenum) using the supplied turnbuckle(s). Use caution tensioning the turnbuckle. Too much tension may cause the bottom of the external supply plenum to pull away from the hood or cause the face of the hood to become deformed. -
It is recommended that caulk be applied at the mating seams and surfaces of the external supply plenum, the hood, and the wall. If the external supply plenum is next to a wall, you will need to caulk around the surface next to the wall. Caulk the joints with NSF-approved silicone caulk (GE SCS1009, or its equivalent). The caulk is not provided.
Installing the Supply Duct Collar to the Plenum
Place the duct collar(s) over the opening, fastening with tack-welds at 1 to 2
in. (2.54 to 5.08 cm) intervals, or sheet metal screws at 3 to 6 in. (7.62 to
15.24 cm) intervals.
Flat Backsplash/Sidesplash Panel
- Material: Stainless
NOTE
- Panel lengths up to 47.25 inches (1200.15 mm) wide ship in one piece; panel lengths over 47.25 inches (1200.15 mm) ship in multiple pieces when panel height is <66 inches (1674.4 mm) or >80 inches (2032 mm).
- Panel lengths up to 48 inches (1219.2 mm) wide ship in one piece; panel lengths over 48 inches (1219.2 mm) ship in multiple pieces when panel height is ≥66 inches (1676.4 mm) or ≤80 inches (2032 mm).
- After the hood is hung into position, slide the flat flange of the backsplash/sidesplash panel behind the back/side of the hood. If the hood is provided with flat backsplash/sidesplash panels, divider bars will be provided. Install divider bars between panels as shown in the flat backsplash/sidesplash panel section view.
- After the panels and dividers have been positioned, drill holes in the panel and fasten to the wall. (Fasteners provided by others). The holes should be spaced to adequately secure the panel to the wall.
- Caulk the joints between the hood and the panel with NSF-approved silicone caulk (GE SCS1009 or its equivalent). Caulk provided by others.
- Caulk the joint between the panels when multiple insulated panels are required with NSF-approved (GE SCS1009 or its equivalent). Caulk provided by others.
Insulated Backsplash/Sidesplash Panel
NOTE
Panels up to 45 in. (1143 mm) wide ship in one piece; over 45 in. (1143 mm) in
multiple pieces.
Installing End Skirts
- After the hood is hung in position, line up the top of the end skirt with the end panels of the hood.
- Drill a hole in the hood end panel to line up with the hole in the end skirt. Attach the end skirt with a 1/4 in. bolt and cap nut to the inside of the hood, or tack-weld the end skirt to the hood.
- Position the end skirt against the wall and attach. The method depends on the wall construction. (Fasteners provided by others).
- Caulk the internal joint formed by the end skirt and the hood end panel with NSF-approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
- To allow for ease in cleaning, also caulk all the external seams.
Plumbing Connections
TOP VIEW OF AUTO SCRUBBER CONTROL PANEL (ASCP)
FRONT VIEW OF AUTO SCRUBBER CONTROL PANEL (ASCP)
- Electrical Control Cabinet
- Detergent Pump
- Detergent Tank
- Hot Water Outlet Connection to Hood
- Hot Water Inlet Connection
- Cold Water Outlet Connection to Hood
- Cold Water Inlet Connection
- Inlet Valve
- Install the factory-provided backflow preventer (shipped loose) and drain connection per local codes.
- Bring a 1-inch hot water supply line to the backflow preventer.
- Plumb a 1-inch line from the outlet of the backflow preventer to the hot water inlet in the control cabinet.
- If the cabinet is remotely mounted, connect the hot water outlet on the controls cabinet to the hot water inlet on the top of the hood.
- If the system is configured for cold water mist, bring 0.75-inch water piping to the cold water mist inlet in the control cabinet.
- If the cabinet is remotely mounted and the system is configured for cold water mist, connect the cold water mist outlet on the controls cabinet to each hood with a cold water mist solenoid valve
- Plumb a 2-inch drain on each hood to grease trap (floor).
NOTE
- Hot water temperature should be 140°F.
- While the hood is washing, water pressure in the control panel should be between 40 and 70 PSI.
- Cold mist water pressure should be between 20 and 40 PSI.
Detergent Tank Installation
The detergent tank is located in the plumbing section of the ASCP. The tank
provided can hold up to 2.5 gallons of detergent. It will need to be checked
periodically depending on detergent use and filled with the recommended
chemical detergent. The tank is also equipped with a float that will trigger
an alarm to warn the user when detergent is low. Steps for removal and
installation of the detergent tank are as follows:
Removal
- Disconnect the two float switch wires at the quick connect electrical fittings.
- Remove the 1/4-inch detergent line that enters the tank thru the screw on cap.
- Lift out the detergent tank from the utility cabinet.
- Unscrew the 63 mm cap from the tank; this will remove the float assembly.
- Fill the tank with the approved detergent.
Install:
- Install the 63 mm cap and float assembly into the detergent tank.
- Lift the detergent tank back into the utility cabinet.
- Install the 1/4-inch detergent line thru the hole in the 63 mm cap.
- Connect the two float switch wires at the quick connect electrical fittings.
Detergent Requirements
Detergent model X-701 manufactured by ZEP, Inc., is recommended by Accurex for
use in the wash system. This product is biodegradable, non-caustic, and safe
for kitchen staff to use. If X-701 detergent is not used, the cleanliness of
the exhaust plenum and filters cannot be guaranteed.
NOTE
- X-701 is manufactured by ZEP, Inc., Atlanta, GA, USA. For details and ordering information, call 1- 800-371-6858.
- If washed once a day, the 2.5 gallon detergent tank will last approximately 24 to 30 days depending on filter type.
Preventative Maintenance
The following practices will prolong the life of the detergent pump:
- Keep detergent tank filled.
- Avoid spilling detergent on the exterior of the pump.
- Clean the detergent tank at least every six months.
- Clean the detergent line strainer at least every six months.
- Check tightness of all fittings periodically.
The detergent pump motor has sealed bearings which do not require lubrication.
Typical Plumbing Connection Layout
HOT WATER CONNECTIONS:
A| 1-inch hot water supply from building to Backflow Preventer
B| 1-inch hot water piping from Backflow Preventer to control cabinet
C| 1-inch hot water piping from control cabinet to hood(s)
COLD WATER CONNECTIONS, optional with continuous cold water mist
D| 3/4-inch cold water supply from building to control cabinet
E| 3/4 inch cold water piping from control cabinet to hood(s)
DRAIN CONNECTIONS FROM AUTO SCRUBBER HOOD(S):
F| 2-inch male NPT connection to building drain with grease trap (one per hood
section)
Electrical Connections
NOTE
All wiring of electrical equipment must be done to meet NEC and local codes.
NOTE
It is recommended that shielded wire be used for all low-voltage connections
(24V or less) to prevent signal interference with other high-voltage circuits.
WARNING
All 115 VAC field wiring (or higher) must be high temperature rated and
must be routed through hard or flex conduit. All low-voltage field wiring
should be plenum-rated if not routed through the conduit. All field wiring
should not come in contact with the surface of the hood.
This section will provide some field wiring information for connections directly to the hood. For all other wiring connection requirements for the Auto Scrubber ControlPanel (ASCP), please refer to both the Auto Scrubber Control Panel Installation, Operation and Maintenance manual and the job specific wiring diagram located on the inside door of the control cabinet.
Hood Lights
If the hood is provided with lights, a junction box will be located on top of
the hood for field connections. Use a minimum 14 AWG copper wire. Light bulbs
will not be provided (unless equipped with LED tube-style fixtures). For
incandescent or compact fixtures, standard light bulbs up to 100 watts may be
used.
- 115 VAC, power for hood lights, one per light circuit (Terminals H1, N1 | H2, N2 | H3, N3 | H4, N4)
- 115 VAC, power to lights, one per light circuit (Terminals B1, W1 | B2, W2 | B3, W3 | B4, W4)
CAUTION
For multiple hood systems that have more than 14 lights total, incandescent or
fluorescent, the hood lights must be wired to multiple circuits. Each circuit
must have less than 14 lights total.
Keypad – if equipped
- Connect factory provided cable from back of keypad to CAREL® PCO5+ controller (Terminal J10) PCO5+ J10 KEYPAD CONNECT FACTORY PROVIDED RJ25 CABLE TO J10 ON PCO5+ AND BACK OF KEYPAD
Touch Screen – if equipped
Power Wiring
- Connect factory provided 2-wire cable from Vari-Flow (Terminals TS24, TSC) to touch screen (Terminals G, GO)
Control Wiring
- Connect factory provided 3-wire cable from Vari-Flow (Terminals -, +, GND) to touch screen (Terminals -, +, GND)
Solenoids and Temperature Sensors
Each Auto Scrubber hood will include an 8x8x4 enclosure factory wired to
the hood solenoids and sensors. If the Auto Scrubber Control Panel (ASCP) is
not mounted on the hood, the field will need to wire from the 8x8x4 enclosure
back to the ASCP. The hood sensors and solenoids are low voltage, therefore,
18 gauge stranded wire is recommended. The two wires of each hood sensor are
not polarity-sensitive. The wiring diagram provided by the ASCP will display a
table showing which sensors/solenoids connect to each hood. If more than one
hood is being controlled, be sure that the appropriate sensor/solenoid is
wired to the appropriate terminals as depicted on this diagram.
Wash Hood Solenoids
- Wire between control panel terminal WO-_A and hood j-box terminal WO-_A
- Wire between control panel terminal WO-_B and hood j-box terminal WO-_B
- Wire between control panel terminal 24C and hood j-box terminal 24C
- Wire between control panel terminal GND and hood j-box terminal GND Wash Hood Temp Sensor 1 – if equipped
- Wire between control panel terminal T-A and hood j-box terminal T-A
- Wire between control panel terminal T-B and hood j-box terminal T-B Wash Hood Temp Sensor 2 – if equipped
- Wire between control panel terminal T-A and hood j-box terminal T-A
- Wire between control panel terminal T-B and hood j-box terminal T-B
NOTE
The resistive temperature detectors (RTD), or sensor probes, should not be
exposed to direct flame. The RTD’s are rated up to 250°F.
CAUTION
Exposing the sensor to direct flame may render the sensor inoperable and will
void the warranty.
Typical Electrical Connection Layout
A | 115/1, 15A Circuit (Control Power) |
---|---|
B | 115/1, 15A Circuit (Light Power) |
C | Input Power for Exhaust Fan(s) (if applicable) |
D | Input Power for Supply Fan(s) (if applicable) |
E | Input Power for Supply Fan(s) Controls (if applicable) |
F | Control Wiring to User Interface (Keypad or Touch Screen) Cable(s) provided |
by Accurex
G| Power to Hood Lights
H| Control Wiring to Wash Solenoids
I| Control Wiring to Temperature Sensors
J| Output Power to Exhaust Fan(s) (if applicable)
K| Output Power to Supply Fan(s) (if applicable)
L| Control Wiring to Supply Fan(s) (if applicable)
- A 115/1, 15A Circuit (Control Power)
- B 115/1, 15A Circuit (Light Power)
- C Input Power for Exhaust Fan(s) (if applicable)
- D Input Power for Supply Fan(s) (if applicable)
- E Input Power for Supply Fan(s) Controls (if applicable)
- F Control Wiring to User Interface (Keypad or Touch Screen) Cable(s) provided by Accurex
- G Power to Hood Lights
- H Control Wiring to Wash Solenoids
- I Control Wiring to Temperature Sensors
- J Output Power to Exhaust Fan(s) (if applicable)
- K Output Power to Supply Fan(s) (if applicable)
- L Control Wiring to Supply Fan(s) (if applicable)
Installing Enclosure Panels
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork attached and all fire system and electrical connections completed.
- Position the end enclosure panels on the hood, and clamp into place with clamps provided or tack-weld the panels into place.
- Fasten the end enclosure panels to the wall; the method depends on wall construction. (Fasteners provided by others). If the hood is a double island, bolt the end enclosure panels together. (Fasteners provided by others).
- Position the front enclosure panel(s) on the hood, and bolt to the end enclosure panels with the 5/16 in. bolts provided in the hardware package.
- Tack-weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be positioned 4 in.(10.16 cm) from the ends and in the center of the front enclosure panel. If hthe ood is provided with supply plenums, the front enclosure panel should be tack welded or use self-tapping screws on the inside of the front panel to secure the panel in place to the ASP.
- To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk
(GE SCS1009, or its equivalent). The caulk is not provided.
NOTE
Installation instructions may not be applicable for concrete ceilings.
Double Island Canopy Style Hoods
NOTE
Before hanging the hoods, please verify the hood marks to ensure the
correct hood is hung on the correct side.
A double island hood is created by installing two wall style hoods back to back. Use the installation procedure described for single island canopy hoods; install and level both hoods. After leveling, secure the hoods together by tack-welding and/or bolting the rear mounting brackets together. Double island hoods may also be provided with a U-Channel to seal the seam between the two hoods. Double island hoods may be provided with a common exhaust duct – if provided, the hoods’ exhaust collars will align to form a single exhaust collar to affix the duct to. When a common exhaust duct is not provided, the collars will be separate and not form one collar.
Installing U-Channel Strip
- After the hood is hung in position and leveled, apply caulk to the inside edge of the double island clip.
- Position and install the clip by tapping into the position along the clip (friction fit).
- Caulk edges to seal out grease and allow for ease of cleaning. Caulk with NSF Approved silicone caulk (GE SCS1009 or its equivalent). The caulk is not provided.
Initial System Start-Up
-
Clean the control cabinet of any debris that may have entered the cabinet during installation.
-
Add detergent to the detergent tank in the cabinet.
-
Turn the power on to the hood and control the cabinet and fans (if applicable).
-
Check electrical power is correct for hood controls, lights (if applicable), and fans (if applicable).
-
Confirm the CAREL controller is operational; the display should be illuminated.
-
If the system is controlling fans, turn the fans on via the user interface. Check fan rotation and confirm exhaust and supply air volumes are correct (per design). After this has been completed, turn the fans off.
-
Turn on the water supply.
-
Prime the detergent pump. On the CAREL controller, navigate to Service > Wash Settings > “Prime Detergent Pump” menu screen. Changing “OFF” to “ON” will start the detergent pump. Monitor the detergent Prime Detergent Pump line and press the ESC key once the detergent reaches the hot water line. This will stop the detergent pump.
-
If the filter access doors are not installed, install them now. Instructions for installing filters and access doors can be found on page 25.
NOTE
Ensure the access doors are installed before starting any wash cycles. Running a wash cycle without the doors in place will result in water spraying on the cooking line-up/area below the hood. -
10. Run a test wash. On the CAREL controller, navigate to Service > Wash Settings > Hood Test Wash Setup menu screen. Adjust the times as necessary on the screen; change NO to YES. A test wash will start.
While the hood is washing, ensure water is not leaking through the edges of the access doors or anywhere else in the exhaust plenum. Ensure the grease drain and trap are not plugged, or kitchen flooding may occur. Water pressure while the hood is washing should be between 40 and 70 PSI. Monitor the inlet pressure and temperature gauge in the ASCP through one wash cycle. At any time, the test wash can be aborted by pressing the ESC key.
System Operation
NOTE
The information given in this section provides basic instructions for
operating the user interface provided with the Auto Scrubber Control Panel
(ASCP). For more detailed information regarding the operation of the control
panel, as well as all electrical and plumbing requirements, please reference
the Auto Scrubber control panel Installation, Maintenance, and Operation
Manual. This manual will ship with the control package and can also be found
on accurex.com
Fan Operation (if equipped)
If the hood system is equipped with fan control, start/stop the fans
exhausting and supplying the hoods from the user interface.
-
KEYPAD – Press the button next to the “ALL HOODS” text on the keypad to start/stop all of the hoods. If the keypad has a button labeled “HOODS”, pressing this button will navigate to a set of screens where the user can individually start/stop different fans.
-
TOUCH SCREEN – Press the “ALL HOODS ON/OFF” icon on the touch screen to start/stop all of the hoods. If the touch screen has an icon labeled “INDIVIDUAL HOOD SYSTEMS ON/OFF”, pressing this will navigate to a screen where the user can individually start/stop different fans.
-
Hood Light Operation (if equipped)
If the hood system is equipped with light control, turn on/off the hood lights from the user interface. -
KEYPAD – Press the button next to the “ALL LIGHTS” text on the keypad to turn on/off all hood lights. If the keypad has a button labeled “LIGHTS”, pressing this button will navigate to a set of screens where the user can individually start/stop different hood light circuits.
-
TOUCH SCREEN – Press the “ALL LIGHTS ON/OFF” icon on the touch screen to turn on/off all hood lights. If the touch screen has an icon labeled “INDIVIDUAL LIGHT ON/OFF”, pressing this will navigate to a screen where the user can individually turn on/off different hood light circuits. Wash Operation (if equipped) A hood wash can be initiated through several different options.
-
Wash by Button (Factory default = ON): A wash can be initiated by pressing either the “WASH” button (if equipped with a keypad) or by pressing the “WASH ON/OFF” icon (if equipped with a touch screen).
-
Wash by Digital Input (Factory default = OFF): A wash can be initiated by engaging a configured digital input on the controller. For the correct terminals to wire this digital input, please reference the Auto Scrubber Control Panel wiring diagram.
-
Wash by BMS Interface (Factory default = OFF): A wash can be initiated by engaging a BMS read-write point. Point lists can be found in the Auto Scrubber Control Panel IOM.
-
Wash by Scheduler ( Factory default = OFF): A wash can be initiated daily at a specific time. If this option
is enabled, this time can be field adjusted within the controller and touch screen if equipped. -
Wash by Auto Start (Factory default = ON): Each individual hood can be washed after that hood’s fan(s) has been running for a pre-determined time (factory default is 8 hours). This time setting and the maximum allowable auto start washes can be field adjusted within the controller and touch screen, if equipped.
NOTE
Auto Start will only enable to Auto Scrubber hoods. It cannot be used to
engage duct sump washes.
With exception to the Auto Start option, when a wash cycle has been initialized the Auto Scrubber hoods will be washed in order starting with Auto Scrubber hood 1. If duct sumps are also connected to this system, they will be washed in order after the Auto Scrubber hoods have been washed. A wash cycle can be stopped at any time by pressing the “WASH” button (if equipped with a keypad) or by the “WASH ON/OFF” icon (if equipped with a touch screen). An Auto Scrubber hood will be prevented, or abort operating in the wash cycle, should one of the following events occur:
- A kitchen fire alarm is detected.
- A sensor linked to the Auto Scrubber hood fails.
- The option to disable a wash during temperature interlock is on (factory defaulted on) and a sensor linked to the Auto Scrubber hood exceeds the temperature interlock on setpoint.
- If the Auto Scrubber control panel is equipped with no fan controls (ASCP-W) and the fan input is triggered.
A fan exhausting an Auto Scrubber hood cannot be controlled by the user (turned on and off) while that Auto Scrubber hood is washing. If multiple Auto Scrubber hoods are employed, a fan linked to an Auto Scrubber hood which is not currently washing can be controlled by the user (turned on and off) as normal.
NOTE
Duct sumps may be controlled by this Auto Scrubber system. A duct sump is a
grease reservoir installed in low points of a grease duct which also requires
routine wash downs.
When duct sumps are washing, fans cannot run, unless:
- A kitchen fire is detected
- A sensor linked to any Auto Scrubber hood fails, or any temperature sensor exceeds the temperature interlock on setpoint
- If the Auto Scrubber control panel is equipped with no fan controls (ASCP-W) and the fan input is triggered
Wash Sequence of Operation
NOTE
The previously stated items regarding ending a wash cycle/skipping a hood wash
still apply. Please use this in conjunction with the information found in the
System Operation section.
Wash Sequence of Operation
Wash Cycle Factory Default Times
Wash Cycle Stage| Time (seconds) Based on Filter Type
Baffle Grease-X-Tractor™| Grease Grabber™
Pre-Wash Delay| 10| 10
Pre-Soak Spray| 60| 60
Pre-Soak Detergent| 30| 30
Soak| 60| 60
Top Wash| 120| 300
Top Wash Detergent| 60| 150
Between Sequence Delay| -5| -5
Bottom Wash| 120| 240
Bottom Wash Detergent*| 60| 60
Drip Dry| 60| 60
Fan Dry| 120| 120
Detergent Stage Runs Detergent Pump Concurrent with Prior Spray/Wash Stage Underlined stages are times when water is spraying Wash consists of one nozzle per foot per manifold. The unit consists of two manifolds, one above and one below the filter. Total water usage is approximately 1.44 gpm/foot.
NOTE
The wash times are based on filter cleaning tests using filters coated heavily
with oil and then baked using high temperatures. Actual required cleaning
times will vary based on cooking equipment, fuel type, cooking frequency, and
the food prepared. The table shown above should be used as a starting point.
After a few weeks, the field can make adjustments as necessary based on the
cleanliness of the filters upon removal/inspection (see Maintenance on page
25).
Airflow Testing Procedure
For measuring exhaust airflow rates (cubic feet per minute = CFM), use a short ridge meter to measure velocities along the inlet slot of the hood. To ensure accurate data, all appliances should be on. Multiple locations need to be tested as outlined below to ensure an accurate reading.
Hood Length | Number of Test Locations |
---|---|
48 to 69 inches | 2 |
70 to 109 inches | 4 |
110 to 139 inches | 6 |
140 to 174 inches | 8 |
175 to 192 inches | 10 |
To take velocity readings along the length of the hood, the short ridge meter must be evenly spaced along the length of each door to provide two readings per door. The vertical placement of the short ridge meter along the inlet slot is shown.
After the appropriate number of readings have been taken from the inlet slot of the hood, an average reading can be calculated by summing the velocity readings and dividing the total value by the number of readings taken.
- Average Velocity
- The sum of Velocity Readings
- Number of Readings
Next calculate the total hood airflow volume (CFM) by using the following equation: Hood CFM = [(Length of Hood in inches x 3.398) x (Average inlet slot velocity x 3.6)] ÷144
NOTE
The constants 3.398 and 3.6 are factory-derived for use with the Auto Scrubber
hood.
Calculation Example:
Four (4) inlet slot velocity readings (minimum)
Hood Length | 96 inches |
---|
Test Location
(left to right; in inches)
| 6| 27| 48| 69
Velocity Reading (fpm)| 224| 242| 228| 236
- Average Velocity (FPM) = (224 + 242 + 228 + 236) ÷ 4 = 233 FPM
- Hood Exhaust Rate (CFM) = [(96 x 3.398) x (233 x 3.6)] ÷ 144 = 1900 CFM
Additional Wiring Schematics
Ansul® Wiring Plan View
- Snap-Action Switches may be wired as shown. Typical examples are shown.
Manual Reset Relay Part No. 426151
Electrical Rating
- 1/3 HP, 10 AMP, 115 VAC
- 1/2 HP, 10 AMP, 240 VAC
- 13 AMP, 28 VDC
Note:
- Denotes field installation.
- Denotes factory installation.
- Gas Valves: “UL Listed electrically-operated safety valve for natural or LP gas as needed, of appropriate pressure and temperature rating, 115V/60Hz” or Ansul gas valves.
- Do not use black wire on the snap-action switch in a normal installation. Black wire may only be used for extraneous alarms, light circuits, etc.
Amerex® Wiring Plan View
Basic Wiring Diagram
NOTES
- Denotes field installation
- Denotes factory installation
- GAS VALVE: UL Listed electronically-operated safety valve for natural or LP Gas as needed of appropriate pressures and temperature rating, 115V/60 Hz or Amerex gas valves, PN 12870, 12871, 12872, 12873, 12874, 12875 and 12876.
- K1a and K1b are N.0. when K1 is de-energized.
Maintenance
Filters
The first or primary stage (baffle or Grease-X-Tractor™) filters and second
stage (Grease Grabber™) bead filters (if applicable) need to be inspected one
week after start-up, then once every two weeks to make certain the filters are
positioned correctly (no gaps between filters) and that the wash system is
adequately cleaning the filters. To inspect the filters, remove all access
doors. Each door is held in place with two cammed latch handles. Turn the
handles and remove the doors. Images 1 and 2.
Once the doors are removed the filters can be removed. If the hood contains second-stage filters, these will also need to be removed. While holding the handles of the filter, push the filter up and lift the bottom of the filter out of its track. Then pull the filter out of the hood. Images 3, 4, and 5. Repeat this for all the second-stage filters.
Once the second-stage filters are out, (Image 5) the first-stage filters can be removed in the same manner. Image 6. Depending on the equipment under the hood, it might be easier to remove the filters from the left or right side. In that case, slide the filters towards the end which allows for easier removal.
After inspection, insert the filters back into the hood. Primary filters go in first, then the second stage filters (if applicable). After installing all the filters, make sure the filters are positioned correctly in the hood. There should be no gaps between the filters. If for some reason the filters don’t seem to be getting adequately cleaned, or if the filters appear damaged, consult the factory.
Capture Tank
The interior surfaces of the hood capture tank should be wiped down weekly.
Auto Scrubber Start-Up Checklist
Check boxes when the item has been verified and reviewed with the customer.
Hook-Up
Electrical Connections
- Confirm all electrical connections are made per the Auto Scrubber Control Panel (ASCP) wiring diagram.
- Turn on all hood, light, and fan power (if applicable).
- Check voltages on incoming lines to confirm these are correct.
Plumbing Connections
- Plumb 1-inch hot water piping to the backflow preventer, then from the backflow preventer to inlet hot water connection in the control cabinet.
- Plumb 0.75-inch cold water piping to inlet cold water mist connection in the controls cabinet (if applicable).
- Plumb water connections from the control cabinet to each hood.
- Plumb 0.75-inch cold water piping to cold water mist connection in the controls cabinet (if applicable).
Detergent
- Detergent tank filled with proper detergent.
- Low detergent tubing and strainer should be at the bottom of the detergent tank.
- Prime detergent pump.
Start-Up
Test Fan/Light Control Modes (if applicable)
- Confirm fan operation/rotation when enabled/disabled by the user interface.
- Confirm hood light operation when enabled/disabled by the user interface.
Run Test Wash
- Test wash instructions on page 20.
- Confirm solenoids and detergent pump are engaging correctly based upon the sequence of operation found on pages 21 and 22.
- Record hot water pressure during the wash. Should be between 40-70 PSI
- Record cold water mist water pressure, if equipped. Should be between 20-40 PSI
- Record hot water temperature during the wash. Should be 140°F
- Adjust water pressure if needed using the throttling valve. For cold water mist only
Miscellaneous
Fire Mode Test
- Trip fire system microswitch. Confirm fan/light operation (if applicable) and wash stopping when in fire mode.
- The alarm message should appear on the user interface and main controller.
Low Detergent Mode
- If removing the float from the tank, the user interface and controller should display a low detergent alarm. Replacing the float in the tank (filled with detergent), the low detergent alarm should disappear.
Hood Access
- Confirm the hood access panels fit tightly to prevent water from spraying out of the exhaust plenum onto appliances.
Cleaning
- Is the hood cleaning properly? If not, refer to the troubleshooting guide on pages 25 through 27.
Troubleshooting
Parts List
Part Number | Description |
---|---|
385987 | Detergent Float |
481461 | Wash Nozzle |
456767 | Cold Water Mist Nozzle |
481463 | 24V Coil for Solenoid |
381050 | 3/4-inch Solenoid Valve |
456765 | Pressure Gauge |
479363 | Temperature Gauge |
851709 | 16H x 16W Grease-X-Tractor™ SS Filter |
851710 | 16H x 20W Grease-X-Tractor™ SS Filter |
852881 | 16H x 16W Grease Grabber™ Second Stage Filter |
852880 | 16H x 20W Grease Grabber™ Second Stage Filter |
457627 | 16H x 16W Stainless Steel Baffle Filter |
457629 | 16H x 20W Stainless Steel Baffle Filter |
Maintenance Log
- Date_ ___Time__ AM/PM
- Notes:____
Our Commitment
As a result of our commitment to continuous improvement, Accurex reserves
the right to change specifications without notice. Product warranties can be
found online at accurex.com, either on the specific product page or in the
Warranty section of the website at
Accurex.com/Resources/Warranty.
- P.O. Box 410 Schofield, WI 54476
- Phone: 800.333.1400 • Fax: 715.241.6191
- Parts: 800.355.5354 • accurex.com
- 481488 • Auto Scrubber, Rev. 6, March 2024