mPower Electronics MP820 Combustible Gas Transmitter Instruction Manual
- June 14, 2024
- mPower Electronics
Table of Contents
mPower Electronics MP820 Combustible Gas Transmitter
Product Information
Specifications:
- Size: 8.9 x 5.9 x 4.9 in (226 x 150 x 125 mm)
- Weight: 5.7 lbs. (2.6 kg)
- Sensors: Catalytic combustion (LEL) sensor modules
- Calibration: Two-point calibration (zero & span)
- Response Time: 15s t90
- Temperature: Operating: TBD°F to TBD°F (TBD°C to TBD°C)
- Humidity: 10% to 95% Relative Humidity (non-condensing)
- Pressure: 86 to 106 kPa (0.85 to 1.05 atm)
- Power: TBD
Product Usage Instructions
Installation:
Follow these steps to install the MP820 Combustible Gas Transmitter:
- Choose a suitable location for installation.
- Mount the transmitter securely using appropriate tools.
- Connect the necessary cables according to the provided manual.
Calibration:
To calibrate the device:
- Access the calibration mode on the transmitter.
- Perform a zero calibration by adjusting the settings accordingly.
- Perform a span calibration using the provided calibration gas.
Operation:
To operate the MP820 Transmitter:
- Power on the device using the designated button.
- Monitor the readings on the display screen.
- Take necessary actions based on the gas levels detected.
FAQ (Frequently Asked Questions)
-
Q: How often should calibration be performed?
A: Calibration should be performed at least once every six months for accurate readings. -
Q: Can the transmitter be used outdoors?
A: The transmitter is designed for indoor use only and should not be exposed to harsh outdoor conditions.
Introduction
The VOXI LEL MP820 is a point-type combustible gas transmitter designed modularly with smart sensor technology and an integral flameproof enclosure for fixed applications. The versatile platform offers catalytic combustible- gas sensors with auto-zeroing and offline calibration. Three-wire 4-20 mA analog and RS485 digital signal outputs are standard, while wireless output is optional. Various applications include oil & gas, petrochemical, chemical, metallurgical, pharmaceutical, semiconductor, environmental monitoring, and other industry facilities.
Features, Functions and Benefits
- Supporting catalytic combustion (LEL) sensor modules with sensor identification and manufacturing data
- Sensor diagnosis, temperature compensation, and auto-zeroing
- LCD with backlight color varying according to alarm status
- Calibration due date
- 3 wires for 4-20 mA and RS485 ModBus output
- Infrared remote programmer for settings, calibrations, and adjustments
- Error codes for easy troubleshooting
- Recoverable factory settings
- IP67 rating
- IECEx certification
- Optional ISM 915MHz modem for wireless connectivity at no subscription fee (check availability)
Specifications
Detector Specifications
Size | 8.9 x 5.9 x 4.9 in (226 x 150 x 125 mm) |
---|---|
Weight | 5.7 lbs. (2.6 kg) |
Sensors | Catalytic combustion (LEL) sensor modules |
Calibration | Two-point calibration (zero & span) |
Response Time | 15s t90 |
Temperature | -40° to +158°F (-40° to +70°C) |
Humidity | 10% to 95% Relative Humidity (non-condensing) |
Pressure | 86 to 106 kPa (0.85 to 1.05 atm) |
Power | <5W; 10-30 VDC supply |
Sampling | Diffusion |
Display | 4-digit segmented LCD |
Configuration | Via remote infrared programmer |
Outputs | Analog: 4-20 mA (3 wires) Digital: RS-485, |
ModBus 3 Relays
Wireless ISM 915MHz (optional) 1-mile line of sight
Alarms| LCD & LED flashing, relays for external alarm devices
Housing| Explosion-proof aluminum alloy
Housing Entries| 4 Conduit entries ¾” NPT 1 Port M28x1 fitting
Installation| Pipe bolt or wall mount
IP Rating| IP-67
EMI/RFI| Compliant with EMC Directive 2014/30/EU
Safety Certifications| IECEx Ex db IIC T6 Gb (non-Wireless)
Ex tb IIIC T80°C Db (non-Wireless) Ex db ia IIC T6 Gb (Wireless)
Ex ia tb IIIC T80oC Db (Wireless)
CNEX **** Ex d IIC T6
Installation| Pipe holding, wall mount
Warranty| 2 Years
Standard
- Gas Transmitter with Sensor installed
- Rain Shield & Calibration Cap
- Infrared Remote Programmer
- Quick Start Guide
- Calibration Certificate
Optional
- ISM 915 MHz Modem with Antenna
- Mounting Bracket
Sensor Options
Sensor Options
Sensor| Range| Resolution
LEL (Combustibles)| 0-100%LEL| 1%LEL
LEL-F (Combustibles with Filters)| 0-100%LEL| 1%LEL
Due to ongoing research and product improvement, specifications are subject to change without notice.
Contact Information
- Santa Clara Houston Shanghai
- www.mpowerinc.com
- HQ Office: 408-320-1266 • 1-866-mPower7