LevelPro TVU Series Universal Multi Color Display Controller Instruction Manual

July 16, 2024
LevelPro

LevelPro TVU Series Universal Multi Color Display Controller

LevelPro-TVU-Series-Universal-Multi-Color-Display-Controller-
product

Specifications

  • General:

    • Display Displayed Values Stability Transmission Parameters
      Protection Class
  • Input Signal | Supply:

    • Standard Voltage: 85 – 260V AC/DC | 16 – 35V AC, 19 –
      50VDC
  • Output Signal | Supply:

    • Standard Voltage Passive current output*
  • Performance:

    • Accuracy
    • Temperatures: Operating Temperatures
  • Materials | Wetted:

    • Housing: Polycarbonate
  • Model Selection:

    • TVU — Universal Multi-Color LED Display
    • Part Number TVU-1421 TVU-1429
    • Input: 4-20mA 4-20mA
    • Output: 4 Relay 4-20mA + 2 Relay
      • optional

Product Usage Instructions

Front Panel Description

  • Thresholds exceeding LED indicators (Relays)
  • Infrared Receiver
  • Bright Large Display
  • Function of Push Buttons
    • Programming Buttons
    • Symbol used in the manual : [ESC/MENU]
    • Symbol used in the manual : [ENTER]
    • Symbol used in the manual : [^] [v]

LevelPro® — TVU Series
Universal Multi-Color Display | Controller

Quick Start Manual

Read the user’s manual carefully before starting to use the unit or software. Producer reserves the right to implement changes without prior notice.

Symbol Explanation

This symbol denotes especially important guidelines concerning the installation and operation of the device. Not complying with the guidelines denoted by this symbol may cause an accident, damage or equipment destruction.

Basic Requirements User Safety

  • Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses and oils.
  • Do not use the unit in areas where there is risk of explosions.
  • Do not use the unit in areas with significant temperature variations, exposure to condensation or ice.
  • The manufacturer is not responsible for any damages caused by inappropriate installation, not maintaining the proper environmental conditions and using the unit contrary to its assignment.
  • If in the case of a unit malfunction there is a risk of a serious threat to the safety of people or property additional, independent systems and solutions to prevent such a threat must be used.
  • The unit uses dangerous voltage that can cause a lethal accident. The unit must be switched off and disconnected from the power supply prior to starting installation of troubleshooting (in the case of malfunction).
  • Do not attempt to disassemble, repair or modify the unit yourself. The unit has no user-serviceable parts.
  • Defective units must be disconnected and submitted for repairs at an authorized service center.

Specifications

General

Display| LED | 4 x 57mm High | Adjustable Color | Adjustable Brightness
Displayed Values| -999 ± 9999
Stability| 50 ppm | °C
Transmission Parameters| 1200…115200 bit/s, 8N1 / 8N2
Protection Class| NEMA 4X | IP67
Input Signal | Supply
Standard| 4-20mA | 0-10V | 0-150mV RTD
Voltage| 85 – 260V AC/DC | 16 – 35V AC, 19 – 50VDC
Output Signal | Supply
Standard| 4 x Relays (5A) | 2 x Relay (5A) + 4-20mA
Voltage| 24VDC
Passive current output
| 4-20mA | (Operating Range Max. 2.8 – 24mA)
Performance
Accuracy| 0.1% @ 25°C One Digit
Temperatures
Operating Temperatures| -40 – 158°F | -40 – 70°C
Materials | Wetted
Housing| Polycarbonate

Model Selection

TVU — Universal Multi-Color LED Display

Part Number| Input| Output
TVU-1421| 4-20mA| 4 Relay
TVU-1429| 4-20mA| 4-20mA + 2 Relay

Front Panel Description

LevelPro-TVU-Series-Universal-Multi-Color-Display-Controller-
\(2\)

Function of Push Buttons LevelPro-TVU-Series-Universal-Multi-Color-
Display-Controller- \(3\)

Wiring Diagram

LevelPro-TVU-Series-Universal-Multi-Color-Display-Controller-
\(4\)

WIRE INSTALLATION

LevelPro-TVU-Series-Universal-Multi-Color-Display-Controller-
\(5\)

  • Carefully remove wire terminal from socket
  • Loosen set screw
  • Insert wire
  • Tighten set screw
  • Replace wire terminal into socket

Due to possible significant interference in industrial installations, appropriate measures assuring correct operation of the unit must be applied.

The unit is not equipped with an internal fuse or power supply circuit breaker.
For this reason, an external time-delay cut-out fuse with a small nominal current value must be used (recommended bipolar, max. 2A) and a power supply circuitbreaker located near the unit.
In the case of using a monopolar fuse it must be mounted on the phase cable.

Programming 4-20mA Input

LevelPro-TVU-Series-Universal-Multi-Color-Display-Controller-
\(6\)

Programming 4-20mA Output LevelPro-TVU-Series-Universal-Multi-Color-
Display-Controller- \(7\)

Calculating 4-20mA Input

Sensor Type 20mA Set Point
Submersible Range of sensor / Specific Gravity = 20mA (for inches)
Ultrasonic Tank Height
Radar Tank Height

Programming Relays

LevelPro-TVU-Series-Universal-Multi-Color-Display-Controller-
\(8\)

Programming Display Color

LevelPro-TVU-Series-Universal-Multi-
Color-Display-Controller- \(1\)

Selected colour proportions

Color Number Red [%] Green [%]
coL1 100 0
coL2 87.5 12.5
coL3 75 25
Color Number Red [%] Green [%]
--- --- ---
coL4 62.5 37.5
coL5 50 50
coL6 37.5 62.5
Color Number Red [%] Green [%]
--- --- ---
coL7 25 75
coL8 12.5 87.5
coL9 0 100

24-0353 © Icon Process Controls Ltd.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>