ICON Truflo PPT Series Digital LED Pressure Transmitter Switch User Manual
- July 15, 2024
- Icon
Table of Contents
ICON Truflo PPT Series Digital LED Pressure Transmitter Switch
Safety Information
- De-pressurize and vent system prior to installation or removal
- Confirm chemical compatibility before use
- DO NOT exceed maximum temperature or pressure specifications
- ALWAYS wear safety goggles or face-shield during installation and service
- DO NOT alter product construction
Warning | Caution | Danger
Indicates a potential hazard. Failure to follow all warnings may lead to
equipment damage, injury, or death.
Installation Instructions
Do not tighten by grasping the case of the transmitter as this may cause
damage. Always pressure test connections for leaks with water prior to use on
chemical service. The user shall ensure that the correct transmitter pressure
range and the correct materials of construction are selected.
Note | Technical Notes
Highlights additional information or detailed procedure.
WARNING
Please ensure that the Instruments are not to be subject to water hammer or pressure spikes! Always Pressure Test System with H2O Prior to Initial Start- Up Before Before installation be certain the appropriate instrument has been selected considering operating pressure, full scale pressure, wetted material requirements, media compatibility, operating temperature, vibration, pulsation, desired accuracy and any other instrument component related to the service application including the potential need for protective attachments and/ or special installation requirements. Failure to do so could result in equipment damage, failure and/or personal injury. Ensure only qualified personnel personnel are permitted to install and maintain this instrument.
Pressurize System Warning
Sensor may be under pressure, take caution to vent system prior to
installation or removal. Failure to do so may result in equipment damage
and/or serious injury. Please Ensure Full Pipe PPT Series can be installed in
a horizontal or vertical direction.
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during installation and service of
Truflo products.
Pressurized System Warning
Sensor may be under pressure. Take caution to vent system prior to
installation or removal. Failure to do so may result in equipment damage and
serious injury.
Digital LED Pressure Transmitter | Switch
Technical Specifications
Sensor Diaphragm| Ceramic (AL2O3 96%) | SS316L
---|---
Measured Fluids| H2O | Liquid Chemicals | Gases
Storage Temperature| -4 – 176ºF | -20 – 80ºC
Accuracy| Ceramic : ± 1.0% of FS @ 25ºC Max. | SS316L : ± 0.3% of FS @ 25ºC
Max.
Repeatability| Ceramic : ≤± 1.0% FS Max. | SS316L : ≤± 0.3% FS Max.
Operating Voltage| 10-30VDC
Current Consumption| 60mA max.
Pressure Unit| Psi | Bar | KPa | Kg/cm2
Display| 0-9999 | Green | Red
Transmitter Output| 4-20mA | 0-10V*
Relay Outputs| 2 X (5A) Relays or 2 PNP | 2 NPN
Current Output| 150mA Max.
Communication| Modbus RTU | ASCII
Thermal Drift| Ceramic : ± 0.1% FS/ºC | SS316L : ± 0.05% FS/ºC
Materials| PP | PVDF | SS316L
Process Connection| 1/4″ – 1/2″ MNPT | 1/2″ FNPT
Operating Temperature| -40 – 120oC
Protection Class| IP67 | NEMA 4X
Approval| cCSAus | cULus | CE | RoHS
Legend
- CV – Current Value
- R1 – Relay 1
- R2 – Relay 2
- AL1 – Alarm 1
- AL2 – Alarm 2
- H – Hysterisis
Display
Alarm Status| Alarm OFF| Alarm 1 | Alarm 2 ON
---|---|---
Home Screen| Green| Red
Display Navigation
Transmitter Range Settings
Programming
Alarm Settings
Alarm Mode
Communication Settings
Address of Data
Mode | Description |
---|---|
ALt.0 | No Alarm |
ALt.1
| R1 ON
(AL1-H) AL1
| R2 ON
AL2 (AL2+H)
CV > (AL1) R1/AL1 ; CV < (AL1 – H) R1/AL1| CV < (AL2) R2/AL2 ; CV > (AL2+H) R2/AL2 OFF
ALt.2
| R1 ON
(AL1-H) AL1
| R2 ON
AL2 (AL2+H)
CV < (AL1 – H) R1/AL1 ; CV > AL1 R1/AL1| CV > (AL2 + H) R2/AL2 CV < AL2 R2/AL2
ALt.3
| R1
(AL1-H) AL1
| R2 ON
(AL2-H) AL2
CV > AL1 R1/AL1 ; CV < (AL1 – H) R1/AL1| CV > AL2 R2/AL2 ; CV < (AL2 – H) R2/AL2
ALt.4
| R1
(AL1-H) AL1
| R2 ON
(AL2-H) AL2
CV > (AL1) R1/AL1 ; CV < (AL1 – H) R1/AL1| CV > AL2 R2/AL2 CV < (AL2 – H) R2/AL2
ALt.5
| R1
(AL1-H) AL1
| R2 ON
AL 2 (AL2+H)
CV > (AL1) R1 / AL1 ; CV < (AL1 – H) R1 / AL1| CV < AL2 R2 / AL2 CV > (AL2 + H) R2 /AL2
ALt.6
| R1 ON
(AL1-H) AL1
| R2 ON
AL2 (AL2+H)
CV < (AL1 – H) R1 / AL1 ; CV > AL1 R1 / AL1| CV > (AL2 + H) R2 / AL2 ; CV < AL2 R2 /AL2
- Alarm Output Status (Output Status): 00 05H [0000 0000] bit.0=1 : R1 ON | bit.1=1 : R2 ON
- Display Error Correction : 00 07H is the address of CV bias
- Ex: CV = 4.98 to be corrected to 5.00, the data of 00 07H must be written 2
Temperature | Pressure Graphs | Non-Shock
Note : The Pressure/Temperature graphs are specifically for the Truflo® PPT Pressure Transmitter. During system design the specifications of all components must be considered.
Wiring Diagram
Address | Description | Read/ Write |
---|---|---|
00 00H | CV : Current Pressure Value | R |
00 01H | CV : Current Pressure Value | R |
00 02H | AL1 : AL1 Alarm Preset Value | R/W |
00 03H | AL2 : AL2 Alarm Preset Value | R/W |
00 04H | HYS : Alarm Hysterisis | R/W |
00 05H | Output Status | R |
00 06H | Zero Point Reset | R/W |
00 07H | Display Correction | R/W |
00 08H | Lck : Lock | R/W |
00 09H | Ut : Pressure Unit Selection | R/W |
Address | Description | Read/ Write |
--- | --- | --- |
00 0AH | ALt : Alarm Mode Selection | R/W |
00 0BH | dn : Alarm Delay Mode Selection | R/W |
00 0CH | dt : Delay Time Setting | R/W |
00 0DH | dP : Decimal Point Selection | R/W |
00 0EH | rt : Response Speed Setting | R/W |
00 0FH | ||
00 10H | Peak : High Pressure Hold Value | R |
00 11H | Val : Low Pressure Hold Value | R |
00 12H | Peak Value Reset : bit.0 = 1 | R/W |
00 13H | Val Value reset : bit.0 = 1 | R/W |
Dimensions (mm)
Warranty, Returns and Limitations
Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products
that such products will be free from defects in material and workmanship under
normal use and service in accordance with instructions furnished by Icon
Process Controls Ltd for a period of one year from the date of sale of such
products. Icon Process Controls Ltd obligation under this warranty is solely
and exclusively limited to the repair or replacement, at Icon Process Controls
Ltd option, of the products or components, which Icon Process Controls Ltd
examination determines to its satisfaction to be defective in material or
workmanship within the warranty period. Icon Process Controls Ltd must be
notified pursuant to the instructions below of any claim under this warranty
within thirty (30) days of any claimed lack of conformity of the product. Any
product repaired under this warranty will be warranted only for the remainder
of the original warranty period. Any product provided as a replacement under
this warranty will be warranted for the one year from the date of replacement.
Returns
Products cannot be returned to Icon Process Controls Ltd without prior
authorization. To return a product that is thought to be defective, go to
www.iconprocon.com, and submit a customer return (MRA) request form and follow
the instructions therein. All warranty and non-warranty product returns to
Icon Process Controls Ltd must be shipped prepaid and insured. Icon Process
Controls Ltd will not be responsible for any products lost or damaged in
shipment.
Limitations
This warranty does not apply to products which: 1) are beyond the warranty
period or are products for which the original purchaser does not follow the
warranty procedures outlined above; 2) have been subjected to electrical,
mechanical or chemical damage due to improper, accidental or negligent use; 3)
have been modified or altered; 4) anyone other than service personnel
authorized by Icon Process Controls Ltd have attempted to repair; 5) have been
involved in accidents or natural disasters; or 6) are damaged during return
shipment to Icon Process Controls Ltd reserves the right to unilaterally waive
this warranty and dispose of any product returned to Icon Process Controls Ltd
where: 1) there is evidence of a potentially hazardous material present with
the product; or 2) the product has remained unclaimed at Icon Process Controls
Ltd for more than 30 days after Icon Process Controls Ltd has dutifully
requested disposition. This warranty contains the sole express warranty made
by Icon Process Controls Ltd in connection with its products. ALL IMPLIED
WARRANTIES, INCLUDING WITHOUT LIMITATION, THE
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE
EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above
are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL
Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL
DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY
PERSON. THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT
OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR
REPRESENTATIONS ON BEHALF OF Icon Process Controls Ltd. This warranty will be
interpreted pursuant to the laws of the province of Ontario, Canada. If any
portion of this warranty is held to be invalid or unenforceable for any
reason, such finding will not invalidate any other provision of this warranty.
For additional product documentation and technical support visit:
www.iconprocon.com
e-mail:sales@iconprocon.com or
support@iconprocon.com
Ph: 905.469.9283
Documents / Resources
| ICON
Truflo PPT Series Digital LED Pressure Transmitter
Switch
[pdf] User Manual
PPT, SS316L, PP, PVDF, Truflo PPT Series Digital LED Pressure Transmitter
Switch, Truflo PPT Series, Digital LED Pressure Transmitter Switch, LED
Pressure Transmitter Switch, Pressure Transmitter Switch, Transmitter Switch,
Switch
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>