Live FMC 11 Way SPD Metal Consumer Unit Instructions

June 13, 2024
LIVE

Live FMC 11 Way SPD Metal Consumer Unit

Product Specifications:

  • Model: LSMC&FMC
  • Versions: / , -RC, and TR
  • Enclosure Type: Metal Clad Consumer Unit
  • Mounting: Surface Mounted or Flush Mounted
  • Available Sizes: 20-way, 22-way

Product Usage Instructions

Installation:

  1. Ensure the unit is installed in a safe and secure location.
  2. Check that all factory connections are correct before proceeding with installation.
  3. If a lock is included, knock out the designated position to install the lock securely.
  4. Remove the standard installation buckle promptly after installation.

Commissioning:

  1. Before commissioning the electrical installation, ensure all connections are checked for correct installation and tightness.
  2. If unsure about any aspect of the installation, seek advice from qualified professionals as electricity can be dangerous.

Contact Information:

Live Electrical Ltd.

Address: Unit , Queensmead Place, Trafford Park, Manchester, M PH

Tel: [insert telephone number]

Web: www.liveelectrical.co.uk

E-mail: sales@liveelectrical.co.uk

Frequently Asked Questions

Q: What should I do if I encounter difficulties during installation?

A: If you face any challenges during installation, refer to the user manual for troubleshooting tips or contact our customer support for assistance.

Q: Can I use this product for outdoor installations?

A: This product is designed for indoor use. For outdoor installations, consult with a professional to ensure proper protection against environmental elements.

Cable and Torque Settings

Check the tightness of all terminals, including factory made terminations, as follows

Operating Instructions

  • In normal use all toggles should be in the upward position indicated by I or ON.

  • To isolate the supply to all the circuits, switch the RED toggle on the main isolating switch (if it is a split load board), or the BLUE toggle on the main RCD to the OFF position if this is used as the Main switch.

  • On a split load unit the circuits controlled by the RCD or individual RCBO, can be isolated separately by switching the BLUE toggle to OFF.
    caution: The circuits not controlled by the RCD will still be live.

  • To isolate the individual circuits, switch OFF the MCB or RCBO controlling that particular circuit.
    Caution: This only isolates one circuit the remainder of the circuits are still live.

  • The RCD which controls several circuits needs to be tested periodically (approx every 3 months) to ensure safe operation.

  • The test is performed by pushing the test button marked T. If the RCD trips reset as normal. If it fails to trip seek qualified advice as the unit may require attention.
    caution: When the RCD trips all circuits connected to it will switch off. If you have any sensitive equipments ie. Computers or electronics. Please disconnect them prior the test.
    The same test should be repeated if rcbos are used to protect any circuits.

  • Should any MCB trip, reset the MCB by pushing toggle upwards. Should it trip again, the circuit may require attention. Leave the MCB in the OFF position and seek qualified advice.

  • If the RCD should trip, reset the switch. If it will not reset, switch OFF all the MCBs connected to the RCD and try to switch RCD back ON.
    If the RCD remains ON, switch MCBs back on one at a time. If the RCD trips during this procedure the particular circuit controlled by the MCB may require attention. Leave the suspect circuit switched OFF and reset the RCD, then seek qualified advice.

NOTE:

  1. Lock available Users with locks can knock outs this position to install the lock.
  2. .Standard installation buckle, please remove it promptly after installation.

Waning
All connections, including factory-made, must be checked for the correct installation tightness, prior to the commissioning of the electrical installation. Electricity is dangerous if in any doubt please seek qualified advice

Description

The distribution equipment and circuit protection range of metal consumer units by Live Distribution UK LTD is designed to fully comply with the requirements of BS EN 61439-3 and requirements of the 18th Edition of BS 7671 IET Wiring Regulations. With multiple configurations available, the range offers flexible versatile solutions for installations.

Features & Benefits

  • Standard: BSEN61008, BS EN60898, BS EN61439-3
  • Operating Voltage: 230/S0Hz
  • Protection Degree: IP40
  • Maximum Load(A}: As indicated on incoming device
  • Material: manufactured from robust steel
  • Fully enclosed metal construction body with drop-down metal lid
  • Multi pie circular cable entry knock-outs (2 5&32mm) on the top and bottom, 32mm on the sides, and back plus larger rear slots
  • Raised key holes for secure easy installation
  • Raised Din rail improves cable routing
  • Modern style finished in white polyester powder coating to RAL9010
  • Large and accessible wiring space, with extra space for RCBOs
  • Flexible connection allows for various configurations of protected ways
  • This operation guide covers /100, -RC and TR versions

Unit Dimension

Outline Dimensions

Notes:
Knockout placements are symmetrical between top and bottom/ left and right sides.
Double-tier board has double the number of side knockouts.

Unit Characteristics

Safety Instructions

  • This unit must be installed and tested in accordance with the requirements of all relevant legislation, regulations and accepted practice.

  • After completion of the installation draw users attention to the instructions contained inside this booklet and leave with user.

  • The total load supplied by this unit must not exceed the rating of the main switch or RCD.

  • The total load of the MCBs may exceed this value where appropriate diversity is applied.

  • This unit is suitable for indoor use only and is rated at IP40.

  • The unit and all its components have been type tested to the following specifications:

  • The MCBs fitted to this unit are calibrated at 30°C in accord with temperature calibration requirements of EN60898. Main Switch BS EN 60947-3 At other temperatures the following rating factors should be used.
    60°C o.as 20°c 1.0 ere 1.15

  • Adjacent Thermal Magnetic MCBs should not be continuously loaded or approach their nominal rated currents when mounted in Enclosures. It is recommended that a 60% diversity factor be applied to the MCBs nominal rated current where it is intended to load the MCB continuously.

Installation

Enclosure Mounting

  • Remove lid by tu ming lid fixing screws until they are free from the base.
  • Remove appropriate cable entry holes. If using compression glands, fit them in the appropriate knockout prior to fixing unit to the wall.
  • Mount the unit using appropriate screws and fixings.
  • Bring all cables in through appropriate cutouts and route to their final location. Connection of Main Incoming Device
  • Cut and dress the main incoming cables and connect them into the appropriate terminals.
  • Tighten the main incoming terminals securely.

MCB Connection

  • Cut the busbar into the required split configuration if required.
  • It is recommended that the largest rating MCBs be fitted closest to the Main Switch.
  • To connect High Integrity circuits RCBOs slide RCD next to Main Switch away from Main Switch and fit RCBOs and busbar.
  • Tighten terminal screw onto busbar to recommended torque of 2.0Nm
  • Cut and dress circuit conductors and connect them to the appropriate MCB,
  • RCBO and corresponding Earth and Neutral terminals. Recommended torque 2.0Nm.

Installation of Control Devices

  • Control devices such as Timers Modular, Contactors and Transformers can be fitted to this unit.
  • The incoming supply for the device should be fed from an MCB and not direct from the bus bar.

Completion of Installation

  • Test installation in accordance with relevant regulations.
  • Fit any Blanking plates that are required on the front cover,
  • Once all circuits are connected, replace lid.
  • Labels are provided and should be used as required.
  • Once the above is complete hand this booklet to the end user.

LIVE ELECTRICAL DISTRIBUTION UK LTD

Unit 4, Queensmead Place, Trafford Park, Manchester, M171PH
Tel: 0161 870 2592
Web:www.liveelectrical.co.uk
E-mail: sales@liveelectrical.co.uk

Ensure that these instructions are made available to the end user for future reference