Altronix XBV Series Power Supply, Charger Boards Installation Guide

June 30, 2024
Altronix

XBV Series Power Supply, Charger Boards

“`html

Specifications:

  • Altronix Model Number
  • Input Rating: 220VAC 50/60Hz
  • AL300XB2V : 1.5A
  • AL400XB2V : 1.5A
  • AL600XB220 : 1.5A
  • AL1012XB220 : 1.3A
  • AL1024XB2V : 2.5A
  • Output Voltage (Current): 12VDC, 24VDC
  • Input Fuse Rating: 5A/250V for all models
  • Battery Maximum Fuse Rating: 15A/250V
  • Battery Charge Current: 0.7A to 3.6A

Product Usage Instructions:

Installation Guide:

  1. Mount the power supply/charger board in the desired
    location/enclosure (mounting hardware included).

  2. Set the desired DC output voltage by configuring SW1 to the
    appropriate position on the power supply board.

Stand-by Specifications:

The stand-by and alarm durations vary based on the model of the
power supply/charger board. Refer to the user manual for specific
information on stand-by and alarm current ratings.

Wiring Instructions:

Wiring methods must comply with Article 760 of The National
Electrical Code or NFPA 72, in addition to all relevant local codes
and authorities having jurisdiction. This product is designed for
indoor use only.

FAQ:

Q: Can I use the power supply/charger board outdoors?

A: No, the product is intended for indoor use only.

Q: How do I set the DC output voltage?

A: You can set the DC output voltage by adjusting SW1 to the
appropriate position on the power supply board.

“`

XBV Series Power Supply/Charger Boards

Installation Guide
Overview:
Altronix XBV Series power supply/chargers convert a 220VAC (working range 198VAC – 256VAC), 50/60Hz input to a 12VDC or 24VDC output.

Specifications:

Altronix Model Number

Input Rating 220VAC 50/60Hz

AL300XB2V

1.5A

AL400XB2V

1.5A

AL600XB220

1.5A

AL1012XB220 1.3A

AL1024XB2V

2.5A

Output Voltage (Current)

12VDC
2.5A 4A 6A 10A ­

24VDC
2.5A 3A 6A ­ 10A

Input Fuse Rating
5A/250V 5A/250V 5A/250V 5A/250V 5A/250V

Battery

Maximum

Fuse Rating Charge Current

15A/250V

0.7A

15A/250V

0.7A

­

0.7A

15A/250V

0.7A

15A/250V

3.6A

Output: · Filtered and electronically regulated output.
Battery Backup: · Built-in charger for sealed lead acid or
gel type batteries. · Automatic switch over to stand-by battery
when AC fails. · Zero voltage drop when switched over to
battery backup.
Visual Indicators: · AL300XB2V, AL400XB2V and AL600XB220:
AC input, DC output and BAT trouble LED indicators. · AL1012XB220 and AL1024XB2V:
AC input (2 LEDs) and DC output. See Fig.1, pg. 4.
Supervision: · AC fail supervision (form “C” contacts). · Low battery and battery presence supervision
(form “C” contacts).

Additional Features: · Short circuit and thermal overload protection.
Board Dimensions (L x W x H approximate): AL300XB2V:
7.1″ x 4.5″ x 1.44″ (180.3mm x 114.3mm x 36.6mm). AL400XB2V: 7.1″ x 4.5″ x 1.44″ (180.3mm x 114.3mm x 36.6mm). AL600XB220: 7.1″ x 4.5″ x 2″ (180.3 mm x 114.3 mm x 50.8 mm). AL1012XB220: 7.25″ x 4.5″ x 1.75″ (184.2mm x 114.3mm x 44.5mm). AL1024XB2V: 8.4″ x 4.5″ x 1.4″ (213.4mm x 114.4mm x 35.6mm).

AL300XB2V: Output 12VDC / 40AH Battery 24VDC / 12AH Battery 24VDC / 40AH Battery

Stand-by Specifications:

4 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 2.5A Alarm = 2.5A
­
Stand-by = 2.5A Alarm = 2.5A

24 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 1.0A Alarm = 2.5A
Stand-by = 200mA Alarm = 2.5A
Stand-by = 1.0A Alarm = 2.5A

60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 2.5A
­
Stand-by = 300mA Alarm = 2.5A

AL400XB2V:

Stand-by Specifications (cont’d):

Output 12VDC / 40AH Battery 24VDC / 12AH Battery 24VDC / 40AH Battery

4 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 4.0A Alarm = 4.0A
­
Stand-by = 3.0A Alarm = 3.0A

24 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 1.0A Alarm = 4.0A
Stand-by = 200mA Alarm = 3.0A
Stand-by = 1.0A Alarm = 3.0A

60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 4.0A
­
Stand-by = 300mA Alarm = 3.0A

AL600XB220:

Output 12VDC / 40AH Battery 24VDC / 12AH Battery 24VDC / 40AH Battery

4 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 6.0A Alarm = 6.0A
­
Stand-by = 6.0A Alarm = 6.0A

24 hr. of Stand-by and 5 Minutes of Alarm
Stand-by = 1.0A Alarm = 6.0A
Stand-by = 200mA Alarm = 6.0A
Stand-by = 1.0A Alarm = 6.0A

60 hr. of Stand-by and 5 Minutes of Alarm Stand-by = 300mA Alarm = 6.0A
­
Stand-by = 300mA Alarm = 6.0A

AL1012XB220:

Output

Access Control Applications Stand-by

12VDC / 12AH Battery

30 minutes of backup @ 10A

AL1024XB2V:

Output

15 min. of Stand-by and
5 min. of Alarm

4 hr. of Stand-by and 5 min. of Alarm

24 hr. of Stand-by and 5 min. of
Alarm

60 hr. of Stand-by and 5 min. of
Alarm

Access Control Applications Stand-by

24VDC / 12AH Stand-By = 8A Stand-By = 1.5A Stand-By = 200mAStand-By = 100mA

Battery

Alarm = 10A Alarm = 10A Alarm = 10A Alarm = 10A

20 mins./8A

Output

15 min. of Stand-by and
5 min. of Alarm

4 hr. of Stand-by and 5 min. of Alarm

24 hr. of Stand-by and 15 min. of Alarm

60 hr. of Stand-by and 15 min. of
Alarm

Access Control Applications Stand-by

24VDC / 65AH Battery

­

Stand-By = 8.0A Stand-By = 1.5A Stand-By = 500mA Alarm = 10A Alarm = 10A Alarm = 10A

4 hrs./8A

Installation Instructions: Wiring methods shall be in accordance with in accordance with article 760 of The National Electrical Code or NFPA 72, as well as all applicable local codes and authorities having jurisdiction. Product is intended for indoor use only. 1. Mount the power supply/charger board in the desired location/enclosure (mounting hardware included). 2. Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board
(Fig. 1e, pg. 4). 3. Connect unswitched AC power (220VAC 50/60Hz) to the terminals marked [L, G, N] (Fig. 1a, pg. 4).
Use 14 AWG or larger for all power connections (Battery, AC input, DC output). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). Keep power-limited wiring separate from non power-limited wiring (220VAC 50/0Hz Input, Battery Wires). Minimum 0.25″ spacing must be provided. CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

– 2 –

XBV Power Supply/Chargers Installation Guide

4. Measure output voltage before connecting devices. This helps avoiding potential damage. 5. Connect devices to be powered to the terminals marked [+ DC ­] (Fig. 1d, pg. 4). 6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result
in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. Connect battery to terminals marked [+ BAT ­] (Fig. 1c, pg. 4). Note: Separate enclosure must be used for housing 40AH or 65AH batteries. 7. It is required to connect appropriate signaling notification devices to [AC FAIL] & [BAT FAIL] (Fig. 1b, pg. 4) supervisory relay outputs. Use 22AWG to 18AWG wires. AC fail will report in 5 minutes. To delay report for 6 hours cut “AC Delay” jumper (Fig. 1, pg. 4).
Wiring:
Use 18 AWG or larger for all low voltage power connections. Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Battery Test:
Replacing Batteries:

Under normal load conditions, the DC output voltage should be checked for proper voltage level. Under normal load conditions check that the battery is fully charged, check specified voltage (12VDC @ 13.2 or 24VDC @ 26.4) both at the battery terminal and at the board terminals marked [+ BAT ­] to ensure that there is no break in the battery connection wires. Disconnect existing batteries. Connect battery to the terminals marked [+ BAT ­]. Use two (2) 12VDC batteries connected in series for 24VDC operation.

Terminal Identification:

Terminal Legend L, G, N (Fig. 1a, pg. 4)
+ DC ­ (Fig. 1d, pg. 4)

Function/Description

Connect 220VAC to these terminals: L to hot, G to ground, N to neutral.

AL300XB2V: AL400XB2V: AL600XB220: AL1012XB220: AL1024XB2220:

12VDC or 24VDC @ 2.5A continuous output. 12VDC @ 4A or 24VDC @ 3A continuous output. 12VDC or 24VDC @ 6A continuous output. 12VDC @ 10A continuous output. 24VDC @ 8A continuous, 10A in alarm.

AC FAIL NO, C, NC (Fig. 1b, pg. 4)

Used to notify loss of AC power, e.g.connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. AC or brownout fail is reported within 1 minute of event. To delay reporting for up to 6 hrs., cut “AC Delay” jumper and reset power to unit.

BAT FAIL NO, C, NC (Fig. 1b, pg. 4)

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. A removed battery is reported within 1 minute. Battery reconnection is reported within 1 minute. Low battery threshold: approximately 21VDC.

+ BAT ­ (Fig. 1c, pg. 4)

Stand-by battery connections. AL300XB2V, AL400XB2V, AL600XB220, AL1012XB220 maximum charge current 0.7A. AL1024XB2V maximum charge current 3.6A.

XBV Power Supply/Chargers Installation Guide

– 3 –

Fig. 1 – XBV Configuration

1e*
OFF ­ 24V ON ­ 12V

ON

+ DC ­

B
AC DC

1d**

+ BAT ­

1c***

A
AC DC BAT

AC DC
C

5A 250V

LG N

BAT FAIL NC C NO NC C NO AC FAIL

1a

1b

LED Position:

A AL300XB2V, AL400XB2V and AL600XB220 AC LED in this position is common on all power supplies

B AL1012ULXB

C AL1024ULXB2

  • Output Voltage Selection DIP Switch. Not applicable for AL1012XB220 and AL1024XB2V ** AL1012XB220 terminals are marked [­ DC +] *** AL1024XB2V terminals are marked [­ BAT +]

LED Diagnostics (AL300XB2V, AL400XB2V and AL600XB220):

Green (AC) Red (DC) Red (BAT) Power Supply Status

ON

ON

ON

Normal operating condition.

OFF

ON

ON

Loss of AC. Stand-by battery is supplying power.

ON

OFF

OFF

No DC output, Battery Trouble.

OFF

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

ON

ON

OFF

Battery missing / Low.

Green (AC) ON OFF ON OFF

LED Diagnostics (AL1012XB220 and AL1024XB2V):

Green (AC) Red (DC) Power Supply Status

ON

ON

Normal operating condition.

OFF

ON

Loss of AC. Stand-by is battery supplying power.

ON

OFF

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Altronix is not responsible for any typographical errors. ­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­­ 140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056

website: www.altronix.com | e-mail: info@altronix.com | Lifetime Warranty

IIXBV Rev. 081518

E01X

MEMBER

– 4 –

XBV Power Supply/Chargers Installation Guide

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Altronix User Manuals

Related Manuals