Lindab CEA Rectangular Diffuser User Guide

June 4, 2024
Lindab

Lindab CEA Rectangular Diffuser

Description

Comdif CEA is a rectangular perforated displacement diffuser for installation against a wall or column. Behind the perforated front plate, CEA is equipped with individually adjustable nozzles, making it possible to alter the geometry of the near zone. The diffuser can be turned and has a circular duct connection (MF measure), so the diffuser can be connected at the top or bottom. The diffuser is suitable for the supply of large volumes of moderately cooled air.

  • The diffuser is suitable for the supply of large volumes of air.
  • The geometry of the near zone can be adjusted using adjustable nozzles.
  • Plinths can be supplied as accessories.

Maintenance

The front plate can be removed from the diffuser, making it possible to clean the nozzles. The visible parts of the diffuser can be wiped with a damp cloth.

Ordering example

Lindab-CEA-Rectangular-Diffuser-FIG-1

Order – accessories

  • Plinth: CEAZ – 2 – size

Dimension

Lindab-CEA-Rectangular-Diffuser-FIG-2

Size| A [mm]| B [mm]| ØD

[mm]| H [mm]| Weight [kg]
---|---|---|---|---|---
2010| 300| 300| 200| 980| 12.0
2510| 500| 350| 250| 980| 24.0
3115| 800| 500| 315| 1500| 80.0
4015| 800| 600| 400| 1500| 96.0

Accessories

  • Can be supplied with plinth.

Materials and finish

  • Diffuser: Galvanised steel
  • Nozzles: Black plastic
  • Front plate: 1 mm galvanized steel
  • Standard finish: Powder-coated
  • Standard color: RAL 9003 or RAL 9010 – white, gloss 30.

The diffuser is available in other colours. Please contact Lindab’s sales department for further information.

Technical data

Recommended maximum volume flow.

  • The near zone is given at an under-temperature of -3 K to a maximum terminal velocity of 0.20 m/s.
  • Conversion to other terminal velocities – see table 1, correction of the near zone for -3 K and -6 K respectively.

Sound effect level

  • Sound effect level LW [dB] = LWA + Kok

Size|

63

|

125

| Centre frequency Hz

250     500      1K       2K

|

4K

|

8K

---|---|---|---|---|---
2010| 11| 4| 4| 1| 8| 14| 25| 37
2510| 8| 4| 2| 0| 6| 16| 27| 40
3115| 14| 6| 3| 1| 8| 17| 29| 25
4015| 11| 3| 2| 1| 10| 18| 30| 37

Sound attenuation

  • Sound attenuation ΔL [dB] including end reflection.

Size| ****

63

| ****

125

| Centre frequency Hz

250     500      1K       2K

| ****

4K

| ****

8K

---|---|---|---|---|---
2010| 10| 6| 1| 4| 5| 3| 4| 4
2510| 10| 6| 6| 4| 2| 2| 4| 3
3115| 9| 6| 5| 3| 3| 4| 4| 5
4015| 8| 5| 3| 3| 2| 3| 4| 4

Nearzone

Table 1

  • Correction of the near zone (a0.2, b0.2)

Under-

temperature Ti – Tr

| Maximum

velocity m/s

| Mean

velocity m/s

| Correction factor
---|---|---|---
| 0.20| 0.10| 1.00
| 0.25| 0.12| 0.80
-K3| 0.30| 0.15| 0.70
| 0.35| 0.17| 0.60
| 0.40| 0.20| 0.50
| 0.20| 0.10| 1.20
| 0.25| 0.12| 1.00
-6K| 0.30| 0.15| 0.80
| 0.35| 0.17| 0.70
| 0.40| 0.20| 0.60

Lindab reserves the right to make changes without prior notice

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals