HAYWARD HP21105T Heat Pump In Ground Pool Instruction Manual
- June 24, 2024
- Hayward
Table of Contents
- HP21105T Heat Pump In Ground Pool
- Product Specifications
- Product Usage Instructions
- Safety Instructions
- Installation
- Electrical Wiring
- Operation
- Maintenance & Service
- Troubleshooting
- Replacement Parts
- Q: Can this Heat Pump be used for above-ground pools?
- Q: What should I do if I notice a decrease in heating
- Q: Is it safe to operate the Heat Pump without
HP21105T Heat Pump In Ground Pool
“`html
Product Specifications
-
Model Numbers: HP21105T, HP21205T, HP21405T, HP31105T,
HP31205T, HP31405T, HCB1105T, HCB1205T, HCB1405T, W3HP21105T,
W3HP21405T -
Manufacturer: Hayward Industries
-
Address: 1415 Vantage Park Dr., Suite 400, Charlotte, NC
28203 -
Phone: 908-355-7995
-
Website: www.hayward.com
-
Maximum Water Pressure: 0.4 MPA (50 psig)
-
Minimum Water Pressure: 0.03 MPA (5 psig)
Product Usage Instructions
Safety Instructions
Before using the Heat Pump, ensure that you have read and
understood all safety instructions in the manual. This appliance
should not be used by individuals with reduced physical, sensory,
or mental capabilities without supervision.
Installation
1. Make sure to install the Heat Pump in accordance with all
local and state codes as well as the requirements of the authority
having jurisdiction over the installation site.
2. Follow the electrical wiring instructions provided in the
manual to ensure proper installation.
Electrical Wiring
1. Ensure that the electrical wiring is done by a qualified
professional to prevent any electrical hazards.
2. Adhere to the wiring diagram provided in the manual for
correct connection.
Operation
1. Familiarize yourself with the operation of the Heat Pump by
reading the operation section of the manual.
2. Follow the recommended settings for optimal performance.
Maintenance & Service
1. Regular maintenance is essential to ensure the efficient
operation of the Heat Pump.
2. Refer to the maintenance schedule in the manual for guidance
on upkeep and service intervals.
Troubleshooting
If you encounter any issues with the Heat Pump, refer to the
troubleshooting section of the manual for common problems and
solutions.
Replacement Parts
When replacing parts of the Heat Pump, use only genuine Hayward
replacement parts to maintain product integrity and
performance.
Frequently Asked Questions (FAQ)
Q: Can this Heat Pump be used for above-ground pools?
A: The Heat Pump is designed for in-ground pool and spa
installations only. It is not recommended for above-ground
pools.
Q: What should I do if I notice a decrease in heating
efficiency?
A: If you experience a decrease in heating efficiency, check the
filters and ensure they are clean. Also, verify that the water flow
rate is adequate for proper heat exchange.
Q: Is it safe to operate the Heat Pump without
supervision?
A: Children should always be supervised when near the Heat Pump
to prevent any accidents or misuse of the appliance.
“`
51300122601 RevC
Heat Pump
For In-Ground Pool & Spa Installations
Installation and Operation Manual
Contents
Safety Instructions……………1 Before You Begin………………4 Installation……………………..8
Electrical Wiring……………..13 Operation………………………14 Maintenance & Service……20
Troubleshooting…………….23 Replacement Parts………….26
HP21105T HP21205T HP21405T
HP31105T HP31205T HP31405T
HCB1105T HCB1205T HCB1405T
W3HP21105T W3HP21405T
Hayward Industries 1415 Vantage Park Dr., Suite 400
Charlotte, NC 28203 Phone: 908-355-7995
www.hayward.com
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
IMPORTANT SAFETY INSTRUCTIONS
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience or
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the
appliance.
Not for use at altitudes above 2400 m.
Maximum/ Minimum Water Temperature – 40°C(104°F) / 5°C(40°F)
Maximum/ Minimum Water Pressure – 0.4 MPA (50 psig) / 0.03 MPA (5 psig) Means
for disconnection must be incorporated in the fixed wiring in accordance with
all applicable National and Local codes.
READ AND FOLLOW ALL INSTRUCTIONS
Basic safety precautions should always be followed, including the following: Failure to follow instructions can cause death and/or severe injury.
! This is the safety-alert symbol. When you see this symbol on your equipment
or in this manual, look for
one of the following signal words and be alert to the potential for personal
injury.
WARNING !
– Warns about hazards that could cause death and/or severe injury or major property
damage and if ignored presents a potential hazard.
CAUTION !
– Warns about hazards that could cause minor or moderate personal injury and/or prop-
erty damage and if ignored presents a potential hazard. It can also make consumers aware of actions
that are unpredictable and unsafe.
NOTICE – Indicates special instructions that are important but not related to hazards.
All Heat Pumps must be installed in accordance with all applicable National
and Local codes. In the absence of local codes, refer to the latest edition of
NSI / NFPA 70 – National Electric Code (NEC) in the United States and of CSA
C22.1 – Canadian Electric Code (CEC) in Canada. This product must be installed
and serviced by authorized personnel, qualified in pool/spa heater
installation. Improper installation and/or operation can cause death, serious
injury and/or property damage. See product rating plate for manufacturer
information.
Conformance With Codes: The heater shall be installed in accordance with all
local and state codes and with the requirements of the authority having
jurisdiction of the installing site. The heater installation must conform to
the latest edition of the installation codes.
SAVE THESE INSTRUCTIONS
1
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
! WARNING – Read, Understand, and Follow all Instructions in this manual and
on the equipment. Failure to follow instructions can cause
death, severe injury and/or serious property damage.
! WARNING – Suction Entrapment Hazard. Suction in suction outlets and/or
suction outlet covers which are, damaged, broken, cracked,
missing, or unsecured can cause death and/or severe injury due to the
following entrapment hazards:
Hair Entrapment – Hair can become entangled in suction outlet cover. Limb
Entrapment – A limb inserted into an opening of a suction outlet sump or
suction outlet cover that is damaged, broken, cracked, missing, or not
securely attached can result in a mechanical bind or swelling of the limb.
Body Suction Entrapment – A negative pressure applied to a large portion of
the body or limbs can result in an entrapment. Evisceration/ Disembowelment –
A negative pressure applied directly to the intestines through an unprotected
suction outlet sump or suction outlet cover which is, damaged, broken,
cracked, missing, or unsecured can result in evisceration/ disembowelment.
Mechanical Entrapment – There is potential for jewelry, swimsuit, hair
decorations, finger, toe or knuckle to be caught in an opening of a suction
outlet cover resulting in mechanical entrapment.
! WARNING – To Reduce the risk of Entrapment Hazards:
o When outlets are small enough to be blocked by a person, a minimum of two
functioning suction outlets per pump must be installed. Suction outlets in the
same plane (i.e. floor or wall), must be installed a minimum of three feet
(3′) [1 meter] apart, as measured from near point to near point.
o Dual suction fittings shall be placed in such locations and distances to
avoid “dual blockage” by a user. o Dual suction fittings shall not be located
on seating areas or on the backrest for such seating areas. o The maximum
system flow rate shall not exceed the flow rating of as listed on Table 2. o
Never use Pool or Spa if any suction outlet component is damaged, broken,
cracked, missing, or not attached. o Replace damaged, broken, cracked,
missing, or not securely attached suction outlet components immediately. o In
addition two or more suction outlets per pump installed in accordance with
latest ASME, APSP Standards and CPSC guidelines, follow
all National, State, and Local codes applicable. o Installation of a vacuum
release or vent system, which relieves entrapping suction, is recommended.
! WARNING – Failure to remove pressure test plugs and/or plugs used in
winterization of the pool/spa from the suction outlets can result in
an increase potential for suction entrapment as described above.
! WARNING – Failure to keep suction outlet components clear of debris, such as
leaves, dirt, hair, paper and other material can result in an
increase potential for suction entrapment as described above.
! WARNING – Suction outlet components have a finite life, the cover/grate
should be inspected frequently and replaced at least every seven
years or if found to be damaged, broken, cracked, missing, or not securely
attached.
! CAUTION – Components such as the filtration system, pumps and heater must be
positioned so as to prevent their being used as means of
access to the pool by young children. To reduce risk of injury, do not permit
children to use or climb on this product. Closely supervise children at all
times. Components such as the filtration system, pumps, and heaters must be
positioned to prevent children from using them as a means of access to the
pool.
! WARNING – Hazardous Pressure. Pool and spa water heating and circulation
systems operate under hazardous pressure during start
up, normal operation, and after pump shut off. Stand clear of circulation
system equipment during pump start up. Failure to follow safety and operation
instructions could result in violent separation of the pump housing and cover,
and/or filter housing and clamp due to pressure in the system, which could
cause death, severe personal injury and/or property damage, Before servicing
pool and spa water circulation system, all system and pump controls must be in
off position and filter manual air relief valve must be in open position.
Before starting system pump, all system valves must be set in a position to
allow system water to return back to the pool. Do not change filter control
valve position while system pump is running. Before starting system pump,
fully open filter manual air relief valve. Do not close filter manual air
relief valve until a steady stream of water (not air or air and water) is
discharged.
! WARNING – Separation Hazard. Failure to follow safety and operation
instructions could result in violent separation of pump and/or filter
components. Strainer cover must be properly secured to pump housing with
strainer cover lock ring. Before servicing pool and spa circulation system,
filters manual air relief valve must be in open position. Do not operate pool
and spa circulation system if a system component is not assembled properly,
damaged, or missing. Do not operate pool and spa circulation system unless
filter manual air relief valve body is in locked position in filter upper
body. Never operate or test the circulation system at more than 50 PSI. Do not
purge the system with compressed air. Purging the system with compressed air
can cause components to explode, with risk of severe injury or death to anyone
nearby. Use only a low pressure (below 5 PSI), high volume blower when air
purging the pump, filter, or piping.
! WARNING – Risk of Electric Shock. All electrical wiring MUST be in
conformance with applicable local codes, regulations, and the
National Electric Code (NEC). Hazardous voltage can shock, burn, and cause
death or serious property damage. To reduce the risk of electric shock, do NOT
use an extension cord to connect unit to electric supply. Provide a properly
located electrical receptacle. Before working on any electrical equipment,
turn off power supply to the equipment. To reduce the risk of electric shock
replace damaged wiring immediately. Locate conduit to prevent abuse from lawn
mowers, hedge trimmers and other equipment. Do NOT ground to a gas supply
line.
2
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
! WARNING – Risk of Electric Shock. Failure to ground all electrical equipment
can cause serious or fatal electrical shock hazard. Electrical
ground all electrical equipment before connecting to electrical power supply.
! WARNING – Risk of Electric Shock. Failure to bond all electrical equipment
to pool structure will increase risk for electrocution and could
result in injury or death. To reduce the risk of electric shock, see
installation instructions and consult a professional electrician on how to
bond all electrical equipment. Also, contact a licensed electrician for
information on local electrical codes for bonding requirements. Means for
contact separation on all poles must be incorporated in the fixed wiring in
accordance with NEC.
Notes to electrician: Use a solid copper conductor, size 8 or larger. Run a
continuous wire from external bonding lug to reinforcing rod or mesh. Connect
a No. 8 AWG (8.4 mm2) [No. 6 AWG (13.3 mm2) for Canada] solid copper bonding
wire to the pressure wire connector provided on the electrical equipment and
to all metal parts of swimming pool, spa, or hot tub, and metal piping (except
gas piping), and conduit within 5 ft. (1.5 m) of inside walls of swimming
pool, spa, or hot tub. IMPORTANT – Reference NEC codes for all wiring
standards including, but not limited to, grounding, bonding and other general
wiring procedures.
! CAUTION – These heaters are intended for use with permanently-installed
pools and may be used with hot tubs and spas if so marked.
Do not use with storable pools. A permanently-installed pool is constructed in
or on the ground or in a building such that it cannot be readily disassembled
for storage. A storable pool is constructed so that it is capable of being
readily disassembled for storage and reassembled to its original integrity.
! WARNING – Risk of Hyperthermia. To avoid hyperthermia the following “Safety
Rules for Hot Tubs” are recommended by the U.S. Con-
sumer Product Safety Commission. 1. Spa or hot tub water temperatures should
never exceed 104°F [40°C]. A temperature of 100°F [38°C] is considered safe
for a healthy
adult. Special caution is suggested for young children. Prolonged immersion in
hot water can induce hyperthermia. 2. Drinking of alcoholic beverages before
or during spa or hot tub use can cause drowsiness, which could lead to
unconsciousness and
subsequently result in drowning. 3. Pregnant women beware! Soaking in water
above 100°F [38°C] can cause fetal damage during the first three months of
pregnancy
(resulting in the birth of a brain-damaged or deformed child). Pregnant women
should adhere to the 100°F [38°C] maximum rule. 4. Before entering the spa or
hot tub, users should check the water temperature with an accurate
thermometer; spa or hot tub thermostats
may err in regulating water temperatures by as much as 4°F (2.2°C). 5. Persons
taking medications, which induce drowsiness, such as tranquilizers,
antihistamines or anticoagulants, should not use spas or hot
tubs. 6. If the pool/spa is used for therapy, it should be done with the
advice of a physician. Always stir pool/ spa water before entering the pool/
spa to mix in any hot surface layer of water that might exceed healthful
temperature limits and cause injury. Do not tamper with controls, because
scalding can result if safety controls are not in proper working order. 7.
Persons with a medical history of heart disease, circulatory problems,
diabetes or blood pressure problems should obtain a physician’s advice before
using spas or hot tubs. 8. Hyperthermia occurs when the internal temperature
of the body reaches a level several degrees above normal body temperature of
98.6°F [37°C]. The symptoms of Hyperthermia include: drowsiness, lethargy,
dizziness, fainting, and an increase in the internal temperature of the body.
The effects of Hyperthermia include: · Unawareness of impending danger. ·
Failure to perceive heat. · Failure to recognize the need to leave the spa. ·
Physical inability to exit the spa. · Fetal damage in pregnant women. ·
Unconsciousness resulting in danger of drowning.
3
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Before You Begin
What to Expect When Operating Your Pool Heater
INSTALLATION – Verify that the installation was done according to owner’s
manual instructions.
FIGURES
AB
Out In Heater
OPEN
Out In Heater
CLOSED
Water diverted to pool
Water goes to heater
INSTALLATION
When heating is required for less than a week, you MUST leave the bypass valve
closed (Figure B) to let the water circulate in the unit. If the heat
exchanger is deprived of water circulation for more than 72 hours, high
chlorine gas could cause excessive corrosion.
FIRST TIME OR SPRING STARTUP – Route all pool water piping, but do not connect
to heater.
Verify and Balance Pool Chemicals
NO Pool Chemicals OK?
YES Connect Water Piping to Heater
Set Required Water Temperature on Touch Pad
IMPORTANT FOR THE HEALTH OF YOUR FAMILY AND FOR YOUR POOL HEATER
– Verify Chlorine or Bromine level every 2-3 days. – Verify pH level once a
week. – Verify Alkalinity level every 3-4 weeks (more often if you own an
automatic Chlorine or Bromine feeder).
NOTE: Above tests can easily be done by yourself with a do-it-yourself kit.
– Verify Hardness and Total Dissolved Solids (TDS) once a month.
NOTE: Above test must be done by your dealer.
YES
Will Heating Be Needed Within a Week’s Time?
NO Open Bypass (Figure A)
and Drain the Heater
Heating Needed?
YES
NO NO
Pool Closing Time?
YES
Close Pool Protect Heater by Covering it
4
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
FIGURE 1: Name of Heat Pump Components
Fan Top Fan Motor & Blades
Evaporator Control Box Front Panel
FIGURE 2: Heat Pump Dimensions
33.6″
Top 30.5″
Compressor
(“44″)
Condenser
Front
Features
· Titanium heat exchanger for harshest water conditions · Quiet/Reliable R410A
Scroll compressors · Digital Electronic Control with
· Easy to read display · Dual thermostats for independent pool and spa
temperature control · Display of diagnostic codes · UV resistant cabinet for
long life · Defrost function to manage evaporator coil frosting for low
ambient temperature operation · High (590PSI) and low (50PSI) refrigerant
pressure switches monitoring extreme operation · Compressor sound blanket ·
Corrosion resistant evaporator
5
Bottom Rear (Water Connections)
2.4″ 12.5″
10.3″
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
MODEL NUMBER RATED VOLTAGE (V) MCA (A) REC. BREAKER SIZE (A) MOP (A)
COMPRESSOR RLA (A) COMPRESSOR LRA (A) FAN MOTOR RLA (A) FAM MOTOR HP (HP)
SHORT CIRCUIT CURRENT (Ka) RMS SYMM. VOLTAGE (V) RATED POWER INPUT (W)
MOISTURE RESISTANCE REFRIGERANT TYPE REFR. SAFETY GROUP REFRIGERANT CHARGE
MAX ALLOWABLE REFR PRESSURE HIGH SIDE
LOW SIDE
MIN WATER FLOW
MAX WATER FLOW
REC. WATER FLOW
MAX WATER INLET TEMP
WATER OPERATING TEMP
AIR OPERATING TEMP
WEIGHT
SHIPPING WEIGHT
SHIPPING DIMENSIONS (L x W x H) WATER CONNECTION DIAMETER
WATER INLET TO OUTLET DISTANCE 80A-80RH-80W CAPACITY
COP 80A-63RH-80W Capacity
COP 50A-63RH-80W Capacity
COP APPROVAL FOR INSTALLATION
HP21105T 38.9 40 65 29.2 185 2.4 1/3 5600
4lb 10oz 2.1 kg
50 GPM 190 LPM
230 LB 104 KG 278 LB 126 KG
110,000 100,000 75,000
W3HP21105T
38.9 40 65 29.2
HCB1105T
38.9 40 65 29.2
TABLE 2: SPECIFICATIONS
HP21205T W3HP21205T HCB1205T HP21405T
230V~ 60Hz 1Ph
38.9
38.9
38.9
42.5
40
40
40
50
65
65
65
70
29.2
29.2
29.2
32.1
185 2.4 1/3 5600
4lb 10oz 2.1 kg
50 GPM 190 LPM
230 LB 104 KG 278 LB 126 KG
110,000 100,000 75,000
185
185
2.4
2.4
1/3
1/3
5600
6100
4lb 10oz 2.1 kg
4lb 14oz 2.24 kg
50 GPM 190 LPM
50 GPM 190 LPM
230 LB 104 KG 278 LB 126 KG
233 106 KG 281 LB 127 KG
110,000 100,000 75,000
120,000 110,000 75,000
185 2.4 1/3 6100
4lb 14oz 2.24 kg
50 GPM 190 LPM
233 LB 106 KG 281 LB 127 KG
120,000 110,000 75,000
185
185
2.4
2.4
1/3
1/3
5
240
6100
8300
IPX4
R-410A
A1
4lb 14oz
4lb 14oz
2.24 kg
2.21 kg
575 PSIG
3.96 MPa
340 PSIG
2.34 MPa
236 PSIG
1.63 MPa
30 GPM
114 LPM
75 GPM
284 LPM
50 GPM
60 GPM
190 LPM 230 LPM
104 °F
40 °C
40 – 104 °F
4 – 40 °C
40-115 °F
4 – 46 °C
233 LB
233 LB
106 KG
106 KG
281 LB
281 LB
127 KG
127 KG
36.5 x 31 x 49 in
93 x 80 x 125 cm
2 in
5 cm
10.25 in
26 cm
120,000
138,000
5.7
110,000
128,000
5.5
75,000
82,000
4
Outdoor Use Only
W3HP21405T HCB1405T
42.5
42.5
50
50
70
70
32.1
32.1
185
185
2.4
2.4
1/3
1/3
8300
8300
4lb 14oz 2.21 kg
4lb 14oz 2.21 kg
60 GPM 230 LPM
60 GPM 230 LPM
233 LB 106 KG 281 LB 127 KG
233 LB 106 KG 281 LB 127 KG
138,000 128,000 82,000
138,000 128,000 82,000
HP31105T HP31205T
38.9
38.9
40
40
65
65
29.2
29.2
185
185
2.4
2.4
1/3
1/3
5600
6100
5lb 0oz 2.27 kg
5lb 4oz 2.27 kg
50 GPM 190 LPM
50 GPM 190 LPM
237 LB 108 KG 285 LB 129 KG
240 LB 109 KG 288 LB 131 KG
110,000 120,000
100,000 110,000
75,000
75,000
HP31405T 42.525 50 70 32.1 185 2.4 1/3 8300
5lb 4oz 2.27 kg
60 GPM 230 LPM
240 LB 109 KG 288 LB 131 KG
135,000 125,000 82,000
6 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
FIGURE 4: 240 VAC / 60 Hz Singe Phase Wiring Diagram
51300122901 REV A 230 VAC, 1 ~, 60 Hz
Field Wiring 230 VAC 230 VAC 24 VAC
WTS Water
Pressostat d’eau Interruptor
Temperature
de presión de
Sensor
agua
DS Defrost
Capteur de
Sensor de
Sensor
dégivrage
descongelaci
ón
HPS High
Pressostat
Interruptor
Pressure haute pression de alta
Switch
presión
LPS Low Pressure Pressostat basse Interruptor
Switch
pression
de baja
presión
FLO Flow Switch Interrupteur de Interruptor
débit
de flujo
RV Reversing Valve
Vanne d’inversion
Válvula de inversión
C1 Capacitor, Condensateur, Condensador, Compressor compresseur compresor
C2 Capacitor, Condensateur, Condensador,
Fan
ventilateur
ventilador
bo Bypass HE Operation,
Heating bo Bypass COL Operation,
Cooling
BK BLACK BL BLUE O ORANGE R RED V VIOLET W WHITE Y YELLOW
Fonctionnement en dérivation, chauffage Fonctionnement en dérivation, refroidissement
Operación de derivación, calefacción Operación de derivación, refrigeración
NOIR BLEU ORANGE ROUGE VIOLET BLANC JAUNE
NEGRO AZUL NARANJA ROJO VIOLETA BLANCO AMARILLO
FAN MOTOR
R BK
BR
C2 BR / W
BK FAN RELAY
C COMPRESSOR S
R
BK LT BL R
C1 BL
L1 L2
COMPRESSOR CONTACTOR
T1 T2
BK O
230VAC
TRANSFORMER
24VAC Y
FUSE
(HEAT/ COOL ONLY) bo COL J7
SPARE J32
W
CONTROL BOARD
GND J36
WTS DS HPS HPS LPS LPS FLO FLO CMPCMPFAN FAN REV REV 24V 24V bo HE
J6
J1
J2 J21 J3 J22 J5 J23 J12 J13 J16 J17 J26 J25 J19 J18 J7
BK BK BK BK BK BK BL BL V V Y Y W O
// //
or or
BL BL R R
WW
WW
Y BL CONTROL BOX
5K
5K
R V HPS LPS FLO
7 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Installation
Read through instructions thoroughly before installation. Installation instructions are intended for use by a qualified technician, specifically trained and experienced in the installation of this type of equipment. Some states or provinces require that the installer be licensed. If this is the case in the state or province where the heater is located, the contractor must be properly certified.
Sprinkler Heads: Be sure that there are no sprinkler heads near the heater that will spray on or into the unit. Many sprinkler systems are connected to a well system whose water is high in minerals, Sulphur, salt and other aggressive contaminates that can cause corrosion and shorten life.
NOTICE: Make sure that sprinklers are placed at a sufficient distance away so that normal wind will not carry the mist to the heat pump.
NOTICE: If located in an oceanfront area, the heat pump should be placed out of direct spray of sand and salt that will clog, damage, and corrode the unit. You may also consider protecting the unit by creating a physical barrier outside of the minimum clearances between the unit and the prevailing beachfront wind.
The Use Of A Pool Cover Is Recommended. A pool cover reduces heat loss, conserves chemicals, lowers the load on filter systems and may provide a valuable safety feature.
Materials Needed For Installation
The following plumbing items are needed.
· 2 inch Isolation Valves
qty (3)
· 2 inch Check Valve
qty (1)
· 2 x 2 x 2 PVC Tee’s
qty (2)
For proper installation, appropriate electrical supplies will be needed along with extra hardware items that may be required for anchoring.
NOTICE: Pipe fittings such as reducers, tees, and elbows cause pressure to drop as water flows through them. Plan the plumbing layout carefully, using as few fittings as possible to connect your heat pump. See pad plumbing layout in the Water Piping section for further direction.
Locating The Heater
The installation location of the heat pump is very important for its efficient
operation. The heat pump will perform more efficiently when placed in direct
sunlight with ample air intake and the avoidance of air re-circulation. Locate
the pool heater in an area where its condensation will not result in damage to
the area adjacent to the heater or a nearby structure.
NOTICE: DO NOT install the heat pump in a fully enclosed space (i.e. garage, shed etc.).
All criteria given in the following sections reflect minimum clearances. However, each installation must also be evaluated on prevailing local conditions such as proximity and height of walls and public access areas.
Outdoor Installation And Service Clearances: The heater must be installed outdoors such that the installation and service clearances shown in Table 3 and Figure 6 are maintained. Additional installation requirements are as listed:
1. Level surface for proper draining. 2. Suitable electrical supply line. See
rating plate on the heat pump units for electrical specifications. A junction
box is not needed at the heat pump; connec-
tions are made inside the heat pump electrical compartment. Minimum wire size
to be selected per NEC based on unit MCA. 3. Electric disconnect switch that
will interrupt all power to the unit. This switch MUST be within line of sight
to the heat pump. 4. Do not install in a location where growing shrubs may in
time obstruct a heater’s air flow areas (sides or top). 5. Do not install this
appliance under an overhang less than 72in from the top of the appliance. The
area under the overhang must be open on (3) sides. 6. Do not install the
heater where water spray from ground level can contact the heater. The water
could damage coil or reach the controls causing electrical
damage. 7. Do not install under a deck. 8. Do not install within 12″ of any
outdoor HVAC equipment. 9. Do not install where water may run-off a roof into
the heater. A gutter may be needed to protect the heater.
8 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
! CAUTION: Make sure the heat pump is not located where large amounts of water
may run-off from the roof into the unit. Sharp sloping roofs without
gutters will allow massive amounts of rainwater, mixed with debris from the
roof to be forced through the unit (see diagram).
1. A minimum of 12″ [31 cm] of clearance on all sides. 2. If the heat pump is
to be installed under a cover or vertical overhang, the
unit must have a minimum of 72″. [183 cm] of clearance from the top of the
heat pump to the bottom of the cover or overhang. 3. Install the heat pump a
minimum of 60″. [1.5 m] from the inside wall of the pool, spa, solid fence, or
permanent barrier. (not shown in Figure 6) Canadian installations require a
minimum of 120″. [3 m] of clearance from pool water.
FIGURE 6: Outdoor Minimum Clearances
TABLE 3: Installation Required Clearances
Heater Panel
Outdoor Clearance
Top
Unobstructed
Front (control)
24 – 36″
Rest of Perimeter*
12″
Overhang
25º Maximum Roof Pitch
Without Gutter
Open
Air Flow Out
12″ (31 cm)
Front Panel Service Access
24″ to 36″ (61 to 91 cm)
Evaporator Coils
Air Flow In
12″ (31 cm)
72″ (183 cm)
12″ (31 cm)
NOTE: The clearances shown above are for best practice and we encourage the
use of the best practice clearances when the space is available. Exceptions
can be made where the size of the lot or the configuration of fences, walls or
other associated structures do not allow for the best practice clearances.
Testing has shown our heat pumps can be installed as close as 12″ (coil sides)
from a restriction (Wall, fence, etc.). Equipment Pad: Place the heat pump on
a level surface such as concrete or a fabricated slab (pad). This allows
proper drainage of condensation and rainwater from the base of the unit. If
possible, the pad should be placed at the same level or slightly higher than
the filter system equipment pad. Flooring: This heater may be installed on
either non-combustible flooring or combustible flooring that does not reduce
the bottom clearance of the heater. UltraliteTM or equivalent concrete-over-
foam HVAC pads are acceptable. Drainage And Condensation: Condensation will be
produced by the evaporator coil when the unit is running and drain at a steady
rate, usually three to five gallons per hour, depending upon ambient air
temperature and humidity. The more humid the conditions, the more condensation
will be produced.
9
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Anchoring: The heater is equipped for installation of anchoring screws when required by local codes. Follow all relevant Local, State and National requirements regarding wind load anchoring. When anchoring is required to secure the heat pump to concrete pad, use the specified hardware shown in the Figure 7. To complete the installation use the following:
· Anchor Clamps (Included) · Concrete tapping screws (Not Included) · Fender washers (Not Included) · ·
qty (8), spaced at least 21/2″ apart qty (8), Tapcons® stainless steel, size to be ¼” diameter with a minimum length of 11/2″ qty (8), stainless steel, size to be 11/2″
FIGURE 7: Equipment Pad and Anchoring
See Anchor Clamp Details
At Right & Above
Min. Edge Distance
3-1/2″ Thick (Min.)
3000 PSI Fibermesh
3″
Conc. Pad by Others
14 GA. GALV. STL Anchor Clamp (4) Provided by Manuf. Into Heater Base
(1) 1/4″x1-1/2″ S.S. Concrete Screw w/ S.S. Fender Washer 4 EA. Anchor Clamp
(4 Total)
Water Piping
General: The heater is for use with pool and spa/hot tub water furnished by
municipal water distribution systems only. Do not use the heater for mineral
water, seawater (PPM>5000), or other non-potable waters. These heat pumps are
designed for nominal water flows through the condenser. A minimum flow of 30
gpm is required to ensure sufficient heat removal from the condenser, thus
avoiding overheating the unit. The minimum flow rate is to be calculated or
measured with the in-floor cleaning system in use, if the pool is so equipped,
as well as any other jets or other demands on the water flow. Flow rates above
75 gpm will create excessive pressure drop through the condenser and require
unnecessarily high pumping energy. Bypass valve setting may be accomplished by
temporarily installing a flow meter on the outlet line of the heater. Then
adjust the manual bypass valve until the flowrate through the heater is within
the flow rate range specified. Once the manual bypass valve is set, note the
position and remove the valve handle to prevent accidental adjustment. Failure
to install an External Bypass Assembly with a flow rate of 75 GPM can cause
damage . Do not install any restriction in the water pipe between the heater
outlet and the pool with the exception of; three-way switching valve, in-line
chlorinator and/or chlorinator check valve as shown in Figure 8.
10 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
FIGURE 8: General Pad Plumbing Layout
Filter
Pool Heater
Pool Pump
Manual Isolation Valves
Check Valve
Manual Bypass Valve
Chemical Loop
Chemical Feeder
From Pool or Spa
To Pool or Spa
! CAUTION: Improperly adjusted manual bypass valves will result in damage to
the heater if the flow rates are not maintained under all operating condi-
tions as specified in listed SPECIFICATION.
! CAUTION: The heat pump must be protected from back siphoning of water. If
there is any chance of back siphoning, provide a check valve between
the pool and the filter pump inlet. Failure to follow the instructions may
result in property damage due to flooding.
! CAUTION: Automatic erosion type chlorinators, if used, must be installed
downstream (between the heat pump and the pool) of the heat pump, and a
check valve (or Hartford Loop) installed in a manner that will not allow the
raw chlorine to drain back to the heat pump when the water pump is off.
Failure to follow the instructions may result in property damage.
! CAUTION: Do not pour chemicals directly into the skimmer. It could result in
damage to your system and heat pump. Arrangement of pool system
components other than as illustrated in Figure 8 can affect the operation of
the heat pump’s water pressure switch. Location of the heat pump above or
below the elevation of the pool water surface can also affect operation of the
switch. In general, the pressure switch can be adjusted to accommodate this
effect if the heat pump water connections are no more than six (6) feet [1,8
m] below the pool water surface or no more than fifteen (15) feet [4,6 m]
above it. See instructions for pressure switch adjustment in the START-UP
section of this manual. If the heat pump is installed outside of this range,
an external pressure switch may need to be installed in the plumbing upstream
of the heat pump.
NOTICE: Be advised, that when pool equipment is located below the pool surface, a leak at this lower level can result in large-scale water loss or flooding. Manufacturer is not responsible for water loss or damage it causes.
Unions: The heater is equipped with two detachable union connectors, (2 union nuts and 2 gaskets) included with the heat pump. These fittings must be installed on the heat pump water inlet and outlet to facilitate servicing and winterizing the unit. (See Figure 9). Heat sinks, heat tapes, firemen switches, and check valves are not required on the heater. However, if there is any chance of “back-siphoning” of hot water when the pump stops running, it is suggested that a check valve be used on the heater outlet pipe down stream of bypass system.
FIGURE 9: Included Union Connectors
Rear of Unit
Gasket Union Connector Union Nut
Gasket
Union Connector
Union Nut
11 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Above Pool Installation
The heater is installed less than three (3) feet above the surface of the
pool/ spa water, install eyeball fittings or directional flow fittings on the
end of the return water line to the pool/spa to create adequate back pressure
at the heater to operate the pressure safety switch when the pump is running.
If the heater is installed more than three (3) feet above the surface of the
pool/spa water, install a loop as shown in Figure 10 to prevent drainage of
water in the heater during a filter change. For installation above or below
the pool/spa surface, refer to START UP section for proper pressure switch
setup.
FIGURE 10: Heater Installation Above Pool
Higher than Top of Heater
Heater
Water Level
Typical Pool Arrangement
Figure 11 illustrates a typical pool piping diagram and layout for the pool equipment. Also shown is implementation of an optional gas or solar heater system for additional capacity. Other pool heaters, such as gas or solar- powered devices must be installed in a parallel circuit and operated independently (only one at a time) for your warranty to be valid.
FIGURE 11: Typical Plumbing to Pool
NOTICE: Because of the intense heat that can be generated by gas and
solar units, isolating it with a shut-off valve and a check valve when gas
F
or solar heater is in operation protects the heat pump. Failure to follow the
P
D
instructions may result in property damage.
V
S
Notes: 1. Isolate the heat pump from hot water flow of heating devices such as gas
V
or solar heater.
H
Gas
2. Install bypass loop for heat pump unit.
or
Pool
Solar
C
R
Multiple Heater System
FIGURE 12: Multiple Heater System
Figure 12 illustrates a multiple heater installation for very large pools with and
without a manual bypass valve.
F
H
1. Maintain 12″ [31 cm] clearance between the units, 12 in. [31 cm] around
D
perimeter, and at least 6 ft [1,8 m] over them. Refer to Locating the Heater section for more details.
P
V
S
2. Install bypass loops for each unit.
H
3. Install union style fittings from the heat pump CONSUMER KIT adjacent to
the unit to facilitate easy service procedures
Pool (Parallel)
H
C
R
12 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Automatic Chlorinators and Chemical Feeders
If used, a chlorinator must be installed downstream from the heater in the
pool return line and at a lower elevation than the heater as shown in Figure
11. Install a separate positive seal corrosion resistant check valve between
the heater outlet and the chlorinator to prevent highly concentrated sanitizer
from back siphoning into the heater. Back siphoning may occur when the pump is
shut off and a pressure differential is created.
Electrical Wiring
General
An external supply of power is required to operate the pool heater system.
Review Specifications for this heater in the Before You Begin section to
properly size field power connections. All wiring connections to the heater
must be made in accordance with the latest edition of the National Electrical
Code ANSI/NFPA 70, unless local code requirements specify otherwise. In
Canada, follow CSA C22.1 Canadian Electrical Code, Part 1. The heater must be
electrically grounded and bonded in accordance with local codes or, in the
absence of local codes, with National Electrical Code, ANSI/NFPA 70. Wiring
connections must be made as shown in the wiring diagram found inside the
heater cabinet, and a copy is provided for convenience in the Before You Begin
section at the beginning of the manual. The heater must also have independent
ground and bond connections. There is a ground lug inside the control box
adjacent to the power connections and a bonding lug on the side of the heater.
Use a solid copper conductor, size 8 or larger. Run a continuous wire from
external bonding lug to reinforcing rod or mesh. Connect a No. 8 AWG (8.4 mm2)
solid copper bonding wire to the grounding lug provided on the heat pump and
to all metal parts of swimming pool or spa, and to all electrical equipment,
metal piping (except gas piping), and conduit within 5 ft. (1.5 m) of inside
walls of swimming pool or spa. IMPORTANT Reference NEC codes for all wiring
standards including, but not limited to, grounding, bonding and other general
wiring procedures.
! WARNING: Risk of Electric Shock Review all safety information provided in
the Before You Begin section of this manual prior to servicing. Always
disconnect power circuit before connecting the heat pump, or working on the
heat pump. This equipment contains wiring that carries high voltage. Contact
with these wires could result in death or personal injury and/or may also
cause property damage.
! WARNING: All electrical wiring MUST be in conformance with all applicable
local codes, regulations and the National Electric Code (NEC), in particular
NEC Article 680: Swimming Pools, Fountains & Similar Installations and Article
440: Air-Conditioning & Refrigeration Equipment.
NOTICE: If voltage drops below 208V, damage may occur. Take proper steps to
ensure correct voltage at the heat pump during operation.
Electrical Connections
Turn OFF source power to the heat pump before working on electrical
connections. Any unused openings must be plugged and all wiring secured for
proper strain relief. The power connections are to be made on the contactor
terminals located in the control box (see Figure 13 Power Connections). Plug
any unused openings with the supplied caps.
FIGURE 13: Power Connections
13 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Remote Control Connection
The heater is equipped for remote control via independent 2-wire connections.
Heat Only models connect the remote relay to terminal J7. Heat/Cool models
connect the heating remote relay to terminal J7 and cooling remote relay to
terminal J28. (See Figure 14 for remote on/off connections).
1. Connect the Heating remote relay to the J7 connection and the Cooling
remote relay to J28 connection L(if applicable) on the control board.
2. Turn the unit on. Press and hold both the “MENU” and the “+” buttons until
“bo” appears. This enables the bypass operation.
3. In bypass operation, when the relays are open the heater will be off. When
the heating relay (J7) is closed, the heater will operate in heating. When the
cooling relay (J28) is closed, the heater will operate in cooling. The
temperature control is done remotely through the remote relays.
4. The heater will shut off when both relays are open or the inlet
temperature exceeds 104°F.
5. If both relays are closed, the heater will operate in heating mode.
Note: The unit must be “On” to operate in bypass mode. In bypass operation
“bo” mode, the heater will only respond to the remote relay closure. To return
to local set point control at the heater, press and hold both the “MENU” and
the “+” buttons until “n” appears. This enables the normal operation mode and
the heater will respond to the local set point.
Note: All remote wiring must be run in a conduit separate from incoming power.
Use 22 AWG wire for runs less than 30 feet. Use 20 AWG wire for runs over 30
feet. The maximum allowable run is 200 feet.
FIGURE 14: Remote On/Off Control
Cooling Remote Relay
bo COL
J28
J32 J31 J34 J33
FID1
GND J36 J35
C13
C15 R5
FID2 D10
24 VAC
WTS DS
FAN FAN HGD HGD HPS HPS LPS LPS FLO FLO CMP CMP REL REL REV REV 24 VAC
bo HE
J27
J6
J1
J2 J21 J3 J22 J5 J23 J12 J13 J16 J17 J26 J25 J19 J18
J7
Operation
Heating Remote Relay
General
After completing the installation connections to the pool heater, follow the
procedures outlined below to ensure that the pool heater is functioning
properly. Before proceeding, MAKE CERTAIN there are no water leaks in any
plumbing connections or piping and water flow is within the proper flow rate
ranges. The heater is equipped with a control system that automatically
monitors the water temperature set points and safety devices. As water
conditioning is needed, it turns on the compressor to start the appropriate
transfer of heat to the water. Figure 15 provides a summary of heater
components and their locations in the system. Check that the pump is operating
and the system is filled with water prior to starting the heater.
14 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
FIGURE 15: Location of Components (Heating Operation Flow Shown)
Heat From
Air
C
TXV
Reversing
A
Valve
E
Hot
Water
Out
D
Cold
Water
In
B
Air Coil (Evaporator)
Compressor
Water Heat Exchanger (Condenser)
The heat pump takes heat from the environment and uses it to heat the pool water. During heat pump operation, high temperature, high-pressure sub cooled liquid Refrigerant (A) is throttled by Metering Device (TXV) and turned into low temperature, low-pressure saturated liquid (B). The two-phase Refrigerant flows through the Air Coil (Evaporator), where the liquid refrigerant evaporates into vapor by absorbing heat from the surrounding air. At the outlet of the Air Coil (Evaporator) it becomes a low temperature, low pressure superheated vapor (C). The Compressor receives this flow at the suction line (D), and compresses it into a high temperature, high pressure superheated vapor, which is discharged from the Compressor (E) and flows into the Water Heat Exchanger (Condenser). The heat carried by the flow is then released to the pool water. At the same time, the high temperature, high-pressure superheated vapor is then condensed back to high-pressure sub cooled liquid (A), which completes the cycle. The water, which is being forced through the Water Heat Exchanger (Condenser) by the pool pump, is thus heated as it passes through.
Heat Pump Protection Features These heat pumps are equipped with safeguards that will stop heater operation to protect the unit in case of the following events:
· Excessively high refrigerant pressure · Excessively high water temperature · Loss of refrigerant · Fan Motor Failure · Evaporator Freeze-up · Low Ambient Temperature
Control Setup Heat Only Models This pool heater is equipped with a digital thermostat which allows the user to select the desired water temperature. The heater will then function automatically to maintain the desired temperature. The heater has 3 modes of operation:
1. SPA – in this mode, the heater will automatically function to maintain the
water temperature setting for SPA mode. 2. POOL – in this mode, the heater
will automatically function to maintain the water temperature setting for POOL
mode. 3. REMOTE OPERATION – In this mode the heater will respond to a remote
call for heat or to control unit operation mode. Use the set button in Figure
16a to
select POOL/SPA modes. The arrows will indicate which mode is currently
active.
Control Setup Heat/Cool Models This pool heater is equipped with a digital thermostat which allows the user to select the desired water temperature. The heater will then function automatically to maintain the desired temperature. The heater has 4 modes of operation:
1. HEAT – in this mode, the heater will automatically function to maintain
the water temperature setting for HEAT mode. 2. COOL – in this mode, the
heater will automatically function to maintain the water temperature setting
for COOL mode 3. AUTO – in this mode, the heater will automatically function
to maintain the water temperature setting for AUTO. It will operate in HEAT or
COOL mode as
required. 4. REMOTE OPERATION – In this mode the heater will respond to a
remote call for HEAT or COOL mode. Use the set button in Figure 16b to select
HEAT/
COOL/AUTO modes. The arrows will indicate which mode is currently active.
15
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
FIGURE 16a: Heat Only User Interface Keypad
Display Window: When powered is supplied to the unit, the display will either
show sensor temperature (in degrees F or C) or the diagnostic code.
Menu Button: Activates the On/Off, Pool, Spa, or Temperature function of the
controller. Mode is confirmed with Heating Mode Indicator “On/OFF”, “POL”,
“SPA”, or “F_C”.
888°C °F
x1,
x2,
x3,
ºF/ºC
x4,
Pool Mode
Run Indicators: Confirms the compressor ( ) or fan ( ) operation and the
thermostat is controlling a demand for heat.
Spa Mode
Plus “+” Button: Raises the heater’s set point temperature or changes
parameters.
Minus “-” Button: Lowers the heater’s set point temperature or changes
parameters.
FIGURE 17a: Heat Only Function Selection
Push the “MENU” button to display the current selection: “On/OFF”, “POL”,
“SPA”, or “F_C” will appear. When in “On/OFF” mode, push the “-” button to
turn the unit off and the “+” button to turn the unit on.
Display
OFF
On
POL
Push the “MENU” button (x2) until “POL” is displayed. Then use the “-” and “+”
buttons to set the Pool temperature set point as shown in display. Setting
temperature will place the heater in POOL mode.
SPA
Push the “MENU” button (x3) until “SPA” is displayed. Then use the “-” and “+”
buttons to set the Spa temperature set point as shown in display. Setting
temperature will place the heater in SPA mode.
F_ C
Push the “SET” button (x4) until “F_C” is displayed. Then use the “-” and “+”
buttons to select °F or °C display as shown.
16
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Heat Only Operation
Automatic Reset Time: The heater will automatically reset when an error
condition is corrected and resume operation.
Temperature Adjustment: This control allows the user to have 2 individual pre-
set temperature settings, “SPA” and “Pool”. To adjust the temperature while in
SPA or POOL mode, use the (Plus) and (Minus) buttons. When the numeric display
adjustment is complete, the control will return to displaying the actual
measured water temperature. The temperature settings for both SPA and POOL
modes are initially set at the factory to 65°F. The minimum allowed settings
for SPA and POOL modes is 50°F. The maximum allowed settings for heating modes
is 104°F.
Dual Pool And Spa Set Points: The unit can keep two temperature settings in
memory: one for pool mode (max: 95°F/35°C), and the other for spa mode (max:
104°F/40°C). The heater will operate in the mode that temperature was last
selected (i.e. if you push either Plus or Minus in “Pool” mode, the heater
will operate in “Pool” mode). Once the heating mode has been programmed, it
will be displayed for five seconds, and will then return to the actual pool
water temperature. The arrows on the right side of the display indicate the
chosen heating mode.
Fahrenheit Versus Celsius: The control will display temperatures in either
degrees Fahrenheit or Celsius. To change the temperature display, Press the
MENU key until you see F_C and by pressing one of the arrow keys, you can
switch to °F or °C. Once the temperature unit has been programmed, it will be
displayed for five seconds, and will then return to the actual pool water
temperature in the mode that you have chosen.
Defrost Function: The Defrost function is provided to prevent the evaporator
coil from freezing when the outside air temperature is near 50°F (10°C). The
temperature at which this function will operate is not exact and each unit
will vary depending upon conditions surrounding the heat pump, clearance
around the heat pump and heat pump maintenance. This time period will vary
from 15 minutes to several hours depending on ambient air conditions.
Normal Operation For Pool & Spa Modes: The control continually compares the
water temperature with the set point and the high limit temperature. When the
water temperature is more than 1° below the set point a call for heat is
generated and a heating cycle is initiated.
1. Apply power to the pool heater by plugging in the non-fused disconnect
block or moving the circuit breaker to the “ON” position.
2. Make sure the pool filter pump is operating properly.
3. Push the “MENU” button (x1) until “On/OFF” is displayed. Then use plus
button to select “On” mode as shown in display. The minus button will select
the “OFF” mode.
4. Push the “MENU” button (x2) until “POL” is displayed. Then use plus and
minus buttons to set Pool temperature set point as shown in display.
5. Push the “MENU” button (x3) until “SPA” is displayed. Then use plus and
minus buttons to set Spa temperature set point as shown in display.
6. Push the “MENU” button (x4) until “F_C” is displayed. Then use plus and
minus buttons to select Fahrenheit or Celsius mode as shown in display.
7. The fan will start immediately. Allow 3 minutes for the Heat Pump to
start.
8. When the unit starts, confirm that air is being discharged upward from the
unit and the air is cooler than the ambient air.
9. Allow the Heat Pump to operate for 10-15 minutes in order for system
pressure to stabilize.
10. Using a thermometer, ensure that the discharge air is at least 8ºF (4ºC)
cooler than the ambient air temperature. If discharge air does not have at
least an 8ºF (4ºC) temperature change, refer to Performance Monitoring /
Troubleshooting section in this manual.
11. If Heat Pump fails to start: a. Check temperature settings to confirm
call for heating
b. Check water flow and water flow switch
c. Ensure that power is on
d. Check TROUBLE SHOOTING SECTION in this manual or Call for service
17
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
FIGURE 16b: Heat/Cool User Interface Keypad
Display Window: When powered is supplied to the unit, the display will either
show sensor temperature (in degrees F or C) or the diagnostic code.
Menu Button: Activates the On/Off, Heating, Cooling, or Automatic function
modes of the controller. Mode is confirmed with the Mode Indicator “On/OFF”,
“HE”, “COL”, “AUt”, or “F_C”.
888°C °F
x1,
x2,
x3,
x4,
ºF/ºC
x5,
Heating Mode
Run Indicators: Confirms the compressor ( ) or fan ( ) operation and the
thermostat is controlling a demand for heat.
Cooling Mode
Plus “+” Button: Raises the heater’s set point temperature or changes
parameters.
Minus “-” Button: Lowers the heater’s set point temperature or changes
parameters.
FIGURE 17b: Heat/Cool Function Selection
Display
OFF On
Push the “MENU” button to display the current selection: “On/OFF”, “HE”, “COL”, “AUT”, or “F_C” will appear. When in “On/OFF” mode, push the “-” button to turn the unit off and the “+” button to turn the unit on.
HE
Push the “MENU” button (x2) until “HE” is displayed. Use the “-” and “+” buttons to set Heat Temperature Set Point as shown in display. Selecting the set point will activate heating mode. Max. Temp. is 104°F.
COL
Push the “MENU” button (x3) until “COL” is displayed. Use the “-” and “+” buttons to set Cool Temperature Set Point as shown in display. Selecting set point will activate cooling mode. Min. Temp. is 55°F.
AUT
Push the “MENU” button (x4) until “AUt” is displayed. Use the “-” and “+”
buttons to set Auto Temperature Set Point as shown in display. Selecting the
set point will activate auto mode. Max. Temp. is 104°F.
F_ C
Push the “MENU” button (x5) until “F_C” is displayed. Use the “-” and “+”
buttons to select °F or °C display as shown.
18
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Heat/Cool Operation
Automatic Reset Time: The heater will automatically reset when an error
condition is corrected and resume operation.
Temperature Adjustment: This control allows the user to have 3 individual pre-
set temperature settings, Heating (“HE”), Cooling (“COL”) and Automatic
(“AUt”). To adjust the temperature while in Heating, Cooling or Automatic
mode, use the (Plus) and (Minus) buttons. When the numeric display adjustment
is complete, the control will return to displaying the actual measured water
temperature. The temperature settings for both Heating and Cooling modes are
initially set at the factory to 65°F. The minimum allowed settings for Heating
and Cooling modes is 40°F. The maximum allowed settings for Heating and
Cooling modes is 104°F. It is best not to try and set the maximum heating
below the minimum cooling set points. FAHRENHEIT VERSUS CELSIUS: The control
will display temperatures in either degrees Fahrenheit or Celsius. To change
the temperature display, Press the MENU key until you see F_C and by pressing
one of the arrow keys, you can switch to °F or °C. Once the temperature unit
has been programmed, it will be displayed for five seconds, and will then
return to the actual pool water temperature in the mode that you have chosen.
Defrost Function: The Defrost function is provided to prevent the evaporator
coil from freezing when the outside air temperature is near 50°F (10°C). The
temperature at which this function will operate is not exact and each unit
will vary depending upon conditions surrounding the heat pump, clearance
around the heat pump and heat pump maintenance. This time period will vary
depending on ambient air conditions.
Normal Operation For Heat, Cool & Auto Modes: The control continually compares
the water temperature with the set point and the high limit temperature. When
the water temperature is more than 1° below the set point, a call for heat is
generated and a heating cycle is initiated.
1. Apply power to the pool heater by plugging in the non-fused disconnect
block or moving the circuit breaker to the “ON” position.
2. Make sure the pool filter pump is operating properly.
3. Push the “MENU” button (x1) until “On/OFF” is displayed. Then use plus
button to select “On” mode as shown in display. The minus button will select
the “OFF” mode.
4. Push the “MENU” button (x2) until “HE” is displayed. Then use plus and
minus buttons to set Heating temperature set point as shown in display.
5. Push the “MENU” button (x3) until “COL” is displayed. Then use plus and
minus buttons to set Cooling temperature set point as shown in display.
6. Push the “MENU” button (x4) until “AUt” is displayed. Then use plus and
minus buttons to set Automatic temperature set point as shown in display. Unit
will activate Heating or Cooling as needed to maintain the set point
temperature.
7. Push the “MENU” button (x5) until “F_C” is displayed. Then use plus and
minus buttons to select Fahrenheit or Celsius mode as shown in display.
8. The fan will start immediately. Allow 3 minutes for the Heat Pump to
start.
9. When the unit starts, confirm that air is being discharged upward from the
unit and the air is cooler than the ambient air for heating mode and warmer
than the ambient air for cooling mode.
10. Allow the Heat Pump to operate for 10-15 minutes in order for system
pressure to stabilize.
11. Using a thermometer, ensure that the discharge air is at least 8ºF (4ºC)
cooler than the ambient air temperature in heating mode. If discharge air does
not have at least an 8ºF (4ºC) temperature change, refer to Performance
Monitoring / Troubleshooting section in this manual.
12. If Heat Pump fails to start: a. Check temperature settings to confirm
call for heating/cooling.
b. Check water flow and water flow switch
c. Ensure that power is on
d. Check TROUBLE SHOOTING SECTION in this manual or Call for service
19
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Water Testing
FIGURE 18: Water Pressure Switch
Water Pressure Switch Test / Adjustment Procedure: The heat pump may have either a water pressure
switch or a water flow switch installed from the factory. The water flow switch is not adjustable. When the
heater is located above or below the level of the pool or spa, the pressure switch will require adjustment to
compensate for the change in static pressure. The following procedure is recommended when the switch
needs adjustment and/or is replaced:
1. Be sure the filter is clean before making any adjustment. 2. Turn “ON” the
filter pump and ensure all air is out of the water lines, and ensure water
flow rate is at
least the rated minimum (see SPECIFICATION SECTION). 3. Turn “ON” the heater
and adjust the temperature control to create a call for heat. 4a. For
Installations with Heater above water level: If the heater does not start,
adjust the pressure switch by
turning the adjustment knob on the pressure switch counter-clockwise, until
the heater starts. Turning the adjustment knob counterclockwise decreases the
pressure needed to close the switch. 4b. For Installations with Heater below
water level: Turn the adjustment knob on the pressure switch clockwise, until
the heater turns off, then turn the knob¼ turn counter-clockwise, so that the
heater turns back on. Turning the adjustment knob clockwise increases the
pressure needed to close the switch. 5. Check the function of the pressure
switch by turning the filter pump on and off several times and confirming that
the heater turn off immediately when the pump is turned off. Never allow the
heater to operate with less than the minimum rated water flow rate.
Adjustment Knob
Two-Speed Pump: In a few cases the pressure from a two-speed pump is below the 1- pound minimum required to operate the water pressure switch on the heater. This is apparent when the pressure switch cannot be further adjusted. In these cases the pump must be run at high speed to operate the heater. If the pump and piping arrangement are such that the required 1-pound minimum pressure cannot be obtained, do not attempt to operate the heater. Correct the installation.
NOTICE: Heater installation, checkout, and start-up should now be completed. Be sure to leave this manual with the pool owner.
Maintenance & Service
Periodic Inspection: The heater is designed and built for long life when
installed and operated according to the manufacturer’s directions. Regular
inspection by qualified service personnel is recommended to keep the heater
working properly. The following inspection points are suggested to help
maximize heater life:
1. Periodically check the fan discharge area. The fan discharge must never be
obstructed in any way and minimum clearances must be observed. Remember that
shrubs grow and in time may obstruct
2. Keep the entire pool heater area clean and free of all debris, corrosive
materials, and other flammable vapors and liquids. Remove any leaves or paper
from around the heater.
3. Do not store chlorine, other pool chemicals, or other corrosives in the
vicinity of the heater. 4. Do not use the heater if any part has been under
water. Contact a qualified service technician to inspect the entire heater and
replace any part of the control
system that was under water. If heater has been totally submerged in water it
must be removed and the entire heater must be replaced. 5. An inspection
program is a good preventative maintenance measure. Keep this manual in a safe
place for future reference for yourself as well as for a
service technician to consult when inspecting or servicing the heater.
Additional inspection procedures to be performed by a qualified service
technician.
Water Chemistry
! WARNING: Water Chemistry. Failure to maintain proper water chemistry may
cause premature heat exchanger damage or failure.
The heat exchanger in your pool heater is made from the highest quality of
materials. The titanium condenser is a premium material and the processes used
to manufacture the heat exchanger are state of the art in pool heater design
and manufacture. However, it remains vital that the heat exchanger be
protected from damaging or corrosive chemicals, insufficient water flow or
improperly balanced water chemistry. Heat exchanger damage or failure
resulting from improper flow, improperly balanced pool water or the improper
addition of sanitizer into the water is NOT covered under the terms of the
warranty. The following factors are critical to heat exchanger protection.
Follow these guidelines to help prevent pre-mature damage or failure to your
heater and heat exchanger.
20
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
1. Water Flow Through Heater: Water must be flowing through the heater at the
minimum rated flow rate during operation. Check that the pump is operating and
the system is filled with water and purged of all air prior to starting the
heater. The minimum rated flow rates are listed in the specifications section.
Some installations may require an adjustment to the water pressure switch for
proper low-flow protection. Test your system and if necessary, adjust the
water pressure switch as described in WATER TESTING SECTION OF MANUAL.
2. Water Chemistry: The chemistry balance and mineral content of swimming
pool and spa water changes rapidly due to the addition of sanitizing
chemicals, user loads, exposed rain, effect of sun, and more. Improper
chemistry balance and mineral content can cause scaling and deposits to form
on pool walls, in the filtration system, in the heat exchanger tubes and
additionally can promote corrosive action to all metals in the water path.
Changing spa water regularly and maintaining the correct chemical balance in
your pool/spa will keep the pool/spa safe and sanitary, and will help heat
exchanger longevity. Use a 4-way pool/spa water test kit to check your water
frequently (at least weekly). Use the following guidelines to help maintain
proper water chemistry:
Chemical Chlorine Bromine
pH
Total Alkalinity Calcium Hardness
Salt
TABLE 4: Water Chemistry
Recommended Level
Effect of Low Levels
1 – 3 ppm 2 – 4 ppm
Hazy water, algae growth, bacteria causing infections
7.4 – 7.6
80 – 120 ppm 200 – 400 ppm 2700 – 5000 ppm
Corrosive to heat exchanger, swimmer irritation
Corrosive to heat exchanger, large fluctuations in pH
Corrosive to heat exchanger Poor salt chlorinator performance
Effect of High Levels Swimmer irritation,
bleaching of clothes/hair, corrosive to heat exchanger
Cloudy water, scaling of heat exchanger, reduced sanitizer effectiveness
Scaling of heat exchanger
Scaling of heat exchanger Corrosive to heat exchanger
3. Skimmer Chlorination: Placing chlorine or bromine Tablets directly into
the skimmer may result in high chemical concentrations flowing through the
heater. DO NOT place chlorine or bromine Tablets in the skimmer.
4. Chlorinator Installation: Chlorinators must be installed downstream of the
heater, and a check valve must be installed between the heater and chlorinator
to prevent high chemical concentrations from back flowing into the heater.
Make sure your piping arrangement meets the chlorinator installation
requirements as shown on page 11.
5. Use Bypass: Until water chemistry is properly balanced, so that corrosive
and potentially damaging water will not flow through the heater and therefore
the heat exchanger. Close the bypass valve once the water is properly
balanced. Ensure water flow through the heater is restored before operating
the heater. A bypass feature is also advantageous for service needs and for
the ability to remove the heater from the water path when not heating.
! WARNING: Bypass. Failure to close the bypass valve when attempting to
operate the heater will result in extensive damage to the heat exchanger.
Winterization
In moderate climates, the heater can continue to operate during short-term
cold spells. Do not use the heater to maintain the water temperature just
above freezing or for freeze protection. Care must be taken to avoid freeze-up
in the heater. When it is used during freezing weather, the pump must run
continuously. The heater is not warranted against freeze-ups. In regions where
freezing temperatures are encountered, all water must be drained from the
heater when it is out of service, to prevent damage to the heater and piping.
Draining the heat exchanger is recommended as part of the season’s shutdown
procedures.
NOTICE: A heater damaged by freezing is not covered under the manufactures
warranty.
Draining The Heat Exchanger: This procedure applies to installations where the
heater is located higher than the pool water level. If it is necessary to
drain a pool heater located below the pool water level, you must either
partially drain the pool, or isolate the pool heater from the pool using
valves, then perform draining the heat exchanger. 1. Set the heater to STANDBY
mode using the keypad. 2. Turn the electricity to the heater OFF at the
circuit breaker panel. 3. Be sure the circulating pump is OFF. 4. If no drain
plug is provided, open lower inlet water union and allow all water to drain
from the heater. 5. Re-install the drain plug or reattach the water union.
21
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Spring Start-Up: This procedure should be performed annually to ready your
heater for the upcoming season. In addition to the steps outlined below, it is
recommended that a PERIODIC INSPECTION also be performed. 1. Inspect and clean
the heater, being sure the heater is free of leaves and debris prior to
startup. 2. Properly attached inlet and outlet piping and confirm the drain
valve is closed. 3. Turn the filtration system pump ON and allow the system to
run long enough to purge all the air from the lines. 4. Turn the electricity
to the heater ON at the circuit breaker panel. 5. Set the temperature control
using the keypad to an operating mode (“POOL”, “SPA”, “HEAT”, “COOL” or
“AUTO”) and adjust the set point to the desired
temperature setting. 6. If operating difficulties are encountered, contact a
qualified service company for assistance.
Component Service
NOTICE: Only qualified service technicians, with appropriate test equipment,
should be allowed to service the heater. For conditions where refrigerant must
be managed, an EPA certified technician is required. All of the components
that comprise the system have an effect on heater operation. Before proceeding
with heater related troubleshooting tips, be certain that the pump is
operating correctly, the filters and strainers are not blocked, the valves in
the piping are properly positioned, and the time clocks are properly set.
! WARNING: Explosion Hazard. Do not attempt to repair broken or faulty
components of this heater. Do not modify the heater or its components in any
manner. To do so may result in a malfunction that could result in death,
personal injury, or property damage. Check with the pool owner to see if any
part of the heater has been under water. Replace any electrically operated
component that has been under water.
! WARNING: Risk of Electric Shock. Review all safety information provided in
the Before You Begin section of this manual prior to servicing. Always
disconnect power circuit before connecting the heat pump, or working on the
heat pump. This equipment contains wiring that carries high voltage. Contact
with these wires could result in death or personal injury and/or may also
cause property damage.
Control System: The control system in this heater consists of the display keypad/control board and the terminal board. The locations of these components are shown in Figure 5. The control board functions as the heater’s thermostat operator and safety control system, To remove/replace the display keypad/control board: 1. Turn pump and heater power OFF. 2. Remove the front access panel. 3. Disconnect all wires from the printed circuit board. 4. Detach the board from the access panel by removing the mounting screws. 5. Replace the board, and reverse the above steps to reassemble.
Thermistor: The thermistor monitors the return water temperature to thermostatically control pool and spa water to the selected temperature and to shut the heater off is the return water reaches 104 F. To replace the thermistor: 1. Turn pump, and heater power “OFF”. 2. Remove the front access panel. 3. Unplug the thermistor connector from the terminal board. 4. Undo wire connection in the control box and push leads through the hole in the control box. 5. Withdraw the thermistor from the well in the water header. 6. Replace the thermistor. 7. Reverse steps above to complete the procedure.
Water Pressure Switch / Flow Switch: The water pressure switch (Figure 18) is preset at the factory for most typical, deck level installations. When the heater is located above or below the level of the pool or spa, the pressure switch may require adjustment to compensate for the change in static head pressure. If adjustment is needed, the procedure is detailed in Water Pressure Switch Test / Adjustment Procedure. Flow switches are not adjustable. Please verify that there is adequate water flow to meet minimum water flow requirements (see Specifications section)
NOTICE: Do not operate the pool heater without the function of a properly adjusted pressure switch or flow switch.
To replace the pressure switch: 1. Turn pump, and heater power “OFF”. 2. Remove hose from switch body external to control box. 3. Remove the wires from the pressure switch. 4. Replace the pressure switch. 5. Reverse steps above to complete the procedure.
To replace the flow switch: 1. Turn pump, and heater power “OFF”. 2. Remove the flow switch wires from the control board. 3. Replace the flow switch. 4. Reverse steps above to complete the procedure.
22 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Transformer: The transformer converts the field supply voltage to 24 VAC
output for powering the control board. To replace the transformer: 1. Turn
pump, and heater power “OFF”. 2. Remove the front access panel. 3. Disconnect
all wires from the transformer leads. 4. Remove the (2) screws that secure the
transformer to the control box. 5. Replace the transformer. Reassembly is the
reversal of steps above. Contactor: The switches the incoming power to the
compressor. To replace the contactor: 1. Turn pump, and heater power “OFF”. 2.
Remove the front access panel. 3. Disconnect all wires from the contactor
terminals keep track of wire locations. 4. Remove the (2) screws that secure
the contactor to the control box. 5. Replace the contactor. Reassembly is the
reversal of steps above.
Troubleshooting
Error and Operation Codes: See Table 5: Display Code Index. Troubleshooting:
See Table 6: Troubleshooting Lookup Chart. Automatic Reset Time: The heater
will automatically reset when an error condition is corrected and resume
operation.
NOTICE: These instructions are intended for the use of qualified personnel
trained and experienced in the installation and servicing of this type of
heating equipment and its related system components. Some states may require
installation and service personnel to be licensed. Persons not qualified
should not attempt to repair this equipment according to these instructions.
These instructions and procedures are not for the use of “do-it-yourself”
consumers. NOTICE: As a preliminary check, make sure that all wire connections
are clean and tight and that all wiring conforms to the wiring diagram.
Internal Wiring: If the heater display is blank after the electrical has been
installed, refer to Troubleshooting Lookup Chart to determine the cause. Note,
the cable between the display board and the terminal board is keyed to ensure
correct connection.
23 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Display (blank)
FLo
LP
HP
SO SS FS dSO dSS
TABLE 5: Display Code Index
Problem
Possible Cause
Information
Tripped circuit breaker, no power supply No power to heat pump
Faulty electrical component
Check breaker and ensure that the unit is properly installed. Call for service.
Unit will not turn on
Master power switch off Unit on 5-minute delay
Turn on master power switch. Wait 5 minutes.
Normal operation for remote on/off.
Water Pressure Switch / Flow Switch circuit open
Low or no water flow
Check water flow to heat pump. Ensure pool pump is on. Clean your filter. Make sure all valves are fully open and bypass valve is closed.
Turn off fountains, etc.
Low Pressure Switch circuit open
Air flow obstruction Low ambient temperature cutoff Unit low on refrigerant
Remove debris, etc. restricting air flow to heat exchanger. Wait for outside temperature to reach 60°F Call for service.
Check water flow to heat pump. Ensure pool pump is on.
High Pressure Switch circuit open
Low water flow
Clean your filter. Make sure all valves are fully open and bypass valve is closed. Turn off fountains, etc.
High water temp
Check pool temperature. Wait until pool needs heat. Call for service.
Water Temperature sensor open
Sensor not connected to control board
Call for service.
Water Temperature sensor short circuit
Sensor or sensor wires shorted
Call for service.
Defrost Mode
Frost buildup on evaporator coil
No action required. Unit is defrosting automatically.
Coil Temperature sensor open
Sensor not connected to control board
Call for service.
Coil Sensor short circuit
Sensor or sensor wires shorted
Call for service.
! WARNING: To avoid possible outer jacket damage or injury: (1) no materials
should be stored against the jacket and (2) care should be taken to avoid
unnecessary contact (especially by children) with the jacket.
24 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
TABLE 6: Troubleshooting Lookup Chart
Problem
Possible Cause
Possible Solution(s)
No power to unit
Make sure power is on.
Breaker is tripped
Check the breaker.
Thermostat not turned up high enough Turn thermostat up until unit comes on.
5-minute delay timer still running
Be sure the 5-minute delay has passed.
Unit is not operating
Low water flow
Make sure filter is clean. Make sure filter pump is on.
Unhook cleaning devices.
Outside temperature too low
Check outside ambient temperature or wait for warmer temperatures to operate (refer to Operation section).
Fan not functioning
Call for service.
Heat pump is running but is not heating; “Run” light does not come on.
Check output air temperature to input air temperature. Differential should be
at least 8°F (4°C).
System component failure
Low ambient air temperature. Allow outside air temperature to exceed 50°F,
then re-check.
Call for service.
Thermostat set too high
Turn thermostat down.
Heat pump runs continuously
Evaporator is dirty
Clean it by running tap water over the coil without additional nozzle attachment. Do not use pressurized water as it can damage the coil and void warranty.
Electrical component failure
Turn off pump. If the unit is still running after 2 minutes, turn off the power to the unit and call for service.
Bad valve or improper water flow
Check valve settings and ensure water flow is sufficient (is the filter pump running continuously?). If heat pump continues to cycle, turn unit off to prevent compressor damage.
Heat pump is cycling on/off too quickly
Low refrigerant, low ambient temp, or high humidity with low ambient temp
Check evaporator coil for severe frost. Turn unit off to prevent compressor
damage.
If heat pump continues to cycle, turn unit off to prevent compressor damage.
Call for service.
Condensation
This is normal and there is no reason to be concerned.
Water is coming out from bottom of unit Possible water leak
Turn the unit off for several hours, but leave the filter pump running continuously. If water quantity decreases, then it is only condensation. Otherwise, there is a possible leak.
25 USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Service Parts List
The following repair parts are available from Hayward and through your local
distributor. When ordering parts, include the complete pool heater model
number listed on the unit’s rating plate, located near the junction boxes on
the exhaust side of the heater. (Example: HP21405T) All service must be
performed by a qualified technician.
REFRIGERATION PARTS · Compressor · Thermal Expansion Valve (TXV) · Evaporator
· Condenser · Filter Drier · Reversing Valve · Compensator
ELECTRICAL PARTS · Fan Motor · Control Board · Capacitor, Compressor ·
Capacitor, Fan · Contactor · Fan Relay · Transformer · HP Switch · LP Switch ·
Defrost Sensor · Water Temperature Sensor · Water Flow Switch · Water Pressure
Switch · Plug, Compressor · Instrument Elbow Assembly
MISCELLANEOUS PARTS · Evaporator Guard · Fan Blade · Fan Guard · Panel-Top
Kit, Black · Panel-Top Kit, Taupe · Gasket-35 In, Neoprene (Qty 2) · Bracket,
Bottom (Qty 4) · Fastener, Tree, 1/4 (Qty 25) · Fastener, U-Type (Qty 25) ·
Consumer Kit
26
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
HAYWARD® Pool Products Limited Warranty
Hayward Pool Products, Inc., warrants the components of this product to be
free from defects in materials and workmanship during the warranty period.
Please visit https://hayward. com/support/resources/warranty for product
warranty details. The limited warranty excludes damage from freezing,
negligence, improper installation, improper use or care, Acts of God or as
specified in installation and operations manual. Parts that fail or become
defective during the warranty period shall be repaired or replaced, at our
option. Proof of purchase is required for warranty service. In the event proof
of purchase is not available, the manufacturing date of the product will be
the sole determination of the purchase date. To obtain warranty service,
please contact the place of purchase or the nearest Hayward Authorized Service
Center. For assistance on your nearest Hayward Authorized Service Center,
please visit us at https://hayward.com/dealerlocator. Hayward shall not be
responsible for cartage, removal, repair or installation labor or any other
such costs incurred in obtaining warranty replacements or repair. The Hayward
Pool products warranty does not apply to components manufactured by others.
For such products, the warranty established by the respective manufacturer
will apply. The express limited warranty above constitutes the entire warranty
of Hayward Pool Products with respect to its’ pool products and is in lieu of
all other warranties expressed or implied, including warranties of
merchantability or fitness for a particular purpose. In no event shall Hayward
Pool products be responsible for any consequential, special or incidental
damages of any nature. Some states do not allow a limitation on how long an
implied warranty lasts, or the exclusion of incidental or consequential
damages, so the above limitation may not apply to you. This warranty gives you
specific legal rights, and you may also have other rights, which vary from
state to state. Hayward Industries, 1415 Vantage Park Dr., Suite 400,
Charlotte, NC 28203 *Supersedes all previous publications
Register your product at https://hayward.com/support/resources/warranty
/product-registration
FOR FURTHER INFORMATION OR CONSUMER TECHNICAL SUPPORT, VISIT OUR WEBSITE AT
www.hayward.com
Hayward is a registered trademark Hayward Industries, Inc. © 2024 Hayward
Industries, Inc. All other trademarks not owned by Hayward are the property of
their respective owners. Hayward is not in any way affiliated with or endorsed
by those third parties. For patent information, refer to
www.hayward.com/patents.
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>