ateco IP40 Remote Indicator Lamp Instruction Manual
- June 25, 2024
- ateco
Table of Contents
Remote Indicator Lamp
Applications
The remote indicator lamp has been designed for direct connection to all
Notifer / System Sensor / Morley IAS fire detectors and also most other brands.
It provides a visual alarm indication of the room in which the detector is
installed.
Typical applications:
- All rooms permanently locked (boiler rooms, computer rooms, cupboards,…).
- Health buildings.
- Make easier the building security management (faster alarm location).
Installation
Install directly on a surface using the four holes provided or over a standard
equipment box.
Make the two-wire connection from the fire detector to the terminal block,
observing polarity.
Open jumper J1 if steady operation is required (no flashing).
Open jumper J2 to prevent the indicator to repeat the detector sampling blink
on analogue systems.
Don’t remove it, leave it inserted on one of the pins, you might need it
later.
Specifications
Dimensions (h x w x d mm) 86 x 86 x 36
Protection index IP40
Terminals screw
Maximum wire section 1,5 mm²
Operating temperature -10 to +70ºC
Storage temperature -10 to +70ºC
Voltage range (current limited) 2,5 to 30VDC
Maximum current 15mA
Note: Feed voltage must not exceed 3,5 VDC without limiting resistor.
Above this, a series resistor must be provided with no less than 40 Ohm per
Volt (usually inside the detector).