GfA 30005154 WSD Door Module 2 To 4 GHz Instruction Manual
- June 21, 2024
- GFA
Table of Contents
Installation Instructions
WSD door- module 2,4 GHz
Model: 30005154
Safety-relevant chapter
Explanation of symbols
The following symbols are used in these installation instructions:
DANGER
Safety note: Non-compliance will result in death or severe injury.
WARNING
Safety note: Non-compliance can result in death or severe injury.
CAUTION
Safety note: Non-compliance can result in injury.
NOTICE
Note: Non-compliance can result in material damage and impairment of product
functionality.
i NOTE
Note: Points out useful additional information.
Target audience of these installation instructions
These installation instructions are geared towards qualified persons trained
in the handling of door systems. Expert knowledge, relevant skills and
practical experience are what set apart qualified persons. They are capable of
safely carrying out the tasks involving installation, maintenance and
modernisation according to the instructions.
Intended use
The WSD door-module is intended to connect a safety edge system to the TS971
door control. The WSD door-module is to be protected from rain, moisture and
aggressive ambient conditions.
The WSD system is suitable for electrical (with 8k2 end of line resistor),
pneumatic (with 1k2 end of line resistor) and optical safety edges.
Two slack-rope switches and one pass-door switch can be connected.
The WSD door-module has cross-fault monitoring.
Cross-fault monitoring: Electronic monitoring of a short circuit between two
wires inside a cable by measuring the resistance.
Installation
WARNING
Danger due to uncontrolled door movement.
- Carry out the following work only when the power supply is switched off.
- Lock the door to through traffic while working.
Installation on the door
- Remove the cover from the door leaf box.
- Screw the door leaf box onto the door leaf.
NOTICE
Observe the following notes for selecting the place of installation:
Mount the WSD door-module as close to the door control as possible. The WSD
door-module should not be obscured by obstacles at stop and during movement
(holes in the ground, crane runways, concrete or steel pillars, shelves, etc.)
Radio systems may be affected by other radio systems or EMC radiation. In case
of frequent interferences, changing the channel may help. Should interferences
occur more frequently despite the channel change, the system must be replaced
by a wired system.
NOTICE
Damage due to moisture!
In humid areas, use the cover to protect the door leaf boxes.
- Covers are available as accessories: Part no.: 40017478.00001 Set switches Q1 and Q2
You will find the switches Q1/Q2 on the board.
Q1/Q2 are used to switch the cross-fault monitoring (see page 2 for definition) of the slack-rope and pass-door switches.
Select the required setting from the following table.
No. | Door control | Slack-rope switch | Pass-door switch | Q1 | Q2 |
---|---|---|---|---|---|
1 | TS 971with software version 3.0 or higher | Switch with an integrated | |||
Switch with an integrated resistor 1) | On | On | |||
--- | --- | --- | --- | --- | --- |
2
3| Switch without an integrated resistor 2)
or no switch present| On| Off
Switch without an integrated resistor or
no switch present| Switch with an integrated resistor 1)| Off| On
4| Switch without an integrated resistor 2) or no switch present| Off| Off
5| TS 971 up to and including software version 2.9| Switch without an
integrated resistor or no switch present (see Note 1)| Switch without an
integrated resistor 2) or no switch present
(see Note 1)| On| On
6| Door controls from other manufacturers| See Note 2
Table: Setting Q1 and Q2
e.g., Model Fraba black or Alpha Deuren black
e.g., Model Fraba light grey or Alpha Deuren light grey
i NOTE
Note 1: Slack-rope or pass-door switches with an integrated resistor cannot
be used with GfA door controls up to and including software version 2.9 or
older controls from other series.
Note 2: If you are using door controls from another manufacturer, check the
associated documentation for information on connecting the door safety
switches. For door controls without cross-fault monitoring, line no. 5 applies
accordingly.
Set switch Q3
Use switch Q3 to select the type of safety edge.
Safety edge type | Switch position |
---|---|
Optical | left |
Pneumatic | right |
Electrical | right |
Laying the cables
NOTICE
Impairment of radio capacity!
Do not route the cables over the antenna. This restricts the radio capacity
and the battery service life is reduced! ➊
- Route excess cable over the battery.➋
- Avoid excess cable length in the door leaf boxes by laying a loop in the profile. ➌
System overview
The available connection options are described below.
Insert cable glands
The WSD door-module is set up for connecting two slack-rope switches and one
pass-door switch.
- If you want to install a pass-door or slack- rope switch, replace the side covers with M16 x 1.5 cable glands.
i NOTE
Please note that only switches with performance level c (PLc) comply with the
current DIN EN 12453 standard.
Connection diagram System 1: OSE ➊ Slack-rope switch ➋ Pass-door switch
i NOTE
Clamping range of the plug-in terminal for slack-rope and pass-door switches:
0.5 – 1.5mm². Stripping length of the single conductors: 6.5 – 7mm, provided
with wire end ferrules.
➊ Slack-rope switch ➋ Pass-door switch
Finish installation
- Fit the cover of the junction end box.
- Switch on the voltage.
i NOTE Damage due to moisture
Make sure that the screws and cable glands are tightened.
Insert battery
The WSD door-module is powered by a battery. The battery life depends on the
safety edge system (optical, electrical), frequency of use and the size of the
door, and is usually more than 1 year.
Replace the batteries during the annual maintenance of the door system.
DANGER
Do not attempt to charge the battery.
Do not short-circuit the battery.
Do not disassemble or deform the battery.
Do not heat the battery. Store the battery in a cool and dry place.
CAUTION
Before inserting the battery, check the contact terminals of the WSD gate
door-module.
Only insert the batteries if they are clean and dry and not deformed.
- The battery must be depassivated before useTap the battery about 6 times on a hard levelsurface.
- Tap only on the side surface, not on the battery contacts.
- Insert the battery.
Teach-in of WSD door-module
The following describes how to teach-in the WSD door-module on the door
control. Also follow the instructions for the door control. Assign a different
radio channel to each door. Note the channels in the door control housing to
facilitate maintenance. Also observe the notes for selecting the channel on
the following pages.
The WSD door-module is now taught-in.
Check the function of the safety edge system.
Selecting the channels
- From door 40, channels are assigned in duplicate. Duplicate radio channels must be as far apart as possible. Plan in advance and draw a hall plan.
- Consequently, if the channels are set incorrectly, the error 1.6 appears on the door control.
TS 971 > SW 1.8 = 39 channels
TS 971 < SW 1.8 = 20 channels
Also note the following frequency table:
Channel | Frequency MHz |
---|---|
2 | 2400 |
22 | 2402 |
3 | 2404 |
23 | 2406 |
4 | 2408 |
24 | 2410 |
5 | 2412 |
25 | 2414 |
6 | 2416 |
26 | 2418 |
7 | 2420 |
27 | 2422 |
8 | 2424 |
Channel | Frequency MHz |
--- | --- |
28 | 2426 |
9 | 2428 |
29 | 2430 |
10 | 2432 |
30 | 2434 |
11 | 2436 |
31 | 2438 |
12 | 2440 |
32 | 2442 |
13 | 2444 |
33 | 2446 |
14 | 2448 |
34 | 2450 |
Channel | Frequency MHz |
--- | --- |
15 | 2452 |
35 | 2454 |
16 | 2456 |
36 | 2458 |
17 | 2460 |
37 | 2462 |
18 | 2464 |
38 | 2466 |
19 | 2468 |
39 | 2470 |
20 | 2472 |
40 | 2474 |
21 | 2476 |
Disposing of old devices and batteries
Old devices and batteries marked with the adjacent symbol must not be
disposed of with unsorted household waste.
Dispose of old devices and batteries appropriately in accordance with local
regulations. Take old devices and batteries to the recycling and collection
systems at your location. You can also return GfA products free of charge.
Please apply enough postage to the package and mark it as “old devices”.
i NOTE Lithium-metal battery!
The product contains an individually packed lithium-metal battery.
According to the safety data sheet, the lithium content is less than 0.5 g.
The batteries are protected against short circuit and must not come into
contact with conductive metal.
TRANSPORTATION NOT RESTRICTED – NON-DANGEROUS GOODS. (According to Special
Provisions SP 188 ADR/RID/IMDG-Code.IATA Packing Instruction 968 Part I for
lithium-metal batteries.)
- Handle the batteries with care.
- In case of damage the batteries must be disposed of properly.
Declaration of incorporation
within the meaning of Machinery Directive 2006/42/EC for partly completed
machinery, Appendix II Part B
Declaration of conformity
within the meaning of EMC Directive 2014/30/EU within the meaning of RoHS
Directive 2011/65/EU within the meaning of RED Directive 2014/53/EU
GfA ELEKTROMATEN GmbH & Co. KG Wiesenstrafie 81 – 40549 Disseldorf Germany
We, GfA ELEKTROMATEN GmbH & Co. KG declare under our sole responsibility that
the following product complies with the above directives and is only intended
for installation in a door system.
WSD door-module Part no.: 30005154
Standards applied:
EN 60335-2-103:2015
EN 61000-6-2:2005
EN 61000-6-3:2007
EN 300328-2:2017
Stephan Kleine
CEO Signature
Düsseldorf, 09.03.2023
Declaration of conformity
within the meaning of Electromagnetic Compatibility Regulations 2016 within
the meaning of Restriction of the Use of Certain Hazardous Substances in
Electrical and Electronic Equipment Regulations 2021 within the meaning of
Radio Equipment Regulations 2017
Declaration of incorporation within the meaning of Supply of Machinery
(Safety) Regulations 2008 for partly completed machinery, Appendix II Part B
We,
GfA ELEKTROMATEN GmbH & Co. KG
declare under our sole responsibility that the following product complies with
the above directives and is only intended for installation in a door system.
WSD- door module Part no.: 30005154
Applied Standards:
BS EN 60335-2-103:2015
BS EN 61000-6-2:2005
BS EN 61000-6-3:2007
BS EN 300328-2:2017
Authorised representative:
Andrew Collett
GfA ELEKTROMATEN UK Ltd Tournament Fields Business Park, Agincourt Rd, Warwick
CV34 6XZ
Stephan Kleine
CEO Signature
Düsseldorf, 09.03.2023
GfA ELEKTROMATEN GmbH & Co. KG
Wiesenstraße 81
D-40549 Düsseldorf
www.gfa-elektromaten.de
info@gfa-elektromaten.de
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>