Honeywell BG-12LX Addressable Pull Station User Manual
- July 15, 2024
- Honeywell
Table of Contents
Honeywell BG-12LX Addressable Pull Station
Product Information
Specifications
- Product Name: BG-12LX Addressable Pull Station
- Document Number: 52141
- Model Number: I56-3655-003
Product Usage Instructions
Installation
The BG-12LX Addressable pull station can be surface mounted to an SB-10 or
SB-I/O surface backbox or semi-flush mounted on a standard single-gang,
double-gang, or 4 (10.16 cm) square electrical box. Use the optional BG-TR
trim ring for semi-flush mounting.
Operation
To activate the pull station, push in and pull down on the handle. The word
‘ACTIVATED’ will appear after pulling down the handle and will remain until
the pull station is reset. The pull station includes a Single Pole, Single
Throw (SPST) Normally Open (N/O) switch.
Resetting the Pull Station
- Insert the key and rotate 1/4 turn counterclockwise.
- Open the door until the handle returns to normal.
- Close and lock the door.
Wiring
Connect from FACP SLC to the next addressable device using the provided wiring
diagram.
Setting the Address
The default address is ’00.’ Set the address by adjusting the rotary address
switches inside the pull station. Record the address on the product ID label.
LED Operation
- Normal : Flashing RED
- Alarm : Steady RED
Description
The BG-12LX Addressable pull station is a non-coded, dual-action manual pull station with a key-lock reset feature. It provides Fire•Lite intelligent control panels with one addressable alarm initiating input. The addressable module is housed inside the pull station. The BG12LX is compatible with all Fire•Lite intelligent panels. The BG-12LX meets the ADAAG controls and operating mechanisms guidelines (section 4.1.3[13]), and the ADA requirement for a 5 lb. maximum pull force to activate the pull station. Operating instructions are molded into the pull station handle along with Braille text. Molded Terminal numbers are also present. Conforms to ANSI/UL Standard 38 and ULC Standard S528.
Ratings
- Normal Operating Voltage: 24 VDC.
- Average Operating Current (LED Flash): 375 µA.
- Maximum Operating Current (LED On): 5 mA.
- Temperature Range: 32° F – 120° F (0° C – 49° C).
- Relative Humidity Range: 10% – 93% non-condensing.
Installation
The BG-12LX Addressable pull station can be surface mounted to an SB-10 or SB-I/O surface backbox or semi-flush mounted on a standard single-gang, double-gang or 4″ (10.16 cm) square electrical box. The optional BG-TR trim ring can be used if the BG-12LX is to be semi-flush mounted.
Operation
To activate the dual-action pull station, push in and pull down on the handle. The word ‘ACTIVATED’ appears after the handle is pulled down. This will remain until the pull station is reset. The pull station includes one Single Pole, Single Throw (SPST) Normally Open (N/O) switch which closes upon activation of the pull station.
Resetting the Pull Station
- Insert the key into the lock and rotate 1/4 turn counterclockwise.
- Open the door until the handle returns to normal.
- Close and lock the door.
Wiring
- NOTE : Closing the door automatically resets the switch to the ‘Normal’ position. Opening the door will not activate or deactivate the alarm switch.
- CAUTION! Do not detach the door of the pull station during installation. The door of the pull station cannot be reattached to the backplate after the backplate has already been installed onto an electrical box.
- CAUTION! Install the Fire•Lite BG-12LX addressable pull station in accordance with these instructions, applicable NFPA standards, national and local Fire and Electrical codes and the requirements of the AHJ (Authority Having Jurisdiction). Regular testing of the devices should be conducted in accordance with the appropriate NFPA standards. Failure to follow these directions may result in failure of the device to report an alarm condition. Fire•Lite is not responsible for devices that have been improperly installed, tested or maintained.
ADA Compliance
For ADA compliance, if the clear floor space only allows forward approach to
an object, the maximum forward reach height allowed is 48 inches (121.92 cm).
If the clear floor space allows parallel approach by a person in a wheelchair,
the maximum side reach allowed is 54 inches (137.16 cm).
Setting the BG-12LX Address
The BG-12LX Addressable pull station is factory preset with address ‘00.’ Set the address for the pull station by turning the rotary address switches on the addressable module mounted inside the pull station. Only one device per address is allowed. Multiple modules may not be set to the same address on the Signaling Line Circuit. Once the address is set, record it in the space provided on the product ID label located inside the pull station.
FAQ
Q: How do I activate the pull station?
A: Push in and pull down on the handle to activate the pull station.
Q: How do I reset the pull station?
A: Insert the key, rotate counterclockwise, open the door, close and lock it.
Q: Can multiple devices have the same address?
A: No, only one device per address is allowed on the Signaling Line Circuit.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>