Lindab CBC Plenum Box Installation Guide
- July 10, 2024
- Lindab
Table of Contents
Lindab CBC Plenum Box Installation Guide
Symbols
-
Supply air
-
Extract air
-
Open damper
-
Closed damper
-
No tools – Magnet
-
Lock
-
Unlock
**Unpacking and protection of CBC/CBE
**
Accessories
- **MHS
**
- **M8
**
- **PC410
**
**Dimensions
**
Ød 1 Ød 2 **mm| B| C| D| e mm|
H| L| W| m kg**
---|---|---|---|---|---|---|---|---
100| 125| 65| 213| 78| 40| 175| 273| 209| 1.4
100| 160| 65| 231| 78| 40| 175| 308| 244| 1.6
125| 160| 78| 250| 78| 40| 200| 327| 244| 1.9
125| 200| 78| 270| 78| 40| 200| 367| 284| 2.3
160| 200| 95| 295| 78| 40| 234| 392| 284| 2.6
160| 250| 95| 320| 78| 40| 234| 442| 334| 3.1
200| 250| 115| 345| 78| 40| 274| 467| 334| 3.6
200| 315| 115| 377| 78| 40| 274| 532| 399| 4.3
250| 315| 140| 423| 118| 60| 325| 558| 399| 6.5
250| 400| 140| 466| 118| 60| 325| 643| 484| 8.6
315| 400| 173| 536| 118| 60| 390| 714| 484| 9.8
**Damper options
**
Mounting of CBC/CBE
Accessory MHS
**Threaded rod M8
**
Directly against ceiling
Mounting of diffuser in CBC/CBE
Diffusers: PKA, PCA, LKA, LCA, LCC, LCP, LKP, NO19
Use self tapping screws Not included
Balancing
k-factors for ceiling diffusers + CBC
Supply air
**CBC
| ****PCA| ****PKA| Formo LCA| ****LKA| Integra
LCC/LCP LKP| ****NQ19
---|---|---|---|---|---|---
| SUPPLY**|
CBC-100-125| 9.92| 9.80| 9.37| 9.19| 8.64| 8.18| –
CBC-100-160| 11.64| 11.87| 10.87| 11.44| 10.75| 10.65| 11.06
CBC-125-160| 14.66| 14.82| 12.88| 13.78| 12.77| 12.32| 10.94
CBC-125-200| 16.96| 18.09| 14.58| 17.06| 15.71| 15.19| 17.82
CBC-160-200| 21.39| 22.90| 17.32| 20.65| 18.26| 17.31| 17.57
CBC-160-250| 25.98| 25.83| 22.85| 24.19| 20.63| 21.58| 23.38
CBC-200-250| 30.91| 30.33| 26.29| 28.23| 23.44| 24.60| 25.17
CBC-200-315| 42.64| 43.58| 33.31| 36.78| 28.17| 29.48| 32.24
CBC-250-315| 43.04| 43.50| 32.23| 35.99| 27.66| 28.60| 36.90
CBC-250-400| 55.65| 55.44| 35.25| 41.35| –| –| 41.78
CBC-315-400| 62.89| 70.18| 35.72| 43.74| –| –| 44.33
Supply
Diffuser| Straight duct
SR
| Bend
BKU, BU, BSU
| Expansion
RCFU
| T-piece + min. 2xD*
TCPU
LCC / LCP / LKP / NQ19| ±5| ±7,5%| ±7,5%| ±10,0%
LCA / LKA| 15| 47.5%| $7.5%| 10.0%
PCA/PKA| 7.5| 10.0%| 10.0%| 12.5%
To fulfill the above-mentioned accuracy levels, the min. air speed at the diffuser connection ( Ød2 ) of the plenum box should be 1.2 m/s, which corresponds to the following min. air flow for different sizes
Diffuser connection Ød 2 | min. Air flow |
---|---|
mm | l/s |
125 | 15 |
160 | 24 |
200 | 38 |
250 | 59 |
315 | 94 |
400 | 151 |
To fulfill accuracy for T-piece the following limitations are to be
considered.
Between T-piece and plenum box it is recommended to have 2xD straight duct, (
where D is the duct connection diameter Ød1 ) .
Furthermore, the air speed in main duct should not exceed 6 m/s.
k-factors for ceiling diffusers + CBE
Extract air
**CBE
| ****PCA| Formo PKA LCA| ****LKA| Integra
LCC/LCP LKP
---|---|---|---|---
| EXTRACT|
CBE-100-125| 27.27| 25.38| 16.86| 16.08| 15.83| 16.05
CBE-100-160| 30.54| 45.55| 26.52| 20.74| 20.84| 21.03
CBE-125-160| 23.68| 30.45| 20.45| 17.99| 18.58| 20.44
CBE-125-200| 42.66| 51.88| 27.70| 27.52| 18.39| 25.90
CBE-160-200| 33.16| 33.80| 25.23| 26.66| 19.98| 21.85
CBE-160-250| 40.15| 59.99| 34.07| 40.18| 22.15| 25.65
CBE-200-250| 42.32| 44.98| 31.05| 35.54| 23.58| 26.28
CBE-200-315| 73.24| 83.27| 45.47| 53.07| 29.64| 28.99
CBE-250-315| 57.35| 59.56| 38.27| 43.60| 22.99| 28.20
CBE-250-400| 114.1| 132.61| 41.62| 47.57| –| –
CBE-315-400| 104.11| 103.77| 40.27| 48.54| –| –
Extract**
Diffuser| All connections
LCC / LCP / LKP| ±5%
LCA / LKA| ±5%
PCA / PKA| ±7.5%
To fulfill the above-mentioned accuracy levels, the min. air speed at the diffuser connection ( Ød2 ) of the plenum box should be 1.2 m/s, which corresponds to the following min. air flow for different sizes:
Diffuser connection Ød 2 | min. Air flow |
---|---|
mm | l/s |
125 | 15 |
160 | 24 |
200 | 38 |
250 | 59 |
315 | 94 |
400 | 151 |
**Maintenance
**
Store the damper in the plenum box
**Installation of C- and E-damper
**
For balancing pull measuring tube and damper strings out of plenum box before clicking on faceplate. When balancing, diffuser faceplate MUST be on ! After balancing store strings in box and lock damper strings, see page 7.
Most of us spend the majority of our time indoors. Indoor climate is crucial
to how we feel, how productive we are and if we stay healthy.
We at Lindab have therefore made it our most important objective to contribute
to an indoor climate that improves people’s lives. We do this by developing
energy-efficient ventilation solutions and durable building products. We also
aim to contribute to a better climate for our planet by working in a way that
is sustainable for both people and the environment.
office
Documents / Resources
|
Lindab CBC Plenum
Box
[pdf] Installation Guide
CBC, CBE, CBC Plenum Box, CBC, Plenum Box, Box
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>