Altronix XBV Series Power Supply, Charger Boards Installation Guide
- June 30, 2024
- Altronix
Table of Contents
XBV Series Power Supply, Charger Boards
“`html
Specifications:
- Altronix Model Number
- Input Rating: 220VAC 50/60Hz
- AL300XB2V : 1.5A
- AL400XB2V : 1.5A
- AL600XB220 : 1.5A
- AL1012XB220 : 1.3A
- AL1024XB2V : 2.5A
- Output Voltage (Current): 12VDC, 24VDC
- Input Fuse Rating: 5A/250V for all models
- Battery Maximum Fuse Rating: 15A/250V
- Battery Charge Current: 0.7A to 3.6A
Product Usage Instructions:
Installation Guide:
-
Mount the power supply/charger board in the desired
location/enclosure (mounting hardware included). -
Set the desired DC output voltage by configuring SW1 to the
appropriate position on the power supply board.
Stand-by Specifications:
The stand-by and alarm durations vary based on the model of the
power supply/charger board. Refer to the user manual for specific
information on stand-by and alarm current ratings.
Wiring Instructions:
Wiring methods must comply with Article 760 of The National
Electrical Code or NFPA 72, in addition to all relevant local codes
and authorities having jurisdiction. This product is designed for
indoor use only.
FAQ:
Q: Can I use the power supply/charger board outdoors?
A: No, the product is intended for indoor use only.
Q: How do I set the DC output voltage?
A: You can set the DC output voltage by adjusting SW1 to the
appropriate position on the power supply board.
“`
XBV Series Power Supply/Charger Boards
Installation Guide
Overview:
Altronix XBV Series power supply/chargers convert a 220VAC (working range
198VAC – 256VAC), 50/60Hz input to a 12VDC or 24VDC output.
Specifications:
Altronix Model Number
Input Rating 220VAC 50/60Hz
AL300XB2V
1.5A
AL400XB2V
1.5A
AL600XB220
1.5A
AL1012XB220 1.3A
AL1024XB2V
2.5A
Output Voltage (Current)
12VDC
2.5A 4A 6A 10A
24VDC
2.5A 3A 6A 10A
Input Fuse Rating
5A/250V 5A/250V 5A/250V 5A/250V 5A/250V
Battery
Maximum
Fuse Rating Charge Current
15A/250V
0.7A
15A/250V
0.7A
0.7A
15A/250V
0.7A
15A/250V
3.6A
Output: · Filtered and electronically regulated output.
Battery Backup: · Built-in charger for sealed lead acid or
gel type batteries. · Automatic switch over to stand-by battery
when AC fails. · Zero voltage drop when switched over to
battery backup.
Visual Indicators: · AL300XB2V, AL400XB2V and AL600XB220:
AC input, DC output and BAT trouble LED indicators. · AL1012XB220 and
AL1024XB2V:
AC input (2 LEDs) and DC output. See Fig.1, pg. 4.
Supervision: · AC fail supervision (form “C” contacts). · Low battery and
battery presence supervision
(form “C” contacts).
Additional Features: · Short circuit and thermal overload protection.
Board Dimensions (L x W x H approximate): AL300XB2V:
7.1″ x 4.5″ x 1.44″ (180.3mm x 114.3mm x 36.6mm). AL400XB2V: 7.1″ x 4.5″ x
1.44″ (180.3mm x 114.3mm x 36.6mm). AL600XB220: 7.1″ x 4.5″ x 2″ (180.3 mm x
114.3 mm x 50.8 mm). AL1012XB220: 7.25″ x 4.5″ x 1.75″ (184.2mm x 114.3mm x
44.5mm). AL1024XB2V: 8.4″ x 4.5″ x 1.4″ (213.4mm x 114.4mm x 35.6mm).
AL300XB2V: Output 12VDC / 40AH Battery 24VDC / 12AH Battery 24VDC / 40AH Battery
Stand-by Specifications:
4 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 2.5A Alarm = 2.5A
Stand-by = 2.5A Alarm = 2.5A
24 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 1.0A Alarm = 2.5A
Stand-by = 200mA Alarm = 2.5A
Stand-by = 1.0A Alarm = 2.5A
60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 2.5A
Stand-by = 300mA Alarm = 2.5A
AL400XB2V:
Stand-by Specifications (cont’d):
Output 12VDC / 40AH Battery 24VDC / 12AH Battery 24VDC / 40AH Battery
4 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 4.0A Alarm = 4.0A
Stand-by = 3.0A Alarm = 3.0A
24 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 1.0A Alarm = 4.0A
Stand-by = 200mA Alarm = 3.0A
Stand-by = 1.0A Alarm = 3.0A
60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 4.0A
Stand-by = 300mA Alarm = 3.0A
AL600XB220:
Output 12VDC / 40AH Battery 24VDC / 12AH Battery 24VDC / 40AH Battery
4 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 6.0A Alarm = 6.0A
Stand-by = 6.0A Alarm = 6.0A
24 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 1.0A Alarm = 6.0A
Stand-by = 200mA Alarm = 6.0A
Stand-by = 1.0A Alarm = 6.0A
60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 6.0A
Stand-by = 300mA Alarm = 6.0A
AL1012XB220:
Output
Access Control Applications Stand-by
12VDC / 12AH Battery
30 minutes of backup @ 10A
AL1024XB2V:
Output
15 min. of Stand-by and
5 min. of Alarm
4 hr. of Stand-by and 5 min. of Alarm
24 hr. of Stand-by and 5 min. of
Alarm
60 hr. of Stand-by and 5 min. of
Alarm
Access Control Applications Stand-by
24VDC / 12AH Stand-By = 8A Stand-By = 1.5A Stand-By = 200mAStand-By = 100mA
Battery
Alarm = 10A Alarm = 10A Alarm = 10A Alarm = 10A
20 mins./8A
Output
15 min. of Stand-by and
5 min. of Alarm
4 hr. of Stand-by and 5 min. of Alarm
24 hr. of Stand-by and 15 min. of Alarm
60 hr. of Stand-by and 15 min. of
Alarm
Access Control Applications Stand-by
24VDC / 65AH Battery
Stand-By = 8.0A Stand-By = 1.5A Stand-By = 500mA Alarm = 10A Alarm = 10A Alarm = 10A
4 hrs./8A
Installation Instructions: Wiring methods shall be in accordance with in
accordance with article 760 of The National Electrical Code or NFPA 72, as
well as all applicable local codes and authorities having jurisdiction.
Product is intended for indoor use only. 1. Mount the power supply/charger
board in the desired location/enclosure (mounting hardware included). 2. Set
desired DC output voltage by setting SW1 to the appropriate position on the
power supply board
(Fig. 1e, pg. 4). 3. Connect unswitched AC power (220VAC 50/60Hz) to the
terminals marked [L, G, N] (Fig. 1a, pg. 4).
Use 14 AWG or larger for all power connections (Battery, AC input, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery
reporting). Keep power-limited wiring separate from non power-limited wiring
(220VAC 50/0Hz Input, Battery Wires). Minimum 0.25″ spacing must be provided.
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before
installing or servicing equipment. There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel.
– 2 –
XBV Power Supply/Chargers Installation Guide
4. Measure output voltage before connecting devices. This helps avoiding
potential damage. 5. Connect devices to be powered to the terminals marked [+
DC ] (Fig. 1d, pg. 4). 6. For Access Control applications batteries are
optional. When batteries are not used, a loss of AC will result
in the loss of output voltage. When the use of stand-by batteries is desired,
they must be lead acid or gel type. Connect battery to terminals marked [+ BAT
] (Fig. 1c, pg. 4). Note: Separate enclosure must be used for housing 40AH or
65AH batteries. 7. It is required to connect appropriate signaling
notification devices to [AC FAIL] & [BAT FAIL] (Fig. 1b, pg. 4) supervisory
relay outputs. Use 22AWG to 18AWG wires. AC fail will report in 5 minutes. To
delay report for 6 hours cut “AC Delay” jumper (Fig. 1, pg. 4).
Wiring:
Use 18 AWG or larger for all low voltage power connections. Note: Take care to
keep power-limited circuits separate from non power-limited wiring (220VAC,
Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as
follows:
Output Voltage Test: Battery Test:
Replacing Batteries:
Under normal load conditions, the DC output voltage should be checked for proper voltage level. Under normal load conditions check that the battery is fully charged, check specified voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the board terminals marked [+ BAT ] to ensure that there is no break in the battery connection wires. Disconnect existing batteries. Connect battery to the terminals marked [+ BAT ]. Use two (2) 12VDC batteries connected in series for 24VDC operation.
Terminal Identification:
Terminal Legend L, G, N (Fig. 1a, pg. 4)
+ DC (Fig. 1d, pg. 4)
Function/Description
Connect 220VAC to these terminals: L to hot, G to ground, N to neutral.
AL300XB2V: AL400XB2V: AL600XB220: AL1012XB220: AL1024XB2220:
12VDC or 24VDC @ 2.5A continuous output. 12VDC @ 4A or 24VDC @ 3A continuous output. 12VDC or 24VDC @ 6A continuous output. 12VDC @ 10A continuous output. 24VDC @ 8A continuous, 10A in alarm.
AC FAIL NO, C, NC (Fig. 1b, pg. 4)
Used to notify loss of AC power, e.g.connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit.
BAT FAIL NO, C, NC (Fig. 1b, pg. 4)
Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery is reported within 1 minute. Battery reconnection is reported within 1 minute. Low battery threshold: approximately 21VDC.
+ BAT (Fig. 1c, pg. 4)
Stand-by battery connections. AL300XB2V, AL400XB2V, AL600XB220, AL1012XB220 maximum charge current 0.7A. AL1024XB2V maximum charge current 3.6A.
XBV Power Supply/Chargers Installation Guide
– 3 –
Fig. 1 – XBV Configuration
1e*
OFF 24V ON 12V
ON
+ DC
B
AC DC
1d**
+ BAT
1c***
A
AC DC BAT
AC DC
C
5A 250V
LG N
BAT FAIL NC C NO NC C NO AC FAIL
1a
1b
LED Position:
A AL300XB2V, AL400XB2V and AL600XB220 AC LED in this position is common on all power supplies
B AL1012ULXB
C AL1024ULXB2
- Output Voltage Selection DIP Switch. Not applicable for AL1012XB220 and AL1024XB2V ** AL1012XB220 terminals are marked [ DC +] *** AL1024XB2V terminals are marked [ BAT +]
LED Diagnostics (AL300XB2V, AL400XB2V and AL600XB220):
Green (AC) Red (DC) Red (BAT) Power Supply Status
ON
ON
ON
Normal operating condition.
OFF
ON
ON
Loss of AC. Stand-by battery is supplying power.
ON
OFF
OFF
No DC output, Battery Trouble.
OFF
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
ON
ON
OFF
Battery missing / Low.
Green (AC) ON OFF ON OFF
LED Diagnostics (AL1012XB220 and AL1024XB2V):
Green (AC) Red (DC) Power Supply Status
ON
ON
Normal operating condition.
OFF
ON
Loss of AC. Stand-by is battery supplying power.
ON
OFF
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Altronix is not responsible for any typographical errors. 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty
IIXBV Rev. 081518
E01X
MEMBER
– 4 –
XBV Power Supply/Chargers Installation Guide
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>