GEA AH12 Electric Heater Heat Pump Instruction Manual
- May 15, 2024
- GEA
Table of Contents
GEA AH12 Electric Heater Heat Pump
Product Specifications
-
Model: AH12H09E3B
-
Heater Voltage: 265V
-
Heater Watts: 3,500
-
Heater BTU: 10,900
-
Heater Amps: 13.2
-
Min Circuit: 20
-
Recommended Protective Device: 20 amp
time-delay fuse or breaker -
Heat Pump Watts: 620
-
Heat Pump BTU: 8,000
-
COP: 3.3
Installation Instructions
- A: 30 inches
- C: 70 inches
Wall Opening Dimensions
- Add 1/4 to A and C dimensions for all cut-outs.
- RAB80: 16-1/4 Min. H x 42-1/4 Min. W
Features and Benefits
This model (AH12H09E3B) comes with the following features and benefits:
- Efficient heating with 3,500 Watts and 10,900 BTU output
- Easy installation with recommended protective devices
- Includes a heat pump with 620 Watts, 8,000 BTU, and a COP of 3.3 for added efficiency
Frequently Asked Questions (FAQ)
Q: What is the recommended protective device for this unit?
A: The recommended protective device is a 20 amp time-delay fuse or breaker.
AH12H09E3B
Hotpoint® PTAC Heat Pump Unit with Electric Heat Backup 20 amps, 265 Volt
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
ELECTRICAL WIRING
All wiring, including installation of receptacle, must be made in accordance
with local electrical codes and regulations.
NOTE: Aluminum wiring may pose special problems – consult a qualified
electrician.
GRILLE OPTIONS
Stamped Aluminum Grille – RAG70
ELECTRICAL CONNECTION
- 265V Hotpoint PTACs require the use of a subbase (sold separately). Installation must comply with local electrical codes and regulations.
- Power cord is permanently attached on all Hotpoint chassis.
WALL CASE DIMENSIONS
RAB80 WALL SLEEVE
Heavy-gauge galvanized steel, with insulation, for quick self-assembly.
A – 42”, B – 13-3/4”, C – 16”
MAXIMUM CORD EXTENSION
WALL OPENING DIMENSIONS
Add 1/4” to A and C dimensions for all cut-outs.
RAB80 16-1/4” Min. H x 42-1/4” Min. W
AH12 ELECTRIC HEATER
265 VOLT| SUBBASE CONNECTED UNITS
Heater Watts| 3,500
Heater BTU| 10,900
Heater Amps| 13.2
Min Circuit| 20
Recommended protective Device| 20 amp time-delay fuse or breaker
AH12 HEAT PUMP
Heat Pump Watts| 620
Heat Pump BTU| 8,000
COP| 3.3
AH12H09E3B
Hotpoint® PTAC Heat Pump Unit with Electric Heat Backup 20 amps, 265 Volt
FEATURE AND BENEFITS
- 9,000 cooling BTU
- 11.3 EER
- 8,000 heating BTU
- 3.3 COP
- R32 Refrigerant – Environmental friendly, low GWP (Global Warming Potential)
- 3-Speed Fan – Give guests control over their comfort with three fan speeds to choose from
- 4-Temperature Limiting Options – Easily select one of four temperature ranges for peak efficiency and total customer comfort
- Intuitive Display – Allow guests to easily customize their preferred settings and reduce maintenance calls with an easy-to-use control panel
- Power Cord (LCDI) Included – Hotpoint PTACs come with an attached cord for a quick and easy installation
- Automatic Emergency Heat – Keep guests comfortable with a heating option that uses electric resistance heat in heat pump mode
- Freeze and Frost Protection – Automatic freeze and indoor frost control keep units operating in peak condition
- Auto Power Recovery – In case of power failures, units automatically resume their operation when power restores, reducing maintenance calls
- Self Diagnostics – Quickly and easily identify service needs with a nine-point diagnostic code system
- Backed by an Industry Leader – With a long history of creating durable products at an affordable price, Hotpoint is your trusted PTAC brand
PRELIMINARY SPECIFICATIONS – SUBJECT TO CHANGE
Read User Manual Online (PDF format)