IDENTIV 7010-B Primis Access Control Reader User Manual

June 5, 2024
IDENTIV

7010-B Primis Access Control Reader
User Manual

Confidential

Author Sixtus Stanly
Version Rev 1.0
Date 23-Sep-20
Document no 701001_UM

Document History

Version Date Description of Chang Author
1 23-Sep-20 Initial Version Sixtus Stanly

Introduction

This document details the Physical Access Control Reader 7010-B PRIMIS Reader and its user instruction and installation procedures.
The 7010-B is a dual Technology RFID reader that works with both 13.56MHz and 125KHz contactless Smart cards to enable the cardholder access to secure areas.
The reader supports an industry-standard Wiegand interface for communication with the control panels.

Reader

Functionality

7010-B is a physical access control Contactless card reader (accessory equipment) that can read the following credentials
Contactless HF (13.56MHz) conforming with ISO 14443 A & B, ISO15693
Contactless LF (125KHz) credentials of type FSK, ASK, PSK
User-feedback interfaces on the reader include Bi-Color LED’s (RED and GREEN) and Buzzer.
The reader can be interfaced with an access control panel equipped with a Wiegand interface.

Front/Top Casing View

IDENTIV 7010 B Primis Access Control Reader - Casing
View

Isometric View

IDENTIV 7010 B Primis Access Control Reader - Isometric
View

Rear View with back plate

IDENTIV 7010 B Primis Access Control Reader - Back
plateIDENTIV 7010 B Primis Access Control
Reader - Back plate 1

Product details

Product Name PRIMIS
Model number 7010-B
Device Type  RFID reader, 13.56MHz (HF)

125 KHz (LF),
Physical Access control Reader (accessory equipment)
Type of equipment| Potted Reader, Suitable for Indoor and outdoor use
Interface Type| Pigtail cable
Voltage Rating| 5 to 12V DC
Current Rating @12V| Peak Current – 140 mA, Average Current – 90 mA
Communication protocol| Wiegand

Specifications

Model| Operating Voltage| Current| Operating temp| Operating humidity
---|---|---|---|---
7010-B| 5 to 12 VDC| Av: 90 mA
Pk: 140 mA| -35 to +66 deg C| 5 to 95 % RH

Product Label

IDENTIV 7010 B Primis Access Control Reader - Product
Label

Product Certification ID’s

FCC Certification ID – MBPRIMIS-00
IC Certification ID – 7485A-PRIMISR0

Installation details

Wiring methods shall be in accordance with the National Electrical Code (ANSI/NFPA70), local codes, and the authorities having jurisdiction.

Parts List
  • 7010-B reader -1
  • Screws (A #6-18X1.5″ SS) – 2Nos – Back Plate mounting screws for Wall
  • Screws (SMF #6-32×3/8″ SS) – 1 No – 1 casing to back plate mounting screw
  • Nylon anchor plug -2 Nos
  • Back Plate – 1 No
Recommended Infrastructure
  • All cabling and wiring shall be UL Listed and/or UL Recognized

  • Cable Wiegand
    – 22AWG Shielded cable or better.
    Max cable length for Wiegand is 150m / 500 ft.
    Cabling shall comply with UL2556 VW-1 for the IEC62368 compliant installations

  • Power Supply – ES1 / PS2 Linear DC PSU – 12 V typ, 500mA min. (for IEC 62368 compliant installations).
    For compliance with CE certification for conducted emission, use a local power supply to power the reader, not more than 3m from the reader.

Pigtail cable color code details
RED POWER
 BLACK + WHITE GROUND
BLACK DRAIN
PINK Tx
GRAY Rx
GREEN DATA 0
WHITE DATA 1
ORANGE LED GRN
YELLOW BUZZER

Table 1

  • Shield Ground/ Drain – Black wire should be connected to the cable shield.
  • Pink/ Grey is not for field use. It is Only for Debug purposes and needs to be taped and secured separately from the other cables.

Caution:
During Wiring make sure that the +VDC lines do not make contact with any other wires, as it might affect reader functionality/ cause damage to the reader.

Mounting the Reader

7.4.1 Reference for the location of mounting holes on the wall
IDENTIV 7010 B Primis Access Control Reader - Mounting the
Reader 7.4.2 Reader Installation Steps
a. Make the required holes on the wall as per the backplate drawing above.
b. The reader is to be mounted at a height less than 2 meters from the floor for MS1 compliance as per IEC 62368-1
c. Insert the nylon screw plugs into the wall.
d. Connect the wires as per the Table 1
e. Secure the backplate onto the wall using the Screws
f. Hook the reader onto the backplate
g. Secure the reader and backplate by the Screw (SMF #6-32×3/8″ SS)
IDENTIV 7010 B Primis Access Control Reader - Reader
Installation

Power up and Testing

  1. Turn power on
    The LED blinks 3 times green with a long beep, then turns red IDENTIV 7010 B
Primis Access Control Reader - Power on

  2. Present a card
    Contactless card ( HF/ LF) – The LED blinks green, and a short Beep is heard IDENTIV 7010 B Primis Access Control Reader - Present a
card

Certifications

FCC

This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:

  1. This device may not cause harmful interference, and
  2. This device must accept any interference received, including interference that may cause undesired operation

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Information to user
Changes or modifications not expressly approved by Identiv could void the user’s authority to operate the equipment.

ISED

This device complies with Innovation, Science, and Economic Development Canada’s license-exempt RSS standard(s).
Operation is subject to the following two conditions.

  1. This device may not cause interference
  2. This device must accept any interference, including interference that may cause undesired operation of the device
CE

Identiv hereby declares that the PRIMIS reader Model 7010-B is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals