DIGITECH Digital Clamp Meter Multimeter User Manual
- June 7, 2024
- Digitech
Table of Contents
- FUNCTIONS
- FUNCTION BUTTONS
- OPERATING INSTRUCTIONS
- CURRENT MEASUREMENTS
- DC VOLTAGE MEASUREMENTS
- AC VOLTAGE MEASUREMENTS
- RESISTANCE MEASUREMENT
- DIODE TEST
- CONTINUITY CHECK
- TEMPERATURE MEASUREMENT
- LINE (LIVE WIRE RECOGNITION) TEST
- MEASUREMENT SPECIFICATIONS
- CAPACITANCE
- FREQUENCY
- TEMPERATURE
- BATTERY INSTALLATION
- SPECIFICATIONS
- WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
1000 Amp AC/DC
SPECIALIST
Clampmeter User Manual
QM-1634
Thank you for purchasing this 1000 Amp AC/DC Clamp Meter. The reading range of
up to 1000A makes this clamp meter ideal for electrical fitters and
contractors working with high currents. Autoranging by default, the
clamp meter also features true RMS for accurate readings. Utilize the data
hold and relative measurement modes to log and compare data. The backlight
will assist you to view various readings in low-light conditions.
Please familiarise yourself with the functions of the clamp meter before use. We recommend retaining this manual for ease of reference.
- Improper use of this meter can cause damage, shock, injury, or death.
- Always remove the test leads before replacing the battery or fuses.
- Before using the meter, please inspect the condition of the test leads and the meter itself for any damage. If damage is present, please discontinue use.
- Do not measure voltage if the voltage on the terminals exceeds 1000V above earth ground.
- Use great care if voltages are greater than 30VAC RMS. Anything above this is considered a shock hazard.
- Do not apply voltage to the meter when the resistance is selected.
- Do not exceed the maximum limits of the input values shown in the specification tables on pages 10-12 of this manual.
- Remove the batteries from the meter if they will be unused for an extended period of time.
FUNCTIONS
Max. Display | 6000 Count |
---|---|
Basic Accuracy | 0.5% |
DC Voltage Range | 600mV – 1000V |
AC Voltage Range | 600mV – 750V |
DC Current Range | 60A – 1000A |
AC Current Range | 60A – 1000A |
Resistance | 600Ω – 60MΩ |
Capacitance | 10nF – 100mF |
Diode Test | Yes |
Continuity | Yes |
Frequency | 10Hz – 10MHz |
NCV (Non-Contact Voltage) Detection | Yes |
Duty Cycle | Yes |
Temperature | -20°C – 1000°C |
Relative Measurement | Yes |
Data Hold | Yes |
Autoranging | Yes |
Auto Power Off | Yes |
The battery compartment is at the rear of the multimeter.
FUNCTIONS
NCV Detection| Move the rotary switch to NCV position, hold the meter once
detect the voltage, the meter will be alarmed and LED flash
---|---
Current Clamp| Clamp the cable once measuring the current, the current reading
will be displayed in LCD
Flash Light| Turn on the flashlight and the light bulb will be lighted
NCV Indicator| Once the NCV function detects the voltage, the LED indicator
will be twinkled
Data Hold| Push this button to hold the readings in LCD, push one more time to
exit the data hold function
Clamp Opening Trigger| The max. jaw opening size is 23mm
Rotary Switch| Move the rotary switch for selecting the proper range and
function
Backlight Button| Push the button to activate the LCD backlight, push one more
time to exit. Once the rotary switch move to the current measurement range,
push this button can also turn on the flashlight
LCD Display| Readings and measurements are taken by the clamp meter appear in
this area.
Input Jacks| • V/TEMP: Positive input jack
• COM: Negative input jack
FUNCTION BUTTONS
SEL | Push SEL to shift AC/DC, °C / °F, resistance, diode & continuity test |
---|---|
RAN | Push this button to switch the proper range under-voltage and resistance |
measurement mode
HOLD| Push this button to hold the readings in LCD, press again to exit the
data hold function
Hz/%| Under AC voltage measurement, press Hz/% to selection function from
voltage frequency to duty cycle
REL| Under DC current measurement, press to measure relative current. Under AC
current measurement hold the button down to activate inrush/surge current
measurement. Hold the button down again to exit the function.
SYMBOL | DESCRIPTION | SYMBOL | DESCRIPTION |
---|---|---|---|
HOLD | Data Hold | Low Voltage Indication | |
Diode Test | Continuity | ||
NCV | Non-Contact Voltage Detection | INR | Inrush Current |
mV V | Unit of Voltage | uA mA A | Unit of Current |
Hz KHz MHz | Unit of Frequency | pF nF uF mF | Unit of Capacitance |
DC | Direct Current | AC | Alternating Current |
°F | Fahrenheit Temperature | °C | Centigrade Temperature |
% | Duty Cycle Measurement | REL | Relative Value Measurement |
TRMS | True RMS Measurement |
OPERATING INSTRUCTIONS
NOTE: Read and understand all Warning and Caution statements in this operation manual prior to using this meter. Set the rotary switch to the OFF position when the meter is not in use.
CURRENT MEASUREMENTS
WARNING:
- Disconnect the test leads before making clamp measurements
- To avoid electrical shock and/or damage to the meter, do not attempt to take any voltage measurement that might exceed 600V.
- Set the rotary switch to the proper current range, select the correct range based on measurement.
- Press the clamp opening trigger to open the jaws and fully enclose one conducting wire.
- Read the measured current value in the LCD display.
- If the display shows “ OL ”, which means overload, should select the higher range of measurements.
- To shift the AC or DC current by pressing the SEL button.
DC VOLTAGE MEASUREMENTS
WARNING:
- The max. input DC voltage is 600V DC, to avoid electrical shock and/or damage the meter, do not attempt to take any voltage measurement that might exceed 600V DC.
- Set the rotary switch to the position.
- Insert the black test lead banana plug into the COM jack, insert the red test lead banana plug into INPUT jack.
- Touch the black test probe tip to the negative side of the circuit; touch the red test lead probe tip to the positive side of the circuit.
- Read the voltage value in the display.
NOTE : Unstable display may occur, especially at the low voltage range measurement (like 200mV range), even no test leads insert at input terminals, and it is the normal situation and not influences the accuracy.
AC VOLTAGE MEASUREMENTS
WARNING:
- The max. input DC voltage is 600V DC, to avoid electrical shock and/or damage the meter, do not attempt to take any voltage measurement that might exceed 600V DC
- Set the function switch to the V position.
- Insert the black test lead banana plug into the COM jack, insert the red test lead banana plug into INPUT jack.
- Touch the black test probe tip to the negative side of the circuit; touch the red test lead probe tip to the positive side of the circuit.
- Read the voltage value in the display.
NOTE: The unstable display may occur, especially at the low voltage range measurement (like 2V range), even no test leads insert at input terminals, and it is a normal situation and not influences the accuracy.
RESISTANCE MEASUREMENT
WARNING:
- To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking any resistance measurements
- Set the function switch to position and press the SEL button to select the range.
- Insert the black test lead banana plug into the COM jack, insert the red test lead banana plug into the INPUT jack.
- Touch the black test probe tip to one side of the resistance of the under test; touch the red test probe tip to the other side.
- Read the resistance value in the display.
DIODE TEST
WARNING:
- To avoid electric shock, disconnect power to the unit under test and discharge all capacitors before taking the diode test
- Set the function switch to position and press the SEL button to choose diode test mode
- Insert the black test lead banana plug into COM jack, insert the red test lead banana plug into the INPUT jack.
- Place the red test lead on the anode of diode and black test lead on the cathode of diode.
- The meter will show the approx. the forward voltage of diode. Reverse voltage will indicate OL.
CONTINUITY CHECK
WARNING:
• To avoid electric shock, disconnect power to the unit under test and
discharge all capacitors before taking continuity check
- Set the function switch to position and press the SEL button to choose continuity check mode
- Insert the black test lead banana plug into COM jack, insert the red test lead banana plug into INPUT jack.
- Touch the test probe tips across the circuit or component under test.
- If the resistance is <30Ω, the audible signal will be sounded.
TEMPERATURE MEASUREMENT
- Set the function switch to °C °F position, the value of environmental temperature shows in the display. Press SEL button to shift °C mode or °F mode.
- Insert the red terminal of the temperature probe into the INPUT jack, black terminal into COM jack, place the temperature probe tip where needed to measure.
- Read the temperature on the display
RESISTANCE MEASUREMENT
WARNING:
Due to external interference source, this function may cause wrong voltage
detection, the detection result is for reference only. Set the function switch
to NCV position, contact the top part of the meter with the circuit under
test, the indicating LED will be flashed and an audible signal will be sounded
once detecting the voltage, the signal strength showed in LCD display.
NOTE:
- The detection result is for reference, do not determine the voltage by NCV detection ONLY
- Detection may interfere by socket design, insulation thickness and other variable conditions
- The external interference sources, such as flashlight, motor, etc, may cause the wrong detection
LINE (LIVE WIRE RECOGNITION) TEST
Set the rotary switch to LINE position, connect the black test lead to the COM jack and the red test lead to VΩ jack, hold the insulation part of black test lead and not put into the circuit under measurement; contact the red test lead to the living wire, the buzzer of the meter will be activated and red LED will be flickered, when the red test lead connects the earth line, the buzzer does not sound and LED will not flicker.
NOTE: When the circuit is in serious leakage (approx. over 15V), the red test lead even contacts the earth line, the buzzer of the meter will be sounded, and the LED will be flickered.
CAPACITANCE MEASUREMENT
WARNING:
• To avoid electric shock, disconnect power to the unit under test and
discharge all capacitors before taking capacitance measurement.
- Set the rotary switch to position and press the SEL button to choose mode.
- Insert the black test lead banana plug into COM jack, insert the red test lead banana plug into INPUT jack.
- Touch the test probe tips across the capacitance under test.
- Read the capacitance value in the display.
MEASUREMENT SPECIFICATIONS
Accuracy: ±(%readings + digit), warranty period: 12 months)
The following guide is based on the environmental temperature of
18-28°C and humidity <80%.
DC VOLTAGE
RANGE | RESOLUTION | ACCURACY |
---|---|---|
600mV | 0.1mV | ±(0.5% reading + 3 digits) |
6V | 0.001V | ±(0.8% reading + 5 digits) |
60V | 0.01V | |
600V | 0.1V | |
1000V | 1V | ±(1.0% reading + 5 digits) |
Input impedance: 10MΩ; Max. input voltage: 1000V DC / 750V AC RMS
AC VOLTAGE
RANGE | RESOLUTION | ACCURACY |
---|---|---|
600mV | 0.1mV | ±(1.0% reading + 10 digits) |
6V | 0.001V | ±(1.0% reading + 5 digits) |
60V | 0.01V | |
600V | 0.1V | |
750V | 1V | ±(1.2% reading + 5 digits) |
Input impedance: 10MΩ; Max. input voltage: 1000V DC / 750V AC RMS Frequency response: TRMS40Hz-1kHz
DC CURRENT
RANGE | RESOLUTION | ACCURACY |
---|---|---|
60A | 0.01A | ±(2.5% readings + 10 digits) |
600A | 0.1A | |
1000A | 1A |
AC CURRENT
RANGE | RESOLUTION | ACCURACY |
---|---|---|
60A | 0.01A | ±(2.5% reading + 10 digits) |
600A | 0.1A | |
1000A | 1A |
Frequency response: TRMS 40Hz-1kHz
RESISTANCE
RANGE | RESOLUTION | ACCURACY |
---|---|---|
600Ω | 0.1Ω | ±(1.0% reading + 10 digits) |
6kΩ | 0.001kΩ | ±(0.8% reading + 5 digits) |
60kΩ | 0.01kΩ | |
600kΩ | 0.1kΩ | |
6MΩ | 0.001MΩ | |
60MΩ | 0.01Ω | ±(2.0% reading + 10 digits) |
Overload protection: 250V DC or 250V AC RMS
DIYODE AND CONTINUITY
RANGE | FUNCTION |
---|---|
**** | Display approximate forward voltage of the diode, the reverse shows OL |
**** | Built-in buzzer will be sounded if resistance is less than 30Ω |
CAPACITANCE
RANGE | RESOLUTION | ACCURACY |
---|---|---|
10nF | 0.01nF | ±(4.0% reading + 25 digits) |
100nF | 0.1nF | ±(4.0% reading + 15 digits) |
1µF | 0.001µF | |
10µF | 0.01µF | |
100µF | 0.1µF | |
1mF | 1µF | ±(5.0% reading + 25 digits) |
10mF | 10µF | |
100mF | 100µF |
Overload protection: 250V DC or 250V AC RMS
FREQUENCY
RANGE | RESOLUTION | ACCURACY |
---|---|---|
10Hz | 0.01Hz | ±(0.5% reading + 2 digits) |
100Hz | 0.1Hz | |
1kHz | 0.001kHz | |
10kHz | 0.01kHz | |
100kHz | 0.1kHz | |
1MHz | 0.001MHz | |
10MHz | 0.01MHz |
Overload protection: 250V DC or 250V AC RMS
TEMPERATURE
RANGE | -20°C – 1000°C |
---|---|
Resolution | 1°C |
Accuracy
| -20°C – 0°C| ±(5% reading + 4 digits)
0°C – 400°C| ±(2% reading + 3 digits)
400°C – 1000°C| ±(3% reading + 3 digits)
RANGE| | 0°F – 1800°F
Resolution| 1°F
Accuracy
| -0°F – 50°F| ±(5% reading + 4 digits)
50°F – 750°F| ±(2% reading + 3 digits)
750°F – 1800°F| ±(3% reading + 3 digits)
Overload protection: 250V DC or 250V AC RMS
MAINTENANCE
WARNING:
- To avoid electric shock, disconnect the test leads from any source of voltage before removing the back cover or the battery or fuse covers
- To avoid electric shock, do not operate the meter until the battery and fuse covers are in place and fastened securely
CLEANING AND STORAGE
Periodically wipe the case with a damp cloth and mild detergent, do not use
abrasives or solvents. If the meter is not be used for a long time, remove the
battery and store it separately.
BATTERY INSTALLATION
To avoid false readings, replace the battery as soon as the battery indicator appears.
- Turn the power off and disconnect the test leads from the meter.
- Open the rear battery cover by using a screwdriver.
- Insert the battery into the battery holder, observing the correct polarity.
- Put the battery cover back in place, secure it with the screws.
SPECIFICATIONS
Operating Temperature: | 0~40°C |
---|---|
Operating Humidity: | < 80%RH |
Storage Temperature: | -10°C~60°C |
Storage Humidity: | < 70%RH (Remove Battery) |
Max Input Voltage | 1000VRMS |
Measuring Principle | Double Integral A/D Conversion |
Measurement Rate: | 2 per second, nominal |
Display | 3 3/4 LCD display, max. reading 5999 |
Range Selection | Auto Range Selection |
Over Range Indication | “OL” |
Power Supply: | 3 x AAA |
Clamp Size: | 23mm opening (approx) |
Dimensions: | 194(H) x 72(W) x 35(D)mm |
Weight: | 230g (including battery) |
BOX CONTENTS
1 x Clampmeter
1 x Test Leads
1 x Carry Case
1 x Temperature Probe
1 x User Manual
WARRANTY
This product is protected by a lifetime warranty (from the date of purchase) covering all product manufacturing defects/faults that may occur within this timeframe. This warranty does not cover damage caused by neglect, misuse, contamination, alteration, accident or abnormal conditions of operation or handling, including failures caused by use outside of the product’s specifications, or the normal wear and tear of mechanical components.
In the event that you suspect your product is defective/faulty, cease using the product when the suspected defect/fault arises and return the product along with proof of purchase to the place of purchase or distributor for assessment. Distributor contact details are available below.
If the assessment concludes that the product is indeed defective/faulty, the product will either be repaired or replaced at no cost to you. Our goods come with guarantees that cannot be excluded under the Australian Consumer Law. You are entitled to a replacement or refund for a major failure and compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure.
Distributed by:
TechBrands by Electus Distribution Pty. Ltd.
320 Victoria Rd, Rydalmere
NSW 2116 Australia
Ph: 1300 738 555
Int’l: +61 2 8832 3200
Fax: 1300 738 500