BLAUBERG KFBK Filter Box User Manual
- June 10, 2024
- BLAUBERG
Table of Contents
BLAUBERG KFBK Filter Box
This user manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about the purpose, technical details,
operating principle, design, and installation of the KFBK, KFBV, KFBT unit and
all its modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work by workplace
safety rules as well as construction norms and standards applicable in the
territory of the country.
SAFETY REQUIREMENTS
-
All user’s manual requirements as well as the provisions of all the applicable local and national construction, electrical, and technical norms and standards must be observed when installing and operating the unit.
-
Disconnect the fan from the power supply before any connection, servicing and repair operations. The casing internals must be free of any foreign objects.
-
While mounting the unit, avoid compression of the casing!
-
Deformation of the casing may result in excessive noise.
-
Misuse of the unit and any unauthorized modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.). -
Do not use the unit in a hazardous or explosive environment containing spirits, gasoline, insecticides, etc.
-
Do not close or block the intake or extract vents in order to ensure efficient airflow.
-
Do not sit on the unit and do not put objects on it.
-
The information in this user’s manual was correct at the time of the document’s preparation. The Company reserves the right to modify the technical characteristics, design, or configuration of its products at any time to incorporate the latest technological developments.
-
Do not touch the unit with wet hands.
-
Do not touch the unit when barefoot.
-
This unit is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning the use of the unit by a person responsible for their safety. Children should be supervised to ensure that they do not play with the unit.
-
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.
THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE OF THE UNIT AS UNSORTED DOMESTIC WASTE.
PURPOSE
- The unit is a device for the purification of air circulating in ventilation systems. The unit is a part and is not designed for stand-alone operation.
- The product is intended for use in supply and recirculation ventilation systems for air purification.
- Not intended for use in residential and public areas.
- The unit is intended for suspended mounting.
- THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL, MENTAL, OR SENSORY CAPACITIES, OR THOSE WITHOUT THE APPROPRIATE TRAINING.
- THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING.
- THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORISED ACCESS BY UNATTENDED CHILDREN.
DELIVERY SET
Name | Number |
---|---|
Filter box | 1 pc. |
User’s manual | 1 pc. |
Packing box | 1 pc. |
DESIGNATION KEY
TECHNICAL DATA
- The unit is designed for operation in an enclosed area at ambient temperatures from -25 ˚C to + +55 ˚C at a relative humidity of up to 80% (at +25 ˚C).
- The ingress protection rating against access to hazardous parts and water ingress is IPХ4.
- The unit casing is made of galvanized steel.
- The unit design is constantly being improved, thus some models may be slightly different from those described in this manual.
Model
| Dimensions [mm]| Weight [kg]
---|---|---
D| B| H| L| L1
KFBK 100| 99| 210| 175| 215| 123| 1.4
KFBK 125| 124| 220| 209| 235| 143| 1.7
KFBK 150| 149| 270| 237| 250| 158| 2.5
KFBK 160| 159| 270| 237| 250| 158| 2.3
KFBK 200| 199| 320| 279| 275| 183| 3.1
KFBK 250| 249| 370| 327| 325| 233| 4.5
KFBK 315| 314| 430| 392| 425| 333| 6.7
Model
| Dimensions [mm]| Weight [kg]
---|---|---
D| B| H| L| L1
KFBV 100| 99| 233| 175| 215| 123| 1.4
KFBV 125| 124| 243| 209| 235| 143| 1.7
KFBV 150| 149| 293| 237| 250| 158| 2.2
KFBV 160| 159| 293| 237| 250| 158| 2.2
KFBV 200| 199| 343| 279| 275| 183| 3.1
KFBV 250| 249| 393| 327| 325| 233| 4.2
KFBV 315| 314| 453| 392| 425| 333| 6.3
Model
| Dimensions [mm]|
Weight [kg]
---|---|---
D| B| B1| H
KFBT 100| 99| 210| 230| 170| 2.41
KFBT 125| 124| 220| 240| 206| 2.69
KFBT 150| 149| 270| 290| 236| 3.20
KFBT 160| 159| 270| 290| 236| 3.26
KFBT 200| 199| 320| 340| 276| 3.76
KFBT 250| 249| 370| 390| 326| 4.39
KFBT 315| 314| 430| 450| 390| 5.17
Model
| Dimensions [mm]| Weight [kg]
---|---|---
B| B1| B2| H| H1| H2
KFBK 400×200| 400| 420| 440| 200| 220| 240| 2.4
KFBK 500×250| 500| 520| 540| 250| 270| 290| 4.1
KFBK 500×300| 500| 520| 540| 300| 320| 340| 4.4
KFBK 600×300| 600| 620| 640| 300| 320| 340| 5.2
KFBK 600×350| 600| 620| 640| 350| 370| 390| 5.8
KFBK 700×400| 700| 720| 740| 400| 420| 440| 6.7
KFBK 800×500| 800| 820| 840| 500| 520| 540| 7.9
KFBK 900×500| 900| 920| 940| 500| 520| 540| 8.4
KFBK 1000×500| 1000| 1020| 1040| 500| 520| 540| 8.9
Model
| Dimensions [mm]|
Weight [kg]
---|---|---
B| B1| B2| H| H1| H2| L
KFBT 400×200| 400| 420| 440| 200| 220| 240| 500| 6.2
KFBT 500×250| 500| 520| 540| 250| 270| 290| 600| 7.8
KFBT 500×300| 500| 520| 540| 300| 320| 340| 600| 8.3
KFBT 600×300| 600| 620| 640| 300| 320| 340| 600| 8.9
KFBT 600×350| 600| 620| 640| 350| 370| 390| 600| 9.5
KFBT 700×400| 700| 720| 740| 400| 420| 440| 720| 16.2
KFBT 800×500| 800| 820| 840| 500| 520| 540| 800| 20.4
KFBT 900×500| 900| 920| 940| 500| 520| 540| 800| 21.7
KFBT 1000×500| 1000| 1020| 1040| 500| 570| 540| 800| 23.5
DESIGN AND OPERATING PRINCIPLE
- The unit is a box with filters of different filter classes installed in it.
- The airflow direction is indicated by the arrow on the fan casing.
- The unit casing is made of galvanized steel.
- The filter box has connection flanges with rubber seals for a tight connection to the ducts.
- The hinged filter cover is equipped with lever locks for quick access to the replaceable filter element. The filter element is made of a non-woven fabric made of synthetic fibres, fixed on a steel frame.
MOUNTING AND SET-UP
- The design of filters for round air ducts allows the filter to be fixed with clamps in any position.
- Rectangular duct filters are installed upstream of the heater and the fan in the direction of airflow.
- Mounting is through a flange connection.
- While installing the unit, ensure convenient access for subsequent maintenance and repair.
- Fixing accessories are not included in the delivery set, to be purchased separately.
- Fastening must be carried out by a service technician.
- To get the best performance of the ventilation system and to minimize turbulence-induced air pressure losses, connect the straight air duct section to the spigots on both sides of the unit while installing.
Minimum straight air duct length:
- equal to 1 air duct diameter on the intake side
- equal to 3 air duct diameters on the outlet side
READ THE USER’S MANUAL BEFORE INSTALLING THE UNIT.
TECHNICAL MAINTENANCE
DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY MAINTENANCE OPERATIONS!
MAKE SURE THE UNIT IS DISCONNECTED FROM THE POWER MAINS BEFORE REMOVING THE
PROTECTION
Maintenance operations of the unit are required 3-4 times per year. Technical
maintenance includes regular cleaning of the unit and periodic cleaning of
filters. Dirty filters increase air resistance. The filters require cleaning
not less than 3-4 times per year.
Vacuum cleaning is allowed.
After two consecutive cleanings filters must be replaced.
For new filters contact the Seller.
Filter replacement sequence:
- Open the lever locks.
- Remove the filter from the unit.
- Re-assemble the unit in the reverse order.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with a temperature range from +5 ˚C to +40 ˚C and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport providing proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product complies with EU norms and standards on low voltage guidelines and
electromagnetic compatibility. We hereby declare that the product complies
with the provisions of Electromagnetic Compatibility (EMC) Directive
2014/30/EU of the European Parliament and of the Council, Low Voltage
Directive (LVD) 2014/35/EU of the European Parliament and of the Council and
CE-marking Council Directive 93/68/EEC. This certificate is issued following
test carried out on samples of the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer through warranty
repair at the factory free of charge. The warranty repair includes work
specific to the elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated through the replacement or repair of the unit components or a
specific part of such unit components.
The warranty repair does not include
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit are committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
CERTIFICATE OF ACCEPTANCE
Unit Type | Filter box |
---|---|
Model | |
Serial Number | |
Manufacture Date |
Quality Inspector’s Stamp
|
SELLER INFORMATION
Seller|
---|---
Address|
Phone Number|
E- mail|
Purchase Date|
This is to certify acceptance of the complete unit delivery with the user’s
manual. The warranty terms are acknowledged and accepted.
Customer’s Signature|
INSTALLATION CERTIFICATE
The……………………………………………………… unit is installed under the requirements stated in the present user’s manual.
Company name|
Address|
Phone Number|
Installation Technician’s Full Name|
Installation Date:| Signature:
The unit has been installed under the provisions of all the applicable local
and national construction, electrical and technical codes and standards. The
unit operates normally as intended by the manufacturer.
Signature:|
WARRANTY CARD
Unit Type | Filter box |
---|---|
Model | |
Serial Number | |
Manufacture Date | |
Purchase Date | |
Warranty Period | |
Seller |