IDEAL 61-773 Clamp Meter Tight Sight 1000Amp Owner’s Manual

July 12, 2024
IDEAL

61-773 Clamp Meter Tight Sight 1000Amp

“`html

Specifications:

General Specification: This technical manual
covers models 61-773 and 61-775 from IDEAL INDUSTRIES, INC.

Voltage Specifications: The device is designed
to measure voltage within specified ranges.

Current Specifications: The device can measure
current accurately within its designated ranges.

Resistance Specifications: This device provides
accurate resistance measurements within specified limits.

Frequency Specification: The device is capable
of measuring frequency within its specified range.

Capacitance Specifications: Capacitance
measurements can be performed using this device within the
specified limits.

Continuity Specifications: The continuity
function provides reliable results for testing circuit
connections.

Product Usage Instructions:

Introduction

Warning: To avoid shock or injury, only
qualified personnel should perform verification tests or
calibration procedures as described in the manual.

Precautions and Safety Information

Use the meter strictly as outlined in the User Manual to
maintain the meter’s protective capabilities. Review the Safety
Information page before servicing the product. Warnings and
Cautions are provided in the manual to highlight hazardous
conditions.

Symbol Table

The symbols used in the meter and manual are explained in Table
A. Pay attention to these symbols for safe operation.

TightSightTM Display Notes

The TightSightTM display primarily shows AC/DC amps units of
measure for current measurements in tight spaces. For other
functions, numerical values are displayed on the main screen.

High Voltage Warning (HI-V)

Review safety precautions to prevent injury and product damage.
Use the product only as specified to avoid hazards. Follow the
specific precautions mentioned, such as not operating without
covers and avoiding electric overload.

FAQ:

Q: Can I use this product without proper training?

A: No, only qualified personnel should operate
this device to avoid risks of injury or damage.

“`

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODELS: 61-773
61-775
The Service Information provides the following information: · Precautions and safety information · Specifications · Performance test procedure · Calibration and calibration adjustment procedure · Basic maintenance (replacing the battery)

Form number: TM61773-5 Revision: 3 Date: July 2010
Form number TM61773-5

Rev 3 July 2010

TABLE OF CONTENTS

Title

Page

Introduction

1

Precautions and Safety Information

1

Symbol Table

1

TightSightTM Display Notes

1

High Voltage Warning (HI-V)

2

Safety Information

2

Certifications and Compliance

3

Specifications

3

General Specification

3

Voltage Specifications

4

Current Specifications

4

Resistance Specifications

4

Frequency Specification

4

Capacitance Specifications

4

Continuity Specifications

4

Performance Verification

5/6

Calibration

7/8

Replacing the Battery

9

Form number TM61773-5

Rev 3 July 2010

Page 1

Introduction

Warning To avoid shock or injury, do not perform the verification tests or calibration procedures described in this manual
unless you are qualified to do so.

The information provided in this document is for the use of qualified personnel only.

Caution The 61-770 series contains parts that can be damaged by static discharge. Follow the standard practices for handling static sensitive
devices.

For additional information about IDEAL INDUSTRIES, INC. and its products, and services, visit IDEAL INDUSTRIES, INC. web site at: www.idealindustries.com

Precautions and Safety Information Use the meter only as described in the Users Manual. If you do not do so, the protection provided by the meter may be impaired. Read the “Safety Information” page before servicing this product. In this manual, a Warning identifies conditions and actions that pose hazard (s) to the user; a Caution identifies conditions and actions that may damage the meter or the test instruments.

The Symbols The symbols used on the meter and in this manual are explained in Table A.

Table A Symbols Symbol Description

Battery

CAT III CAT IV

Cautionary or important information in manual Danger- Risk of electrical shock Double Insulation- Protection Class II IEC Over-voltage Category III IEC Over- voltage Category IV

Symbol HI-V

Description High Voltage Indicator >30 V indicator is on (on VAC,VDC ranges)
Continuity indicator

TightSightTM Display Notes:
Only AC/DC amps units of measure are displayed in the TightSightTM display since primary use is for viewing current measurements in tight locations. The display will show numerical values only for other functions. The main display is to be used to view units of measure for all other functions.

Form number TM61773-5

Rev 3 July 2010

Page 2
High Voltage Warning (HI-V):
The meter beeps and lights an LED when >30V AC/DC voltage is present through test leads of the meter. This enhanced safety feature alerts the user that dangerous voltage is present across the leads even if the meter is set on an incorrect function or range. Notes: This feature does not work through the clamp head as the clamp is intended to only measure current. Audible indication can be turned off by pressing and holding the MAX/MIN button while turning the function switch from OFF to the desired range position.
SAFETY
Review the following safety precautions to avoid injury and prevent damage to this product or any products connected to it. To avoid potential hazards, use the product only as specified.
CAUTION. These statements identify conditions or practices that could result in damage to the equipment or other property.
WARNING. These statements identify conditions or practices that could result in personal injury or loss of life.
Specific precautions
Do not operate without covers. To avoid personal injury, do not apply any voltage or current to the product without the covers in place.
Electric overload. Never apply a voltage to a connector on the product that is outside the range specified for that connector.
Avoid electric shock. To avoid injury or loss of life, do not connect or disconnect probes or test leads while they are connected to a voltage source.
Do not operate in wet/damp conditions. To avoid electric shock, do not operate this product in wet or damp conditions.

Form number TM61773-5

Rev 3 July 2010

Certifications and Compliances

Safety

Designed to UL 61010-1,second edition, IEC 61010-2-032 second edition, IEC 61010-031)specifications

1000V DC Category III

Input rating

600V DC Category IV 750V AC Category III

600V AC Category IV

Over voltage category CAT IV: Outside and service entrance.

CAT III: Distribution level mains, fixed installation.

CAT II: Local level mains, appliances, and portable equipment. CAT I: Signal level, special equipment or parts of
equipment, telecommunication, electronics.

Page 3

General Specifications Characteristics Display Display Count Over range Indication Sampling Rate Operating Relative Humidity Storage Environment: Power source: Battery Life:
Low Battery Indicator: Auto power off Dimensions
Maximum Cable Size Weight:

Description 4 Digit LCD display 9999 count, maximum reading 9999 “OL” is displayed 2.0 time/second 0 C to 50 C (32 F to 122 F) 0 ~ 70% RH -20 C to 60 C (-4 F to 140 F) at <80% relative humidity 9V Battery (NEDA 1604) 100 hours typical (alkaline) {61-773} 100 hours typical (alkaline) {61-775}
symbol indicates low battery voltage Approximately 30 minutes 10.6″ H X 4.1 ” W X 1.9 ” D 270mm H X 103mm W X 48.5mm D ACA 2.0″ (51mm) Approximately 1.1 lbs. or 500g including battery

RANGES and ACCURACY SPECIFICATION Accuracy: Accuracy specifications at 23°C ±5°C (73.4°F ±9°F) less than 75% RH. Temperature Coefficient: 0.1 times the applicable accuracy specification per degree C from 0 C to 18 C and 28 C to 50 C (32 F to 64 F and 82 F to 122 F) Electrical Specification: Accuracy are ±(reading plus number of digits) at 23°C ±5°C (73.4°F ±9°F) <75% RH

Form number TM61773-5

Rev 3 July 2010

Page 4

61-773 Function / Range
AC Voltage (True RMS) (45-400Hz)
DC Voltage
AC Current (True RMS) (45-400Hz) Resistance Capacitance Frequency Continuity

Ranges
0.0V ~ 600.0V, 45Hz – 100Hz 600.0V ~ 750.0V, 45Hz – 100Hz 0.0V ~ 750.0V, 100Hz – 400Hz 0.0V ~ 600.0V 600.0V ~ 999.9V 0.0A ~ 999.9A, 45Hz – 60Hz 0.0A ~ 999.9A, 60Hz – 400Hz
0.0 ~ 999.9 , 1000 ~ 9999 0.0µF ~ 999.9uF 20.0Hz ~ 400.0Hz (Auto-ranging) <30 on Continuity

Accuracy
1.0% + 5 digits 1.5% + 5 digits 6.0% + 5 digits 1.0% + 5 digits 1.5% + 5 digits 2.0% + 5 digits 6.0% + 5 digits
1.5% + 5 digits 5.0% + 10 digits 0.5% + 5 digits Not specified

61-775 Function / Range
AC Voltage (True RMS) (20-400Hz)
DC Voltage
AC Current (True RMS) (20-400Hz) DC Current Resistance Capacitance Frequency Continuity

Ranges
0.0V ~ 100.0V, 20Hz – 100Hz 100.0V ~ 600.0V, 45Hz – 100Hz 600.0V ~ 750.0V, 45Hz – 100Hz 0.0V ~ 750.0V, 100Hz – 400Hz 0.0V ~ 600.0V 600.0V ~ 999.9V 0.0A ~ 999.9A, 20Hz – 100Hz 0.0A ~ 999.9A, 100Hz – 400Hz
0 ~ 999.9A 0.0 ~ 999.9 , 1000 ~ 10000 0.0µF ~ 999.9uF 20.0Hz ~ 400.0Hz (Auto- ranging) <30 on Continuity

Accuracy
1.0% + 5 digits 1.0% + 5 digits 1.5% + 5 digits 6.0% + 5 digits 1.0% + 5 digits 1.5% + 5 digits 2.0% + 5 digits 6.0% + 5 digits
2.0% + 5 digits 1.5% + 5 digits 5.0% + 15 digits 0.5% + 5 digits Not specified

AC Converter: 61-773, 61-775 ­ True RMS sensing Overload Protection:
AC and DC Voltage: Not to exceed 1000V DC or 750VAC RMS AC Current: Not to exceed 1000A AC DC Current: Not to exceed 1000A DC Resistance: Not to exceed 600V DC or VAC RMS Capacitance, Frequency, Continuity: Not to exceed 600V DC or VAC RMS

1 Frequency Sensitivity: 5V rms on AC VOLTS range Frequency can be measured through clamp head. ( 5AAC at 20 to 100Hz ) ( 10AAC at 100 to 400Hz ), Frequency Overload protection: 1000AAC, 1000VDC or 750VAC rms

Form number TM61773-5

Rev 3 July 2010

PERFORMANCE VERIFICATIONS

Page 5

Perform the following analysis; if the meter conforms to the limits listed in Table 1 through 7 the meter is functioning correctly. If the meter does not conform to any of the listed limits the calibration procedure must be performed.

Performance Verification Preparation 1. Turn on the calibrator, allow calibrator to warm up. Temperature stabilization
should be reached after 30 minutes. 2. Remove battery cover and using a calibrated meter to ensure the battery measures a minimum of 7.5V
DC. If the battery measures under 7.5V DC, replace the battery (see Battery Replacement page 11) before beginning the performance test. 3. Input the values listed in Table 1 through 7.

Table 1 AC Voltage Test

Function /Range V AC 750V V AC 750V V AC 750V V AC 750V

Input
120V AC @ 45Hz 120V AC @ 400Hz 700V AC @ 45Hz 700V AC @ 400Hz

Low Limit 118.3 112.3 689.0 657.5

High Limit 121.7 127.7 711.0 742.5

Model Number
61-773, 61-775 61-773, 61-775 61-773, 61-775 61-773, 61-775

Table 2 DC Voltage Test

Function /Range V DC 1000V V DC 1000V

Input
350V 900V

Low Limit 346.0 886.0

High Limit 354.0 914.0

Model Number
61-773, 61-775 61-773, 61-775

Table 3 AC Current Test

Function /Range A AC 1000A A AC 1000A A AC 1000A A AC 1000A

Input
10A AC @ 50Hz 10A AC @ 400Hz 900A AC @ 50Hz 500A AC @ 400Hz

Low Limit 9.3 8.9 881.5 469.5

High Limit 10.7 11.1 918.5 530.5

Model Number
61-773, 61-775 61-773, 61-775 61-773, 61-775 61-773, 61-775

Table 4 DC Current Test

Function /Range A DC 1000A A DC 1000A

Input
100A DC 900A DC

Low Limit 97.5 881.5

High Limit 102.5 918.5

Model Number
61-775 61-775

Table 5 Resistance Test

Function /Range Input

1000

100

10000

1K

Low Limit 98.5 985

High Limit 101.5 1015

Model Number
61-773, 61-775 61-773, 61-775

Form number TM61773-5

Rev 3 July 2010

Page 6

Table 6 Capacitance and Frequency Tests

Function /Range Input

Hz {through clamp} Hz {auto} {through clamp} Hz {V and COM jacks} MFD 500µF

50Hz @ 5A 200Hz @ 10A 60Hz @ 120V 100µ F

Low Limit 49.70
198.5
59.2
94.0

High Limit 50.30
201.5
60.8
106.0

Model Number 61-773, 61-775 61-773, 61-775 61-773, 61-775 61-773, 61-775

Table 7 Continuity Check

Function /Range
Continuity

Test Value
20 beep on 40 beep off

Low limits

High Limit

Model Number 61-773, 61-775

Form number TM61773-5

Rev 3 July 2010

Page 7
CALIBRATION
Calibration Preparation 1. Turn on the calibrator, allow calibrator to warm up. Perform calibration at
23±2°C (73.4°F ±3.5°F) at relative humidity of < 70%. Temperature stabilization should be reached after 30 minutes. 2. Disconnect the test leads and turn the range switch to “OFF”. 3. Remove the screws holding the battery cover, one at the jaw, and the screw for the TightSightTM cover. 4. Remove the case bottom using care not to damage the leads of battery snap and spring to the continuity beeper. (Beeper is attached to the bottom case cover.) 5. Using a calibrated meter ensure the battery measures a minimum of 7.5V DC. If the battery measures under 7.5V DC, replace the battery (see Battery Replacement page 9).
Calibration Procedure It is recommended that all IDEAL meters undergo the following calibration procedure on an annual basis. The class of calibrator or equipment should have an accuracy that exceeds, by an expectable ratio the accuracy of this instrument.
Auto Calibration: Set the short circuit 2-pin connector, mounted on PC board, from J2 to J1 position. Replace the case bottom of the meter. It is allowed to do calibration for any one of the following functions individually that is inaccurate. There is no need to do calibration for all functions.
V AC Calibration 1. Set Function Switch from OFF to ACV position. 2. Short the V and COM inputs on the meter. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 000.0V ± 1 digit. Zero adjustment is complete. 3. Connect the calibrator to the V and COM inputs on the meter. 4. Output AC 50V/50Hz. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 48V ~ 50V. Adjustment is complete. 5. Output AC 500V/50Hz. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 500.0V ± 2 digits. Adjustment is complete.
V DC Calibration
1. Set the function switch to DCV range. After a reading in the LCD is settled (about 5 seconds), press
MAX/MIN button until unit display reads 000.0 ± 1 digit. Zero adjustment is complete. 2. Connect the calibrator to the V and COM inputs on the meter. 3. Output DC +500V. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button
until unit display reads 500.0V ± 2 digits. Adjustment is complete.
Continuity Calibration 1. Set the function switch to Continuity range. Short the V and COM inputs on the meter. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 000.0 ± 1 digit. Zero adjustment is complete. 2. Connect the calibrator to the V and COM inputs on the meter.
3. Output 800.0 . After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button
until unit display reads 800.0 ± 2 digits. Adjustment is complete.

Form number TM61773-5

Rev 3 July 2010

Page 8
Resistance Calibration 1. Set the function switch to range. Short the V and COM inputs on the meter. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 000.0 ± 1 digit. Zero adjustment is complete. 2. Connect the calibrator to the V and COM inputs on the meter. 3. Output 800.0 . After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 800.0 ± 2 digits. Adjustment is complete. 4. Output 8K . After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 8000 ± 2 digits. Adjustment is complete.
Capacitance Calibration
is settled (about 5 seconds), press MAX/MIN button until unit display reads 000.0 ± 1 digit. Zero adjustment is complete.
2. Plug a 390uF standard capacitor to V and COM inputs. Press MAX/MIN button until unit display
reads 390.0 ± 5 digits. Adjustment is complete.
A DC Calibration (61-775 only)
1. Set the function switch to DCA range. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 000.0 ± 1 digit. Zero adjustment is complete.
2. Set output of the DC calibrator for 7.8A DC and connect it to Coil = 50N = 390.0A DC. 3. Clamp the jaws to the coil = 50N. 4. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display
reads 390.0A ± 2 digits. Adjustment is complete.
A AC Calibration 1. Set the function switch to ACA range. When a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 000.0 ± 1 digit. Zero adjustment is complete. 2. Set output of the AC calibrator for 1.0A/50Hz and connect it to Coil = 50N = 50.0A AC. 3. Clamp the jaws to the coil = 50N. 4. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads about 48A ~ 50A. Adjustment is complete. 5. Set output of the AC calibrator for 7.8A AC/50Hz and connect it to Coil = 50N = 390.0A AC. 6. Clamp the jaws to the coil = 50N. 7. After a reading in the LCD is settled (about 5 seconds), press MAX/MIN button until unit display reads 390.0A ± 2 digits. Adjustment is complete.
Calibration of the 61-770 series is complete. Remove all leads from the calibrator and equipment. Open the case bottom again, and set the short circuit 2-pin connector on PC board from J1 back to J2 position, then replace the case bottom of the meter. Turn the Function Switch from OFF to any position to restart the meter.

Form number TM61773-5

Rev 3 July 2010

Battery Replacement (Refer to Figure 1) 1. Disconnect the test leads from any circuit under test and turn off meter. 2. Use a Philips head screwdriver to remove the screws on battery cover. 3. Remove battery from the battery compartment. 4. Install new 9V battery (NEDA #1604). An alkaline type is recommended. 5. Install new battery into compartment using care to install to proper polarity. 6. Reinstall battery cover.

Page 9

Figure 1

Form number TM61773-5

Rev 3 July 2010

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>