mPower Electronics MP820 Combustible Gas Transmitter Instruction Manual

June 14, 2024
mPower Electronics

mPower Electronics MP820 Combustible Gas Transmitter

Product Information

Specifications:

  • Size: 8.9 x 5.9 x 4.9 in (226 x 150 x 125 mm)
  • Weight: 5.7 lbs. (2.6 kg)
  • Sensors: Catalytic combustion (LEL) sensor modules
  • Calibration: Two-point calibration (zero & span)
  • Response Time: 15s t90
  • Temperature: Operating: TBD°F to TBD°F (TBD°C to TBD°C)
  • Humidity: 10% to 95% Relative Humidity (non-condensing)
  • Pressure: 86 to 106 kPa (0.85 to 1.05 atm)
  • Power: TBD

Product Usage Instructions

Installation:
Follow these steps to install the MP820 Combustible Gas Transmitter:

  1. Choose a suitable location for installation.
  2. Mount the transmitter securely using appropriate tools.
  3. Connect the necessary cables according to the provided manual.

Calibration:
To calibrate the device:

  1. Access the calibration mode on the transmitter.
  2. Perform a zero calibration by adjusting the settings accordingly.
  3. Perform a span calibration using the provided calibration gas.

Operation:
To operate the MP820 Transmitter:

  1. Power on the device using the designated button.
  2. Monitor the readings on the display screen.
  3. Take necessary actions based on the gas levels detected.

FAQ (Frequently Asked Questions)

  • Q: How often should calibration be performed?
    A: Calibration should be performed at least once every six months for accurate readings.

  • Q: Can the transmitter be used outdoors?
    A: The transmitter is designed for indoor use only and should not be exposed to harsh outdoor conditions.

Introduction

The VOXI LEL MP820 is a point-type combustible gas transmitter designed modularly with smart sensor technology and an integral flameproof enclosure for fixed applications. The versatile platform offers catalytic combustible- gas sensors with auto-zeroing and offline calibration. Three-wire 4-20 mA analog and RS485 digital signal outputs are standard, while wireless output is optional. Various applications include oil & gas, petrochemical, chemical, metallurgical, pharmaceutical, semiconductor, environmental monitoring, and other industry facilities.

Features, Functions and Benefits

  • Supporting catalytic combustion (LEL) sensor modules with sensor identification and manufacturing data
  • Sensor diagnosis, temperature compensation, and auto-zeroing
  • LCD with backlight color varying according to alarm status
  • Calibration due date
  • 3 wires for 4-20 mA and RS485 ModBus output
  • Infrared remote programmer for settings, calibrations, and adjustments
  • Error codes for easy troubleshooting
  • Recoverable factory settings
  • IP67 rating
  • IECEx certification
  • Optional ISM 915MHz modem for wireless connectivity at no subscription fee (check availability)

Specifications

Detector Specifications

Size 8.9 x 5.9 x 4.9 in (226 x 150 x 125 mm)
Weight 5.7 lbs. (2.6 kg)
Sensors Catalytic combustion (LEL) sensor modules
Calibration Two-point calibration (zero & span)
Response Time 15s t90
Temperature -40° to +158°F (-40° to +70°C)
Humidity 10% to 95% Relative Humidity (non-condensing)
Pressure 86 to 106 kPa (0.85 to 1.05 atm)
Power <5W; 10-30 VDC supply
Sampling Diffusion
Display 4-digit segmented LCD
Configuration Via remote infrared programmer
Outputs Analog: 4-20 mA (3 wires) Digital: RS-485,

ModBus 3 Relays

Wireless ISM 915MHz (optional) 1-mile line of sight

Alarms| LCD & LED flashing, relays for external alarm devices
Housing| Explosion-proof aluminum alloy
Housing Entries| 4 Conduit entries ¾” NPT 1 Port M28x1 fitting
Installation| Pipe bolt or wall mount
IP Rating| IP-67
EMI/RFI| Compliant with EMC Directive 2014/30/EU
Safety Certifications| IECEx Ex db IIC T6 Gb (non-Wireless)

Ex tb IIIC T80°C Db (non-Wireless) Ex db ia IIC T6 Gb (Wireless)

Ex ia tb IIIC T80oC Db (Wireless)

CNEX **** Ex d IIC T6

Installation| Pipe holding, wall mount
Warranty| 2 Years

Standard

  • Gas Transmitter with Sensor installed
  • Rain Shield & Calibration Cap
  • Infrared Remote Programmer
  • Quick Start Guide
  • Calibration Certificate

Optional

  • ISM 915 MHz Modem with Antenna
  • Mounting Bracket

Sensor Options

Sensor Options

Sensor| Range| Resolution
LEL (Combustibles)| 0-100%LEL| 1%LEL
LEL-F (Combustibles with Filters)| 0-100%LEL| 1%LEL

Due to ongoing research and product improvement, specifications are subject to change without notice.

Contact Information

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>