neptronic SKE4 Steam Humidifier Modbus Communication Module User Guide
- June 15, 2024
- neptronic
Table of Contents
neptronic SKE4 Steam Humidifier Modbus Communication Module
Introduction
The SKE4 Modbus Communication Module User Guide provides information for using Neptronic® communication feature. The controller uses Modbus communication protocol over serial line in the RTU mode and provides a Modbus network interface between client devices and Neptronic SKE4 devices.
The SKE4 Modbus Guide assumes that you are familiar with Modbus terminology.
The following are the requirements for Modbus:
-
Data Model. The SKE4 Steam Humidifier Modbus server data model uses only the Modbus Registers table.
-
Register Address:
- As per protocol base (base 0); for PLC add 1 to protocol base.
- As per holding register (base 400001).
Note: Ensure that the Modbus communication software used does not have a limit on the range of the register addresses that can be viewed and supports 6-digit holding registers.
-
Function Codes. The SKE4 Steam Humidifier Modbus server supports a limited function codes subset comprising:
- Read Holding Registers (0x03)
- Write Single Register (0x06)
- Write Multiple Registers (0x10)
-
Exception Responses. The SKE4 Steam Humidifier Modbus server supports the following exception codes:
- Illegal data address
- Illegal data value
- Slave device busy
-
Serial Line. The SKE4 Steam Humidifier Modbus over serial line uses RTU transmission mode over a two-wire configuration RS485 (EIA/TIA-485 standard) physical layer.
- The physical layer can use fixed baud rate selection or automatic baud rate detection (default) as per the Modbus Auto Baud Rate device menu item or holding register index 1.
- The supported baud rates are 9600, 19200, 38400, and 57600.
- The physical layer also supports variable parity control and stop bit configuration as per the Modbus Comport Config device menu item or holding register index 2.
- In auto baud rate configuration, if the device detects only consecutive bad frames (2 or more) for one second with any given baud rate, it will reinitialize itself to the next baud rate.
-
Addressing. The SKE4 Steam Humidifier device only answers at the following address:
- The device’s unique address (1 to 246) that can be set through the device menu or through holding register index 0.
Modbus Registers
Table Glossary
Name | Description | Name | Description |
---|---|---|---|
W | Writable Register | ASCII | For registers containing ASCII (8-bit) characters |
RO | Read Only Register | MSB | Most Significant Byte |
Unsigned | For range of values from 0 to 65,535, unless otherwise specified | ||
LSB | Least Significant Byte | ||
Signed | For range of values from -32,768 to 32,767, unless otherwise | ||
specified | MSW | Most Significant Word | |
Bit String | For registers with multiple values using bit mask (example, | ||
flags) | LSW | Least Significant Word |
Modbus Registers Table
Protocol Base| Holding Register| Description| Data
Type| Units, Limits, State Texts| Writable| Default Value
---|---|---|---|---|---|---
0| 40000 1| Modbus Address and Product Type| Unsigned| MSB = Product
type, not writable
LSB = Modbus Address (1 to 247), writable| W|
1| 40000 2| Device Baud Rate| Unsigned
Scale 100| 0, 9600, 19200, 38400, and 57600, 0 = Auto Baud
Rate Detection Value/100 (e.g. 38400 baud = 384)| W| 19200
2| 40000 3| Modbus Slave Communication Port Configuration| Unsigned| 0 =
No parity, 2 Stop bits 1 = Even parity, 1 Stop bit 2 = Odd parity, 1 Stop bit|
W| No parity, 2 Stops bits
3| 40000 4| Product Name (characters 8 & 7)| ASCII| MSB = char 6, LSB =
char 7| W|
4| 40000 5| Product Name (characters 6 & 5)| ASCII| MSB = char 4, LSB =
char 5| W|
5| 40000 6| Product Name (characters 4 & 3)| ASCII| MSB = char 2, LSB =
char 3| W|
6| 40000 7| Product Name (characters 2 & 1)| ASCII| MSB = char 0, LSB =
char 1| W|
7| 400008| Product Actual Firmware Version (in Integer x100)| Unsigned
Scale 100| 1 to 65535 (e.g. 100)| RO|
8| 400009| Product Actual EEPROM Version (in Integer x100)| Unsigned
Scale 100| 1 to 65535 (e.g. 100)| RO|
2000| 402001| Control Signal| Unsigned
Scale 1000| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2001| 402002| Room RH Signal| Unsigned
Scale 1000| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2002| 402003| Supply RH Signal| Unsigned
Scale 1000| Units: Volt (V), Range: 0V to 15V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2003| 402004| Water Level Signal| Unsigned
Scale 1| Units: Hz, Range: 0 to 30000Hz
Value x 1 (e.g. 10Hz = 10)| RO| 0Hz
2004| 402005| Water Level Low Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2005| 402006| Water Level High Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2006| 402007| Water Temperature Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2007| 402008| Foam Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2008| 402009| SSR Temperature Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2009| 402010| Cabinet Temperature Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2010| 402011| Current Sensor 1 Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 3.30V
Value x 1000 (e.g. 1V = 1000)| RO| 0V
2011| 402012| Current Sensor 2 Signal| Unsigned
Scale 1000
| Unit: Volt (V), Range: 0V to 3.30V
Vale x 1000 (e.g. 1V = 1000)| RO| 0V
2012| 402013| Board Temperature Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
2013| 402014| Main Power Supply| Unsigned
Scale 10| Unit: Volt (V), Range: 0V to 40V
Value x 10 (e.g. 2V = 20)| RO| 0V
4000| 404001| Power Output Feedback Signal| Unsigned
Scale 1000| Unit: Volt (V), Range: 0V to 10V
Value x 1000 (e.g. 2V = 2000)| RO| 0V
4001| 404002| Heater SSR Stage| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| RO| 0%
6000| 406001| Control Input| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| RO| 0%
6001| 406002| Control Min| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| W| 0%
6002| 406003| Control Max| Unsigned
Scale 100
| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| W| 0%
6003| 406004| Control Bias| Signed
Scale 100| Unit: %, Range: -10% to 10%
Value x 100 (e.g. 10% = 1000)| W| 0%
6004| 406005| Room RH| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)
| RO| 0% RH
6005| 406006| Room RH Min| Unsigned
Scale 100
| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6006| 406007| Room RH Max| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6007| 406008| Room RH Bias| Unsigned
Scale 100| Unit: % RH, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6008| 406009| Supply High Limit RH| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6009| 406010| Supply High Limit RH Min| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6010| 406011| Supply High Limit RH Max| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6011| 406012| Supply High Limit RH Bias| Signed
Scale 100| Unit: %, Range: -10% RH to 10% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6012| 406013| Water Temperature| Unsigned
Scale 100| Unit: ºC/ºF, Range: 0°C to 125°C or 32°F to 257°F
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)| RO| 50°C or 122°F
6013| 406014| Water Temperature Bias| Signed
Scale 100| Unit: ºC/ºF, Range: -10°C to 10°C or -18°F to 18°F
Value x 100 (e.g. 5°C = 500 or 14ºF = 1400)| RO| 0°C or 32°F
6014| 406015| SSR Temperature| Signed
Scale 100| Unit: ºC/ºF, Range: -20°C to 100°C or -4°F to 212°F, Value x 100
(e.g. 5°C = 500 or 10ºF = 1000)| RO| 0°C or 32°F
6015| 406016| Cabinet Temperature| Signed
Scale 100| Unit: ºC/ºF, Range: -20°C to 100°C or -4°F to 212°F
Value x 100 (e.g. 5°C = 500 or 10ºF = 1000)| RO| 0°C or 32°F
6016| 406017| Current Sensor 1| Unsigned
Scale 100| Unit: Amps (A), Range: 0A to 150A
Value x 100 (e.g. 10A = 1000)| RO| 0A
6017| 406018| Current Sensor 2| Unsigned
Scale 100| Unit: Amps (A), Range: 0A to 150A
Value x 100 (e.g. 10A = 1000)| RO| 0A
6018| 406019| Board Temperature| Unsigned
Scale 100| Unit: ºC/ºF, Range: 0°C to 100°C or 32°F to 212°F
Value x 100 (e.g. 5°C = 500 or 32ºF = 3200)| RO| 0°C or 32°F
6019| 406020| Power Output Feedback Bias| Unsigned
Scale 1000| Unit: V, Range: -1V to 1V
Value x 100 (e.g. 10V = 1000)| W| 0V
6020| 406021| Power Output Feedback Min| Unsigned
Scale 1000| Unit: V, Range: 0V to 10V
Value x 100 (e.g. 10V = 1000)| W| 0V
6021| 406022| Power Output Feedback Max| Unsigned
Scale 1000| Unit: V, Range: 0V to 10V
Value x 100 (e.g. 10V = 1000)| W| 0V
6022| 406023| Power Output Feedback| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)
| RO| 0%
6023| 406024| Water Level| Unsigned
Scale 10| Unit: %, Range: 0% to 120%
Value x 10 (e.g. 10% = 100)| RO| 78%
6024| 406025| Water Probe Low Pos Reading| Unsigned
Scale 1| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)| RO| 30000Hz
6025| 406026| Water Probe High Pos Reading| Unsigned
Scale 1| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)| RO| 30000Hz
6026| 406027| Water Probe Abs Low Pos Reading| Unsigned
Scale 1| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)| RO| 30000Hz
6027| 406028| Water Probe Abs High Pos Reading| Unsigned
Scale 1| Unit: Hz, Range: 0 to 30000 Hz
Value x 1 (e.g. 1 Hz = 1)| RO| 30000Hz
6028| 406029| Room RH Network Reading| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6029| 406030| Room RH Setpoint| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 40% RH
6030| 406031| Room RH Unoccupied Setpoint| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 30% RH
6031| 406032| Room RH Vacant Setpoint| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 20% RH
6032| 406033| Room Demand Proportional Gain| Unsigned
Scale 10| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)| W| 20
6033| 406034| Room Demand Integral Time| Unsigned
Scale 10| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10 sec = 100)| W| 0 sec
6034| 406035| Room Demand Derivative Time| Unsigned
Scale 10| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10 sec = 100)| W| 0 sec
6035| 406036| Room Demand| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6036| 406037| Supply High Limit Network Reading| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 0% RH
6037| 406038| Supply High Limit Setpoint| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| W| 80% RH
6038| 406039| Supply High Limit Proportional Gain| Unsigned
Scale 10| No Unit, Range: 1 to 200
Value x 10 (e.g. 10 = 100)| W| 10
6039| 406040| Supply High Limit Integral Time| Unsigned
Scale 10| Unit: Seconds (sec), Range: 0 to 900 sec
Value x 10 (e.g. 10 sec = 100)| W| 0 sec
6040| 406041| Supply High Limit Derivative Time| Unsigned
Scale 10| Unit: Seconds (sec), Range: 0 to 60 sec
Value x 10 (e.g. 10 sec = 100)| W| 0 sec
6041| 406042| Supply High Limit Demand| Unsigned
Scale 100| Unit: % RH, Range: 0% RH to 100% RH
Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6042| 406043| Humidity Control Network Demand| Unsigned Scale 100| Unit: %,
Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| W| 0%
6043| 406044| Humidity Control Network High Limit| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| W| 100%
6044| 406045| Humidity Demand| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| RO| 0%
6045| 406046| SDU Fan Off Delay| Unsigned
Scale 1| Unit: Minutes (min), Range: 5 to 20 mins
Value x 1 (e.g. 5 mins = 5)| W| 5 min
6046| 406047| System Power Output| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| RO| 0%
6047| 406048| System Steam Capacity| Unsigned
Scale 10| Unit: kg/hr or lb/hr, Range: 0 to 3000
kg/hr or 0 to 6614 lb/hr
Value x 10 (e.g. 10kg/hr = 100 or 10lb/hr = 100)| RO| 0 kg/hr or
0 lb/hr
6048| 406049| Boiler Demand| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| W| 0%
6049| 406050| Boiler Capacity| Unsigned
Scale 10| Unit: kg/hr or lb/hr, Range: 0 to 3000 kg/hr or 0 to 6614 lb/hr
Value x 10 (e.g. 10kg/hr = 100 or 10lb/hr = 100)| RO| 0 kg/hr or
0 lb/hr
6050| 406051| Boiler Power Output| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| RO| 0%
6051| 406052| Boiler Run Time (0)| Unsigned
Scale 100| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)| RO| 0h
6052| 406053| Boiler Run Time (1)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6053| 406054| Boiler Run Time (2)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6054| 406055| Boiler Run Time (3)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6055| 406056| Boiler On Time (0)| Unsigned
Scale 100| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)| RO| 0h
6056| 406057| Boiler On Time (1)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6057| 406058| Boiler On Time (2)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6058| 406059| Boiler On Time (3)| | Units: Hours (h), Range: 0 to 2147483647
h| |
6059| 406060| Boiler Service Run Time (0)| Unsigned
Scale 100| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)| RO| 0h
6060| 406061| Boiler Service Run Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6061| 406062| Boiler Service Run Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6062| 406063| Boiler Service Run Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6063| 406064| Boiler Service On Time (0)| Unsigned
Scale 100| Units: Hours (h), Range: 0 to 2147483647 h
Value x 100 (e.g. 10 h = 1000)| RO| 0h
6064| 406065| Boiler Service On Time (1)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6065| 406066| Boiler Service On Time (2)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6066| 406067| Boiler Service On Time (3)| | Units: Hours (h), Range: 0 to
2147483647 h| |
6067| 406068| Boiler Minimum Steam Output| Unsigned
Scale 1| Unit: %, Range: 1 to 25%
Value x 1 (e.g. 1% = 1)| W| 5%
6068| 406069| Boiler Drain Interval| Unsigned
Scale 1| Units: Hours (h), Range: 0 to 24 h
Value x 1 (e.g. 1 h = 1)| W| 6h
6069| 406070| Boiler Drain Volume| Unsigned
Scale 1| Unit: %, Range: 25 to 100%
Value x 1 (e.g. 30% = 30)| W| 100%
6070| 406071| Boiler Max Steam Output| Unsigned
Scale 1| Unit: %, Range: 0 to 100%
Value x 1 (e.g. 1% = 1)| W| 100%
6071| 40672| Boiler Idle Time Drain| Unsigned
Scale 1| Unit: Hours (h), Range: 0 to 72 h
Value x 1 (e.g. 1 h = 1)| W| 24h
6072| 406073| Boiler Idle Temperature Setpoint| Unsigned
Scale 1| Unit: ºC/ºF, Range: 0°C to 60°C or 32°F or 140°F
Value x 1 (e.g. 5°C = 500 or 10ºF = 1000)| W| 0°C or 32°F
6073| 406074| Boiler Blowdown Rate| Unsigned
Scale 1| Unit: %, Range: 0% to 100%
Value x 1 (e.g. 10% = 10)| W| 0%
6074| 406075| Boiler Service Interval| Unsigned
Scale 1| Unit: Hours (h), Range: 1000 to 3000 h
Value x 1 (e.g. 1500 h = 1500)| W| 1000h
6075| 406076| Room Demand Proportional Band| Unsigned
Scale 10| Unit: %, Range: 1% to 100%
Value x 100 (e.g. 10% = 100)| RO| 5%
6076| 406077| HRL Temperature| Signed
Scale 100| Unit: ºC/ºF, Range: -40°C to 260°C or-40°F to 500°F, Value x 100
(e.g. 5°C = 500 or 10ºF = 1000)| RO| 0°C or 32°F
6077| 406078| Supply High Limit Proportional Band| Unsigned
Scale 10| Unit: %, Range: 1% to 100%
Value x 100 (e.g. 10% = 100)| RO| 10%
6078| 406079| HRL Humidity| Unsigned Scale 100| Unit: %, Range: 0% RH to 100%
RH
Value x 100 (e.g. 10% RH = 1000)| RO| 0% RH
6079| 406080| Modbus TCP IP Keep Alive Time Out| Unsigned
Scale 1| Unit: Minutes (min), Range: 1 to 1440 mins
Value x 1 (e.g. 5 mins = 5)| W| 5 min
6080| 406081| Humidity Demand Low Dead Band| Unsigned
Scale 100| Unit: %, Range: 0% to 100%
Value x 100 (e.g. 10% = 1000)| W| 1%
6081| 406082| Network Timeout| Unsigned
Scale 1| Unit: Seconds (sec), Range: 1 to 900 sec
Value x 1 (e.g. 10sec = 10)| W| 900 sec
6082| 406083| Water Level Replace Interval| Unsigned
Scale 1| Unit: Days, Range: 1 to 7 days
Value x 1 (e.g. 1 day = 1)| W| 3day
6083| 406084| Boiler Manual Calibration Time (0)| Unsigned
Scale 1| Unit: Hours (h), Range: 0 to 21474836.47 h
Value x 1 (e.g. 1 h = 1)| RO| 0h
6084| 406085| Boiler Manual Calibration Time (1)| | Unit: Hours (h), Range: 0
to 21474836.47 h| |
6085| 406086| Boiler Manual Calibration Time (2)| | Unit: Hours (h), Range: 0
to 21474836.47 h| |
6086| 406087| Boiler Manual Calibration Time (3)| | Unit: Hours (h), Range: 0
to 21474836.47 h| |
6087| 406088| HRL Temperature Bas| Signed
Scale 10| Unit: ºC/ºF, Range: -10°C to 10°C or -18°F to 18°F
Value x 10 (e.g. 5°C = 50 or 14ºF = 140)| W| 0°C or 32°F
6088| 406089| HRL Humidity Bias| Signed
Scale 10| Unit: %RH, Range: -10%RH to 10%RH
Value x 10 (e.g. 5%RH = 50)| W| 0%RH
6089| 406090| Fill Delay| Unsigned
Scale 1| Unit: Minutes (min), Range: 1 to 15 mins
Value x 1 (e.g. 5 mins = 5)| RO| 0 min
6090| 406091| Clean Valve Delay| Unsigned
Scale 1| Unit: %, Range: 0% to 80%
Value x 1 (e.g. 10% = 10)| W| 50%
10000| 410001| Air Flow| Unsigned
Scale 1| 0 = Closed
1 = Open| RO| Closed
10001| 410002| Supply High Limit| Unsigned
Scale 1| 0 = Closed
1 = Open| RO| Closed
10002| 410003| Interlock| Unsigned
Scale 1| 0 = Closed
1 = Open| RO| Closed
10003| 410004| Binary External Demand| Unsigned
Scale 1| 0 = 0%
1 = 100%| RO| 0%
10004| 410005| Water Leak Detection| Unsigned
Scale 1| 0 = Ok
1 = Leak| RO| Ok
10005| 410006| Thermal Cutout| Unsigned
Scale 1| 0 = Closed
1 = Open| RO| Closed
10006| 410007| RS485 Interface| Unsigned
Scale 1| 0 = No
1 = Yes| RO| No
10007| 410008| Ethernet Interface| Unsigned
Scale 1| 0 = No
1 = Yes| RO| No
10008| 410009| Contactors PCB Fuse| Unsigned
Scale 1| 0 = Normal
1 = Blown Fuse| RO| Normal
10009| 410010| Control PCB Fuse| Unsigned
Scale 1| 0 = Normal
1 = Open Fuse| RO| Normal
11000| 411001| Alarm Warning Relay| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11001| 411002| Service Warning Relay| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11002| 411003| Water Level Valve| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11003| 411004| Tank Water Valve| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11004| 411005| Drain Cooler Valve| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11005| 411006| Drain Pump| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11006| 411007| Drain Valve| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11007| 411008| Main Contactor| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11008| 411009| Heater Stage 1| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11009| 411010| Heater Stage2| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11010| 411011| Heater Stage 3| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11011| 411012| SDU Fan| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11012| 411013| Alarm LED| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11013| 411014| Power LED| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
11014| 411015| Buzzer| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
12000| 12001| Manual Water Calibration State| Unsigned
Scale 1| 0 = Ok
1 = Required| RO| Ok
12001| 412002| Water Level Low| Unsigned
Scale 1| 0 = Inactive
1 = Active| RO| Inactive
12002| 412003| Water Level High| Unsigned
Scale 1| 0 = Inactive
1 = Active| RO| Inactive
12003| 412004| Foam Sensor| Unsigned
Scale 1| 0 = No Foam
1 = Foam| RO| No Foam
12004| 412005| SDU Fan Fault| Unsigned
Scale 1| 0 = Off
1 = On| RO| Off
12005| 412006| Boiler Service Operation| Unsigned
Scale 1| 0 = Not Allowed 1 = Allowed| W| Allowed
12006| 412007| Boiler Service Due| Unsigned
Scale 1| 0 = No
1 = Yes| RO| No
12007| 412008| Foam| Unsigned
Scale 1| 0 = Ok
1 = Detected| RO| Ok
12008| 412009| HRL Lock Setpoint| Unsigned
Scale 1| 0 = Unlock
1 = Lock| W| Unlock
12009| 412010| Network Control State| Unsigned
Scale 1| 0 = Normal
1 = Fault| W| Normal
12010| 412011| Inhibit Resistive Probe| Unsigned
Scale 1| 0 = No
1 = Yes|
W
|
No
12011| 412012| Notify Alarm| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
12012| 412013| Notify Warning| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
12013| 412014| Notify App Msg| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
12014| 412015| Boiler Line Rinse| Unsigned
Scale 1| 0 = Off
1 = On| W| On
12015| 412016| Anti Freeze Warning| Unsigned
Scale 1| 0 = Inactive
1 = Drain| RO| Inactive
15000| 415001| System Log Verbose Level| Unsigned
Scale 1| 0 = None
1 = Emergency
2 = Alert
3 = Critical
4 = Error| 5 = Warning
6 = Notice
7 = Info
8 = Debug| W| Debug
15001| 415002| Modbus Server Units| Unsigned
Scale 1| 0 = Metric
1 = Imperial| W| Metric
15002| 4 15003| Control Signal Type| Unsigned
Scale 1| 0 = 0-10Vdc
1 = 2-10Vdc
2 = 4-20mA
3 = 0-20mA| W| 0-10Vdc
15003| 4 15004| Room RH Signal Type| Unsigned
Scale 1| 0 = 0-10Vdc
1 = 2-10Vdc
2 = 4-20mA
3 = 0-20mA| W| 0-10Vdc
15004| 4 15005| Supply RH Signal Type| Unsigned
Scale 1| 0 = 0-10Vdc
1 = 2-10Vdc
2 = 4-20mA
3 = 0-20mA| W| 0-10Vdc
15005| 4 15006| Control Profile| Unsigned
Scale 1| 0 = Extern Analog
1 = Extern Network
2 = Intern Analog| 3 = Intern Network
4 = HRL
5 = Custom| W| Extern Analog
15006| 4 15007| Modulating High Limit Profile| Unsigned
Scale 1| 0 = Disabled
1 = Extern Analog
2 = Extern Network| 3 = Intern Analog
4 = Intern Network
5 = Custom| W| Disabled
15007| 4 15008| Occupancy State| Unsigned
Scale 1| 0 = Occupied
1 = Unoccupied| 2 = Vacant
3 = Off| RO| Occupied
15008| 415009| Room RH Source| Unsigned
Scale 1| 0 = None
1 = RoomRH| 2 = Network
3 = HRL| W| None
15009| 415010| Room RH Setpoint Source| Unsigned
Scale 1| 0 = None
1 = Internal| 2 = Control Input| W| None
15010| 415011| Supply High Limit Reading Source| Unsigned
Scale 1| 0 = None
1 = SuppyHLRH| 2 = Network| W| None
15011| 415012| Supply High Limit Setpoint Source| Unsigned
Scale 1| 0 = None
1 = Internal| 2 = Control Input| W| None
15012| 415013| Humidity Control Demand Source| Unsigned
Scale 1| 0 = None
1 = Control Input| 2 = Room Demand
3 = Network
| W| Control Input
15013| 415014| Humidity Control High Limit Source| Unsigned
Scale 1| 0 = None
1 = Control Input| 2 = SupplyHLDemand
3 = Network
| W| None
15014| 415015| Humidity Control Cutout State| Unsigned
Scale 1| 0 = Off
1 = Normal
2 = Low Limit| 3 = HighLimit
4 = No Air Flow
5 = Interlock| RO| Off
15015| 4 15016| SDU Fan Target| Unsigned
Scale 1| 0 = None
1 = SDU Fan| W| None
15016| 4 15017| Boiler Request| Unsigned
Scale 1| 0 = None
1 = Reset Alarms 2 = Drain| 3 = Reset Counters 4 = Filling
5 = WaterCalib
| W| None
15017| 4 15018| Boiler State| Unsigned
Scale 1| 0 = Off
1 = Idle
2 = Line Rinse
3 = Tank Rinse
4 = Filling| 5 = Draining
6 = Heating
7 = Boiling
8 = Alarm| RO| Off
15018| 4 15019| Boiler Fill Mode| Unsigned
Scale 1| 0 = One Shot
1 = Pulsed| W| Pulsed
15019| 4 15020| Boiler Alarm| Unsigned
Scale 1| 0 = Normal
1 = Failed ump
2 = Fill Timeout
3 = Blocked Piping
4 = Heat Timeout
5 = Overheat| 6 = WaterLeak
7 = Service
8 is Reserved
9 = Tank Blocked
10 = Refill Delay
| RO| Normal
15020| 4 15021| Boiler Idle Tank Rinse On| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
15021| 4 15022| Boiler Idle Tank Rinse Off| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
15022| 4 15023| Water Probe Auto Calib.| Unsigned
Scale 1| 0 = Off
1 = On| W| On
15023| 4 15024| System Power State| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
15024| 4 15025| Water Level Probe Warning| Unsigned
Scale 1| 0 = Ok
1 = Replace| RO| Ok
15025| 4 15026| Water Level Probe Failure| Unsigned
Scale 1| 0 = None
1 = Capacitive| 2 = Resistive
3 = Both
| RO| None
15026| 4 15027| Water Level Probe Alarm| Unsigned
Scale 1| 0 = Ok
1 = Defect| 2 = No Calib| RO| Ok
15027| 4 15028| Boiler Startup Tank Rinse| Unsigned
Scale 1| 0 = Off
1 = On| W| Off
CUSTOMER SUPPORT
400 Lebeau blvd, Montreal, Qc, H4N 1R6, Canada
www.neptronic.com
Toll free in North America:
1-800-361-2308
Tel.: 514-333-1433
Fax: 514-333-3163
Customer service fax: 514-333-1091
Monday to Friday : 8:00am to 5:00pm (Eastern time)
References
- Neptronic | Home - Humidifier Distributor & HVAC Products
- Neptronic | Home - Humidifier Distributor & HVAC Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>