SMART KITCHEN Alarm Management User Manual
- June 3, 2024
- SMART KITCHEN
Table of Contents
SMART KITCHEN Alarm Management
Close- up Of A Person’s Hand Using Smart Home Application On Smartphone In Kitchen
ALARM MANAGEMENT IN THE SMARTKITCHEN SERVICE
In alarm management, the unit main user defines the events that cause the alarm and to whom the alarm notification is forwarded. There can be multiple recipients of an alarm. The alarms are sent as both a text message (SMS) and an email.
The alarm is triggered by three events:
- Exceeding or falling below the alarm limit set for the measurement device
- Measurement device is disconnected
- Gateway is disconnected
- With the set temperature alarm limit, the service user receives an alarm if, for example, the door of the freezer room is left open or the refrigeration appliance is broken. The temperature alarm limit can be used to avoid extensive damage by preventing cold chain breakage and food spoilage. In addition to temperature, the alarm limit can be set for humidity and carbon dioxide content.
- A disconnection of the measurement device will cause an alarm if the device has not transferred the measurements to the SmartKitchen service within the last 4 hours. This may be due to, for example, running out of batteries or placing the meter out of range. If the measurement device has been switched on during the disconnection, the measurement results are stored in its internal memory. The data can be read and transferred to the service after an interruption with the SmartKitchen Handy application.
- A disconnection of the Gateway device causes an alarm if the device has not been connected to the SmartKitchen service during the last 3 hours. The connection loss may be due to, for example, poor mobile network coverage or by accidentally unplugging the Gateway. Note that a Gateway disconnection usually also causes a measurement device disconnection, which is corrected when the problem that caused the Gateway disconnection is corrected. If the measurement devices have been switched on during the disconnection, the measurement results are stored in their internal memories. The data can be read and transferred to the SmartKitchen service after an interruption with the SmartKitchen Handy application.
The user must take immediate corrective action whenever an alarm is received. Managing alarms requires that your account has a valid SmartKitchen license.
SETTING ALARM RECIPIENTS
The unit main user directs alarms to the desired email addresses and / or SMS numbers. To activate the contact, the recipient of the alarm must acknowledge the confirmation message sent to the e-mail address and SMS number. This ensures that the correct and functional contact information has been entered into the service.
To add the alarm recipients, select:
- Settings
- Alarm manager
- Recipients of the alarms
Figure 1. Alarm manager main menu.
In the Alarm manager main menu, go to the “Recipients of the alarms” menu, where the SMS numbers and e-mail addresses of the recipients are added. By selecting an alarm on a per-user basis, it is possible to select which alarm event is forwarded to which contact as a text message and / or e-mail. The same alarm can be transmitted to several users simultaneously.
To add recipients for alarms, select “Add new recipient”.
Figure 2. Recipients of the alarms, Add new
You can then select whether to add an email address or a phone number for the text message to your contacts.
Figure 3. Select how the alarm message is forwarded.
Figure 4. Adding new alarm recipient email address.
Figure 5. Unverified alarm recipient email address entered in the service.
The verification link sent to the email address must be clicked / followed to verify the email address. When the verification is complete, the text “Not verified” after the email address will disappear. A corresponding link is also sent to the entered SMS number, which is clicked to verify the phone number. Note that a verification message will be sent as soon as OK is selected after adding the contact. If the verification message does not arrive, check your email spam folder.
SETTING ALARMS: Disconnection of the measurement device
In the “Measurement device alarms” menu, unit main user selects which device will sent an alarm if no measurements have been transferred to the service during the last 4 hours. Disconnection alarms must always be selected on the measurement devices used in the kitchen environment. If the measuring device is used, for example, to record the temperature during food transport, in which case the connection will inevitably be lost, it is advisable to deselect it.
Figure 6. Measurement device alarms menu.
SETTING ALARMS: Disconnection of the Gateway
The Gateway device must be registered in the main user’s account to receive alarms about disconnections. Usually, the gateway is already registered. Select from the Alarm Management main page:
- Gateway Alarms
The gateway devices registered for the account are displayed. Select which devices will send an alarm if it has been disconnected from a server for more than 3 hours.
Figure 7. Gateway alarms menu
If the gateway device in use does not appear in the list, it must be registered in the account. Registration is done by selecting from the main view:
- Settings
- Gateway devices
The numeric serial number on the label of the Gateway device is entered here. After entering the number, check that the Gateway device is displayed in the Gateway alarms and that the alarm selection is on.
SETTING ALARMS: Temperature alarm limits
The user defined in the alarm management receives information by email or SMS when the measurement limit is exceeded or falls below (for example, the measured temperature is higher than the upper temperature limit). Alarms also appear in the SmartKitchen service, where they are easy to analyze later.
Set temperature alarm:
- Settings
- Measurement devices: Choose the device for which you want to set an alarm.
- Set temperature limits: Enter the highest and/or the lowest allowed value. Click OK.
Figure 8. Setting alarm temperature limits.
Timed alarms
If necessary, the unit main user can enable alarms only at specified times. Timed alarms are enabled by unchecking the “Available always” check box. Choose the days of the week when you want the device to respond to the alarm limits and, if necessary, set the times between which alarms should be monitored.
Figure 9. Setting a timed alarm.
Delayed alarms
If necessary, the unit main user can set a delayed alarm for devices that may momentarily exceed or fall below the set limit. To enable delayed alarms, clear the “Alarm immediately” check box. A delayed alarm is only sent when the measurement has been continuously above or below a given limit for a specified time. In this way, the user avoids the so-called “unnecessary alarmsâ€, for example when new products are added to the freezer.
Figure 10. Setting a delayed alarm.
When the alarm settings are complete, click → OK to save.
The service now sends alarms (by email and / or SMS) if the measured value exceeds the maximum allowed value or falls below the minimum. In SmartKitchen service, alarms are displayed on the front page. The bell icon next to the measurement device name indicates which device caused the alarm. When the device that triggered the alarm is selected, the user can see the latest alarm. The user must acknowledge the alarm and at the same time the cause can be recorded. Previous alarms are displayed below the graph.
Figure 11. A temperature alarm displayed in the service.
ALARM FUNCTION
The user defined in the alarm manager will be notified by email and / or SMS
about the last alarm. If the previous alarm has not been acknowledged, the
service will not send a new message. However, all notifications will appear on
the SmartKitchen service.
The recipient of the alarm notification must ensure that the problem that
caused the alarm has been fixed and the alarm is acknowledged at the service.
A successful alarm also requires that the device has stored temperatures
within the set limit before the measurement can cause an alarm. In other
words, the measurements must exceed the alarm limit to generate an alarm.
The service always shows the most recently occurred alarm. Selecting the “This
device has alarmed at” link (see example in Figure 11. “This device has
alarmed at 11.12.2020 11:15”) will take you to view the moment when the alarm
occurred. The alarm must be acknowledged, after which notifications of new
alarms can be sent again.
Remove alarm
- Settings
- Measurement devices → Select the device from which you want to remove the alarm
- Set temperature alarm → Choose Remove alarm in the limit values.
Ceruus Oy, SmartKitchen smartkitchen.solutions
Technical Support :
helpdesk@SmartKitchen.com
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>