LEITER Vacuum Plate 300 Instruction Manual

June 9, 2024
LEITER

LEITER Vacuum Plate 300

LEITER-Vacuum-Plate-300-product-image

Operating instructions (Translation of the Original User Manual)

Congratulations on purchasing your VACUUM PLATE 300
You have chosen a first-class vacuum testing device.
It was developed and produced in accordance with the latest technology in the plastics-processing industry. It has also been manufactured using high-quality materials.
Please always store these operating instructions with the device.

VACUUM PLATE 300 testing device
You can find more information about the VACUUM PLATE 300 at www.leister.com

LEITER-Vacuum-Plate-300-1

Important safety instructions

Warning
Dangerous voltage, danger to life from electric shock:
There are live components inside the device. Maintenance and repairs are to be carried out by trained specialist personnel only. If the housing is damaged, the power cord must be disconnected from the power source immediately. Keep the device away from moisture and wet conditions. Before starting, check the power cord, the plug and the extension cable for electrical and mechanical damage.

Fire and explosion hazard
Admixtures (e.g. combustible or explosive gases or vapors), traces of oil, oil vapor and grease must not be sucked in. Any operation in a potentially explosive environment is prohibited. The device must only be operated with the filter plate installed.
No hazardous leak tracer is to be used for testing the weld seams. There is a risk of inhalation of liquid particles. Read the material safety data sheet from the manufacturer of the material and follow that company’s instructions.

Risk of injury from plastic chips at startup
Damaged plastic glass can lead to implosion. This may cause eye injuries. The plastic glass must be protected against mechanical damage by impact or fall, for example. Do not put a defective VACU-UM PLATE into operation. Wear protective goggles.
Vacuum blower causes high noise levels. There is therefore a risk of hearing damage while operating the device. Wear hearing protection.
Risk of inhalation of dust particles while operating the device. If the membrane is contaminated, dust particles can be sucked in and ejected by the blower. The membrane must be free of impuri-ties in the test area.
If the device is being used on construction sites, a fault current circuit breaker must be used to protect site personnel from electrical shock due to dampness and moisture.

Caution
Risk of burns
The device may only be operated at intervals. If the on duration is too long (>2min), the temperature on the motor housing can cause burns. Always allow the device to cool down. The device can only be operated using the handles and switches provided. The main switch must be switched off in the event of a mains voltage failure.
The device should only be operated by trained specialists or under their supervision. Children are not permitted to operate the device.
Be aware of hazards in the surrounding area, e.g., risk of tripping, risk of slipping, strong sunlight, unattended equipment, etc.
The local supply voltage must match the nominal voltage specified on the device. Incorrect mains voltage can cause the device to fail. The main switch must be switched off in the event of a mains voltage failure.

Application

Intended use

The VACUUM PLATE 300 is intended for professional use and is used to check the weld seams for leaks.
The VACUUM PLATE 300 is intended for generating a vacuum in interval operation for max. 2 minutes ON/30 seconds OFF.

Material types and material thicknesses
The VACUUM PLATE 300 can be used for testing various material types such as PE-HD, PE-LD, TPO/FPO, PP and PVC. The permissible material thicknesses of the indicated materials are 1 – 3 mm.
Use only original Leister spare parts and accessories; otherwise, any warranty or guarantee claims will be invali-dated.

Non-intended use

Any other use or any use beyond the type of use described for the VACUUM PLATE 300 is deemed non-intended use. Test operation is not permitted in case of condensation (e.g. rain).

Technical data

LEITER-Vacuum-Plate-300-2

Subject to change without prior notice.

Transport

Warning
Do not use the carrying handle (8) on the device for transporting with a crane.

Note
When transporting the device, store and secure it in a way that prevents any mechanical damage. The device must always be stored on a flat surface, otherwise the sealing lip (7) can become permanently deformed.

Use the carrying handles (8) to lift the vacuum tester.LEITER-Vacuum-
Plate-300-3

Your VACUUM PLATE 300

Type plate and identification

The model and serial number are indicated on your device’s name plate (10). Please transfer this information to your instruction manual. In the event of any inquiries to our representatives or authorized Leister Service Centers, please always refer to this information.
Model:…………………………………………………………………………………………………………………………………………..
Serial no.: ………………………………………………………………………………………………………………………………………

Example:

LEITER-Vacuum-Plate-300-4

Scope of delivery (Standard equipment in cardboard box)
  • 1 x VACUUM PLATE 300 device
  • 1 x Original Quick Guide
  • 1 x Safety instructions
Overview of device parts

LEITER-Vacuum-Plate-300-5

  1. Mains connection line
  2. Main switch
  3. Vacuum blower
  4. Filter plate
  5. Pressure gauge
  6. Sight glass
  7. Sealing lip
  8. Carrying handle
  9. Pressure setting valve (Vari-Flow valve)
  10. Type plate with model designation and series marking
  11. Cooling openings
  12. Suction air outlet
  13. Device-protective circuit-breaker

Operation of your VACUUM PLATE 300

Work environment and safety

Warning
Dangerous voltage, danger to life from electric shock:
If the housing is damaged, the power cord must be disconnected from the power source immediately. Keep the device away from moisture and wet conditions. Before starting, check the power cord, the plug and the extension cable for electrical and mechanical damage.

Fire and explosion hazard
Admixtures (e.g. combustible or explosive gases or vapors), traces of oil, oil vapor and grease must not be sucked in. Any operation in a potentially explosive environment is prohibited. The device must only be operated with the filter plate installed.
No hazardous leak tracer is to be used for testing the weld seams. There is a risk of inhalation of liquid particles. Read the material safety data sheet from the manufacturer of the material and follow that company’s instructions.

Risk of injury from plastic chips at startup.
Damaged plastic glass can lead to implosion. This may cause eye injuries. The plastic glass must be protected against mechanical damage by impact or fall, for example. Do not put a defective VACU-UM PLATE into operation. Wear protective goggles.
Vacuum blower causes high noise levels. There is therefore a risk of hearing damage while operating the device. Wear hearing protection.
Risk of inhalation of dust particles while operating the device. If the membrane is contaminated, dust particles can be sucked in and ejected by the blower. The membrane must be free of impuri-ties in the test area.
If the device is being used on construction sites, a fault current circuit breaker must be used to protect site personnel from electrical shock due to dampness and moisture.

Caution
Risk of burns
The device may only be operated at intervals. If the on duration is too long (>2min), the temperature on the motor housing can cause burns. Always allow the device to cool down. The device can only be operated using the handles and switches provided. The main switch must be switched off in the event of a mains voltage failure.
Be aware of hazards in the surrounding area, e.g., risk of tripping, risk of slipping, strong sunlight, unattended equipment, etc.
The local supply voltage must match the nominal voltage specified on the device. Incorrect mains voltage can cause the device to fail. The main switch must be switched off in the event of a mains voltage failure.

Power cord and extension cable

  • The power cord (1) must be able to move freely and must not hinder the user or third parties during work (trip hazard).
  • The extension cables must be authorized for the utilization site (such as, outdoors) and be marked accordingly. Take the necessary minimum cross-section for extension cables into account as required.
  • 230 V~ up to 50 m 3 × 1.5 mm2 up to 100 m 3 × 2.5 mm2
  • 120 V~ up to 50 m 3 × 1.5 mm2 up to 100 m 3 × 2.5 mm2

On-site generators for power supply
When using on-site generators as a power supply, please ensure that the generators are equipped with residu-al-current circuit breakers.
The formula “2 × nominal power of the devices used” applies to the nominal power of generators.

Preparation and operation
  • Before each start, check the VACUUM PLATE for faults and damage, e.g. cracks, splits or scratches; a defec-tive VACUUM PLATE can implode
  • Visually inspect that the filter plate (4) is present and whether it is clean.
  • Check the power supply line and plug (1) as well as the extension cable for electrical and mechanical damage.
  • Check the cooling air openings (11) must be open at all times and air must be able to be suctioned and purged unhindered
  • Ensure the sealing lip (7) is not damaged
  • Warning: Excessive damage to the sealing lip (7) may prevent the required test pressure from being reached.
  • Connect the VACUUM PLATE to the nominal voltage. The nominal voltage specified on the device must match the supply voltage.
Test with VACUUM PLATE
  • The welding area must be dry and free of contamination. Dirt particles may compromise the test.
  • The seam area to be inspected must be sprayed with a liquid forming bubbles (e.g. soapy water) directly before the inspection. The liquid must not damage the seam and the weld material.
  • Set the pressure setting valve (Vari-Flow Valve) (9) to minimum pressure before the test. Turn counter-clockwise until stop (-).
  • Position the VACUUM PLATE on the location to be tested
  • Place the VACUUM PLATE so that the seam to be tested is approximately in the middle of the longitudinal axis of the testing device. For longer test sections, the VACUUM PLATE needs to be repositioned accordingly. When moving the VACUUM PLATE, the test areas must be overlapped.
  • In order to generate a negative pressure, the VACUUM PLATE must be pressed lightly on the location to be tested with bothhandles (8).
  • Turn on the main switch (2) on the VACUUM PLATE
  • Turn the pressure setting valve (Vari-Flow Valve) (9) clockwise (+) until the desired or specified test pressure is set.
  • The existing negative pressure can be read on the manometer (5).
  • Visual inspection of the weld seam for leaks
  • The seam is sealed if there are no bubbles in the test liquid.
  • Switch off the main switch (2) of the VACUUM PLATE, let the device cool down
  • Then disconnect the power cord (1) from the electrical mains.
  • Mark and repairany leaks

Turn anti-clockwise (-)
pressure setting valve open/minimum pressure

LEITER-Vacuum-Plate-300-6

Turn clockwise (+)
pressure setting valve closed/maximum pressure

Quick guide VACUUM PLATE 300

Switch on device (left column)
  1. Connect power supply cord (1) to the voltage source.
  2. Open the pressure setting valve (Vari-Flow Valve) (9) (turn counter-clockwise to the stop),
  3. hold the device by the carrying handles (8), place it on the test location and gently press
  4. Switch on the main switch (2).
  5. Set the pressure required with the pressure set-ting valve (Vari-Flow Valve) (9) (turn clockwise)
Switch off device (right column)
  1. Switch off the device on the main switch (2)
  2. Disconnectthe power cord (1) from the voltage source

Frequently asked questions, causes and actions VACUUM PLATE 300

Do not allow test pressure to build up

  • Check the flatness of the membrane while pressing the VACUUM PLATE. The VACUUM PLATE can compensate an unevenness of approx. 10 mm via the sealing lip (7). There is a risk of leakage if there is a higher level of unevenness.
  • Check whether the sealing lip (7) is damaged. If the sealing lip is damaged, there is a risk of leakage.
  • Filter plate (4) clogged. Clean the filter plate with a brush with plastic bristles.

Diaphragm is touching the sight glass (6)

  • Reduce the pressure with the pressure adjustment valve (Vari-Flow Valve) (9).

Device-protective circuit-breaker (13) trips during operation or does not lock into place (recognizable by protruding reset button)

Causes Action
Ambient temperature too high (> 60°C) Allow the device to cool down. Then

press the reset button on the device protection switch and repeat the process.
Defective vacuum motor| If the device circuit breaker switches the device off again immediately after resetting, the device must be inspected by an authorized Leister service center.

Excessive on-time

| The appliance may only be operated at the prescribed intervals

Maintenance

Warning
Dangerous voltage, danger to life from electric shock:
There are live components inside the device. Maintenance and repairs are to be carried out by trained specialist personnel only.

Note
Avoid contact with aggressive substances (e.g. acetone, diluent, etc.). There is a risk of damage to the installed components.

  • Repairs must only be carried out by authorized Leister service centers.
  • Clean cloths must be used to clean the device.
  • Leister Service Centers guarantee a professional and reliable repair service within 24 hours with original spare parts in accordance with circuit diagrams and spare parts lists.

You can find more information at www.leister.com

Recommended maintenance intervals for the device:

Period of time (operating hours)| Monitoring and maintenance work| Spare parts| Tools
---|---|---|---
After each use of the device| Visual inspection of the sealing lip for damage| –| Service
After each use of the device| Cleaning the sight glass| –| Water, clean cloth
After each use of the device| Visual inspection of the filter plate for contami- nation| –| Brush with plastic bristles
After each use of the device| Pressure adjustment valve moves freely| –| Service
after approx. 300 h| Functional check of the drive| Vacuum motor| Service

Declaration of Conformity

EU Declaration of Conformity
Leister Technologies AG, Galileo-Strasse 10, 6056 Kaegiswil, Switzerland confirms that this product in the model made available for purchase, fulfills the requirements of the following EU directives.

  • Directives: 2006/42/EG, 2014/30/EU, 2011/65/EU
  • Harmonized EN ISO 12100:2010, EN 60335-1:2012 + A11:2014 + A13:2017 + AC:2014,
  • Standards: EN 55014-1:2017 + A11:2020, EN 55014-2:1997 + A1:2001 + A2:2008 + AC:1997, EN IEC 63000:2018

UK Declaration of Conformity
Leister Technologies AG, Galileo-Strasse 10, 6056 Kaegiswil, Switzerland confirms that this product in the model made available for purchase, fulfills the requirements of the following UK Statutory Instruments.
UK Statutory

  • Instruments: 2008 No.1597, 2016 No. 1091, 2012 No. 3032
  • Designated EN ISO 12100:2010, EN 60335-1:2012 + A11:2014 + A13:2017 + AC:2014,
  • Standards: EN 55014-1:2017 + A11:2020, EN 55014-2:1997 + A1:2001 + A2:2008 + AC:1997, EN IEC 63000:2018

Disposal

Do not dispose of electrical equipment with household refuse.
Electrical appliances, accessories and packaging should be recycled in an environmentally friendly manner. When you are disposing of our products, please observe the national and local regulations.

Warranty

  • The guarantee or warranty rights granted for this device by the direct distribution partner/salesperson apply from the date of purchase. In the event of a guarantee or warranty claim (verification by invoice or delivery note), manufacturing or processing errors will be rectified by the sales partner through replacement delivery or repair. Heating elements are excluded from warranty obligations or guarantees.
  • Other guarantee or warranty claims are excluded within the framework of mandatory law.
  • Damage resulting from natural wear, overload, or improper handling is excluded from the warranty.
  • No guarantee or warranty claims exist for devices that have been converted or modified by the purchaser.

Sales and service center
Leister Technologies AG Galileo-Strasse 10
6056 Kaegiswil/Switzerland Tel. +41 41 662 74 74 Fax +41 41 662 74 16
www.leister.com
[email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals