EMERSON 1F75C-11PR Programmable Thermostat Installation Guide
- July 8, 2024
- Emerson
Table of Contents
EMERSON 1F75C-11PR Programmable Thermostat
1F75C-11PR (Programmable)
Installation and Operating Instructions
Single Stage Thermostat
Battery Powered or Hardwired with Common
INDEX
Thermostat Installation | 2-4 |
---|---|
Wiring | 2 |
Installer Menu | 3-4 |
Test Equipment | 4 |
Using the Thermostat | 5-7 |
Thermostat Overview | 5 |
Thermostat Operation | 6 |
Thermostat Schedule/Programming | 6-7 |
Troubleshooting | 7-8 |
Homeowner Help Line | 8 |
Thermostat Applications | Maximum Stages Heat/Cool |
--- | --- |
Conventional Gas, Oil, Electric (mV and 24V), Heat Only, Cool Only or Heat/
Cool Systems| 1/1
Heat Pump (air source or geothermal) with no Aux. Heat| 1/1
MERCURY NOTICE: This product does not contain mercury. However, this product may replace a product that contains mercury. Mercury and products containing mercury must not be discarded in household trash. Refer to www.thermostat- recycle.org for information on disposing of products containing mercury.
SPECIFICATIONS
- Electrical Rating
- Battery Power ……………………………….. mV to 30 VAC, NEC Class II, 50/60 Hz
- Input-Hardwire ………………………………. 20 to 30 VAC, NEC Class II, 50/60 Hz
- Terminal Load. …………………………………… 1.0 A per terminal, 1.5A maximum all terminals combined
- Setpoint Range ………………………………….. 45° to 99° F (7° to 37° C)
- Rated Differentials: Fast Med Slow
- Heat (@ 6°F/ Hr). ……………………………. 0.5°F 0.75°F 1.9°F
- Cool (@ 6°F/ Hr). ……………………………. 0.9°F 1.2°F 1.7°F
- Operating Ambient …………………………….. 32°F to +105°F (0° to +41°C)
- Display Temperature Range …………………… 32°F to +99°F (0 to 37°C)
- Operating Humidity ……………………………. 90% non-condensing max
- Shipping Temperature Range ……………….. -20°F to + 150°F (-29° to +65°C)
- Thermostat Dimensions. ……………………… 3-3/4” H x 6” W x 1-1/8” D
THERMOSTAT INSTALLATION
WIRING
Refer to equipment manufacturer’s instructions for specific system wiring
information. After wiring, see INSTALLER MENU for proper thermostat
configuration. Wiring table shown are for typical systems and describe the
thermostat terminal functions.
Terminal Designations | Terminal Function |
---|---|
RC* | Power for Cooling |
RH* | Power for Heating |
O/B | Changeover Terminal-Energized in Heat (B) or Cool (O) for Heat Pump or |
Damper Systems
Y| Cooling Relay
G| Fan Relay
W| Heating Relay
C| Common wire for 24V (optional with batteries)
*When both RC and RH wires are present, cut RC/RH jumper (see next page). **For heat pump systems, add a jumper wire to connect terminals Y and W
Precautions
- Do not exceed the specification ratings.
- All wiring must conform to local and national electrical codes and ordinances.
- This control is a precision instrument, and should be handled carefully. Rough handing or distorting components could cause the control to malfunction.
WARNING
Do not use on circuits exceeding specified voltage. Higher voltage will
damage control and could cause shock or fire hazard.
Do not short out terminals on gas valve or primary control to test. Short or
incorrect wiring will burn out thermostat and could cause personal injury
and/or property damage.
CAUTION
To prevent electrical shock and/or equipment damage, disconnect electrical
power to system, at main fuse or circuit breaker box,until installation is
complete.
-
Gas/Elec Switch
If the system is a heat pump or electric furnace, the GAS/ELEC Switch must be set to Elec. If your system is a gas or oil furnace, the switch must be set to Gas. -
O/B Terminal Switch
The O/B switch on this thermostat is factory set to the O position. This will accommodate the majority of heat pump applications, which require the changeover relay to be energized in Cool. If the heat pump being installed requires a B terminal, to energize the changeover relay in Heat, the O/B switch must be moved to the B position. -
RC/RH Jumper Wire
This thermostat electrically connects the RC and RH terminals so a jumper wire is not required. If the application provides a separate wire for RC and RH, clip the RC/RH jumper. This will isolate both terminals so they can be independently used.
INSTALLER MENU
To access the INSTALLER’S MENU set the system switch to the OFF position and
then press hold the temperature and buttons for 3 seconds. The display will
show item 30 in the table below. Use the temperature buttons by pressing them
simultaneously to navigate through menu items. Press to change a menu setting.
Installer’s Menu #
(Hold Menu 3 Seconds)
| Description| Default Setting
(flashing icons)
| Settings
( Press or)
---|---|---|---
30| Heat Cycle Rate (how often the heat will turn on)|
MEd| SLO – slow MEd – medium FAS – fast
35
| Cool Cycle Rate (how often the cooling will turn on)| MEd| SLO
– slow MEd – medium FAS – fast
50
| Compressor Lockout (protects the compressor from short cycling)| OFF| On – 5 minute display
OFF – no delay
65| Maximum Heat Limit
(maximum set point for heat mode)
| 99| 47 to 99
66| Minimum Cool Limit (minimum set point for cool mode)| 45|
45 to 97
74| Schedule Type (set as either 7-Day, 5-1-1 Day or Non-
Programmable)| 5| 7 – 7 Day
5 – 5-1-1 Day
0 – Non Programmable
(Installer Menu continued on next page)
Installer’s Menu #
(Hold Menu 8 Seconds)
| Description| Default Setting
(flashing icons)
| Settings
---|---|---|---
76| Early Start (starts heating or cooling early so your programmed
temperature is reached by the programmed time)| OFF| On – start
early
OFF – start at program period time
79| Fahrenheit or Celsius| °F| °F – Fahrenheit
°C – Celsius
81| Temperature Display Adjustment (adjust the displayed “Room
Temperature”)| 0| -5 to +5
83
| Continuous Display Light (keep the backlight always on – “C” wire required)| OFF| On – always on
OFF – momentarily
86| Change Air Filter (set up a monthly reminder)| OFF| 1 to 12 – reminder time (months)
OFF – no filter reminder
TEST EQUIPMENT
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
- Move fan switch to On position. The blower should begin to operate.
- Move fan switch to Auto position. The blower should stop immediately.
Heating System
- Move System Switch to Heat position.
- Press to adjust thermostat setting to 1° above room temperature. The system should begin to operate and the thermostat will indicate Heat On.
- Press to adjust thermostat setting 1° below room temperature. The heating system should stop operating and the thermostat should indicate Heat.
Cooling System
- Move System Switch to Cool position.
- Press to adjust thermostat setting 1° below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
- Press to adjust thermostat setting to 1° above room temperature. The cooling system should stop operating and the thermostat will indicate Cool.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating. There will be up to a 5 minute delay before the compressor turns on.(see INSTALLER MENU, item 50)
CAUTION
To prevent compressor and/or property damage, if the outdoor temperature is
below 50°F, DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been
operational for 6 hours and the system has not been operational for at least 5
minutes.
USING THE THERMOSTAT
THERMOSTAT OVERVIEW
Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches.
THERMOSTAT BUTTONS AND SWITCHES | THE DISPLAY |
---|---|
1.) Fan Switch | 9.) Thermostat is protecting the equipment from short cycling |
(5-minute delay)
2.) System Switch| 10.) Indicates that the system is running in cool or heat
3.) Set Correct Time| 11.) Displays the current time
4.) Hold a Permanent Temperature or Run Program| 12.) Battery status indicator
5.) Access Programming| 13.) Low battery indicator
6.) Raises Temperature Setting| 14.) Day of the week used when programming a
schedule
7.) Lowers Temperature Setting| 15.) Permanent hold (bypassing the schedule)
8.) Access Menu Options| 16.) Temperature setpoint
| 17.) Displays when the thermostat setpoint has reached the maximum or
minimum setting.
| 18.) SEE TROUBLESHOOTING
Whenever appears in the display, new premium brand AA alkaline batteries should be installed. If the house will be unoccupied for an extended period and either or Replace ” is displayed, install new batteries before leaving.
THERMOSTAT OPERATION
Set Current Time and Day
Note: Time icons will flash at initial power up or after a reset.
- Press Set Time
- Use to adjust the hour
- Press Set Time to advance to set the minutes and day of the week
- Press Run/Hold when finished.
The default program is 5-1-1 Day, but can be setup as a 7-Day or Non- Programmable thermostat (refer to the Installer Menu above)
- Hold Temperature (bypassing the schedule) – With the System switch set to Heat or Cool, momentarily press the Hold button. Hold will be displayed. Use to adjust the temperature. The thermostat will hold the room temperature at the selected setting until you press Run to start program operation again.
- Program Override (Temporary Hold) – Press until the desired temperature is displayed. The thermostat will override the schedule until the next programmed time period with a minimum override of 2 hours. Then the thermostat will automatically revert
THERMOSTAT SCHEDULE / PROGRAMMING
For tips on programming your thermostat to receive optimal comfort, convenience and energy savings go to: thermostathelper.com
Energy Saving Factory Schedule
This thermostat is programmed with the energy saving settings shown in the
table below for all days of the week.
| P 1 /Wake| P 2 /Leave| P 3 /Return|
P 4 /Sleep
---|---|---|---|---
Heating Schedule| 6:00 AM – 70°F| 8:00 AM – 62°F| 5:00 PM – 70°F|
10:00 PM – 62°F
Cooling Schedule| 6:00 AM – 78°F| 8:00 AM – 85°F| 5:00 PM – 78°F|
10:00 PM – 82°F
Note: Thermostat can be programmed on or off the subbase
Note: Thermostat can be programmed on or off the subbase
ENTERING YOUR PROGRAM
Set Current Time and Day
-
Press TIME button once. The display will show the hour only.
EXAMPLE: -
Press and hold either until you reach the correct hour and AM/PM designation (AM begins at midnight; PM begins at noon).
-
Press TIME once again. The display window will show the minutes only.
EXAMPLE: -
Press and hold either until you reach the correct minutes.
-
Press TIME once again. The display will show the day of the week.
-
Press until you reach the current day of the week.
-
Press RUN/HOLD once. The display will show the correct time, day, room temperature and set-point temperature.
Enter Heating Program
- Move the SYSTEM switch to HEAT.
- Press PRGM once. “Mo Tu We Th Fr” (indicating weekday program) will appear in the display. Also displayed are the currently programmed start time for the 1st heating period and the currently programmed temperature (flashing).
- Press to change the displayed temperature to your selected temperature for the 1st heating program period.
- Press PROGRAM once (the programmed time will flash). Press until your selected time appears. The time will change in 15 minute increments. When your selected time is displayed, press PROGRAM again to return to the change temperature mode.
- Press PROGRAM once. The currently programmed start time and setpoint temperature for the 2nd heating program period will appear.
- Repeat steps 3 and 4 to select the start time and heating temperature for the 2nd heating program period.
- Repeat steps 3 through 5 for the 3rd and 4th heating program periods.
- Press PROGRAM once. “SA” (indicating Saturday program) will appear in the display, along with the start time for the 1st heating period and the currently programmed temperature.
- Repeat steps 3 through 7 to complete Saturday heating programming.
- Press PROGRAM once to change to SU (Sunday) heating programming and repeat steps 3 through 7 to complete Sunday programming.
- When you have completed entering your heating program, press RUN/HOLD.
Enter Cooling Program
- Move SYSTEM switch to COOL position.
- Follow Enter Heating Program for entering your cooling program, using your selected cooling times and temperatures.
CAUTION
If the outside temperature is below 50°F, disconnect power to the cooling
system before programming. Energizing the air conditioner compressor during
cold weather may cause personal injury or property damage.
TROUBLESHOOTING
| |
---|---|---
Symptom| Possible Cause| Corrective Action
No Heat/ No Cool/ No Fan
(common problem)
|
- Blown fuse or tripped circuit breaker
- Furnace power switch to OFF
- Furnace blower compartment door panel loose or not properly installed
- Loose connection to thermostat or system
|
- Replace fuse or reset breaker
- Turn switch to ON
- Replace door panel in proper position to engage safety interlock or door switch
- Tighten Connections
No Heat|
- System Switch not set to Heat
- Loose connection to thermostat or system
- Heating System requires service or thermostat requires replacement
| Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within five minutes the thermostat should make a soft click sound and “Heat On” should appear on display. This sound indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed below. If the thermostat does not click after being reset, contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly.
(Troubleshooting continued on next page)
Symptom | Possible Cause | Corrective Action |
---|---|---|
No Cool |
- System Switch not set to Cool
- Loose connection to thermostat or system
- Cooling System requires service or thermostat requires replacement
| Verify thermostat and system wires are securely attached.
Diagnostic: Set System Switch to Cool and lower setpoint below room temperature. Same procedures as diagnostic for “No Heat” condition except set the thermostat to Cool and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the installer menu. (see INSTALLER MENU, item 50)
Heat, Cool or Fan Runs Constantly| Possible short in wiring, thermostat, heat,
cool or fan system| Check each wire connection to verify they are not shorted
or touching other wires. Try resetting the thermostat. If the condition
persists contact your HVAC service person.
Thermostat Display & Thermometer Disagree| Thermostat display requires
adjustment| Display can be adjusted +/-5°. See User Menu item
04
Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature
swing)| The location of the thermostat and/or the size of the Heating System
may be influencing the cycle rate| Digital thermostats provide precise control
and cycle faster than older mechanical models. The system turns on and off
more frequently but runs for a shorter time. If you would like to increase
cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu
items 30 & 35) If an acceptable cycle rate is not achieved, contact your HVAC
service person.
“Call for Service” icon appears on displayed|
- Heating system is not able to heat the space to within 10 degrees of the setpoint within 2 hours
- Cooling system is not able to cool the space to within 10 degrees of the setpoint within 2 hours
- If “–” is displayed for the Room Temperature, a replacement thermostat is needed
- None of the buttons operate on the thermostat
|
- See corrective action for “No Heat”
- See corrective action for “No Cool”
- Replace thermostat
- Make sure keypad lockout is not turned on (denoted by icon)
Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or does not
respond to key presses, the thermostat should be reset by removing the
batteries for 2 minutes. This reset will not change the menu settings or
program. If the condition persists after reinstalling the batteries, replace
the thermostat.
To conveniently reset only the schedule and user settings back to factory defaults, press and Set Time buttons at the same time and hold until the display goes blank and resets.
WARNING: This product contains a chemical known to the state of California to cause cancer and birth defects and other reproductive harm.
HOMEOWNER HELP LINE: 1-800-284-2925
- Emerson and White-Rodgers are trademarks of Emerson Electric Co. ©2021 Emerson Electric Co.
- All rights reserved.
- emerson.com/white-rodgers