mPower Electronics MP820 Combustible Gas Transmitter Instruction Manual

June 14, 2024
mPower Electronics

mPower Electronics MP820 Combustible Gas Transmitter

Product Information

Specifications:

  • Size: 8.9 x 5.9 x 4.9 in (226 x 150 x 125 mm)
  • Weight: 5.7 lbs. (2.6 kg)
  • Sensors: Catalytic combustion (LEL) sensor modules
  • Calibration: Two-point calibration (zero & span)
  • Response Time: 15s t90
  • Temperature: Operating: TBD°F to TBD°F (TBD°C to TBD°C)
  • Humidity: 10% to 95% Relative Humidity (non-condensing)
  • Pressure: 86 to 106 kPa (0.85 to 1.05 atm)
  • Power: TBD

Product Usage Instructions

Installation:
Follow these steps to install the MP820 Combustible Gas Transmitter:

  1. Choose a suitable location for installation.
  2. Mount the transmitter securely using appropriate tools.
  3. Connect the necessary cables according to the provided manual.

Calibration:
To calibrate the device:

  1. Access the calibration mode on the transmitter.
  2. Perform a zero calibration by adjusting the settings accordingly.
  3. Perform a span calibration using the provided calibration gas.

Operation:
To operate the MP820 Transmitter:

  1. Power on the device using the designated button.
  2. Monitor the readings on the display screen.
  3. Take necessary actions based on the gas levels detected.

FAQ (Frequently Asked Questions)

  • Q: How often should calibration be performed?
    A: Calibration should be performed at least once every six months for accurate readings.

  • Q: Can the transmitter be used outdoors?
    A: The transmitter is designed for indoor use only and should not be exposed to harsh outdoor conditions.

Introduction

The VOXI LEL MP820 is a point-type combustible gas transmitter designed modularly with smart sensor technology and an integral flameproof enclosure for fixed applications. The versatile platform offers catalytic combustible- gas sensors with auto-zeroing and offline calibration. Three-wire 4-20 mA analog and RS485 digital signal outputs are standard, while wireless output is optional. Various applications include oil & gas, petrochemical, chemical, metallurgical, pharmaceutical, semiconductor, environmental monitoring, and other industry facilities.

Features, Functions and Benefits

  • Supporting catalytic combustion (LEL) sensor modules with sensor identification and manufacturing data
  • Sensor diagnosis, temperature compensation, and auto-zeroing
  • LCD with backlight color varying according to alarm status
  • Calibration due date
  • 3 wires for 4-20 mA and RS485 ModBus output
  • Infrared remote programmer for settings, calibrations, and adjustments
  • Error codes for easy troubleshooting
  • Recoverable factory settings
  • IP67 rating
  • IECEx certification
  • Optional ISM 915MHz modem for wireless connectivity at no subscription fee (check availability)

Specifications

Detector Specifications

Size 8.9 x 5.9 x 4.9 in (226 x 150 x 125 mm)
Weight 5.7 lbs. (2.6 kg)
Sensors Catalytic combustion (LEL) sensor modules
Calibration Two-point calibration (zero & span)
Response Time 15s t90
Temperature -40° to +158°F (-40° to +70°C)
Humidity 10% to 95% Relative Humidity (non-condensing)
Pressure 86 to 106 kPa (0.85 to 1.05 atm)
Power <5W; 10-30 VDC supply
Sampling Diffusion
Display 4-digit segmented LCD
Configuration Via remote infrared programmer
Outputs Analog: 4-20 mA (3 wires) Digital: RS-485,

ModBus 3 Relays

Wireless ISM 915MHz (optional) 1-mile line of sight

Alarms| LCD & LED flashing, relays for external alarm devices
Housing| Explosion-proof aluminum alloy
Housing Entries| 4 Conduit entries ¾” NPT 1 Port M28x1 fitting
Installation| Pipe bolt or wall mount
IP Rating| IP-67
EMI/RFI| Compliant with EMC Directive 2014/30/EU
Safety Certifications| IECEx Ex db IIC T6 Gb (non-Wireless)

Ex tb IIIC T80°C Db (non-Wireless) Ex db ia IIC T6 Gb (Wireless)

Ex ia tb IIIC T80oC Db (Wireless)

CNEX **** Ex d IIC T6

Installation| Pipe holding, wall mount
Warranty| 2 Years

Standard

  • Gas Transmitter with Sensor installed
  • Rain Shield & Calibration Cap
  • Infrared Remote Programmer
  • Quick Start Guide
  • Calibration Certificate

Optional

  • ISM 915 MHz Modem with Antenna
  • Mounting Bracket

Sensor Options

Sensor Options

Sensor| Range| Resolution
LEL (Combustibles)| 0-100%LEL| 1%LEL
LEL-F (Combustibles with Filters)| 0-100%LEL| 1%LEL

Due to ongoing research and product improvement, specifications are subject to change without notice.

Contact Information

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>