DOMUSA TEKNIK 06-24-V1 Dual Clima HT Domestic Hot Water Production Systems User Guide
- July 23, 2024
- DOMUSA TEKNIK
Table of Contents
- DOMUSA TEKNIK 06-24-V1 Dual Clima HT Domestic Hot Water Production
- Pre-Commissioning
- Heat Pump Electrical Connections
- Heat Pump Controller and Settings
- System Configuration
- Domestic Hot Water
- High Flow Temperatures and Underfloor
- Resetting Errors
- Troubleshooting
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
DOMUSA TEKNIK 06-24-V1 Dual Clima HT Domestic Hot Water Production
Systems
Pre-Commissioning
Pre-Commissioning Checks
Pre-commissioning
- Ensure the heat pump is installed by the installation manual.
- Ensure power is isolated.
- Remove the side and front panels as well as the isolation panel of the electrical enclosure.
- Check the pre-charge of the expansion vessel(s) is set to 1 Bar.
- Ensure the condensate drain is not covered during installation and has adequate drainage.
- Ensure all electrical connections are made as per manufacturers’ or CHNZ wiring diagrams.
- Ensure hydronic connections of the heat pump and all accessories are correct and as per design.
- Ensure the deaerator is installed correctly by the installation manual and the bleed cap is left open.
- Ensure the heat pump electrical enclosure is completely sealed after making electrical connections.
Filling the System with Water
Fill and thoroughly flush the system with a flushing cart or suitable mains
pressure, until there is no sign of air returning through the primary feed
pipes. This will remove most of the air from the system. Now pressurise the
system to 0.1 mPa on the heat pump’s pressure gauge. Ensure the automatic air
vents in the system and heat pump are open. Ensure all system water joints and
connections are leak-tight. Once all necessary components are installed, the
system can be run.
Heat Pump Electrical Connections
Controller Connection
The heat pump touch screen controller must be connected as per the diagram above. The connection between Power Card PCB and Controller must be made from COMM4 to BAGV. This connection is LOW VOLTAGE ONLY. A maximum distance of 30 metres and cable diameter of 0.25mm² – 1.25mm² should be observed. Care must be taken to avoid running the interconnecting cable near any 230V mains cables. Installation of the heat pump controller is required for heat pump operation. The heat pump controller must be installed indoors ie. in the garage or HWC cupboad and be accessable for service and maintenance.
Room Thermostat Connection
Connection of room thermostat(s) to the heat pump for HEATING must be made
using terminals (24-25). When these contacts are closed the heat pump will
receive a run signal to operate in heating mode only. Connection of room
thermostat(s) to the heat pump for COOLING must be made using terminals
(24-26) for cooling. When these contacts are closed the heat pump will receive
a run signal to operate in cooling mode only. Terminals 24 (common), 25 and 26
come from the factory with bridge connectors installed. This allows
Heating/Cooling, On/Off control from the heat pump controller. This control
will be based of water flow temp only. BOTH factory bridges must be removed
(24-25 and 24-26) if a room thermostat is being connected. Even if the system
is heating only.
VOLT FREE CONTACTS ONLY – DO NOT CONNECT 230V
DHW Connection
DHW Sensor
Connection of the DHW sensor must be made into terminals 19 and 20. The 5m
long sensor supplied with the heat pump is a 5K NTC type. A maximum distance
of 20 metres and cable diameter of 0.25mm2 – 1.25 mm2 should be observed.
Before sensor connection ensure the resistor connected to terminals 19 and 20
is removed.
DHW 3-Way Valve or Diverter Valve (motor return)
Connection of Additional Circulating Pumps
Connecting a single backup pump for use in both Heating/Cooling and DHW
mode
This circulation pump will run in parallel with the appliance’s internal pump
(C1) and will be active when the appliance is running in either Heating,
Cooling or DHW production mode. The pump is connected between electrical
terminals 9 (Live) and 11 (Neutral). A jumper must be installed between
terminals 9 and 10. (Live)
Backup pump connection for heating and/or cooling (C2)
This circulation pump (C2) will run in parallel with the appliance’s internal
pump (C1), but only when the appliance is running in Heating or Cooling mode.
The pump is connected between electrical terminals 10 (Live) and 11 (Neutral).
Connecting a backup pump for DHW production mode (C3)
This circulation pump (C3) will run in parallel with the appliance’s internal
pump (C1), but only when the appliance is running in DHW production mode. The
pump is connected between electrical terminals 9 (Live) and 12 (Neutral).
Heat Pump Controller and Settings
Switching the heat pump ON and OFF
To switch on the heat pump, press and hold the On button (9) for 5 seconds. The heat pump will switch on in the last previously selected operating mode and the On button will light up in red.
- Temperature selection: Drag the slider to change the temperature for the different operating modes
- DHW setpoint temperature: This selects and displays the DHW setpoint temperature.
- Heating setpoint temperature: This selects and displays the heating setpoint temperature.
- Cooling setpoint temperature: This selects and displays the cooling setpoint temperature.
- Programming Menu touch button: Press this button to access the heat pump programming menu.
- User Menu touch button: Press this button to access the heat pump user menu.
- Settings Menu touch button: Press this button to access the heat pump configuration menu.
- Operating Mode Menu touch button: Press this button to access the different operating modes.
- On/Off button: This button switches the heat pump on and off.
- “+” touch button: Press this button to increase the setpoint temperature for the different operating modes.
- “-” touch button: Press this button to reduce the setpoint temperature for the different operating modes.
- Date and time: This selects and displays the date and time. Hold down to change.
Working Status Screen
To access the Working Status screen, press setting menu button (7) and then
System Parameters. This is used to live view all vital heat pump operations.
- Suction temperature.
- Suction Pressure
- Discharge Pressure
- Discharge Temperature
- Return Button
- Errors display access button.
- Information C parameters access button.
- Water Outlet Temperature
- Current water circuit flow.
- Water Inlet Temperature
- Saturated Discharge Temperature
- Saturated Suction Temperature
- DHW Temperature
- Inverter Power Module (IPM) temperature.
- Liquid line temperature
- EEV position
- Compressor current draw
- Compressor frequency
- Coil outlet temperature.
- E2 heating back-up outlet state.
- E1 DHW back-up outlet state.
- G2 heating/cooling 3WV position (ON-Heating / OFF-Cooling)
- DHW/heating-cooling 3WV position (ON-DHW / OFF- heating-cooling)
- DHW back-up pump outlet state.
- C2 Heating back-up outlet state.
- C1 Heat pump circulation back-up state.
- Fan Speed RPM
- Home button (return to main display).
System Configuration
To Access parameters, press setting menu button (7) and then System Parameters, Enter the password 99. Below is a list of parameters relevant to different system types. Work through each parameter and change to suit your system type, emitters and DHW requirements. For a full list of parameters see Installation Manual.
Temperature Set Points
Parameter | Description | Default | Set To |
---|
P02
or changed from main screen
|
Heating Temperature Setpoint
|
45°C
|
Radiators = 50°C – 65°C
Underfloor = 35 °C – 50°C
P03
or changed from main screen
|
Cooling temperature Setpoint
|
12°C
|
Fan Coil = 7°C – 12°C
Underfloor or Module panel = 10°C (Dew Point control must be used)
OTC Mode Set Points – Outdoor Temperature Conditions (Weather Compensation)
Parameter | Description | Default | Set To |
---|
P08
|
Used to adjust the maximum temperature of the OTC operating curve according to the outdoor temperature. Heating mode only.
|
65°C
|
Radiators = 65°C
Underfloor = 45°C
P09
or changed from main screen
|
Used to adjust the offset of the OTC operating curve according to the outdoor temperature. Heating mode only.
|
0°C
| Climate zone specific
+3°C = Upper North Island
0°C = Lower North & Upper South Island
-3°C = Lower South Island
P19
or change from the main screen – Operating Modes
|
OTC mode activation
|
1
|
0 = Disable if OTC (weather compensation) not required
1 = Enable if OTC (weather compensation) is required
If installation is a heating-only or cooling-only system, please set it appropriately.
Parameter | Description | Default | Set To |
---|
P62
|
This parameter can be used to activate and deactivate the heating and/or cooling operating modes.
|
0
|
0 – Heating + Cooling 1 – Cooling Only
2 – Heating Only
Domestic Hot Water
If not using DHW, change parameter P63 to 0 and disregard the following To meet requirements set in MBIE NZBC, clause G12 stored DHW must be heated to 60°C once a day, or 60°C for the period of one hour once a week, for protection against Legionella. CHNZ recommend using a setpoint for DHW of 60°C which will meet this requirement. If using a setpoint lower than 60°C it is recommended to enable the anti- legionella mode and its associated functions as seen below.
Parameter | Description | Default | Range | Set To |
---|
P04
or changed from main screen
|
DHW temperature Setpoint
|
45°C
|
10°C-75°C
|
60°C
P10
|
Interval between days for anti-legionella activation
|
7 (day)
|
7-9 days
|
7
P11
|
Hour at which the anti-legionella function will be activated
|
23 (hour)
|
0-23 hours
|
23
P12
|
Duration of anti-legionella function
|
10 (min)
|
5-99 minutes
|
60 mins
P13
|
Anti-legionella function setpoint
|
70°C
|
50°C-70°C
|
60°C
P14
|
Anti-legionella function mode
|
2
|
0: Auto Mode
1: Manual Mode
2: Disabled
|
2 – if P13 set to 60°C or greater 0 – if P13 set below 60°C
P63
|
DHW mode activation
|
1
|
0: Disable
1: Enable
|
0 – if not using DHW 1 – if using DHW
It’s recommended that a suitably sized electric element is installed in the HWC and left OFF as a redundancy only.
High Flow Temperatures and Underfloor
With underfloor installations it is important that high flow temperature ie.
50°C are not introduce to the floor. High temperatures can cause damage to certain construction materials as well as being uncomfortable. Please fit the supplied sticker to the bezel/surround of the heat pump controller to advise users of hazards when increasing the setpoint. Sticker can be found with the Commissioning Guide QR code, fixed to the outside of the heatpump box.
WARNING
Your system is designed to operate with low water temperatures. Don’t turn
the heating set point up before talking to your installer or CHNZ Aftersales
Resetting Errors
To reset errors, the heat pump power supply must be cycled off and on at the isolation switch. At the point of commissioning a common error is E15 (Insufficient water flow) this is likely caused by air still being present in the system or installation debris blocking the filter ball valve. Cheak and clean the filter ball valve installed at the heat pump and reset. For all other faults please refer to the manufacturer’s instruction manual.
Troubleshooting
For all troubleshooting please refer to page 120-157 of the Domusa Service Manual. If any error persists, please contact our technical aftersales team for assistance with the fault.