Progressive Dynamics PD9300 Series Power Converter Installation Guide
- June 30, 2024
- Progressive Dynamics
Table of Contents
PD9300 Series Power Converter
Installation and Operation Guide for
PD9300 Series Power Converter
INTRODUCING
Multi-Battery Charging System
Selectable charging for
Flooded Lead Acid – AGM – Lithium
Utilizing Progressive Dynamics
TCMS technology
www.progressivedyn.com 111426B
INSTALLATION INSTRUCTIONS
NOTES:
• Horizontal mounting of the power converter is
recommended although it can be mounted in any position
that provides unobstructed ventilation to the fan and vent
holes.
• The OEM should test the power converter under full load
conditions in its intended mounting location. This will
ensure that there is sufficient unobstructed ventilation to
the converter allowing it to operate at its maximum rated
load. Failure to provide adequate ventilation to the
converter will cause the converter output to be reduced as
it responds to ambient conditions.
• The INTELI-POWER converters are not designed for
zero clearance compartments.
• Use a 5/32” hex driver to tighten the output screws. Do
not exceed 50 in-lbs. torque on the output terminals.
• The INTELI-POWER converters are not weather tight or
designed for wet mounting locations. They must be
protected from direct contact with water.
• Avoid the introduction of foreign materials into the case
as this could damage or cause a malfunction of the
converter.
WARNING:
THIS EQUIPMENT EMPLOYS COMPONENTS THAT
TEND TO PRODUCE ARCS OR SPARKS – TO
PREVENT FIRE OR EXPLOSION DO NOT INSTALL
IN COMPARTMENTS CONTAINING BATTERIES OR
FLAMMABLE MATERIALS
Installation Steps:
1. Secure converter firmly to mounting surface.
2. Connect chassis ground lug (found on unit base) to
chassis.
• Ground wire to be between 6 and 12AWG wire.
3. Disconnect battery from both positive (+) and ground (-)
cables.
4. Connect battery ground (-) to converter NEG (-) lug.
• Conductor to be between 2 and 10AWG (follow all
applicable codes when sizing conductor)
5. Disconnect any optional pendant.
6. Plug converter into appropriate outlet.
7. Set converter to correct output mode.
8. Using a DC voltmeter, verify converter output.
If no output is present, refer to the trouble shooting
guide in this manual and on the website.
9. Disconnect power to converter.
10. Connect battery positive (+) to converter POS (+) lug.
• Conductor to be between 2 and 10AWG (follow all
applicable codes when sizing conductor)
Note: When connecting battery to converter POS (+),
a spark may occur. This is normal.
11. Reconnect battery cables.
12. Reconnect any optional pendants or modules.
13. Reconnect power to converter.
⚠ CAUTION RISK OF FIRE:
Chassis bonding wire must be a separate wire ran directly
from the grounding lug provided on the converter. DO
NOT connect output negative to chassis using the same
wire.
Torque Data
DC Lugs: 30 – 50 IN LBS
Battery Ground Lug: 25 – 35 IN LBS
DO NOT REMOVE TERMINAL BLOCK SCREWS
FEATURES
SELECTABLE CHARGE PROFILES… Allow you to select
the right profile for the battery being charged. The unit can also
provide a constant output voltage for special needs.
GFCI PROTECTION… INTELI-POWER converters have
the LOWEST ground fault leakage. The user can confidently
utilize the RV’s AC outlets without concern of ground fault
interruption of the facilities power source.
REVERSE BATTERY PROTECTION prevents damage if
battery leads are cross connected. Since the only consequence
of cross connection is a blown fuse, damage to or possible
replacement of the converter is avoided. Cross connection of
battery leads is the only thing that will blow these fuses.
Replacement fuses are available at any automotive store
GENERAL OPERATION
The INTELI-POWER series converter will supply “clean”
power from input voltages that range from 105-130 VAC.
CONSTANT VOLTAGE (MAGENTA LIGHT) – The full
rated load is available for load, battery charging or both.
When charging the battery, the converter has a nominal
voltage output of 13.6 VDC.
CAUTION
DO NOT STORE VEHICLE FOR EXTENDED
PERIODS OF TIME IN THIS MODE.
LITHIUM W/ 2 STAGE CHARGE (BLUE LIGHT) –
When charging the battery, the converter has a nominal
voltage output of 14.4 VDC. When the converter senses an
output current drop below a preset level, the converter will
automatically switch to IDLE mode and the voltage output
will drop to 13.6VDC
CAUTION
DO NOT USE TO RECHARGE FLOODED
LEAD/ACID BATTERIES WHILE IN EITHER
LITHIUM (BLUE) OR AGM (WHITE) MODE
Side of Converter
Accessory Port Mode Button Access
Mode Indicator LED
Green – Lead Acid w/ Wizard
Blue – Lithium
White – AGM
Magenta – Constant Voltage
⚠ CAUTION
IF THE REVERSE BATTERY PROTECTION FUSES ARE BLOWN DURING INSTALLATION, CHECK TO SEE THAT THE BATTERY HAS BEEN CONNECTED PROPERLY BEFORE REPLACING THE FUSES. REPLACE THE FUSES ONLY WITH THE SAME TYPE AND RATING AS THE ORIGINAL FUSES. USING OTHER FUSES MAY RESULT IN CONVERTER DAMAGE, VEHICLE DAMAGE, INJURY OR OTHER CONSEQUENCES (SEE WARRANTY).
⚠ CAUTION
IT IS IMPORTANT THAT THE FLUID LEVEL OF ANY CONNECTED BATTERIES BE CHECKED ON A REGULAR BASIS. ALL BATTERIES WILL “GAS” AND LOSE SOME FLUIDS WHEN CONTINUOUSLY CONNECTED TO ANY CHARGING SOURCE.
FLOODED LEAD ACID (GREEN LIGHT) – When charging the battery, the converter will sense voltage on the battery and automatically select the proper operating mode to provide the correct charge level to the batteries. If the voltage drops below a preset level the converter will automatically switch to BOOST mode and the output voltage will increase to approximately 14.4 VDC to rapidly recharge the battery. When the converter senses an output drop below a preset level, the converter will automatically switch to NORMAL mode and the voltage output will drop to 13.6VDC. If there is no significant battery usage for 33 hours the converter will automatically switch to STORAGE mode and the output voltage will drop to 13.2 VDC. In storage mode, the output voltage increases to 14.4 VDC for approximately 15 minutes every 21 hours to help prevent sulfation of the battery plates.
AGM (WHITE LIGHT) – When charging the battery, the converter has a nominal voltage output of 14.0 VDC. After a preset time, the converter will automatically switch to ABSORPTION mode and the voltage output will increase to 14.7VDC. When the converter senses an output current drop below a preset level, the converter will automatically switch to FLOAT mode and the voltage output will drop to 13.6VDC
Press and hold the MODE BUTTON for at least 3 seconds until the LED changed color. Continue to depress button until the desire battery type is selected.
See www.progressivedyn.com for more detailed description of operation
PD9330
Input: 105-130 VAC 60 Hz
500 Watts
Output: 13.6 VDC – 14.7 VDC, 30 Amps
Dimensions: 4.5H x 8.25L x 7.25W Weight: 4.5lbs
|
PD9345
Input: 105-130 VAC 60 Hz
725 Watts
Output: 13.6 VDC – 14.7 VDC, 45 Amps
Dimensions: 4.5H x 8.25L x 7.25W Weight: 4.5lbs
|
PD9360
Input: 105-130 VAC 60 Hz
1000 Watts
Output: 13.6 VDC – 14.7 VDC, 60 Amps
Dimensions: 3.6H x 8L x 9W Weight: 5.8lbs
|
PD9380
Input: 105-130 VAC 60 Hz
1300 Watts
Output: 13.6 VDC – 14.7 VDC, 80 Amps
Dimensions: 3.6H x 8L x 9W Weight: 6.0lbs
---|---|---|---
TROUBLE SHOOTING GUIDE
PROBLEM
|
POSSIBLE CAUSES
|
ACTION
---|---|---
1. No Output
|
Proper AC power not connected
|
Connect power supply
Check AC distribution panel for proper operation
External Fuses Blown
|
Check for reverse polarity
Replace fuses with same type and rating
Short Circuit
|
Trace circuits for possible fault
Unit has shutdown due to overheating
|
Check air flow
Allow unit to cool
Unit has shutdown due to over voltage (Also see Item 4 below)
|
Check input voltage
Converter will shut down if the input voltage exceeds 132 Volts
Correct input voltage
2. External Fuses Blown
|
Reverse Battery Hook Up
|
Correct hook up and replace fuses with same type and rating
3. Low Output
|
Excessive load for converter
|
Reduce load requirements or install larger converter
Input voltage not between 105-130 VAC
|
Correct input supply voltage
Bad battery cell(s)
|
Replace battery
Mild Overheating
|
Check air flow
Allow unit to cool
Incorrect Output Mode
|
Change output mode
4. Intermittent or no Output on Generator, works on Shore Power
|
Unit has shutdown due to over voltage.
|
Add another load to the generator, this may reduce the “spikes” to an acceptable level
Some generators exhibit excessive voltage spikes on the AC power output, this may cause the over voltage protection to shut the unit down
|
Contact generator manufacturer for possible defect in the generator
5. High Output
|
Incorrect Output Mode
|
Change output mode
Please refer to website for further trouble shooting information.
See website www.progressivedyn.com for more troubleshooting information and return instructions.
LIMITED WARRANTY: Progressive Dynamics, Inc. warrants its power control center to be free from defects in material or workmanship under normal use and service for a period of two years from the original date of purchase; and limits the remedies to repair or replacement.
This warranty is valid only within the continental limits of the United States and Canada.
See website www.progressivedyn.com for more warranty information and return instructions
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>