BLAUBERG KOMFORT Series Air Handling Unit User Manual

July 6, 2024
BLAUBERG

KOMFORT Series Air Handling Unit

“`html

Specifications

  • Model: KOMFORT EC S5(B) 270

  • Model (with Energy Recovery): KOMFORT EC S5(B)
    270-E

  • Air Capacity: 162 m3/h

  • Heat Exchanger Type: Counter-flow

  • Motor Type: EC (Electronically
    Commutated)

  • Temperature Range: -25°C to +40°C

  • Filter Type: G4 (Optionally F8)

Product Usage Instructions

Design and Operating Principle

The unit consists of various components including exhaust and
supply fans, control unit, filters, heat exchanger, drain pan, and
bypass damper. The service side allows for easy access to clean and
replace filters and the heat exchanger. Condensate generated by
temperature differentials is collected in the drain pan and removed
through the drain pipe.

Installation

  1. Ensure the unit is switched off from the mains before
    installation.

  2. Position the unit in a suitable location for optimal air
    circulation.

  3. Connect the power and grounding cables securely to the control
    unit.

  4. Test the unit after installation to ensure proper
    functionality.

Maintenance

Regular maintenance is essential for optimal performance:

  • Clean or replace filters as needed to maintain air
    quality.

  • Check for any obstructions in the drain pipe and ensure proper
    drainage of condensate.

  • Inspect the unit for any signs of wear or damage and address
    promptly.

Frequently Asked Questions (FAQ)

Q: How should I dispose of the unit at the end of its service

life?

A: The product must be disposed of separately
at the end of its service life. Do not dispose of the unit as
unsorted domestic waste.

Q: What precautions should I take to ensure safe

operation?

A: Ensure that the unit is switched off from
the supply mains before any maintenance or cleaning procedures.
Take precautions to prevent back-flow of gases and ensure proper
ventilation.

“`

Air hAndling unit
KOMFOrt EC S5B 270 KOMFOrt EC S5B 270-E KOMFOrt EC S5 270 KOMFOrt EC S5 270-E
EN uSEr’S MAnuAl

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

CONTENTS
Safety requirements………………………………………………………………………………………………………………………………………………… 2 Purpose………………………………………………………………………………………………………………………………………………………………………… 4 Delivery set…………………………………………………………………………………………………………………………………………………………………. 4 Technical data……………………………………………………………………………………………………………………………………………………………. 5 Design and operating principle …………………………………………………………………………………………………………………………. 7 Installation and set- up……………………………………………………………………………………………………………………………………………. 9 Connection to power mains ……………………………………………………………………………………………………………………………….. 13 Technical maintenance………………………………………………………………………………………………………………………………………….. 16 Troubleshooting……………………………………………………………………………………………………………………………………………………….. 17 Storage and transportation regulations………………………………………………………………………………………………………….. 17 Manufacturer’s warranty……………………………………………………………………………………………………………………………………….. 18 Certificate of acceptance………………………………………………………………………………………………………………………………………. 19 Seller information…………………………………………………………………………………………………………………………………………………….. 19 Installation certificate……………………………………………………………………………………………………………………………………………… 19 Warranty card…………………………………………………………………………………………………………………………………………………………….. 19
This user’s manual is a main operating document intended for technical, maintenance, and operating staff. The manual contains information about purpose, technical details, operating principle, design, and installation of the KOMFORT EC S5(B) 270(-E) unit and all its modifications. Technical and maintenance staff must have theoretical and practical training in the field of ventilation systems and should be able to work in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country.
SAFETY REQUIREMENTS
This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the unit by a person responsible for their safety. Children should be supervised to ensure that they do not play with the unit. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Cleaning and user maintenance shall not be done by children without supervision. Children shall not play with the appliance.

If the supply cord is damaged, it must be replaced by the manufacturer, its service agent, or similarly qualified persons in order to avoid a safety hazard.
Ensure that the unit is switched off from the supply mains before removing the guard.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.
The appliance may adversely affect the safe operation of appliances burning gas or other fuels (including those in other rooms) due to back flow of combustion gases. These gases can potentially result in carbon monoxide poisoning. After installation of the unit the operation of flued gas appliances should be tested by a competent person to ensure that back flow of combustion gases does not occur.

2

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

All operations described in this manual must be performed by qualified personnel only, properly trained and qualified to install, make electrical connections and maintain ventilation units. Do not attempt to install the product, connect it to the mains, or perform maintenance yourself. This is unsafe and impossible without special knowledge. Disconnect the power supply prior to any operations with the unit. All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit. Disconnect the unit from the power supply prior to any connection, servicing, maintenance, and repair operations. Connection of the unit to power mains is allowed by a qualified electrician with a work permit for the electric units up to 1000 V after careful reading of the present user’s manual. Check the unit for any visible damage of the impeller, the casing, and the grille before starting installation. The casing internals must be free of any foreign objects that can damage the impeller blades. While mounting the unit, avoid compression of the casing! Deformation of the casing may result in motor jam and excessive noise. Misuse of the unit and any unauthorised modifications are not allowed. Do not expose the unit to adverse atmospheric agents (rain, sun, etc.). Transported air must not contain any dust or other solid impurities, sticky substances, or fibrous materials. Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc. Do not close or block the intake or extract vents in order to ensure the efficient air flow. Do not sit on the unit and do not put objects on it. The information in this user’s manual was correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time in order to incorporate the latest technological developments. Never touch the unit with wet or damp hands. Never touch the unit when barefoot. BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.

THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
3

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

PURPOSE
The unit is designed to ensure continuous mechanical air exchange in houses, offices, hotels, cafes, conference halls, and other utility and public spaces as well as to recover the heat energy contained in the air extracted from the premises to warm up the filtered stream of intake air. The unit is not intended for organizing ventilation in swimming pools, saunas, greenhouses, summer gardens, and other spaces with high humidity. Due to the ability to save heating energy by means of energy recovery, the unit is an important element of energy-efficient premises. The unit is a component part and is not designed for stand-alone operation. It is rated for continuous operation. Transported air must not contain any flammable or explosive mixtures, evaporation of chemicals, sticky substances, fibrous materials, coarse dust, soot and oil particles or environments favourable for the formation of hazardous substances (toxic substances, dust, pathogenic germs).
DELIVERY SET

NAME
Air handling unit User’s manual Control unit user’s manual Control panel Installation kit Packing box

NUMBER
1 pc. 1 pc. 1 pc. 1 pc. 1 pc. 1 pc.

DESIGNATION KEY

KOMFORT EC S 5 B 270 E

S21
Control S2/S14/S21
Heat exchanger type : heat recovery air handling unit E: energy recovery air handling unit Rated air capacity [m3/h] Extra components : no bypass B: bypass Additional components 5: EPP casing Spigot orientation S: vertical Motor type EC: electronically commutated Series

4

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

TECHNICAL DATA
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up to 60 % without condensation. In cold, damp rooms, there is a possibility of freezing or condensation inside and outside the casing. In order to prevent condensation on the internal walls of the unit, it is necessary that the surface temperature of the casing is 2-3 °C above the dew point temperature of the transported air. The unit should be operated continuously, and in cases where ventilation is not necessary, reduce the air flow of the fans to a minimum (20%). This will ensure a favorable indoor climate and reduce the amount of condensation inside the unit, which can damage electronic components. Never use the unit for dehumidification, for example, of new buildings. The unit is rated as a Class I electrical appliance. Hazardous parts access and water ingress protection rating: IP22 for the unit connected to the air ducts IP44 for the unit motors The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.

MODEL
Unit voltage [V/50 (60) Hz] Maximum fan power [W] Maximum unit current (without a heater) [A] Maximum air capacity [m3/h] Sound pressure level at a distance of 3 m [dBA] Transported air temperature [°C] Casing material Heat insulating material Filtering class of the extract filter Filtering class of the supply filter Connected spigot diameter Weight [kg] Heat recovery efficiency [%] Heat exchanger type Heat exchanger material SEC Class for the KOMFORT EC S5B 270(-E) S14, KOMFORT EC S5B 270(-E) S21 units SEC Class for the KOMFORT EC S5 270(-E) EC S2 units

KOMFORT EC S5(B) 270

KOMFORT EC S5(B) 270-E

13 87-98
polystyrene

1 ~ 230 162 1.2 300 34
from -25 to +40 EPP
EPP 15…26 mm G4
G4 (optionally F8) 125
counter-flow

13.5 72-94
enthalpy

A+

A

B

5

www.blaubergventilatoren.de
ØD

KOMFOrt EC S5(B) 270(-E)
L1 L3 L4

H1 H
H2 H3 H5 H4

L5

ØD1

L

B

Model

Dimensions [mm] Ø D Ø D1 B L L1 L2 H H1 H2 L3 L4 L5 H3 H4 H5

KOMFORT EC S5(B) 270(-E) S2/S14 125 15 590 316 118 288 852 893 41 — — — — — —

KOMFORT EC S5B 270(-E) S21

125 15 590 316 118 288 852 893 41 324 313 93 180 330 196

6

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

DESIGN AND OPERATING PRINCIPLE
The unit has the following operating logic: warm stale extract air from the room flows into the unit, where it is filtered by the extract filter, then air flows through the heat exchanger and is exhausted outside by the extract fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the supply filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. Heat energy of warm extract air is transferred to clean intake fresh air from the outside and warms it up. The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in the cold season.
UNIT DESIGN

1

6

7

2

8 3

4
9
5
1 – exhaust fan; 2 – control unit; 3 – supply air filter; 4 – counter-flow heat exchanger; 5 – drain pipe; 6 – supply fan; 7 – bypass damper; 8 extract air filter; 9 – drain pan
The service side of the unit is equipped with a detachable plate for filter and heat exchanger cleaning and replacement operations. The control unit is positioned inside the unit casing. The power cable and grounding cables are connected to the control unit via the cable gland at the side of the unit. The temperature differential between the supply and extract air flows leads to condensate generation. Condensate is collected in the drain pan and is removed outside through the drain pipe.
Additional components (not included in the delivery set, optionally available for purchase): Humidity sensor (FS2 is connected to the terminal block, HR-S is connected to the controller). Based on the humidity sensor readings the unit keeps the set indoor humidity level. When the extract air humidity crosses the set humidity point, the unit goes automatically to the high speed. When the indoor humidity drops down below the set point, the unit reverts to the previous operation mode. CO2 sensor (connected to the controller). Measures indoor CO2 concentration and sends control signal to control the fan capacity. Air capacity control based on CO2 concentration is an efficient energy-saving ventilation solution.

7

www.blaubergventilatoren.de

Supply air Extract air Intake air
Exhaust air

Exhaust air Intake air Extract air Supply air

KOMFOrt EC S5(B) 270(-E)
UNIT OPERATION MODES
Heat recovery Warm stale extract air from the room flows into the unit, where it is filtered by the exhaust filter, then air flows through the heat exchanger and is exhausted outside by the exhaust fan. Cold fresh air from the outside flows into the unit, where it is cleaned by the supply filter. Then the air flows through the heat exchanger and is directed to the room with the supply fan. Supply air is heated in the heat exchanger by transferring the heat energy of warm and humid extract air to the cold fresh air. The air flows are fully separated while flowing through the heat exchanger. Heat recovery minimizes heat losses, which reduces the cost of space heating in the cold season.
Freeze protection The heat exchanger freeze protection function of the unit is implemented with a temperature sensor installed in the exhaust air duct downstream of the heat exchanger. In case of a freezing danger the supply fan is turned off and the heat exchanger is warmed up with warm extract air flow. The recommended sensor or thermostat operating temperature is +3 °C (exhaust air temperature behind the heat exchanger). If necessary, this set point can be edited using the software. After temperature increase the unit returns to the previous operation mode.

Summer Cooling mode The bypass dampers are open and both air flows do not come in contact with the heat exchanger.

Exhaust air Intake air Extract air Supply air

8

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

INSTALLATION AND SET-UP
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT
FS2 HUMIDITY SENSOR INSTALLATION AND CONNECTION (FOR UNITS WITH S14 AND S21 CONTROL)
The FS2 humidity sensor is not included in the delivery set and is available as a specially ordered accessory. The humidity sensor must be installed prior to the unit mounting. Install the humidity sensor through the extract spigot into the mount on the extract air duct panel. After that connect the humidity sensor plug to the respective socket on the control unit, refer to the External wiring diagram.

UNIT INSTALLATION To attain the best performance of the unit and to minimize turbulence-induced air pressure losses, connect the straight air duct section to the spigots while installing.
Minimum straight air duct length: · equal to 1 air duct diameter on the intake side · equal to 3 air duct diameters on outlet side
Push the air ducts onto the flanges of the unit until stop. Flexible ducts must be fixed rigidly with a metal worming clamp.

9

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

If the air ducts are too short or not connected, protect the unit parts from ingress of foreign objects. To prevent uncontrollable access to the fans, the spigots may be covered with a protecting grille or other protecting device with mesh width not more than 12.5 mm. While installing the unit, ensure convenient access for subsequent maintenance and repair. The unit must be mounted on a flat floor. Installing the unit to an uneven surface could lead to the unit’s casing distortion and operation disturbance. Do not expose the unit to direct sunlight.

The plate opposite to the service side must be fixed with screws (included in the delivery set) before installation.

Unit floor mounting
Install the unit on the pre-mounted floor supports, minimum 150 mm height, to ensure sufficient access for the drain pipe connection to the U-trap and for condensate drain system installation.

Unit wall mounting
Fasteners (dowels, self-tapping screws) for wall mounting are not included in the delivery set and must be ordered separately.
While choosing fasteners consider the material of the mounting surface as well as the weight of the unit, refer to the Technical data section. Fasteners for unit installation should be selected by a qualified technician.
Secure the wall bracket at required height. Hang the unit on the wall bracket and secure it with a screw.

10

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

Control unit mounting for KOMFORT EC S5B 270(-E) S21 Fasteners (dowels, self- tapping screws) for the control unit mounting are not included in the delivery set, must be purchased separately. While choosing fasteners consider the material of the mounting surface. Fasteners for unit installation should be selected by a qualified technician. To fix the control unit on the mounting surface the mounting brackets are provided. If necessary, the mounting brackets can be removed.

Design of hinges allows to change the opening side of a control unit cover. Unscrew the fixing screws, open the cover and unhinge it. Fix the cover to the opposite hinges, tighten the fixing screws.

CONDENSATE DRAINAGE Condensate drainage is required for the KOMFORT EC S5(B) 270 unit series. The KOMFORT EC S5(B) 270-E units are equipped with an enthalpy membrane heat exchanger. No condensate is generated in heat exchangers of this type, therefore, no condensate drainage is required. The hole for the drain pipe connection is located at the bottom of the unit in the exhaust air duct. Open the service panel, remove the heat exchanger and the filters. Glue extra insulation sheet material (supplied) to the outside of the unit where the plastic plugs are located. Drill a 22 mm hole in the plastic plug and install the drain pipe (supplied) in the hole. Then connect the drain pipe to the sewage system using a U-trap kit (purchased separately). The pipe slope downwards must be at least 3°.

11

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

1

min 3°

2 3

4

5

6

1 – drain pipe; 2, 4 – drain hose; 3 – U-trap; 5 – sewage system; 6 – additional insulation.

The condensate drainage system is designed for normal operation in premises with air temperatures above 0 °C! If the expected ambient air temperatures are below 0 °C, the condensate drainage system must be equipped with heat insulation and pre-heating facilities.

SERVICE SIDE CHANGE

Right-handed installation

Intake air

Extract air

Exhaust air

Supply air

Left-handed installation

Supply air

Extract air Intake air Exhaust air

Make sure of the correct unit service side selection. Unit mounting position should enable free excess to the opening plate for maintenance and service operations. The plate opposite to the service side must be fixed with screws (included in the delivery set).

12

KOMFOrt EC S5(B) 270(-E)
CONNECTION TO POWER MAINS

www.blaubergventilatoren.de

TURN OFF POWER SUPPLY PRIOR TO ANY OPERATIONS WITH THE UNIT. THE UNIT MUST BE CONNECTED TO POWER SUPPLY BY A QUALIFIED ELECTRICIAN.
THE RATED ELECTRICAL PARAMETERS OF THE UNIT ARE GIVEN ON THE MANUFACTURER’S LABEL.
ANY TAMPERING WITH THE INTERNAL CONNECTIONS IS PROHIBITED AND WILL VOID THE WARRANTY.
DO NOT LAY THE POWER CABLE OF THE UNIT IN CLOSE PROXIMITY TO THE CONTROL PANEL CABLE! DO NOT COIL THE CABLE FROM THE CONTROL PANEL IN LOOPS WHILE LAYING IT.
The unit is rated for connection to single-phase AC 230 V/50 (60) Hz power mains. Connect the unit to power mains using the supplied power cable with the mains plug (included in the delivery set).. The external power input must be equipped with an automatic circuit breaker built into the stationary wiring to open the circuit in the event of overload or short-circuit. The position of the external circuit breaker must ensure free access for quick power-off of the unit. The trip current must be in compliance with the consumption current, refer to Technical data. Complete the electrical connections through the terminal block in the control unit as shown in the external wiring diagram.

Access to the control unit KOMFORT EC S5(B) 270(-E) S2/S14 Access to the control unit KOMFORT EC S5B 270(-E) S21
13

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

EXTERNAL WIRING DIAGRAM FOR UNITS KOMFORT EC S5B 270(-E) S14
X1

12
L

A1

3 4 5 6 7 8 9 10 11 12 13 14

X9

Gnd Ctr +V

N PE PK PK NO C GND Tx Rx +U SM-L SM-N 22 23 24

1

remove jumper
White Brown Green Yellow

QF

L

N

230 V/50 (60) Hz

PE
PK fire alarm panel

External device NO (CO2 sensor)

– Tx Rx Control panel

L1 N L1 N +

SM1

SM2

supply exhaust

Electric actuators of the external air dampers

123 0-10V GND +U
Humidity sensor

Designation

Name

Model

Wire**

NO

External control device contacts

SM1*

Supply air damper actuator

SM2 *

Extract air damper actuator

PK*

Contact from fire alarm panel

*Is not included in the delivery set. ** Maximum connecting cable length is 20 m!

LF230 LF230 NO

2 x 0.75 mm2 2 x 0.75 mm2 2 x 0.75 mm2 2 x 0.75 mm2

EXTERNAL WIRING DIAGRAM FOR UNITS KOMFORT EC S5B 270(-E) S21

X1 L F1 N PE NC C NO C NO C In2 Out1 NO In1 In2 Out1 NO In1 NO C NO C IN GND

L 2,5A N

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

23

66

**U

**U

Electric shock hazard

Power input ~230 V

12 PK1*

12 Boost*

12

12
N In

Fireplace EVH

34 12
90 60 N In
ENH*

3 4 21
90 60
SM1*

21 SM2*

21
ENH RT2*

1 RS485
GND A B 24V

KKB NO C

Green Brown Yellow White
CCU*

Gnd A B +24V

P1

Designation
S1 S2 1 Boost

Name
Supply air damper actuator Extract air damper actuator Contact from fire alarm panel On/Off Boost contacts

14

Type
NO NO NC NO

Wire**
2 x 0,75 mm2 2 x 0,75 mm2 2 x 0,75 mm2 2 x 0,75 mm2

Remark
3A, 30DC/~250AC 3A, 30DC/~250AC remove jumper 23

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

Designation

Name

Type

Wire**

Fireplace*

On/Off Kamin contacts

NO

2 x 0,75 mm2

ENH RT2**

Channel temperature sensor

IN

2 x 0,25 mm2

P1*

External control panel

2 x 0,75 mm2

CCU*

Cooler control

NO

4 x 0,25 mm2

EVH*

Channel heater (preheating)

4 x 0,75 mm2

ENH*

Channel heater (afterheater)

4 x 0,75 mm2

*Is not included in the delivery set. **The supply voltage U of the SM1, SM2 external dampers is selected depending on the type of dampers.

Remark remove jumper 66
3A, 30DC/~250AC

WIRING DIAGRAM FOR CONNECTION OF THE EXTERNAL CONTROL UNIT TO KOMFORT EC S5B 270(-E) S21UNITS

XS3 XS4 XS5 XS6 XS7 XS8 XS9 XS10

NC C NO L N

LN

M2 0-10V

GND

M2 tacho

M1 0-10V

GNDHMtach1o

RH 0-10V

GND

R +24V

T3

T4

GND

T1

T2

GND

12312312312341234123123123

brown
47 W3
white

white
46

21,45

21 42 43 44 45, 46

green

gre y

yellow

brown

green

grey Green

yellow
W2

brown
W12
white brown
W1 blue yellow/green pink blue

Electric shock hazard

W1: Connection cable for M1, M2 motors. W2: Cable for connection of the control signals for M1, M2 motors and RH1 humidity sensor. W3: Connection cable for temperature sensors. W12: Connection cable for dampers control.

EXTERNAL WIRING DIAGRAM FOR UNITS KOMFORT EC S5 270(-E) S2

QF
230 V/50 (60) Hz

Speed controller
+10V CTR GND

White

Brown

XP
Electric shock hazard

L N PE +10V Ctr GND
1234 567

Name
Speed controller
** Maximum connecting cable length is 20 m!

X1
Wire*
3 x 0.25 mm2

15

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS.
FOLLOW THE SAFETY REGULATIONS WHEN CARRYING OUT MAINTENANCE. Maintenance operations of the unit are required 3-4 times per year. It includes general cleaning of the unit and the following operations:

1. Filter maintenance (3-4 times per year). Dirty filters increase air resistance in the system and reduce supply air volume. The filters require cleaning not less than 3-4 times per year. Vacuum cleaning is allowed. After two consecutive cleanings filters must be replaced. For new filters, contact the Seller. To clean or replace the filters, detach the removable plates located on the service side of the unit. After cleaning install the filters and the detachable plates in the reverse order.

2. Heat exchanger maintenance (once per year). Some dust may accumulate on the heat exchanger even in case of regular maintenance of the filters. To maintain the high heat recovery efficiency, regular cleaning is required. Before removing the heat exchanger, detach the removable plate located on the service side of the unit. Remove the heat exchanger and the drain pan from the unit. Flush the heat exchanger with warm detergent solution. After cleaning install the dry heat exchanger with the drain pan back to the unit.

3. Drain system maintenance (once per year) The condensate drainage (drain line) may get clogged by dirt and dust particles contained in the exhaust air. Pour some water inside the drain pan to check the pipe for clogging. Clean the U-trap and the drain pipe if required. 4. Technical maintenance of air duct system (every 5 years). Even regular fulfilling of all the maintenance operations prescribed above may not completely prevent dirt accumulation in the air ducts, which reduces the unit capacity. Duct maintenance means regular cleaning or replacement. 5. Control unit maintenance (if necessary). The control unit maintenance must be performed by an expert qualified for unassisted operations with electrical installations with the voltage up to 1000 V after careful reading of the user’s manual.

16

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

TROUBLESHOOTING

Problem
The fan(s) does not start when the unit is on

TROUBLES AND TROUBLESHOOTING

Possible reasons No power supply. The motor is jammed, the impeller blades are soiled.

Troubleshooting Make sure the power supply line is connected correctly, otherwise troubleshoot the connection error.
Turn the unit off. Troubleshoot the motor jam and the impeller clogging. Clean the blades. Restart the unit.

Alarm in the system.

Turn the unit off. Contact the Seller.

Automatic circuit breaker trips following the unit turning on
Low air flow
Cold supply air

Overcurrent as a result of short circuit in the electric circuit.
Low set fan speed. The filters and the fans are clogged, the heat exchanger is clogged. Ventilation system elements (air ducts, diffusers, louver shutters, grilles) are clogged, damaged, or closed. The extract filter is soiled. The impeller(s) is soiled.

Noise, vibration

The fan or casing screw connection is loose.

Water leakage (only for the
KOMFORT EC S5(B) 270). units)

No anti-vibration connectors on air duct pipe flanges.
The drainage system is soiled, damaged, or installed incorrectly.

Turn the unit off. Contact the Seller.
Set higher speed. Clean or replace the filters, clean the fans, and the heat exchanger. Clean or replace the ventilation system elements, such as air ducts, diffusers, louver shutters, grilles. Clean or replace the extract filter. Clean the impeller(s). Tighten the screw connection of the fans or the casing all the way.
Install anti-vibration connectors.
Clean the drain line if necessary. Check the drain line slope angle. Make sure that the U-trap is filled with water and the drain pipes are frost protected.

STORAGE AND TRANSPORTATION REGULATIONS
· Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range +5 …+40 °C and relative humidity up to 70 %.
· Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
· Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit. · Follow the handling requirements applicable for the particular type of cargo. · The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and
mechanical damage. The unit must be transported only in the working position. · Avoid sharp blows, scratches, or rough handling during loading and unloading. · Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at
least 3-4 hours.
17

www.blaubergventilatoren.de

KOMFOrt EC S5(B) 270(-E)

MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage guidelines and electromagnetic compatibility. We hereby declare that the product complies with the provisions of Electromagnetic Compatibility (EMC) Directive 2014/30/EU of the European Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the European Parliament and of the Council and CE-marking Council Directive 93/68/EEC. This certificate is issued following test carried out on samples of the product referred to above. The manufacturer hereby warrants normal operation of the unit for 24 months after the retail sale date provided the user’s observance of the transportation, storage, installation, and operation regulations. Should any malfunctions occur in the course of the unit operation through the Manufacturer’s fault during the guaranteed period of operation, the user is entitled to get all the faults eliminated by the manufacturer by means of warranty repair at the factory free of charge. The warranty repair includes work specific to elimination of faults in the unit operation to ensure its intended use by the user within the guaranteed period of operation. The faults are eliminated by means of replacement or repair of the unit components or a specific part of such unit component.
The warranty repair does not include: · routine technical maintenance · unit installation/dismantling · unit setup To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases: · User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing
component parts previously dismounted by the user. · Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual. · User’s failure to ensure timely technical maintenance of the unit. · External damage to the unit casing (excluding external modifications as required for installation) and internal components caused
by the user. · Redesign or engineering changes to the unit. · Replacement and use of any assemblies, parts and components not approved by the manufacturer. · Unit misuse. · Violation of the unit installation regulations by the user. · Violation of the unit control regulations by the user. · Unit connection to power mains with a voltage different from the one stated in the user’s manual. · Unit breakdown due to voltage surges in power mains. · Discretionary repair of the unit by the user. · Unit repair by any persons without the manufacturer’s authorization. · Expiration of the unit warranty period. · Violation of the unit transportation regulations by the user. · Violation of the unit storage regulations by the user. · Wrongful actions against the unit committed by third parties. · Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades). · Missing seals if provided by the user’s manual. · Failure to submit the user’s manual with the unit purchase date stamp. · Missing payment paperwork certifying the unit purchase.

FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE- FREE OPERATION OF THE UNIT
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL
WITH THE PURCHASE DATE STAMP
18

KOMFOrt EC S5(B) 270(-E)

www.blaubergventilatoren.de

CERTIFICATE OF ACCEPTANCE
Unit Type Model
Serial Number
Manufacture Date Quality Inspector’s Stamp

Air handling unit

SELLER INFORMATION
Seller Address Phone Number E-mail Purchase Date This is to certify acceptance of the complete unit delivery with the user’s manual. The warranty terms are acknowledged and accepted.
Customer’s Signature

INSTALLATION CERTIFICATE

The _____ unit is installed pursuant to the requirements stated in the present user’s manual.

Company name

Address

Phone Number

Installation Technician’s Full Name

Installation Date:

Signature:

The unit has been installed in accordance with the provisions of all the applicable local and national construction, electrical and technical codes and standards. The unit operates normally as intended by the manufacturer.
Signature:

WARRANTY CARD
Unit Type Model
Serial Number
Manufacture Date Purchase Date Warranty Period Seller

Air handling unit

Seller’s Stamp Installation Stamp
Seller’s Stamp

19

www.blaubergventilatoren.de B170-1EN-09