SUNGROW SG6.0RT-P2 3 Phase PV Grid Connected Inverter User Manual
- July 9, 2024
- SUNGROW
Table of Contents
- SUNGROW SG6.0RT-P2 3 Phase PV Grid Connected Inverter
- Product Specifications
- FAQs
- About This Manual
- Safety Instructions
- Product Description
- Unpacking and Storage
- Mechanical Mounting
- Electrical Connection
- Commissioning
- iSolarCloud App
- System Decommissioning
- Troubleshooting and Maintenance
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SUNGROW SG6.0RT-P2 3 Phase PV Grid Connected Inverter
Product Specifications
- Model: SG3.0RT / SG4.0RT / SG5.0RT / SG6.0RT / SG7.0RT / SG8.0RT / SG10RT / SG12RT / SG15RT / SG17RT / SG20RT /SG5.0RT-P2 / SG6.0RT-P2 / SG7.0RT-P2 / SG8.0RT-P2 / SG10RT-P2 / SG12RT-P2 / SG15RT-P2 / SG17RT-P2 / SG20RT-P2
- 3-Phase PV Grid-Connected Inverter
- User Manual: SG3.0-20RT_SG5.0-20RT-P2-UEN-Ver12-202310
Safety Instructions
Ensure to follow all safety instructions provided in the manual to prevent any potential hazards or injuries.
Product Description
The inverter is designed for grid-connected PV systems to convert solar energy into usable electrical power.
Unpacking and Storage
Unpacking and Inspection
When unpacking, carefully inspect the inverter for any damages that may have occurred during transit.
Inverter Storage
Store the inverter in a dry and well-ventilated area away from direct sunlight or moisture.
Mechanical Mounting
Safety During Mounting
Follow safety guidelines during the mounting process to prevent accidents.
Location Requirements
Install the inverter in a location that meets the specified requirements mentioned in the manual.
Electrical Connection
Safety Instructions
Adhere to all safety precautions while making electrical connections to avoid electric shock or damage.
Terminal Description
Refer to the terminal description section for understanding the connection points on the inverter.
Electrical Connection Overview
Get an overview of the electrical connections required for proper functioning of the inverter.
External Protective Grounding Connection
Ensure proper grounding connection is established to prevent electrical faults.
FAQs
- Can I install the inverter myself?
- No, the inverter must only be installed by professional technicians to ensure proper installation and operation.
- What should I do if I notice any damage during unpacking?
- If any damage is noticed during unpacking, contact the supplier or manufacturer for further instructions.
User Manual
3-Phase PV Grid-Connected Inverter
SG3.0RT / SG4.0RT / SG5.0RT / SG6.0RT / SG7.0RT / SG8.0RT / SG10RT / SG12RT /
SG15RT / SG17RT / SG20RT /SG5.0RT-P2 / SG6.0RT-P2 / SG7.0RT-P2 / SG8.0RT-P2 /
SG10RT-P2 / SG12RT-P2 / SG15RT-P2 / SG17RT-P2 / SG20RT-P2
SG3.0RT / SG4.0RT / SG5.0RT / SG6.0RT / SG7.0RT / SG8.0RT / SG10RT / SG12RT /
SG15RT / SG17RT / SG20RT /SG5.0RT-P2 / SG6.0RT-P2 / SG7.0RT-P2 / SG8.0RT-P2 /
SG10RTP2 / SG12RT-P2 / SG15RT-P2 / SG17RT-P2 / SG20RT-P23-Phase PV Grid-
Connected InverterUser SG3.0-20RT_SG5.0-20RT-P2-UEN-Ver12-202310
All Rights Reserved
All Rights Reserved No part of this document can be reproduced in any form or
by any means without the prior written permission of Sungrow Power Supply Co.,
Ltd (hereinafter “SUNGROW”). Trademarks
and other Sungrow trademarks used in this manual are owned by SUNGROW. All
other trademarks or registered trademarks mentioned in this manual are owned
by their respective owners. Software Licenses · It is prohibited to use data
contained in firmware or software developed by SUNGROW,
in part or in full, for commercial purposes by any means. · It is prohibited
to perform reverse engineering, cracking, or any other operations that
compromise the original program design of the software developed by SUNGROW.
I
About This Manual
The manual mainly contains the product information, as well as guidelines for
installation, operation, and maintenance. The manual does not include complete
information about the photovoltaic (PV) system. Readers can get additional
information at www.sungrowpower. com or on the webpage of the respective
component manufacturer. Validity This manual is valid for the following model
of low-power grid-connected PV string inverters: · SG3.0RT · SG4.0RT · SG5.0RT
· SG6.0RT · SG7.0RT · SG8.0RT · SG10RT · SG12RT · SG15RT · SG17RT · SG20RT ·
SG5.0RT-P2 · SG6.0RT-P2 · SG7.0RT-P2 · SG8.0RT-P2 · SG10RT-P2 · SG12RT-P2 ·
SG15RT-P2 · SG17RT-P2 · SG20RT-P2
It will be referred to as “inverter” hereinafter unless otherwise specified.
Target Group This manual is intended for professional technicians who are
responsible for installation, operation, and maintenance of inverters, and
users who need to check inverter parameters. The inverter must only be
installed by professional technicians. The professional technician is required
to meet the following requirements:
II
· Know electronic, electrical wiring and mechanical expertise, and be familiar
with electrical and mechanical schematics.
· Have received professional training related to the installation and
commissioning of electrical equipment.
· Be able to quickly respond to hazards or emergencies that occur during
installation and commissioning.
· Be familiar with local standards and relevant safety regulations of
electrical systems. · Read this manual thoroughly and understand the safety
instructions related to
operations. How to Use This Manual Please read this manual carefully before
using the product and keep it properly at a place for easy access. All
contents, pictures, marks, and symbols in this manual are owned by SUNGROW. No
part of this document may be reprinted by the non-internal staff of SUNGROW
without written authorization. Contents of this manual may be periodically
updated or revised, and the actual product purchased shall prevail. Users can
obtain the latest manual from support.sungrowpower.com or sales channels.
Symbols This manual contains important safety instructions, which are
highlighted with the following symbols, to ensure personal and property safety
during usage, or to help optimize the product performance in an efficient way.
Please carefully understand the meaning of these warning symbols to better use
the manual.
Indicates high-risk potential hazards that, if not avoided, may lead to death
or serious injury.
Indicates moderate-risk potential hazards that, if not avoided, may lead to
death or serious injury.
Indicates low-risk potential hazards that, if not avoided, may lead to minor
or moderate injury.
Indicates potential risks that, if not avoided, may lead to device
malfunctions or financial losses.
III
“NOTE” indicates additional information, emphasized contents or tips that may be helpful, e.g., to help you solve problems or save time.
Safety Instructions
When installing, commissioning, operating, and maintaining the product,
strictly observe the labels on the product and the safety requirements in the
manual. Incorrect operation or work may cause: · Injury or death to the
operator or a third party. · Damage to the product and other properties.
· Do not operate the product and cables (including but not limited to moving
the product, installing the product, operating the product and cables,
powering up the product, maintaining the product, and working at heights) in
harsh weather conditions such as flooding, lightning, rain, snow, and level 6
or stronger wind.
· In case of fire, evacuate from the building or product area and call the
fire alarm. Re-entry into the burning area is strictly prohibited under any
circumstances.
· Tighten the screws with the specified torque using tools when fastening the
product and terminals. Otherwise, the product may be damaged. And the damage
caused is not covered by the warranty.
· Learn how to use tools correctly before using them to avoid hurting people
or damaging the device.
· Maintain the device with sufficient knowledge of this manual and use proper
tools.
· The safety instructions in this manual are only supplements and cannot cover
all the precautions that should be followed. Perform operations considering
actual onsite conditions.
· SUNGROW shall not be held liable for any damage caused by violation of
general safety operation requirements, general safety standards, or any safety
instruction in this manual.
· When installing, operating, and maintaining the product, comply with local
laws and regulations. The safety precautions in this manual are only
supplements to local laws and regulations.
1
1 Safety Instructions
1.1 Unpacking and Inspection
User Manual
· Check all safety signs, warning labels and nameplates on devices.
· The safety signs, warning labels and nameplates must be clearly visible and
cannot be removed or covered before the device is decommissioned.
After receiving the product, check whether the appearance and structural parts
of the device are damaged, and check whether the packing list is consistent
with the actual ordered product. If there are problems with the above
inspection items, do not install the device and contact your distributor
first. If the problem persists, contact SUNGROW in time.
1.2 Installation Safety
· Make sure there is no electrical connection before installation. · Before
drilling, avoid the water and electricity wiring in the wall.
Improper installation may cause personal injury! · If the product supports
hoisting transport and is hoisted by hoisting tools, no
one is allowed to stay under the product. · When moving the product, be aware
of the product weight and keep the balance
to prevent it from tilting or falling.
Before operating the product, must check and ensure that tools to be used have been maintained regularly.
2
User Manual
1.3 Electrical Connection Safety
1 Safety Instructions
· Before electrical connections, please make sure that the inverter is not
damaged, otherwise it may cause danger!
· Before electrical connections, please make sure that the inverter switch and
all switches connected to the inverter are set to “OFF”, otherwise electric
shock may occur!
The PV string will generate lethal high voltage when exposed to sunlight.
· Operators must wear proper personal protective equipment during electrical
connections.
· Must ensure that cables are voltage-free with a measuring instrument before
touching DC cables.
· Respect all safety instructions listed in relevant documents about PV
strings.
· The inverter must not be connected to a PV string that requires positive or
negative grounding.
Danger to life due to a high voltage inside the inverter! · Be sure to use
special insulation tools during cable connections. · Note and observe the
warning labels on the product, and perform operations
strictly following the safety instructions. · Respect all safety instructions
listed in this manual and other pertinent
documents.
Damage to the product caused by incorrect wiring is not covered by the
warranty. · Electrical connection must be performed by professionals. · All
cables used in the PV generation system must be firmly attached, properly
insulated, and adequately dimensioned.
3
1 Safety Instructions
User Manual
· Check the positive and negative polarity of the PV strings, and connect the
PV connectors to corresponding terminals only after ensuring polarity
correctness.
· During the installation and operation of the inverter, please ensure that
the positive or negative poles of PV strings do not short-circuit to the
ground. Otherwise, an AC or DC short-circuit may occur, resulting in equipment
damage. The damage caused by this is not covered by the warranty.
Comply with the safety instructions related to PV strings and the regulations
related to the local grid.
1.4 Operation Safety
When routing cables, ensure a distance of at least 30 mm between the cables
and heat-generating components or areas to protect the insulation layer of
cables from aging and damage. When the product is working: · Do not touch the
product enclosure. · It is strictly forbidden to plug and unplug any connector
on the inverter. · Do not touch any wiring terminal of the inverter.
Otherwise, electric shock may
occur. · Do not disassemble any parts of the inverter. Otherwise, electric
shock may
occur. · It is strictly forbidden to touch any hot parts of the inverter (such
as the heat
sink). Otherwise, it may cause burns. · Do not connect or remove any battery.
Otherwise, electric shock may occur. · Do not connect or remove any PV string
or any PV module in a string. Other-
wise, electric shock may occur. · If the inverter is equipped with a DC
switch, do not operate it. Otherwise, it may
cause device damage or personal injury.
4
User Manual
1.5 Maintenance Safety
1 Safety Instructions
Risk of inverter damage or personal injury due to incorrect service!
· Before maintenance, disconnect the AC circuit breaker on the grid side and
then the DC switch. If a fault that may cause personal injury or device damage
is found before maintenance, disconnect the AC circuit breaker and wait until
the night before operating the DC switch. Otherwise, a fire inside the product
or an explosion may occur, causing personal injuries.
· After the inverter is powered off for 10 minutes, measure the voltage and
current with professional instrument. Only when there is no voltage nor
current can operators who wear protective equipment operate and maintain the
inverter.
· Even if the inverter is shut down, it may still be hot and cause burns. Wear
protective gloves before operating the inverter after it cools down.
Touching the power grid or the contact points and terminals on the inverter
connected to the power grid may lead to electric shock!
· The power grid side may generate voltage. Always use a standard voltmeter to
ensure that there is no voltage before touching.
To prevent misuse or accidents caused by unrelated personnel, post prominent warning signs or demarcate safety warning areas around the product.
To avoid the risk of electric shock, do not perform any other maintenance operations beyond those described in this manual. If necessary, contact your distributor first. If the problem persists, contact SUNGROW. Otherwise, the losses caused is not covered by the warranty.
5
1 Safety Instructions
User Manual
· If the paint on the inverter enclosure falls or rusts, repair it in time.
Otherwise, the inverter performance may be affected.
· Do not use cleaning agents to clean the inverter. Otherwise, the inverter
may be damaged, and the loss caused is not covered by the warranty.
· As the inverter contains no parts that can be maintained, never open the
enclosure of the inverter or replace any internal components without
authorization. Otherwise, the loss caused is not covered by the warranty.
1.6 Disposal Safety
Please scrap the product in accordance with relevant local regulations and
standards to avoid property losses or casualties.
6
Product Description
2.1 System Introduction
The inverter is a transformerless 3-phase PV grid-connected inverter. As an
integral component in the PV power system, the inverter is designed to convert
the direct current power generated from the PV modules into grid-compatible AC
current and feeds the AC current to the utility grid.
· The inverter must only be operated with PV strings with class II protection
in accordance with IEC 61730, application class A. It is not allowed for the
positive pole or the negative pole of the PV strings to be grounded. This can
cause damage to the inverter.
· Do not connect any local load between the inverter and the AC circuit
breaker.
The inverter applies only to the scenarios described in this manual. The
intended usage of the inverter is illustrated in the following figure (what
are in the dashed box are optional).
7
2 Product Description
User Manual
figure 2-1 Inverter Application in PV Power System
Item A
B
C D E
Description PV strings
Inverter Metering device Utility grid Optimizer
Note Compatible with monocrystalline silicon, polycrystalline silicon, and
thin-film modules without grounding SG3.0RT, SG4.0RT, SG5.0RT, SG6.0RT,
SG7.0RT, SG8.0RT, SG10RT, SG12RT, SG15RT, SG17RT, SG20RT, SG5.0RT-P2,
SG6.0RT-P2, SG7.0RT-P2, SG8.0RT-P2, SG10RT-P2, SG12RT-P2, SG15RT-P2,
SG17RT-P2, SG20RT-P2 Meter cupboard with power distribution system
TT, TN-C, TN-S, TN-C-S Inverters that are compatible with the optimizer
include: SG5.0RT-P2, SG6.0RT-P2, SG7.0RT-P2, SG8.0RT-P2, SG10RT-P2, SG12RT-P2,
SG15RT-P2, SG17RT-P2, SG20RT-P2
Please refer to the optimizer user manual for details.
8
User Manual
2 Product Description
Please contact your local sales staff to confirm that the optimizer is available for sale in your territory. SP600S optimizer is not compatible with third-party products.
It is recommended to use the optimizer produced by SUNGROW. Optimizers from
third-party manufacturers may fail or even cause unknown losses.
The following figure shows the common grid configurations.
2.2 Product Introduction
Model Description The model description is as follows (take SG10RT as an
example):
Appearance The following figure shows the appearance of the inverter. The
image shown here is for reference only. The actual product received may
differ.
9
2 Product Description
User Manual
figure 2-2 Inverter Appearance
No. Name
1
Nameplate
2
LED indicator
3
Hanger
Description To clearly identify the product, including device model, S/N, important specifications, marks of certification institutions, etc. To indicate the current working state of the inverter. Complement to the included wall-mounting bracket for hanging the inverter.
4
Label
DC switch
5
(Optional)
Information about COM2 pin definition, supported DRM modes, etc.
To safely disconnect the DC circuit whenever necessary.
Electrical connec- DC terminals (SG20RT for example), AC terminal, additional
6 tion area
grounding terminal and communication terminals.
Optimization of the inverter’s heat dissipation. Only the
7
Fans
SG15RT, SG17RT, SG20RT, SG15RT-P2, SG17RT-P2 and
SG20RT-P2 are equipped with fans.
Dimensions The following figure shows the dimensions of the inverter.
10
User Manual
2 Product Description
figure 2-3 Dimensions of the Inverter(in mm)
2.3 Symbols on Product
Symbol
Explanation Regulatory compliance mark.
TÜV mark of conformity. CE mark of conformity. EU/EEA Importer. UKCA mark of conformity.
Do not dispose of the inverter together with household waste.
The inverter does not have a transformer. Disconnect the inverter from all the
external power sources before maintenance! Read the user manual before
maintenance!
Burn danger due to the hot surface that may exceed 60.
11
2 Product Description
User Manual
Symbol
Explanation Danger to life due to high voltages! Do not touch live parts for
10 minutes after disconnection from the power sources. Only qualified
personnel can open and maintain the inverter.
External protective grounding terminal.
- The table shown here is for reference only. The actual product received may differ.
2.4 LED Indicator
The LED indicator on the front of the inverter indicates the working state of the inverter.
table 2-1 LED Indicator State Description
LED Color
State On
Definition The inverter is operating normally.
Blue
Blink
The inverter is at standby or startup state (not feeding power into the grid).
On
A system fault has occured.
Red
Gray
Off
Both the AC and DC sides are powered down.
Voltage may still be present in AC side circuits after the indicator is off.
Pay attention to the electricity safety when operating.
2.5 Circuit Diagram
The following figure shows the main circuit of the inverter.
12
User Manual
2 Product Description
figure 2-4 Circuit Diagram (SG5.0RT for example) · DC Switches can safely
disconnect the PV input when necessary to ensure the safe op-
eration of the inverter and the safety of personnel. · The DC SPD provides a
discharge circuit for the DC side overvoltage to prevent it from
damaging the internal circuits of the inverter. · EMI filters can filter out
the electromagnetic interference inside the inverter to ensure that
the inverter meets the requirements of electromagnetic compatibility
standards. · The MPPT is used to ensure a maximum power from PV arrays at
different PV input
conditions. · The Inverter Circuit converts the DC power into grid-compliant
AC power and feeds it into
the grid. · The AC filter filters the output AC component of high frequency to
ensure that the output
current meets the grid requirements. · The AC relay isolates the AC output of
the inverter from the grid, making the inverter safe
from the grid in case of inverter failure or grid failure. · The AC SPD
provides a discharge circuit for the AC side overvoltage to prevent it from
damaging the internal circuits of the inverter.
If the lightning level exceeds the protection level of the product, surge
protection and overvoltage protection may fail, resulting in electric shock
and fatal injury!
2.6 Function Description
Basic Function · Conversion function
The inverter converts the DC power from the PV array to the AC power, in
conformity with the grid requirements. · Data storage The inverter logs
running information, error records, etc. · Parameter configuration
13
2 Product Description
User Manual
The inverter provides various parameter configurations for optimal operation.
Parameters can be set via the iSolarCloud App or the cloud server. ·
Communication interface
The inverter is equipped with two communication interfaces.The communication
device can be connected to the inverter via both interfaces.
After communication connection is established, users can view inverter
information, operational data and can set inverter parameters through the
iSolarCloud.
It is recommended to use the communication module from SUNGROW. Using a device from other companies may lead to communication failure or other unexpected damage.
· Protection Function
Several protective functions are integrated in the inverter, including short
circuit protection, grounding insulation resistance monitoring, residual
current protection, grid monitoring, DC overvoltage/overcurrent protection,
etc. Earth Fault Alarm The inverter is equipped with a DO relay for the local
earth fault alarm. The additional equipment required is a light indicator
and/or a buzzer that needs additional power supply. After the connection, if
the earth fault occurs, the DO dry-contact will switch on automatically to
signal the external alarm. DRM (“AU”/”NZ”) The DRM function is only applicable
to a single inverter. The inverter provides terminals for connecting to a
Demand Response Enabling Device (DRED). After the connection, the DRED asserts
demand response modes (DRMs). The inverter detects and initiates a response to
all supported demand response modes listed in the following table.
table 2-2 Demand Response Mode Explanation
Mode Explanation
DRM0 The inverter is in the state of shutdown.
Ripple Control The inverter provides terminals (DRM) for connecting to a
Ripple Control Receiver (RCR). After the connection, the grid dispatching
center issues regulation instructions via dry contact (DI). The inverter can
control power output according to the local preset instructions. PID Recovery
· For positive voltage scheme, after the PID function is enabled, the voltage
to ground of all PV strings is greater than 0, and therefore the PV string-to-
ground voltage is a positive value.
14
User Manual
2 Product Description
· For negative voltage scheme, after the PID function is enabled, the voltage to ground of all PV strings is lower than 0, and therefore the PV string-to- ground voltage is a negative value.
· Before enabling the PID recovery function, make sure the voltage polarity of
the PV modules to ground meets requirement. If there are any questions,
contact the PV module manufacturer or read its corresponding user manual.
· If the voltage scheme for the PID recovery function does not meet the
requirement of corresponding PV modules, the PID function will not work as
expected or even damage the PV modules.
When the inverter is not running, the PID module will apply inverse voltage to
PV modules, to restore the degraded modules.
· If the PID recovery function is enabled, it only works at night. · After the
PID recovery function is enabled, the voltage of the PV strings to
ground is 500 V DC by default, and the default value can be modified through
the App.
Auto-test (for Italy CEI0-21 Grid Code Only) The Italy CEI0-21 grid code
requires auto-test for the inverter before grid connection. During the auto-
test, the inverter checks the protection threshold and protection time of the
1-level overvoltage (59.S1), 2-level overvoltage (59.S2),1-level undervoltage
(27.S1), 2-level undervoltage (27. S2),1-level overfrequency (81>. S1),
2-level overfrequency (81>. S2), 1-level underfrequency (81<.S1), 2-level
underfrequency (81<.S2) to ensure that the inverter could
15
2 Product Description
User Manual
meet the requirements of CEI0-21 to protect the grid from abnormality after
the inverter is operational. AFCI Function(Optional) · AFCI activation
This function can be enabled to detect whether serial fault arc occurs in the
loop between PV array and inverter. · AFCI self-test
This function is intended to test whether AFCI works as normal. · Clear AFCI
Alarm
When the inverter detects the AFCI alarm, it stops working. Clear the AFCI
alarm so that the inverter can restart the detection.
The fault arc detection function meets the standard requirements, please test
under the working conditions as required by the standard.
SPI Function(for Italy CEI0-21 Grid Code Only) The inverter SPI interface, only for Italy, is able to easily choose the grid protection mode based on the local plant requirements:
· Local SPI Mode: protected by the preset values in inverter. · External SPI Mode: protected by a separate SPI protection device on site.
Plant Size SPI Control Modes
11.08 kVA
Local SPI Mode (Default in Inverter)
SPI Interface
Integrated in Inverter
External
SPI Sig-
nal
0
0
Setting
Local
0
SPI Sig-
nal
(Default in
1
Setting
Inverter)
11.08 kVA
Local SPI Mode (Default in Inverter)
Integrated in Inverter
External SPI Mode
Separate SPI Protection Device on Site
0
0
1
0
(Default in
1
1
Inverter)
16
User Manual
2 Product Description
Plant Size 59.S1 59.S2 27.S1 27.S2 81>.S1 81<.S1 81>.S2 81<.S2
Notes
11.08 kVA
11.08 kVA
253 V / < 603 s
264.5 V / 0.2 s
195.5 V / 1.5 s
34.5 V / 0.2 s
—
—
51.5 Hz / 0.1 s
47.5 Hz / 0.1 s
253 V / < 603 s
264.5 V / 0.2 s
195.5 V / 1.5 s
34.5 V / 0.2 s 50.2 Hz / 0.1
s 49.8 Hz / 0.1
s 51.5 Hz / 0.1
s 47.5 Hz / 0.1
s
253 V / < 603 s
264.5 V / 0.2 s
195.5 V / 1.5 s
34.5 V / 0.2 s
—
—
51.5 Hz / 0.1 s
51.5 Hz / 0.1 s
253 V / < 603 s
264.5 V / 0.2 s
195.5 V / 1.5 s
34.5 V / 0.2 s 50.2 Hz / 0.1
s 49.8 Hz / 0.1
s 51.5 Hz / 0.1
s 51.5 Hz / 0.1
s
—
—
—
—
253 V / <603 s
264.5 V / <4 s
195.5 V / <4 s
34.5 V / <4 s 51.5 Hz / <4
s 47.5 Hz / <4
s 51.5 Hz / <4
s 47.5 Hz / <4
s Values from SPI Protection Device on site shall not exceed the above
Optimizer Functions · Module-level MPPT
Increase the power generation of the PV system by continuously tracking the
maximum power point of the PV module.
· Module-level shutdown
Quickly reduce module voltage. · Module-level monitoring
The optimizer can monitor the performance of modules. · Module-level IV curve diagnosis
The optimizer can scan the module IV curve and judge whether a module fault occurs.
17
Unpacking and Storage
3.1 Unpacking and Inspection
The product is thoroughly tested and strictly inspected before delivery.
Nonetheless, damage may still occur during shipping. For this reason, please
conduct a thorough inspection after receiving the product. · Check the packing
case for any visible damage. · Check the scope of delivery for completeness
according to the packing list. · Check the inner contents for damage after
unpacking. Contact SUNGROW or the transport company in case of any damage or
incompleteness, and provide photos to facilitate services. Do not dispose of
the original packing case. It is recommended to store the device in the
original packing case when the product is decommissioned.
· After receiving the product, check whether the appearance and structural
parts of the device are damaged, and check whether the packing list is
consistent with the actual ordered product. If there are problems with the
above inspection items, do not install the device and contact your distributor
first. If the problem persists, contact SUNGROW in time.
· If any tool is used for unpacking, be careful not to damage the product.
3.2 Inverter Storage
Proper storage is required if the inverter is not installed immediately. ·
Store the inverter in the original packing case with the desiccant inside. ·
The storage temperature must be always between -30 and +70, and the storage
rel-
ative humidity must be always between 0 and 95 %, non-condensing. · In case of
stacking storage, the number of stacking layers should never exceed the limit
marked on the outer side of the packing case. · The packing case should be
upright. · If the inverter needs to be transported again, pack it strictly
before loading and transport-
ing it. · Do not store the inverter in places susceptible to direct sunlight,
rain, and strong electric
field.
18
User Manual
3 Unpacking and Storage
· Do not place the inverter in places with items that may affect or damage the
inverter.
· Store the inverter in a clean and dry place to prevent dust and water vapor
from eroding.
· Do not store the inverter in places with corrosive substances or susceptible
to rodents and insects.
· Carry out periodic inspections. Inspection shall be conducted at least once
every six months. If any insect or rodent bites are found, replace the
packaging materials in time.
· If the inverter has been stored for more than a year, inspection and testing
by professionals are required before it can be put into operation.
Please store the inverter according to the storage requirements. Product damage caused by failure to meet the storage requirements is not covered by the warranty.
19
Mechanical Mounting
Respect all local standards and requirements during mechanical installation.
4.1 Safety During Mounting
Make sure there is no electrical connection before installation. Before
drilling, avoid the water and electricity wiring in the wall.
Poor installation environment will affect system performance! · Install the
inverter in a well-ventilated place. · Ensure that the heat dissipation system
or vent is not blocked. · Do not install the inverter in an environment with
flammable and explosive ob-
jects or smoke.
Improper handling may cause personal injury! · When moving the inverter, be
aware of its weight and keep the balance to pre-
vent it from tilting or falling. · Wear proper protective equipment before
performing operations on the inverter. · The bottom terminals and interfaces
of the inverter cannot directly contact the
ground or other supports. The inverter cannot be directly placed on the
ground.
When installing devices, ensure that no device in the system causes it hard
for the DC switch and the AC circuit breaker to act or hinders maintenance
personnel from operating. If drilling is required during installation: · Wear
goggles and protective gloves when drilling holes. · Make sure to avoid the
water and electricity wiring in the wall before drilling. · Protect the
product from shavings and dust.
20
User Manual
4 Mechanical Mounting
4.2 Location Requirements
To a large extent, a proper installation location ensures safe operation,
service life, and performance of the inverter.
· The inverter with protection rating IP65 can be installed both indoors and
outdoors.
· The inverter should be installed at a height that allows easy viewing of the
LED indicator panel, as well as easy electrical connection, operation and
maintenance.
4.2.1 Environment Requirements · The installation environment must be free of
inflammable or explosive materials. · The location should not be accessible to
children. · The ambient temperature and relative humidity must meet the
following requirements.
· Install the inverter in a sheltered area to avoid direct sunlight and bad
weather (e.g. snow, rain, lightning, etc.). The inverter will derate in high
temperature environments for protection. If the inverter is installed in
direct sunlight, it may cause power reduction as the temperature rises.
· The inverter is IP65 rated. In dusty environments such as places full of
dust, smoke, or cotton fibers, particles may cling to the device’s air outlet
or heat sink, thus impacting its heat dissipation performance or even getting
it damaged. Therefore, it is prohibited to install the inverter in dusty
environments. If the inverter has to be installed in such environments, please
clean its fans and heat sink on a regular basis to ensure a good heat
dissipation performance.
· The inverter should be well ventilated. Ensure air circulation. · It is
strictly prohibited to install the inverter in environments with vibration and
strong elec-
tromagnetic field. Strong-magnetic-field environments refer to places where
magnetic field strength measures over 30A/m. · The inverter generates noise
during operation and is not recommended to be installed in living areas.
21
4 Mechanical Mounting
User Manual
4.2.2 Carrier Requirements
The mounting structure where the inverter is installed must comply with
local/national standards and guidelines. Ensure that the installation surface
is solid enough to bear four times the weight of the inverter and is suitable
for the dimensions of the inverter (e.g. cement walls, plasterboard walls,
etc.). The structure should meet the following requirements:
4.2.3 Angle Requirements
nstall the inverter vertically. Never install the inverter horizontally, or at
forward/backward tilted, side tilted, or upside down.
4.2.4 Clearance Requirements Reserve enough clearance around the inverter to
ensure sufficient space for heat dissipation.
22
User Manual
4 Mechanical Mounting
In case of multiple inverters, reserve specific clearance between the inverters.
Install the inverter at an appropriate height for ease of viewing LED
indicator and operating switch(es).
4.3 Installation Tools
Installation tools include but are not limited to the following recommended
ones. If necessary, use other auxiliary tools on site. table 4-1 Tool
specification
Goggles
Earplugs
Dust mask
Safety gloves
23
4 Mechanical Mounting
User Manual
Safety shoes
Utility knife
Marker
Anti-static wrist strap
Wire cutter
Wire stripper
Hydraulic pliers
Rubber mallet
Hammer drill (10)
Phillips screwdriver (M3, M4, M6)
Electric screwdriver (M3, M4, M6)
Open-end wrench (30 mm, 35 mm, 46
mm)
RJ45 crimping tool Vacuum cleaner
Measuring tape
Heat shrink tubing
Heat gun
OT terminal crimping tool (4 mm26
mm2)
MC4 terminal crimping tool (0.5 mm2
1.0 mm2)
Multimeter ( 1100 Vdc)
24
User Manual
4 Mechanical Mounting
Slotted screwdriver (M2)
Connector wrench
4.4 Moving the Inverter
Before installation, remove the inverter from the packing case and move it to
the installation site. Follow the instructions below as you move the inverter:
· Always be aware of the weight of the inverter. · Lift the inverter using the
handles positioned on both sides of the inverter. · Move the inverter by one
or two people or by using a proper transport tool. · Do not release the
equipment unless it has been firmly secured.
Improper handling may cause personal injury!
· Arrange an appropriate number of personnel to carry the inverter according
to its weight, and installation personnel should wear protective equipment
such as anti-impact shoes and gloves.
· Attention must be paid to the center of gravity of the inverter to avoid
tilting during handling.
· Placing the inverter directly on a hard ground may cause damage to its metal
enclosure. Protective materials such as sponge pad or foam cushion should be
placed underneath the inverter.
· Move the inverter by holding the handles on it. Do not move the inverter by
holding the terminals.
4.5 Installing the Inverter
Inverter is installed on the wall by means of wall-mounting bracket and the
expansion plug sets. The expansion plug set shown below is recommended for the
installation.
25
4 Mechanical Mounting
User Manual
(1) Self-tapping screw M6
(2) Expansion tube (3) Fender washer (4) Spring washer
Step 1 Place the wall-mounting bracket to a proper position on the wall. Observe the level on the bracket and adjust until the bubble is in the middle position. Mark the positions and drill the holes.
The depth of the holes should be about 70 mm.
- The image shown here is for reference only. The actual product received may differ.
Step 2 Place the expansion tubes into the holes. Then secure the wall-mounting bracket to the wall firmly with the expansion bolt sets.
26
User Manual
4 Mechanical Mounting
Step 3 Lift the inverter and slide it down along the wall-mounting bracket to make sure they match perfectly. Use the fastener set to lock the device.
– – End
27
4 Mechanical Mounting
User Manual
4.6 Installing Optimizer(Optional)
Step 1 As shown in the figure below, clamp the optimizer parallel to the back of the PV module by clips.
· Please ensure that the optimizer is installed facing the back of the module.
Otherwise, the clip may get damaged.
· Do not forcibly bend the clips when installing the optimizer by clips.
Otherwise, the clip may be damaged.
· Do not clamp the optimizer into holes in the module frame during
installation. Otherwise, the optimizer cannot be removed or the clips may be
damaged.
· It is recommended to install optimizers on the same side of modules. · Do
not clamp and remove the optimizer multiple times. Otherwise, the clip may
become loose, affecting normal use. – – End 28
Electrical Connection
5.1 Safety Instructions
The PV string will generate lethal high voltage when exposed to sunlight. ·
Operators must wear proper personal protective equipment during electrical
connections. · Must ensure that cables are voltage-free with a measuring
instrument before
touching DC cables. · Respect all safety instructions listed in relevant
documents about PV strings.
· Before electrical connections, please make sure that the inverter switch and
all switches connected to the inverter are set to “OFF”, otherwise electric
shock may occur!
· Ensure that the inverter is undamaged and all cables are voltage free before
performing electrical work.
· Do not close the AC circuit breaker until the electrical connection is
completed.
Do not damage the ground conductor. Do not operate the product in the absence
of a properly installed ground conductor. Otherwise, it may cause personal
injury or product damage. Please use measuring devices with an appropriate
range. Overvoltage can damage the measuring device and cause personal injury.
Damage to the product caused by incorrect wiring is not covered by the
warranty. · Electrical connection must be performed by professionals. ·
Operators must wear proper personal protective equipment during electrical
connections. · All cables used in the PV generation system must be firmly
attached, properly
insulated, and adequately dimensioned. Cables used shall comply with the
requirements of local laws and regulations. · The factors that affect cable
selection include rated current, cable type, routing mode, ambient
temperature, and maximum expected line loss.
29
5 Electrical Connection
User Manual
All electrical connections must comply with local and national/regional
electrical standards.
· Cables used by the user shall comply with the requirements of local laws and
regulations.
· Only with the permission of the national/regional grid department, the
inverter can be connected to the grid.
· Install the external protective grounding cable first when performing
electrical connection and remove the external protective grounding cable last
when removing the inverter.
· Keep the AC output cable and the DC input cable close to each other during
electrical connection.
· Comply with the safety instructions related to PV strings and the
regulations related to the utility grid.
· After being crimped, the OT terminal must wrap the wires completely, and the
wires must contact the OT terminal closely.
· When using a heat gun, protect the device from being scorched.
· Keep the PV+ cable and PV cable close to each other when connecting DC
input cables.
· Before connecting a power cable (such as the AC cable, the DC cable, etc.),
confirm that the label and identifier on the power cable are correct.
· When laying out communication cables, separate them from power cables and
keep them away from strong interference sources to prevent communication
interruption.
· All vacant terminals must be covered with waterproof covers to prevent
affecting the protection performance.
· Ensure that AC output cables are firmly connected. Failing to do so may
cause inverter malfunction or damage to its AC connectors.
· When the wiring is completed, seal the gap at the cable inlet and outlet
holes with fireproof/waterproof materials such as fireproof mud to prevent
foreign matter or moisture from entering and affecting the long-term normal
operation of the inverter.
30
User Manual
5 Electrical Connection
The cable colors in figures in this manual are for reference only. Please select cables according to local cable standards.
5.2 Terminal Description
All electrical terminals are located at the bottom of the inverter.
figure 5-1 Terminals (SG20RT for example)
- The image shown here is for reference only. The actual product received may differ.
table 5-1 Terminal Description
No. Name PV1+, PV1, PV2+,
1 PV2, PV3+, PV3, PV4+, PV4
2 COM1
3 AC
Description
MC4 terminals for PV input. The terminal number depends on inverter model.
Communication accessory port to be connected to WiNet-S/WiNet-S2 for countries
except Brazil or to WiFi for Brazil. AC terminal to connect to the grid.
Decisive Voltage Classification DVC-C
DVC-A
DVC-C
4
External grounding terminal.
Not applicable
5 COM2
Communication connection for DI/ DRM, DO, Logger, and meter.
The pin definition of COM2 terminal is shown in the following label.
DVC-A
31
5 Electrical Connection
User Manual
figure 5-2 Label of COM2 Terminal
table 5-2 Label Description of COM2 Terminal
Label RSD NS DRM
RS485-1
DO RS485-3 Meter
RSD-1, RSD-2 NS-1, NS-2 D1/5, D2/6, D3/7, D4/8, R, C
A1, B1
NO, COM
A3, B3 A2, B2
Description
For inverter emergency stop
For inverter emergency stop For external Demand Response Enabling Device
(“AU”/ “NZ”) For Ripple Control For inverter daisy chain (Cannot be used
simultaneously with COM1 port for WiNetS/WiNet-S2) External alarm interface,
e.g. light indicator and/or buzzer The external DC voltage should not be
higher than 30 V and the current not higher than 1 A. Reserved Meter interface
5.3 Electrical Connection Overview
The SG3.0-20RT electrical connection should be realized as follows:
(A) PV string (D) External device
32
(B) Inverter (E) AC circuit breaker
(C) Grid (F) Meter
User Manual
5 Electrical Connection
The SG5.0-20RT-P2 electrical connection should be realized as follows (Includes optimizer):
(A) PV string (D) Grid (G) Meter
(B) Optimizer (E) External device
(C) Inverter (F) AC circuit breaker
table 5-3 Cable Requirements
No. Cable
Type
Cable Diameter
Outdoor multi-core
copper wire cable
1 DC cable
complying with
6 mm9 mm
1100 V and 30 A
standard
2 Ethernet
CAT 5E outdoor
cable
shielded network 5.3 mm7 mm
cable
3 Meter
Shielded twisted
RS485 cable
(1)
pair
5.3 mm7 mm
Wire Conductor Cross-section 4 mm26 mm2
8 0.2 mm2 2 (0.51.0) mm2
33
5 Electrical Connection
User Manual
No. Cable
4 AC cable (2)
Additional 5 Grounding
cable
Type
Outdoor 5-core copper wire cable
Cable Diameter
SG3.0RT to SG12RT, SG5.0RTP2 to SG12RTP2: 10 mm21 mm SG15RT to SG20RT,
SG15RT P2 to SG20RTP2: 14 mm25 mm
Wire Conductor Cross-section
SG3.0RT to SG12RT, SG5.0RTP2 to SG12RTP2: 4 mm2 6 mm2
SG15RT to SG20RT, SG15RTP2 to SG20RTP2: 6 mm2 10 mm2
Outdoor single-core The same as that of the PE wire in the AC copper wire cable cable
(1) The cable requirements for COM2 terminal connection are the same. (2) All the AC wires should be equipped with correctly colored cables for distinguishing. Please refer to related standards about the wiring color.
5.4 External Protective Grounding Connection
Electric shock!
· Make sure that the grounding cable is connected reliably. Otherwise, it may
cause electric shock.
· Since the inverter is not equipped with a transformer, neither the negative
electrode nor the positive electrode of the PV string can be grounded.
Otherwise, the inverter will not operate normally.
· Connect the grounding terminal to the external protective grounding point
before AC cable connection, PV string connection, and communication cable
connection.
· The external protective grounding point provides a reliable ground
connection. Do not use an improper grounding conductor for grounding,
Otherwise, it may cause product damage or personal injury.
· Depending on Local Rules, please also ground the PV panel subconstruction to
the same common grounding point (PE Bar) in addition to local lightning
protection rules.
34
User Manual
5 Electrical Connection
The external protective grounding terminal must meet at least one of the
following requirements.
· The cross-sectional area of the grounding cable is not less than 10 mm2 for
copper wire or 16 mm2 for aluminum wire. It is recommended that both the
external protective grounding terminal and the AC side grounding terminal be
reliably grounded.
· If the cross-sectional area of the grounding cable is less than 10 mm2 for
copper wire or 16 mm2 for aluminum wire, ensure that both the external
protective grounding terminal and the AC side grounding terminal are reliably
grounded.
The grounding connection can be made by other means if they are in accordance
with the local standards and regulations, and SUNGROW shall not be held liable
for the possible consequences.
5.4.1 External Protective Grounding Requirements
All non-current carrying metal parts and device enclosures in the PV power
system should be grounded, for example, brackets of PV modules and inverter
enclosure. When there is only one inverter in the PV system, connect the
external protective grounding cable to a nearby grounding point. When there
are multiple inverters in the PV system, connect the external protective
grounding terminals of all inverters and the grounding points of the PV module
brackets to ensure equipotential connections to ground cables (according to
the onsite conditions).
5.4.2 Connection Procedure
External grounding cable and OT/DT terminal are prepared by customers.
35
5 Electrical Connection
Step 1 Prepare the cable and OT/DT terminal.
User Manual
(1) Heat shrink tubing
(2) OT/DT terminal
After being crimped, the OT terminal must wrap the wires completely, and the
wires must contact the OT terminal closely. When using a heat gun, protect the
device from being scorched.
Step 2 Remove the screw on the grounding terminal and fasten the cable with a
screwdriver.
Step 3 Apply paint to the grounding terminal to ensure corrosion resistance. –
– End
36
User Manual
5.5 AC Cable Connection
5.5.1 AC Side Requirements
5 Electrical Connection
Only with the permission of the local grid department, the inverter can be connected to the grid.
Before connecting the inverter to the grid, ensure the grid voltage and frequency comply with requirements, for which, refer to “Technical Date”. Otherwise, contact the electric power company for help.
AC Circuit Breaker An independent three or four-pole circuit breaker must be installed on the output side of the inverter to ensure safe disconnection from the grid. The recommended specifications are as follows.
Inverter Model SG3.0RT/SG4.0RT/SG5.0RT/ SG6.0RT/SG5.0RT-P2/SG6.0RTP2 SG7.0RT/SG8.0RT/SG7.0RT-P2/ SG8.0RT-P2 SG10RT/SG10RT-P2 SG12RT/SG12RT-P2 SG15RT/SG17RT/SG15RT-P2/ SG17RT-P2 SG20RT/SG20RT-P2
Recommended Specification
16 A
20 A 25 A 32 A 40 A 50 A
AC circuit breakers should be installed on the output side of the inverter and
the grid side to ensure safe disconnection from the grid.
· Determine whether an AC circuit breaker with greater overcurrent capacity is
required based on actual conditions.
· Do not connect any local load between the inverter and the AC circuit
breaker. · Multiple inverters cannot share one AC circuit breaker.
Residual Current Monitoring Device With an integrated universal current-
sensitive residual current monitoring unit included, the inverter will
disconnect immediately from the mains power once a fault current with a value
exceeding the limit is detected.
37
5 Electrical Connection
User Manual
However if an external residual current device (RCD) (type A is recommended)
is mandatory, the switch must be triggered at a residual current of 300 mA
(recommended). RCD of other specifications can also be used according to local
standard. In Australia, a RCD is not required according to the local standard
AS3000-2018 when either of the following installation methods is adopted if
the PV array capacitance to ground is large (such as a tin roof):
· Use heavy duty conduits (such as metal bushing) when run PV and AC cables
through Cavity walls.
· Route the PV and AC cables through pipes (PVC or metal tubing), lay the
cables and install them.
Multiple Inverters in parallel Connection If multiple inverters are connected
in parallel to the grid, ensure that the total number of parallel inverters
does not exceed 5. Otherwise, please contact SUNGROW for technical scheme.
5.5.2 Assembling the AC Connector (< 15 kW)
The AC terminal block is on the bottom side of the inverter. AC connection is
the threephase-four-wire grid + PE connection (L1, L2, L3, N, and PE).
Step 1 Unscrew the swivel nut of the AC connector.
Step 2 Take out the spring-loaded terminal from the housing.
38
User Manual
5 Electrical Connection
Step 3 Thread the AC cable of appropriate length through the swivel nut, the sealing ring and the housing.
Step 4 Remove 45 mm of the cable jacket and 12 mm16 mm of the wire
insulation.
Step 5 Open the clamp on the spring-loaded terminal and insert the wires into
the corresponding holes. Close the clamp and push the terminal into the
housing until there is an audible click.
Observe the terminal assignment. Do not connect any phase line to the “PE”
terminal or PE wire to “N” terminal. Otherwise, unrecoverable damage to the
inverter may follow.
39
5 Electrical Connection
User Manual
Step 6 Ensure that the wires are securely in place by slightly pulling them. Tighten the swivel nut to the housing.
– – End 5.5.3 Installing the AC Connector (< 15 kW)
High voltage may be present in inverter! Ensure all cables are voltage-free
before electrical connection. Do not connect the AC circuit breaker until all
inverter electrical connections are completed.
Step 1 Disconnect the AC circuit breaker and secure it against reconnection.
Step 2 Remove the waterproof lid from the AC terminal.
40
User Manual
5 Electrical Connection
Step 3 Lift the locking part upwards and insert the AC connector into the AC terminal on the bottom side of the inverter. Then press the locking part and secure it with the screw.
Step 4 Connect the PE wire to ground and the phase lines and the “N” line to
AC circuit breaker. Then Connect the AC circuit breaker to electric board.
Step 5 Make sure all wires are firmly installed via the right torque tool or
dragging the cables slightly. – – End
5.5.4 Assembling the AC Connector ( 15 kW) The AC terminal block is on the
bottom side of the inverter. AC connection is the threephase-four-wire grid +
PE connection (L1, L2, L3, N, and PE).
Step 1 Unscrew the swivel nut of the AC connector.
Step 2 (Optional) Remove the inner sealing ring if the cable diameter is 19
mm25 mm. Otherwise skip this step.
41
5 Electrical Connection
Step 3 Take out the screw-type terminal plug from the housing.
User Manual
Step 4 Thread the AC cable of appropriate length through the swivel nut and the housing.
Step 5 Remove 80 mm90 mm of the cable jacket and 12 mm of the wire
insulation.
Step 6 (Optional) When using a multi-core multi-strand copper wire cable,
connect the AC wire head to the cord end terminal (hand-tight). In case of
single-strand copper wire, skip this step.
42
User Manual
5 Electrical Connection
Step 7 Fix all the wires to the screw-type terminal according to the assignment and tighten to a torque of 1.2 N·m 1.5 N·m with a screwdriver. Then push the terminal into the housing until there is an audible click.
Observe the terminal assignment. Do not connect any phase line to the “PE”
terminal or PE wire to “N” terminal. Otherwise, unrecoverable damage to the
inverter may follow. Step 8 Ensure that the wires are securely in place by
slightly pulling them. Tighten the swivel nut to the housing.
– – End 5.5.5 Installing the AC Connector ( 15 kW)
High voltage may be present in inverter! Ensure all cables are voltage-free
before electrical connection. Do not connect the AC circuit breaker until all
inverter electrical connections are completed. Step 1 Disconnect the AC
circuit breaker and secure it against reconnection.
43
5 Electrical Connection
Step 2 Remove the waterproof lid from the AC terminal.
User Manual
Step 3 Insert the AC connector into the AC terminal on the bottom of the inverter until there is an audible sound.
44
User Manual
Step 4 (Optional) Secure the AC connector, as shown in the figure below.
5 Electrical Connection
Step 5 Connect the PE wire to ground and the phase lines and the “N” line to
AC circuit breaker. Then connect the AC circuit breaker to electric board.
Step 6 Make sure all wires are firmly installed via the right torque tool or
dragging the cables slightly. – – End
5.6 DC Cable Connection
The PV string will generate lethal high voltage when exposed to sunlight. ·
Respect all safety instructions listed in relevant documents about PV strings.
45
5 Electrical Connection
User Manual
· Make sure the PV array is well insulated to ground before connecting it to
the inverter.
· Make sure the maximum DC voltage and the maximum short circuit current of
any string never exceed inverter permitted values specified in “Technical
Data”.
· Check the positive and negative polarity of the PV strings, and connect the
PV connectors to corresponding terminals only after ensuring polarity
correctness.
· During the installation and operation of the inverter, please ensure that
the positive or negative electrodes of PV strings do not short-circuit to the
ground. Otherwise, an AC or DC short-circuit may occur, resulting in equipment
damage. The damage caused by this is not covered by the warranty.
· Electric arc or contactor over-temperature may occur if the DC connectors
are not firmly in place, and the loss caused is not covered by the warranty.
· If the DC input cables are reversely connected or the positive and negative
terminals of different MPPT are shorted to ground at the same time, while the
DC switch is in the “ON” position, do not operate immediately. Otherwise, the
inverter may be damaged. Please turn the DC switch to “OFF” and remove the DC
connector to adjust the polarity of the strings when the string current is
lower than 0.5 A.
· Use the DC connectors supplied with the product for DC cable connection.
Using incompatible DC connectors may result in serious consequences, and the
device damage is not covered under warranty.
· Inverters do not support full parallel connection of strings (Full parallel
connection refers to a connection method in that strings are connected in
parallel and then connected to the inverter separately).
· Do not connect one PV string to multiple inverters. Otherwise, the inverters
may be damaged.
The following requirements about PV string connection must be met. Otherwise,
it may cause irreversible damage to the inverter, which is not covered by the
warranty.
· Mixed use of PV modules of different brands or models in one MPPT circuit,
or PV modules of different orientation or inclination in a string may not
damage inverter, but will cause system bad performance!
· The inverter enters standby state when the input voltage ranges between
1,000 V and 1,100 V. The inverter returns to running state once the voltage
returns to the MPPT operating voltage range, namely, 160 V to 1,000 V.
46
User Manual
5 Electrical Connection
Note the following items when laying out cables on site:
· The axial tension on PV connectors must not exceed 80 N. Avoid axial cable
stress on the connector for a long time during field wiring.
· Radial stress or torque must not be generated on PV connectors. It may cause
the connector waterproof failure and reduce connector reliability.
· Leave at least 50 mm of slack to avoid the external force generated by the
cable bending affecting the waterproof performance.
· Refer to the specifications provided by the cable manufacturer for the
minimum cable bending radius. If the required bending radius is less than 50
mm, reserve a bending radius of 50 mm. If the required bending radius is
greater than 50 mm, reserve the required minimum bending radius during wiring.
5.6.1 PV Input Configuration
· The inverters SG3.0RT/SG4.0RT/SG5.0RT/SG6.0RT/SG5.0RT-P2/SG6.0RT-P2 have two
PV inputs, SG7.0RT/SG8.0RT/SG10RT/SG12RT/SG7.0RT-P2/SG8.0RT-P2/
SG10RT-P2/SG12RT-P2 have three PV inputs and SG15RT/SG17RT/SG20RT/
SG15RT-P2/SG17RT-P2/SG20RT-P2 have four PV inputs.
· The inverters have two MPP trackers. Each DC input area can operate
independently.
· The PV strings to the same DC input area should have the same type, the same
number of PV panels, identical tilt and identical orientation for maximum
power.
· The PV strings to two DC input areas may differ from each other, including
PV module type, number of PV modules in each string, angle of tilt, and
installation orientation.
figure 5-3 PV Input Configuration (SG20RT for example)
Prior to connecting the inverter to PV inputs, the specifications in the following table should be met:
Inverter Model All models
Open-circuit Voltage Limit 1100 V
Max. current for input connector 30 A
47
5 Electrical Connection
User Manual
The following figure shows the open-circuit voltage limits at different altitudes. Before configuring the PV panels, need to take this derating curve in consideration under high altitude situation.
figure 5-4 Open-circuit Voltage Derating Curve
5.6.2 Assembling PV Connectors
High voltage may be present in the inverter! · Ensure all cables are voltage-
free before performing electrical operations. · Do not connect the AC circuit
breaker before finishing electrical connection.
· Use MC4 DC terminals if the maximum input voltage is no more than 1,000 V. ·
Use MC4-Evo2 DC terminals if the maximum input voltage is greater than 1,000
V. To purchase the MC4-Evo2 DC terminals, contact SUNGROW. · Select
appropriate DC terminals as required above. Otherwise, SUNGROW shall
be held no liability for the damage caused. To ensure IP65 protection, use
only the supplied connector.
Step 1 Strip 7 mm8 mm of the insulation from each PV cable.
48
User Manual
Step 2 Assemble the cable ends with the crimping pliers.
5 Electrical Connection
1: Positive crimp contact
2: Negative crimp contact
Step 3 For some countries such as Australia where the DC protection cover delivered separately need to be installed on site, please firstly lead the PV cables through the waterproof terminal on the DC protection cover before assembling the connector. See the guidance with the DC protection cover for details.
PV cables with connectors cannot go through the waterproof terminal on the DC
protection cover. Rework may cause damage to the connectors, which will not be
covered by the warranty.
Step 4 Lead the cable through the cable gland, and insert the crimp contact
into the insulator until it snaps into place. Gently pull the cable backward
to ensure firm connection. Tighten the cable gland and the insulator (torque
2.5 N.m to 3 N.m).
Step 5 Check for polarity correctness. – – End
49
5 Electrical Connection
5.6.3 Installing the PV Connectors Step 1 Rotate the DC switch to “OFF”
position.
User Manual
Step 2 Check the cable connection of the PV string for polarity correctness
and ensure that the open circuit voltage in any case does not exceed the
inverter input limit of 1,100 V.
The multimeter must have a DC voltage range of at least 1100 V. If the voltage
is a negative value, the DC input polarity is incorrect. Please correct the DC
input polarity. If the voltage is greater than 1100V, too many PV modules are
configured to the same string. Please remove some PV modules. Step 3 Connect
the PV connectors to corresponding terminals until there is an audible click.
Seal the unused PV terminals with the terminal caps.
50
User Manual
5 Electrical Connection
Step 4 Connect the PV+ and PV- of the optimizer to the positive and negative terminals in the junction box of the PV module respectively.
Do not connect the PV module to the OUT+ and OUT- of the optimizer. Otherwise, the optimizer or PV module will be damaged, and the loss is not covered by the warranty.
51
5 Electrical Connection
User Manual
Step 5 Connect the positive probe of a multimeter to OUT- of the optimizer, and the negative probe of the multimeter to OUT+ of the optimizer to check whether the optimizer is faulty. If typical value of output voltage is 1V, no fault occurs to the optimizer.
1. Use a multimeter to measure the output voltage of each optimizer after
wiring. 2. Considering the effect of the accuracy of the multimeter on the
actual measurement on site, the optimizer can function normally as long as the
output voltage falls in the range of 0.9V – 1.1V. 3. If the output voltage is
less than 0.9 V, check the following items: · Check whether the sunlight is
sufficient. · Check whether the input side of the optimizer is connected to
the PV module. · If the fault is not caused by foregoing reasons and still
persists, please replace
the optimizer. 4. If the output voltage is greater than 1.1 V, the optimizer
fails. Please replace the optimizer. 5. If no voltage is detected, replace the
optimizer or component.
52
User Manual
5 Electrical Connection
Step 6 When connecting multiple optimizers, connect OUT- of the first optimizer to OUT+ of the second optimizer, and so on. Use a multimeter to measure the optimizer voltage. If typical value of output voltage is 1V*N (N is the number of optimizers), no fault occurs to the system.
Whether connecting OUT+ of the first optimizer to OUT- of the second optimizer or connecting OUT- of the first optimizer to OUT+ of the second optimizer is dependent on the polarity of the extension cable that is connected to the inverter on site.
53
5 Electrical Connection
User Manual
Step 7 Connect OUT+ of the first optimizer and OUT- of the last optimizer to the PV input terminals of the inverter.
If each PV module is equipped with an optimizer, the total power of PV modules
in a PV input shall not exceed the maximum input power of a single PV input of
the inverter.
· Branch-connector connection on the input side of the inverter is not
supported by the optimizer.
· Please refer to the optimizer user manual for details.
– – End
5.7 WiNet-S/WiNet-S2 Connection
SG3.0-20RT uses WiNet-S2 module, and the WiNet-S2 module supports Ethernet
communication and WLAN communication. It is not recommended to use both
communication methods at the same time. SG5.0-20RT-P2 is used with optimizer,
and uses WiNet-S module. The WiNet-S module supports Ethernet communication
and WLAN communication. It supports EasyConnect and can receive and transmit
data of optimizers, meters, and chargers.
54
User Manual
5 Electrical Connection
The WiNet-S/WiNet-S2 communication for Ethernet cannot be used simultaneously with A1 and B1 terminals for RS485 daisy chain. For details, see the quick guide for the WiNet-S module. Scan the following QR code for the quick guide.
For more information about WiNet-S2, please scan the following QR code to view the quick guide.
5.7.1 Ethernet Communication
The WiNet-S/WiNet-S2 communication for Ethernet cannot be used simultaneously
with A1 and B1 terminals for RS485 daisy chain.
Step 1 (Optional) Strip the insulation layer of the communication cable with
an Ethernet wire stripper, and lead the corresponding signal cables out.
Insert the stripped communication cable into the RJ45 plug in the correct
order, and crimp it with a crimper.
1: RJ45 plug
2: Protective cap
Skip this step if a standard network cable with RJ45 plug is prepared.
55
5 Electrical Connection
User Manual
Step 2 Unscrew the swivel nut from the communication module and take out the inner sealing ring.
Step 3 Unscrew the housing from the communication module.
Step 4 Thread the network cable through the swivel nut and gasket. Afterwards, route the cable into the opening of the sealing. Finally, insert the cable through the housing.
56
User Manual
5 Electrical Connection
Step 5 Insert the RJ45 plug into the front plug connector until there is an audible click and tighten the housing. Install the gasket and fasten the swivel nut.
Step 6 Remove the waterproof lid from the COM1 terminal and install WiNet-S/WiNet-S2.
Step 7 Slightly shake it by hand to determine whether it is installed firmly.
– – End
5.7.2 WLAN Communication Step 1 Remove the waterproof lid from the COM1
terminal.
57
5 Electrical Connection
User Manual
Step 2 Install the module. Slightly shake it by hand to determine whether it is installed firmly, as shown below.
Step 3 Refer to the guide delivered with the module for the set-up. – – End
5.8 WiFi Connection (for Brazil)
Step 1 Remove the waterproof lid from the COM1 terminal. Step 2 Install the
module. Slightly shake it by hand to determine whether it is installed firmly,
as
shown below.
Step 3 Refer to the guide delivered with the module for the set-up. – – End
58
User Manual
5 Electrical Connection
5.9 Meter Connection
In a single inverter scenario, the meter (A2, B2) terminals are designed to connect to the meter for the feed-in power function. The export control functionality has not been tested to AS/ NZS 4777.2:2020. The energy meter is mainly used to detect the direction and magnitude of the current. And the energy meter data may not be used for billing purposes.
The meter is mainly used to detect the direction and magnitude of the current.
And the meter data may not be used for billing purposes.
5.9.1 Assembling the COM Connector Step 1 Unscrew the swivel nut from the
connector.
Step 2 Take out the terminal block.
Step 3 Remove the seal and lead the cable through the cable gland.
59
5 Electrical Connection
Step 4 Remove the cable jacket and strip the wire insulation.
User Manual
Step 5 (Optional) When using a multi-core multi-strand wire cable, connect the wire head to the cord end terminal. In case of single-strand copper wire, skip this step.
60
User Manual
5 Electrical Connection
Step 6 Plug the wires or terminals into the corresponding terminals as shown in the following figure.
figure 5-5 A2, B2 connection Step 7 Ensure that the wires are securely in
place by slightly pulling them and insert the terminal
plug into the housing until there is an audible click.
Step 8 Fasten the swivel nut. – – End
61
5 Electrical Connection
5.9.2 Installing the COM Connector Step 1 Remove the waterproof lid from the
COM2 connector.
User Manual
Step 2 Insert the COM connector into COM2 terminal on the bottom of the inverter until there is an audible click.
– – End
5.10 RS485 Connection
5.10.1 RS485 Communication System The RS485 (A1, B1) connection can establish
the communication between the inverter and an external device, as well as the
communication between two inverters in parallel. In case of multiple
inverters, all the inverters can be connected via RS485 cables in daisy chain
manner.
62
User Manual
5 Electrical Connection
figure 5-6 Multi-inverter Connection · The maximum number of inverters allowed
to be connected in the same point
of connection is 5. · The RS485 communication cable should be shielded twisted
pair cables or
shielded twisted pair Ethernet cables. · The RS485 cable between two devices
should be not longer than 10 m. · The RS485 communication cannot be used
simultaneously with COM1 port for
WiNet-S/WiNet-S2. · Refer to the manual of Logger for the communication
connection to the meter. 5.10.2 Assembling the COM Connector Step 1 Unscrew
the swivel nut from the connector.
Step 2 Take out the terminal block.
63
5 Electrical Connection
Step 3 Remove the seal and lead the cable through the cable gland.
User Manual
Step 4 Remove the cable jacket and strip the wire insulation.
Step 5 (Optional) When using a multi-core multi-strand wire cable, connect the
wire head to the cord end terminal. In case of single-strand copper wire, skip
this step.
64
User Manual
5 Electrical Connection
Step 6 Plug the wires or terminals into the corresponding terminals as shown in the following figure.
figure 5-7 A1, B1 connection
Step 7 Ensure that the wires are securely in place by slightly pulling them
and insert the terminal plug into the housing until there is an audible click.
65
5 Electrical Connection
User Manual
Step 8 For RS485 daisy chain: Crimp two wires A to a two-wire core end terminal and two wires B to another terminal. Plug the terminals to A1 and B1 respectively.
Step 9 Fasten the swivel nut.
figure 5-8 RS485 daisy chain connection
– – End 5.10.3 Installing the COM Connector Step 1 Remove the waterproof lid from the COM2 connector.
66
User Manual
5 Electrical Connection
Step 2 Insert the COM connector into COM2 terminal on the bottom of the inverter until there is an audible click.
– – End
5.11 DO Connection
The inverter is equipped with a DO relay for an earth fault alarm. The
additional equipment required is a light indicator and/or a buzzer that needs
additional power supply. Once fault occurs, the relay trips and the circuit is
connected. The external indicator gets on. The relay remains triggered until
the fault is removed.
figure 5-9 DO Normal Open Connect The additional DC power supply should comply
with related requirements: · Max. voltage: 30 V · Max. current: 1 A Refer to
section “5.9.1 Assembling the COM Connector” for detailed assembling
procedure. Plug the wires to NO and COM terminals according the labels on the
bottom of the inverter.
67
5 Electrical Connection
User Manual
Refer to section “5.10.3 Installing the COM Connector” to install the
connector.
5.12 DRM Connection
In Australia and New Zealand, the inverter supports the demand response modes
as specified in the standard AS/NZS 4777. The following figure shows the
wiring between the inverter and the external DRED.
table 5-4 Method of Asserting DRM
Mode
Asserted by Shorting Terminals on Switch Operation on External
Inverter
DRED
DRM0 R & C
Close S1 and S5
Refer to section “5.9.1 Assembling the COM Connector” for detailed assembling procedure. Plug the wires to R and C terminals according the labels on the bottom of the inverter.
68
User Manual
5 Electrical Connection
Refer to section “5.10.3 Installing the COM Connector” to install the
connector.
5.13 DI Connection
The grid company uses a Ripple Control Receiver to convert the grid
dispatching signal and send it as a dry contact signal. The following figure
shows the wiring between the inverter and the ripple control receiver.
table 5-5 Method of Asserting DI Mode
S- S2 S3 S4 Switch Operation on
1
External RCR
0 0 0 0 None
1 0 0 0 Close S1 0 1 0 0 Close S2 0 0 1 0 Close S3 1 1 0 0 Close S1 and S2
Output power (in % of the Rated AC output power)
100 % (configurable according to need)
100 % 60 % 30 % 0 % (disconnect from grid)
69
5 Electrical Connection
Step 1 Unscrew the swivel nut from the connector.
Step 2 Take out the terminal block.
User Manual
Step 3 Remove the seal and lead the cable through the cable gland.
Step 4 Remove the cable jacket by 7 mm10 mm.
70
User Manual
5 Electrical Connection
Step 5 Plug the wires into the corresponding terminals as shown in the following figure.
figure 5-10 DI connection Step 6 Ensure that the wires are securely in place
by slightly pulling them and insert the terminal
plug into the housing until there is an audible click.
Step 7 Fasten the swivel nut.
Step 8 Refer to section “5.10.3 Installing the COM Connector” to install the
connector. – – End
5.14 NS Protection Connection
NS terminal: NS Protection is used for the German market currently. For plants
sized more than 30kVA, inverter NS Protection terminals could be used in daisy
chain to external NS Protection Relay to realize emergency stop when the NS
Protection Relay changes its dry contact status due to the grid abnormal
running status. For detailed assembling procedure for inverters in daisy chain
mode refer to section “5.10.2 Assembling the COM Connector”.
71
5 Electrical Connection
User Manual
For SG3.020RT, NS Protection(including Passive Valid) can be set. When NS-1 and NS-2 are connected, the inverters will emergently stop; otherwise, the inverters will operate normally. But if NS Protection is enabled on the iSolarCloud, refer to ” NS Protection(Passive Valid)”, the inverters will operate normally when NS-1 and NS-2 are connected, and the inverters will emergently stop when NS-1 and NS-2 are disconnected. See the table below for details.
table 5-6
NS Protection is disabled on iSolarCloud
NS-1 and NS-2 Shorted Disconnected
Inverter Emergency stop Normal operation
NS Protection is enabled on iSolarCloud
Shorted Disconnected
Normal operation Emergency stop
The recommended wire conductor cross-section is 0.5 – 0.75 mm2,and the maximum wiring distance of NS protection loop must be less than 100 m. Refer to section “5.9.1 Assembling the COM Connector” for detailed assembling procedure. Plug the wires to NS-1 and NS-2 terminals according the labels on the bottom of the inverter. When terminals NS-1 and NS-2 are turned on by the external NS protection relay, the inverter will stop immediately.
Refer to section “5.10.3 Installing the COM Connector” to install the
connector. SG5.0-20RT-P2 can be used with optimizers. NS-1 and NS-2, as well
as RSD-1 and RSD-2 can be used for emergency stop. See the table below for
details:
72
User Manual
5 Electrical Connection
table 5-7
NS-1 and NS- RSD-1 and
2
RSD-2
Whether the system contains optimizers
No
Shorted Yes
Shorted No
NS Protection(including Passive Valid) is disabled on iSolarCloud
Disconnected Yes
No
Shorted Yes
Disconnected
No Disconnected
Yes
Inverter
Emergency stop The inverter is in the standby status if the DC voltage is
greater than 40 V The inverter is in the emergency stop status if the DC
voltage is lower than 40 V Emergency stop The inverter is in the standby
status if the DC voltage is greater than 40 V The inverter is in the emergency
stop status if the DC voltage is lower than 40 V Emergency stop
The inverter is in the standby status if the DC voltage is greater than 40 V
The inverter is in the emergency stop status if the DC voltage is lower than
40 V
Normal operation
Normal operation
73
5 Electrical Connection
User Manual
NS-1 and NS- RSD-1 and
2
RSD-2
Whether the system contains optimizers
Inverter
No Shorted
Yes
Normal operation Normal operation
No
Emergency stop
Shorted
Disconnected Yes
The inverter is in the standby status if the DC voltage is greater than 40 V
The inverter is in the emergency stop status if the DC voltage is lower than
40 V
NS Protection(including Passive Valid) is enabled on iSolarCloud
No
Shorted Yes
Disconnected No
Emergency stop
The inverter is in the standby status if the DC voltage is greater than 40 V
The inverter is in the emergency stop status if the DC voltage is lower than
40 V
Emergency stop
Disconnected Yes
The inverter is in the standby status if the DC voltage is greater than 40 V
The inverter is in the emergency stop status if the DC voltage is lower than
40 V
Refer to the figure below for short connection between NS-1 and NS-2, RSD-1 and RSD-2.
74
User Manual
5 Electrical Connection
Refer to section “5.9.1 Assembling the COM Connector””5.10.3 Installing the COM Connector” for detailed assembling procedure.
75
Commissioning
6.1 Inspection Before Commissioning
Check the following items before starting the inverter: · All equipment has
been reliably installed. · DC switch(es) and AC circuit breaker are in the
“OFF” position. · The ground cable is properly and reliably connected. · The
AC cable is properly and reliably connected. · The DC cable is properly and
reliably connected. · The communication cable is properly and reliably
connected. · The vacant terminals are sealed. · No foreign items, such as
tools, are left on the top of the machine or in the junction box (if
there is). · The AC circuit breaker is selected in accordance with the
requirements of this manual
and local standards. · All warning signs & labels are intact and legible.
6.2 Powering on the System
If all of the items mentioned above meet the requirements, proceed as follows
to start up the inverter for the first time. Step 1 Turn on the AC circuit
breaker between the inverter and the grid. Step 2 Rotate the DC switch of the
inverter to “ON” position. Step 3 Turn on the external DC switch (if
applicable) between the inverter and the PV string. Step 4 If the irradiation
and grid conditions meet requirements, the inverter will operate normally.
Observe the LED indicator to ensure that the inverter operates normally. Refer
to “2.4 Indicator Definition” for details. Step 5 Refer to the quick guide for
communication module for its indicator definition. Step 6 Set initial
protection parameters via the iSolarCloud App. · For WiFi module, please refer
to “7.2 Installing App”, “7.4.2 Login Procedure” and “7.5 In-
itial Settings”. · For WiNet-S/WiNet-S2 module, please refer to sections 6.3
to 6.6. – – End
76
User Manual
6 Commissioning
· Before closing the AC circuit breaker between the inverter and the power
grid, use a multimeter that is set to the AC gear to ensure that the AC
voltage is within the specified range. Otherwise, the inverter may be damaged.
· If the DC side is powered up while the AC side is not, the inverter
indicator may turn red, and the inverter will report a fault named “Grid Power
Outage” (the fault information can be viewed on the iSolarCloud App, see
“Records” for details). The fault is automatically cleared when the AC circuit
breaker between the inverter and the grid is closed.
6.3 App Preparation
Step 1 Install the iSolarCloud App with latest version. Refer to “7.2
Installing App”. Step 2 Register an account. Refer to “7.3 Account
Registration”. If you have got the account and
password from the distributor/installer or SUNGROW, skip this step. Step 3
Download the firmware package to the mobile device in advance. Refer to
“Firmware Upa-
date”. This is to avoid download failure due to poor on-site network signal.
– – End
6.4 Plant Creation
Prerequisites: · The account and password for logging in to iSolarCloud App
have been obtained from
the distributor/installer or SUNGROW. · The communication device is normally
connected to the inverter. · System positioning is enabled and iSolarCloud App
is allowed to access location
information.
77
6 Commissioning
User Manual
Step 1 Open the App, tap address.
in the upper right corner of the interface, and select the correct access
figure 6-1 Select Access Address Step 2 Enter the account and password on the
login interface, and tap LOGIN to log in.
Step 3 Tap in the upper right corner to enter the plant creation interface.
78
User Manual
6 Commissioning
Step 4 Fill in the content according to actual needs, and the parameters containing * are required. Tap Next to enter the next interface.
Parameter Name
Plant name
figure 6-2 Plant Creation Settings Description
The name of the plant.
Plant type
The type of the plant, which should be set corresponding to the actual plant type.
Installed power The installed power of the plant.
Country/Region The country/region where the plant is located.
Time zone
The time zone where the plant is located, which can be filled through automatic positioning and manual input.
79
6 Commissioning
User Manual
Parameter Name
Description The location of the plant, which can be filled in two ways:
Plant address
· Manually: Manually enter the plant location in the input box.
· Automatically: Tap to automatically obtain the current location or search
for the location of the plant, and then tap Confirm.
Grid-connection type
The way the plant is connected to the grid, including 100% Feed-in, Self- Consumption, Zero Export, and Off-grid.
Grid-connected The time when the plant is connected to the grid. date
Owner’s email Fill in the owner information of the plant, and both registered and un-
address
registered email addresses are supported.
Postal code
The postal code of the place where the plant is located.
Plant image
Take photos of the plant and upload them.
The feed-in tariff can be set in two ways:
· Enter the feed-in tariff directly in the input box.
Feed-in tariff
· Tap More Configurations, select the tariff unit, enter the feed-in tariff, and tap Confirm. Enable Time-of-Use Tariff if needed. Tap Add Time-of-Use Tariff, add time intervals and price, and tap Confirm. Please note that if Time-of-use Tariff is enabled, the time periods shall cover 24 hours a day, and can not overlap.
Consumption tariff
Set the consumption tariff as follows:
· Tap More Configurations, select the tariff unit, enter the consumption
tariff, and tap Confirm. Enable Time-of-Use Tariff if needed, and refer to the
setting methods of the feed-in tariff.
80
User Manual
6 Commissioning
Step 5 Bind a device through scanning the QR code on the device, manually inputting the device S/ N, or uploading a QR code picture. Tap Confirm after the QR code is identified or the S/N is verified.
Step 6 After a device is bound, tap Device and Commissioning to go to corresponding interface.
81
6 Commissioning
User Manual
Step 7 Tap Network Configuration to go to the WLAN connection interface. Tap the home network in the WLAN list, enter the password, and then tap Confirm.
Step 8 Enter the Activate EasyConnect interface, and press the multi-function
button on the WiNet-S/WiNet-S2 to enable the Easyconnect mode according to the
prompt on the screen. The App automatically enters a waiting processing
interface if this mode is enabled, and automatically returns to the
commissioning interface after the processing is completed.
Only the 2.4 GHz working band is supported under the networking mode. If the
Easyconnect fails, please refer to other methods in the WiNet-S/WiNet-S2
manual to establish the connection.
82
User Manual
6 Commissioning
Step 9 Tap Device Initialization to go to the Device initialization interface. Set the initialization protection parameters as needed and tap Settings to return to the commissioning interface.
When the country is set to Australia, additionally set the applicable network
service provider and then the grid type.
83
6 Commissioning
User Manual
The image shown here is for reference only. Refer to the actual interface for the supported network service providers.
table 6-1 Description of Network Service Provider and Grid Type
Network Service Provider AS/NZS 4777.2:2015 AS/NZS 4777.2:2020 Australia A AS/NZS 4777.2:2020 Australia B AS/NZS 4777.2:2020 Australia C
Grid Type / /
/
/
ENERGEX & Ergon Energy
· STNW1170: single-phase < 10 kVA & three-phase < 30 kVA
· STNW1174: 30 kVA < Pn 1500 kVA
Jemena
Endeavour Energy Ausgrid
· 10 kVA per phase (or 30 kVA per three phase)
· ELE GU 0014: 30 kVA200 kVA MDI 0043 NS194
CitiPower & Powercor
· 5 kVA for single-phase & 30 kVA for three-phase
· > 30 kVA three-phase
United Energy PowerWater
· UE-ST-2008.1: 10 kVA for singlephase & 30 kVA for three-phase
· UE-ST-2008.2: > 30 kVA three-phase Embedded Generation Notice Photovoltaic
Systems:2020
SA Power Networks
Horizon Power westernpower AusNet Services
· TS129-2019: < 10 kW for single-phase & 30 kW for three-phase
· TS130-2017: > 30 kW & 200 kW
· TS131-2018: > 200 kW
· HPC-9DJ-13-0001-2019: 10kVA for single-phase & 30 kVA for three-phase
· HPC-9DJ-13-0002-2019: > 30kVA & 1MVA
EDM#33612889-2019 Basic Micro Embedded Generation: 2020
84
User Manual
6 Commissioning
- For compliance with AS/NZS 4777.2:2020, please select from Australia A/B/C. Please contact your electricity grid operator for which region to use.
· Please check the country supported by this product at http://
support.sungrowpower.com/.
· Set Country/Region to the country/region where the inverter is installed.
Otherwise, the inverter may report a fault.
Step 10 After a plant is successfully created, return to the App home page to
view the plant information.
– – End
6.5 Optimizer Physical Layout (Optional)
· If PV modules are installed and optimizers are configured, check to ensure
that all devices are reliably installed.
· Remove QR code labels from the optimizers and attach them to corresponding
square cells on the physical layout.
· Please refer to the optimizer user manual for details of the optimizer
physical layout.
85
iSolarCloud App
7.1 Brief Introduction
The iSolarCloud App can establish communication connection to the inverter via
the WLAN, providing remote monitoring, data logging and near-end maintenance
on the inverter. Users can also view inverter information and set parameters
through the App. * To achieve direct login via WLAN, the wireless
communication module developed and manufactured by SUNGROW is required. The
iSolarCloud App can also establish communication connection to the inverter
via Ethernet connection.
· This manual describes only how to achieve near-end maintenance via WLAN
direct connection.
· Screenshots in this manual are based on the V2.1.6 App for Android system,
and the actual interfaces may differ.
7.2 Installing App
Method 1 Download and install the App through the following application
stores: · MyApp (Android, mainland China users) · Google Play (Android, users
other than mainland China ones) · App Store (iOS) Method 2 Scan the following
QR code to download and install the App according to the prompt information.
The App icon appears on the home screen after installation.
86
User Manual
7 iSolarCloud App
7.3 Account Registration
The account distinguishes two user groups, end user and distributor/installer.
· The end user can view plant information, create plants, set parameters,
share plants, etc. · The distributor/installer can help the end user to create
plants, manage, install, or main-
tain plants, and manage users and organizations. Step 1 Tap REGISTER to enter
the registration screen.
Step 2 Select the relevant server for your area.
87
7 iSolarCloud App
Step 3 Select End user or Distributor/Installer to enter the corresponding
screen.
User Manual
Step 4 Fill in the registration information, including email, verification
code, password and affirmance and country (region). The distributor/installer
has the permission to fill in the company name and the code of upper level
installer/distributor.
The code of upper level distributor/installer can be obtained from the upper
level distributor/installer. Only when your organization belongs to the upper
level distributor/installer organization, can you fill in the corresponding
code.
Step 5 Tick Accept privacy protocol and tap Register to finish the
registration operation. – – End
7.4 Login
7.4.1 Requirements The following requirements should be met: · The AC and DC
sides or the AC side of the inverter is powered-on. · The WLAN function of the
mobile phone is enabled. · The mobile phone is within the coverage of the
wireless network produced by the communication module.
88
User Manual
7 iSolarCloud App
7.4.2 Login Procedure
Step 1 (Optional) For the WiNet-S/WiNet-S2 module, press the multi-function
button 3 times to enable the WLAN hotspot. No password is required and the
valid time is 30 minutes.
figure 7-1 Enabling the WLAN Hotspot
Step 2 Connect the mobile phone to the WLAN network named as “SG-xxxxxxxxxxx”
(xxxxxxxxxxx is the serial number indicated on the side of the communication
module).
Step 3 Open the App to enter the login screen. Tap Local Access to enter the
next screen.
89
7 iSolarCloud App
User Manual
Step 4 Tap Confirm, then enter the password and tap LOGIN.Or tap MANUAL CONNECTION at the bottom of the interface and select WiNet-S/WiNet-S2, then enter the password and tap LOGIN.
· If the WiFi signal, serial number or inverter related data information
cannot be found, unplug and reinsert the Winet-S/WiNet-S2 or press the multi-
function button of the Winet-S/WiNet-S2 three times.
· The default account is “user” and the initial password is “pw1111” which
should be changed for the consideration of account security. Tap “More” at the
lower right corner on home page and choose “Change Password”.
figure 7-2 WLAN Local Access Step 5 If the inverter is not initialized,
navigate to the quick setting screen to initialize the protection
parameters. For details, please refer to “Initial Settings”.
The “Country/Region” must be set to the country where the inverter is
installed at. Otherwise, the inverter may report errors.
90
User Manual
7 iSolarCloud App
figure 7-3 WLAN Local Access Step 6 After finishing the settings, tap TUNR ON
DEVICE at the upper right corner and the device
will be initialized. The App will send start instructions and the device will
start and operate. Step 7 After initialization settings, the App will return
automatically to the home page.
– – End
7.5 Initial Settings
Tap Country/Region and select the country where the inverter is installed. For
countries except Australia and Germany, the initialization is completed.
91
7 iSolarCloud App
User Manual
The actual initializing procedure may differ due to different countries.
Please follow the actual App guidance. For some countries, you should
initialize parameters according to local grid requirements. For details,
please refer to the relevant technical documents on http://
support.sungrowpower.com/.
7.6 Function Overview
The App provides parameter viewing and setting functions, as shown in the
following figure.
92
User Manual
7 iSolarCloud App
figure 7-4 App Function Tree Map
7.7 Home
Home page of the App is shown in the following figure.
figure 7-5 Home
table 7-1 Home Page Description
No.
Name
Description
1
Inverter state Present operation state of the inverter
Shows the PV power generation power, feed-in power, etc.
Energy flow
The line with an arrow indicates energy flow between con-
2
chart
nected devices, and the arrow pointing indicates energy flow
direction.
93
7 iSolarCloud App
User Manual
No.
Name
Description
Real-time
3
power
Shows the present output power of the inverter.
4
Nominal power Shows the installed power of the inverter.
5
Today yield
Shows today power generation of the inverter
6
Total yield
Shows accumulative power generation of the inverter
7
Navigation bar Includes menus of “Home”, “Run Infomation”, “Records”
and “More”.
If the inverter runs abnormally, the fault icon will appear on the upper left corner of the screen. Users can tap the icon to view detailed fault information and corrective measures.
7.8 Run Information
Tap Run Information on the navigation bar to enter the screen showing running information, slide the screen upwards to view all detailed information.
table 7-2 Description of Run Information
Item PV information Inverter information Input
Output
Grid information
Description Shows voltage and current of every PV string. Shows basic information such as running state, on-grid running time, negative voltage to grid, bus voltage, internal air temperature, inverter efficiency, etc. Shows total DC power, voltage and current of MPPT1 and MPPT2. Shows daily/monthly/annual/total yield, total active/reactive/apparent power, total power factor, grid frequency, phase voltage and current. Shows daily/total feed-in energy, daily/total purchased energy.
7.9 Records
Tap Records on the navigation bar to enter the screen showing event records,
as shown in the following figure.
figure 7-6 Records Chart Tap Chart to enter the screen showing daily power
generation, as shown in the following figure.
94
User Manual
7 iSolarCloud App
figure 7-7 Chart
The App displays power generation records in a variety of forms, including
daily power generation graph, monthly power generation histogram, annual power
generation histogram and total power generation histogram.
table 7-3 Description of Power Curve
Item Daily Month Year Total
Description Daily curve that indicates the real-time power. Monthly curve that indicates daily yield and equivalent hours in a month. Annual curve that indicates monthly yield and equivalent hours in a year. A curve that indicates annual yield and equivalent hours since installation.
Fault Alarm Record Tap Fault Alarm Record to enter the screen, as shown in the following figure.
95
7 iSolarCloud App
User Manual
figure 7-8 Fault Alarm Record Click to select a time segment and view
corresponding records. Select one of the records in the list and click the
record, to view the detailed fault info as shown in following figure.
figure 7-9 Detailed Fault Alarm Information Event Record Tap Event Record to
enter the screen, as shown in the following figure.
96
User Manual
7 iSolarCloud App
figure 7-10 Event Record
Click to select a time segment and view corresponding records.
7.10 More
Tap More on the navigation bar to enter the corresponding screen, as shown in
the following figure.
figure 7-11 More In addition to viewing the WLAN configuration and App
software version, the More screen supports the following operations: · Set
parameters including inverter system parameters, operation parameters, power
reg-
ulation parameters and communication parameters. · Upgrade inverter firmware.
97
7 iSolarCloud App
User Manual
7.10.1 System Parameters
Tap “SettingsSystem Parameters” to enter the corresponding interface, as shown
in the following figure.
figure 7-12 System Parameters * The image shown here is for reference only.
Boot/Shutdown Tap Boot/Shutdown to send the boot/shutdown instruction to the
inverter. For Australia and New Zealand, when the DRM state is DRM0, the
“Boot” option will be prohibited. Date Setting/Time Setting The correct system
time is very important. Wrong system time will directly affect the data
logging and power generation value. The clock is in 24-hour format. Software
Version Version information of the current firmware.
7.10.2 Operation Parameters Running Time Tap “SettingsOperation
ParametersRunning Time” to enter the corresponding screen, on which you can
set the “Connecting Time” and “Reconnecting Time”.
figure 7-13 Running Time PID Parameters Tap “SettingsOperation ParametersPID
Parameters” to enter the corresponding screen, on which you can set “PID
Parameters”.
98
User Manual
7 iSolarCloud App
figure 7-14 PID Setting
table 7-4 PID Parameter Description
Parameter PID Recovery
Clear PID alarm PID Scheme
Description Set enabling/disabling of the PID night recovery function. PID night recovery functions between 22:00 pm and 5:00 am by default. If ISO impedance abnormality or PID function exception is detected during running of the PID function, the inverter reports a PID false alarm and reminds the user to take corresponding measures. After processing, clear the alarm via this parameter. Apply negative or positive voltage.
· For the selection of negative or positive voltage, please consult the
supplier of PV panels.
· After the PID night recovery function is enabled, the fault indicator on the
inverter front panel turns green.
NS Protection(Passive Valid) Tap “SettingsOperation ParametersRegular
Parameters” to enter the corresponding screen, on which you can set the “NS
Protection(Passive Valid)”. When the NS Protection (Passive Valid) button is
set to green, the Passive Valid mode is turned on. When the NS
Protection(Passive Valid) button is set to gray, the Active Valid mode is
turned on.
figure 7-15 NS Protection(Passive Valid) AFCI Parameters(Optional) Tap
“SettingsOperation ParametersAFCI Parameters” to enter the corresponding
screen, on which you can set “AFCI Parameters”.
99
7 iSolarCloud App
User Manual
figure 7-16 AFCI Setting
7.10.3 Power Regulation Parameters Active Power Regulation Tap “SettingsPower
Regulation ParametersActive Power Regulation” to enter the screen, as shown in
the following figure.
figure 7-17 Active Power Regulation
table 7-5 Description of Active Power Regulation Parameters
Parameter Active Power Soft Start after Fault
Active Power Soft Start Time after Fault Active Power Gradient Control Active
Power Decline Gradient Active Power Rising Gradient
Description Switch for activating/deactivating the function of active power soft start after a fault occurs The soft start time required for raising active power from 0 to rated value after a fault occurs Set whether to enable active power gradient control Decline gradient of inverter active power per minute Rising gradient of inverter active power per minute
Range On/Off 1 s1200 s On/Off
1%/min 6000 %/min
100
User Manual
7 iSolarCloud App
Parameter Active Power Setting Persistence Active Power Limit Active Power
Limit Ratio
DRM
Description Switch for activating/deactivating the function of active power setting persistence Switch for limiting active power The ratio of active power limit to rated power in percentage Switch for activating/deactivating the DRM function
Range
On/Off
On/Off 0.0 % 110.0 % On/Off
Feed-in Limitation Tap “SettingsPower Regulation ParametersFeed-in Limitation” to enter the screen, as shown in the following figure.
figure 7-18 Feed-in Limitation
table 7-6 Description of Feed-in Limitation Parameters
Parameter Installed PV Power
Zero-export per Phase
Feed-in Limitation
Description
DC side power
For a three-phase inverter, the feed-in power of Phase A, Phase B, and Phase C
are required shall be 0. This function has higher priority than Feed-in
Limitation. If Zero-export per Phase is enabled, Feed-in Limitation is
automatically disabled. It is supported to limit the feed-in power of the
inverter
Range 3.00 kW 20.00 kW
On/Off
On/Off
101
7 iSolarCloud App
User Manual
Parameter
Feed-in Limitation Value
Feed-in Limitation Ratio
Rated Power of Original Power Generation Systems
Description
Set Feed-in Limitation in numerical value (unit: kW)
Set Feed-in Limitation as a percentage. Feedin Limitation Ratio = Feed-in
Value / Inverter Rated Voltage
Range Rated Power of Original Power Generation Systems (Rated Power of
Original Power Generation Systems + Installed PV Power)
[Rated Power of Original Power Generation Systems / (Rated Power of Original
Power Generation Systems + Installed PV Power)] *100% 100.00 %
Rated power of the existing inverter before in- 0.00 kW–
stalling the inverter
300.00 kW
Reactive Power Regulation Tap “SettingsPower Regulation ParametersReactive Power Regulation” to enter the screen, as shown in the following figure.
102
User Manual
7 iSolarCloud App
figure 7-19 Reactive Power Regulation
table 7-7 Description of Reactive Power Regulation Parameters
Parameter Reactive Power Setting Persistence Reactive Power Regulation Mode
Reactive Response
Reactive Response Time
Description Switch for activating/deactivating the function of reactive power
setting persistence
Off/PF/Qt/Q(P)/Q(U)
Switch for activating/deactivating the function of reactive response
Range On/Off Off/PF/Qt/Q (P)/Q(U) On/Off
Time for reactive response
0.1 s-600 s
“Off” Mode The reactive power regulation function is disabled. The PF is fixed at +1.000. “PF” Mode The power factor (PF) is fixed and the reactive power is regulated by the parameter PF. The PF ranges from 0.8 leading to 0.8 lagging. This mode can be enabled only with a bus voltage of not less than 800V.
· Leading: the inverter is sourcing reactive power to the grid. · Lagging: the inverter is injecting reactive power into the grid.
“Qt” Mode In the Qt mode, the reactive power can be regulated by the parameter Q-Var limits (in %). The system rated reactive power is fixed, the system injects reactive power according to the delivered reactive power ratio. The “Reactive Power Ratio” is set through the App. The setting range of the reactive power ratio is from -100 % to 100 %, corresponding to the ranges of inductive and capacitive reactive power regulation respectively. “Q(P)” Mode The PF of the inverter output varies in response to the output power of the inverter.
103
7 iSolarCloud App
User Manual
table 7-8 “Q(P)” Mode Parameters Explanation
Parameter
Explanation
Q(P) Curve
Select corresponding curve according to local regulations
QP_P1
Output power at point P1 on the Q(P) mode curve (in %)
QP_P2
Output power at point P2 on the Q(P) mode curve (in %)
QP_P3
Output power at point P3 on the Q(P) mode curve (in %)
QP_K1
Power factor at point P1 on the Q(P) mode curve
QP_K2
Power factor at point P2 on the Q(P) mode curve
QP_K3
Power factor at point P3 on the Q(P) mode curve
QP_ EnterVoltage
Voltage for Q(P) function activation (in %)
QP_ ExitVoltage
Voltage for Q(P) function deactivation (in %)
QP ExitPower
QP EnableMode
Power for Q(P) function deactivation (in %)
Unconditional activation/deactivation of Q(P) function
- Curve C is reserved and consistent with Curve A currently.
Range A, B, C*
0 %100.0 %
20.0 %100.0 %
20.0 %100.0 %
Curve A/C: 0.800 to 1.000 Curve B: -0.600 to 0.600 100.0 %110.0 % 90.0
%100.0 %
1.0 %100.0 %
Yes, No
figure 7-20 Reactive Power Regulation Curve in Q(P) Mode “Q(U)” Mode
104
User Manual
7 iSolarCloud App
The reactive power output of the inverter varies in response to the grid voltage.
table 7-9 “Q(U)” Mode Parameter Explanation
Parameter Q(U) curve
Explanation
Select corresponding curve according to local regulations
Range A, B, C*
Hysteresis Ratio
QU_V1
Voltage hysteresis ratio on the Q(U) mode curve
0.0 %5.0 %
Grid voltage limit at point P1 on the Q(U) mode curve
(in %)
80.0 %100.0 %
QU_V2
Grid voltage limit at point P2 on the Q(U) mode curve
(in %)
80.0 %100.0 %
QU_V3
Grid voltage limit at point P3 on the Q(U) mode curve 100.0 %120.0
(in %)
%
QU_V4
Grid voltage limit at point P4 on the Q(U) mode curve 100.0 %120.0
(in %)
%
QU_Q1
Value of Q/Sn at point P1 on the Q(U) mode curve (in
%)
-60.0 % to 0.0 %
QU_Q2
Value of Q/Sn at point P2 on the Q(U) mode curve (in -60.0 % to 60.0
%)
%
QU_Q3
Value of Q/Sn at point P3 on the Q(U) mode curve (in
%)
-60.0 % to 60 %
QU_Q4
Value of Q/Sn at point P4 on the Q(U) mode curve (in
%)
0.0 % to 60.0 %
QU EnterPower
QU ExitPower
QU_ EnableMode
Active power for Q(U) function activation (in %) Active power for Q(U) function deactivation (in %) Unconditional activation/deactivation of Q(U) function
20.0 %100.0 %
1.0 %20.0 % Yes, No, Yes (Limited by PF)
QU_Limited PF Value
Preset PF value
01.00
- Curve C is reserved and consistent with Curve A currently.
105
7 iSolarCloud App
User Manual
figure 7-21 Reactive Power Regulation Curve in Q(U) Curve
7.10.4 Communication Parameters Tap “SettingsCommunication Parameters” to
enter the corresponding screen, as shown in the following figure. The device
address ranges from 1 to 246.
figure 7-22 Communication Parameters
7.10.5 Firmware Update
To avoid download failure due to poor on-site network signal, it is
recommended to download the firmware package to the mobile device in advance.
Step 1 Enable the “Mobile data” of the mobile device.
Step 2 Open the App, enter the account and password on the login screen. Tap
Login to enter the home screen.
Step 3 Tap “MoreFirmware Download” to enter corresponding screen on which you
can view the device list.
Step 4 Select the device model before downloading the firmware. Tap the device
name in the device
list to enter the firmware upgrade package detail interface, and tap upgrade package to download it.
behind the firmware
106
User Manual
7 iSolarCloud App
Step 5 Return to the Firmware Download screen, tap in the upper right corner
of the screen to view the downloaded firmware upgrade package.
Step 6 Login the App via local access mode. Refer to “7.4 Login”.
Step 7 Tap More on the App home screen and then tap Firmware Update.
Step 8 Tap the upgrade package file, a prompt box will pop up asking you to
upgrade the firmware with the file, tap CONFIRM to perform the firmware
upgrade.
Step 9 Wait for the file to be uploaded. When the upgrade is finished, the interface will inform you of the upgrade completion. Tap Complete to end the upgrade.
– – End 7.10.6 Auto-test
Tap “Auto-test” to enter the corresponding screen, as shown in the following
figure.
figure 7-23 Auto-test Launch Auto-test Tap Launch Auto-test carry out an auto-
test. Auto-testing will take about 5 minutes. When the auto-test is completed,
the auto-test report is displayed, as shown in the figure below. Tap DOWNLOAD
to download the report.
107
7 iSolarCloud App
User Manual
figure 7-24 Auto-test Result Clear Auto-test Fault Tap “Clear Auto-test FaultCONFIRM” to clear the auto-test fault.
108
User Manual
7 iSolarCloud App
figure 7-25 Clear Auto-test Fault
7.10.7 SPI(for Italy CEI0-21 Grid Code Only) Contact your distributor to
obtain the advanced account and corresponding password before setting the SPI
parameters. If the distributor is unable to provide the required information,
contact SUNGROW. Unauthorized personnel are not allowed to log in with this
account. Otherwise, SUNGROW shall not be held liable for any damages caused.
Tap “MoreSettingsProtection ParametersOther Parameters” to enter the
corresponding screen, on which you can modify the value of “External Signal
for Italian Grid” ,”SPI Local Signal for Italian Grid”, “SPI Mode”, “Grid
Voltage Adaption” and confirm the settings by enabling “External Grid Network
Protection”.
figure 7-26 SPI
109
System Decommissioning
8.1 Disconnecting Inverter
Danger of burns! Even if the inverter is shut down, it may still be hot and
cause burns. Wear protective gloves before operating the inverter after it
cools down.
For maintenance or other service work, the inverter must be switched off.
Proceed as follows to disconnect the inverter from the AC and DC power
sources. Lethal voltages or damage to the inverter will follow if otherwise.
Step 1 Disconnect the external AC circuit breaker and prevent it from
inadvertent reconnection. Step 2 Rotate the DC switch to the “OFF” position
for disconnecting all of the PV string inputs. Step 3 Wait about 10 minutes
until the capacitors inside the inverter completely discharge. Step 4 Ensure
that the DC cable is current-free with a current clamp. – – End
8.2 Dismantling the Inverter
Risk of burn injuries and electric shock! After the inverter is powered off
for 10 minutes, measure the voltage and current with professional instrument.
Only when there is no voltage nor current can operators who wear protective
equipment operate and maintain the inverter.
· Before dismantling the inverter, disconnect the inverter from both AC and DC
power sources.
· If there are more than two layers of inverter DC terminals, dismantle the
outer DC connectors before dismantling the inner ones.
· If the original packing materials are available, put the inverter inside
them and then seal them using adhesive tape. If the original packing materials
are not available, put the inverter inside a cardboard box suitable for the
weight and size of this inverter and seal it properly.
110
User Manual
8 System Decommissioning
Step 1 Refer to “5 Electrical Connection”, for the inverter disconnection of all cables in reverse steps. In particular, when removing the DC connector, use an MC4 wrench to loosen the locking parts and install waterproof plugs.
Step 2 Refer to”4 Mechanical Mounting”, to dismantle the inverter in reverse
steps. Step 3 If necessary, remove the wall-mounting bracket from the wall.
Step 4 If the inverter will be used again in the future, please refer to “3.2
Inverter Storage” for a prop-
er conservation. – – End
8.3 Disposal of Inverter
Users take the responsibility for the disposal of the inverter.
Please scrap the inverter in accordance with relevant local regulations and
standards to avoid property losses or casualties.
Some parts of the inverter may cause environmental pollution. Please dispose
of them in accordance with the disposal regulations for electronic waste
applicable at the installation site.
111
Troubleshooting and Maintenance
9.1 Troubleshooting
Once the inverter fails, the fault information is displayed on the App interface. If the inverter is equipped with an LCD screen, the fault information can be viewed on it. The fault codes and troubleshooting methods of all PV inverters are detailed in the table below, and only some of the faults may occur to the model you purchased. When a fault occurs, you can check the fault information according to the fault code on the mobile app.
Fault Code 2, 3, 14, 15
4, 5
Fault Name Grid Overvoltage
Grid Undervoltage
Corrective Measures Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly: 1. Measure the actual grid voltage, and contact the local electric power company for solutions if the grid voltage is higher than the set value. 2. Check whether the protection parameters are appropriately set via the App or the LCD. Modify the overvoltage protection values with the consent of the local electric power operator. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly:
- Measure the actual grid voltage, and contact the local electric power company for solutions if the grid voltage is lower than the set value. 2. Check whether the protection parameters are appropriately set via the App or the LCD. 3. Check whether the AC cable is firmly in place. 4. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists.
112
User Manual
Fault Code 8 9
10
12
13
9 Troubleshooting and Maintenance
Fault Name Grid Overfrequency Grid Underfrequency
Grid Power Outage
Excess Leakage Current
Grid Abnormal
Corrective Measures Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly: 1. Measure the actual grid frequency, and contact the local electric power company for solutions if the grid frequency is beyond the set range. 2. Check whether the protection parameters are appropriately set via the App or the LCD. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly: 1. Check whether the grid supplies power reliably. 2. Check whether the AC cable is firmly in place. 3. Check whether the AC cable is connected to the correct terminal (whether the live wire and the N wire are correctly in place). 4. Check whether the AC circuit breaker is connected. 5. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. 1. The fault can be caused by poor sunlight or damp environment, and generally the inverter will be reconnected to the grid after the environment is improved. 2. If the environment is normal, check whether the AC and DC cables are well insulated. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly:
- Measure the actual grid, and contact the local electric power company for solutions if the grid parameter exceeds the set range. 2. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists.
113
9 Troubleshooting and Maintenance
User Manual
Fault Code 17
28, 29, 208, 212, 448-479
532-547, 564579
Fault Name
Grid Voltage Imbalance
PV Reserve Connection Fault
PV Reverse Connection Alarm
Corrective Measures Generally, the inverter will be reconnected to the grid after the grid returns to normal. If the fault occurs repeatedly: 1. Measure the actual grid voltage. If grid phase voltages differ greatly, contact the electric power company for solutions. 2. If the voltage difference between phases is within the permissible range of the local power company, modify the grid voltage imbalance parameter through the App or the LCD. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. 1. Check whether the corresponding string is of reverse polarity. If so, disconnect the DC switch and adjust the polarity when the string current drops below 0.5 A. 2. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. The code 28 to code 29 are corresponding to PV1 to PV2 respectively. The code 448 to code 479 are corresponding to string 1 to string 32 respectively. 1. Check whether the corresponding string is of reverse polarity. If so, disconnect the DC switch and adjust the polarity when the string current drops below 0.5 A. 2. Contact Sungrow Customer Service if the preceding causes are ruled out and the alarm persists. The code 532 to code 547 are corresponding to string 1 to string 16 respectively. The code 564 to code 579 are corresponding to string 17 to string 32 respectively.
114
User Manual
9 Troubleshooting and Maintenance
Fault Code 548-563, 580595
37 43
Fault Name
PV Abnormal Alarm
Excessively High Ambient Temperature
Excessively Low Ambient Temperature
Corrective Measures Check whether the voltage and current of the inverter is abnormal to determine the cause of the alarm. 1. Check whether the corresponding module is sheltered. If so, remove the shelter and ensure module cleanness. 2. Check whether the battery board wiring is loose, if so, make it reliably connected. 3. Check if the DC fuse is damaged. If so, replace the fuse. 4. Contact Sungrow Customer Service if the preceding causes are ruled out and the alarm persists. The code 548 to code 563 are corresponding to string 1 to string 16 respectively. The code 580 to code 595 are corresponding to string 17 to string 32 respectively. Generally, the inverter will resume operation when the internal or module temperature returns to normal. If the fault persists: 1. Check whether the ambient temperature of the inverter is too high; 2. Check whether the inverter is in a well-ventilated place; 3. Check whether the inverter is exposed to direct sunlight. Shield it if so; 4. Check whether the fan is running properly. Replace the fan if not; 5. Contact Sungrow Power Customer Service if the fault is due to other causes and the fault persists. Stop and disconnect the inverter. Restart the inverter when the ambient temperature rises within the operation temperature range.
115
9 Troubleshooting and Maintenance
User Manual
Fault Code 39 106 88
Fault Name
Low System Insulation Resistance
Grounding Cable Fault
Electric Arc Fault
Corrective Measures Wait for the inverter to return to normal. If the fault
occurs repeatedly:
1. Check whether the ISO resistance protection value is excessively high via
the app or the LCD, and ensure that it complies with the local regulations.
2. Check the resistance to ground of the string and DC cable. Take corrective
measures in case of short circuit or damaged insulation layer.
3. If the cable is normal and the fault occurs on rainy days, check it again
when the weather turns fine.
4. If there are batteries, check whether battery cables are damaged and
whether terminals are loose or in poor contact. If so, replace the damaged
cable and secure terminals to ensure a reliable connection.
5. Contact Sungrow Customer Service if the preceding causes are ruled out and
the fault persists. 1. Check whether the AC cable is correctly connected.
2. Check whether the insulation between the ground cable and the live wire is
normal.
3. Contact Sungrow Customer Service if the preceding causes are ruled out and
the fault persists. 1. Disconnect the DC power supply, and check whether any
DC cable is damaged, the connection terminal or fuse is loose or there is a
weak contact. If so, replace the damaged cable, fasten the terminal or fuse,
and replace the burnt component.
2. After performing step 1, reconnect the DC power supply, and clear the
electric arc fault via the App or the LCD, after that the inverter will return
to normal.
3. Contact Sungrow Customer Service if the fault persists.
116
User Manual
Fault Code 84
514
323
75
9 Troubleshooting and Maintenance
Fault Name Reverse Connection Alarm of the Meter/CT
Meter Communication Abnormal Alarm
Grid Confrontation
Inverter Parallel Communication Alarm
Corrective Measures 1. Check if the meter is wrongly connected. 2. Check if the input and output wiring of the meter is reversed. 3. If the existing system is enabled, please check if the rated power setting of the existing inverter is correct. 1. Check whether the communication cable and the terminals are abnormal. If so, correct them to ensure reliable connection. 2. Reconnect the communication cable of the meter. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the alarm persists. 1. Check whether the output port is connected to actual grid. Disconnect it from the grid if so. 2. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists. 1. Check whether the communication cable and the terminals are abnormal. If so, correct them to ensure reliable connection. 2. Reconnect the communication cable of the meter. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the alarm persists.
117
9 Troubleshooting and Maintenance
Fault Code 7, 11, 16, 19 25, 3034, 36, 38, 4042, 44 50, 5258, 60 69, 85,
87, 92, 93, 100105, 107114, 116 124, 200211, 248255, 300 322, 324328,
401412, 600 603, 605, 608, 612, 616, 620, 622624, 800, 802, 804, 807,
10961122
59, 7074, 76 83, 89, 216 218, 220233, 432434, 500 513, 515518, 635638,
900, 901, 910, 911, 996
Fault Name System Fault System Alarm
264-283
MPPT Reverse Connection
Corrective Measures
User Manual
1. Wait for the inverter to return to normal. 2. Disconnect the AC and DC switches, and disconnect the battery side switches if there are batteries. Close the AC and DC switches in turn 15 minutes later and restart the system. 3. Contact Sungrow Customer Service if the preceding causes are ruled out and the fault persists.
1. The inverter can continue running.
2. Check whether the related wiring and terminal are abnormal, check whether
there are any foreign materials or other environmental abnormalities, and take
corresponding corrective measures when necessary.
3. If the fault persists, please contact Sungrow Power Customer Service. 1.
Check whether the corresponding string is of reverse polarity. If so,
disconnect the DC switch and adjust the polarity when the string current drops
below 0.5 A.
2. Contact Sungrow Customer Service if the preceding causes are ruled out and
the fault persists.
*The code 264 to code 279 are corresponding to string 1 to string 20 respectively.
118
User Manual
Fault Code 332-363
364-395
1548-1579
9 Troubleshooting and Maintenance
Fault Name Boost Capacitor Overvoltage Alarm
Boost Capacitor Overvoltage Fault
String Current Reflux
Corrective Measures 1. The inverter can continue running.
2. Check whether the related wiring and terminals are abnormal, check whether
there are any foreign materials or other environmental abnormalities, and take
corresponding corrective measures when necessary.
If the fault persists, please contact Sungrow Power Customer Service. 1.
Disconnect the AC and DC switches, and disconnect the battery side switches if
there are batteries. Close the AC and DC switches in turn 15 minutes later and
restart the system.
2. If the fault persists, please contact Sungrow Power Customer Service. 1.
Check whether the number of PV modules of the corresponding string is less
than other strings. If so, disconnect the DC switch and adjust the PV module
configuration when the string current drops below 0.5 A.
2. Check whether the PV module is shaded;
3. Disconnect the DC switch to check whether the open circuit voltage is
normal when the string current drops below 0.5 A. If so, check the wiring and
configuration of the PV module,
4. Check whether the orientation of the PV module is abnormal.
119
9 Troubleshooting and Maintenance
User Manual
Fault Code 1600 – 1615, 1632 – 1655
1616
Fault Name
PV Grounding Fault
System Hardware Fault
Corrective Measures 1. When the fault occurs, it is forbidden to directly
disconnect the DC switch and unplug PV terminals when the direct current is
greater than 0.5 A;
2. Wait until the direct current of the inverter falls below 0.5 A, then
disconnect the DC switch and unplug the faulty strings;
3. Do not reinsert the faulty strings before the grounding fault is cleared;
4. If the fault is not caused by the foregoing reasons and still exists,
contact Sungrow Customer Service. 1. It is prohibited to disconnect the DC
switch when the DC current is greater than 0.5 A when t
References
- Homepage | Power Integrations
- support.sungrowpower.com
- support.sungrowpower.com/
- Contact Us - Sungrow
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>