APC Smart-UPS X Uninterruptible Power Supply User Manual
- June 7, 2024
- APC
Table of Contents
Operation Manual
Smart-UPS™ X
Uninterruptible Power Supply
SMX750 VA
SMX1000 VA
SMX 1500 VA
120 Vac/230 Vac
Rack-Mount 2U
For Professional Business Applications – Not For Consumer Use
Important Safety Messages
SAVE THESE INSTRUCTIONS – This manual contains important instructions that
should be followed during the installation and maintenance of the Smart-UPS
and batteries.
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service or maintain it. The
following special messages may appear throughout this document or on the
equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of this symbol either to a “Danger” or “Warning” safety label
indicates that an electrical hazard exists which will result in personal
injury if the instructions are not followed. This is the safety alert symbol.
It is used to alert you to potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation that, if not avoided, will result in
death or serious injury.
WARNING
WARNING indicates a hazardous situation that, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation that, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Product Handling Guidelines
Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U
Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if
there is any damage.
Read the Safety Guide supplied with this unit before installing the UPS.
- Adhere to all local and national electrical codes.
- This UPS is intended for indoor use only.
- Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
- Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
- The battery typically lasts for two to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power, and frequent short-duration discharges will shorten battery life.
- Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.
Product Description
The APC by Schneider Electric Smart-UPS™ is a high-performance uninterruptible
power supply (UPS). The UPS provides protection for electronic equipment from
utility power blackouts, brownouts, sags, and surges, small utility power
fluctuations and large disturbances. The UPS also provides battery backup
power for connected equipment until utility power returns to safe levels or
the batteries are fully discharged.
This user manual is available on the enclosed CD and on the APC by Schneider
Electric Web site, www.apc.com.
Battery
CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE
- Replace the battery at least every 5 years.
- Replace the battery immediately when the UPS indicates battery replacement is necessary.
- Replace battery at the end of its service life.
- Replace batteries with the same number and type of batteries as originally installed in the equipment.
- Replace the battery immediately when the UPS indicates a battery overtemperature condition, or UPS internal overtemperature, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.
- *Replace all battery modules (including the modules in External Battery Packs) which are older than one year, when installing additional battery packs or replacing the battery module(s).
Failure to follow these instructions could result in equipment damage and minor or moderate injury.
*Contact APC by Schneider Electric Worldwide Customer Support to determine the age of the installed battery modules.
Product Overview
Front Panel Features
- Battery
- Battery connector
- Display interface
- Bezel
Rear Panel Features
- SmartSlot
- External battery pack connector
- Outlets
- EPO connector
- USB port
- Serial port
- Chassis ground screw
- UPS input
- Circuit breaker
Specifications
Environmental Specifications
For additional specifications, refer to the APC by Schneider Electric Web site
at www.apc.com.
Temperature | Operating | 0° to 40° C (32° to 104° F) |
---|---|---|
Storage | -15° to 45° C (5° to 113° F) |
Charge UPS battery every six months
Maximum
Elevation| Operating| 3,000 m (10,000 11)
Storage| 15,000 m (50,000 ft)
Humidity| 0% to 95% relative humidity, non-condensing
Installation
UPS
For UPS installation information, refer to the Smart-UPS X Installation Guide
that is included with the. The guide is also available on the enclosed CD and
the APC by Schneider Electric Web site at www.apc.com.
Network Management Card
For installation information, refer to the user manual provided with the
Network Management Card (NMC). The user manual is also available on the APC by
Schneider Electric Web site at www.apc.com.
External Battery Pack
For installation information, refer to the SMX48RMBP2U external battery pack
Installation Guide that is included with the external battery pack (XLBP). The
guide is also available on the enclosed CD and the APC by Schneider Electric
Web site at www.apc.com.
Operation
Connect Equipment to the UPS
CAUTION
RISK OF ELECTRIC SHOCK
- Adhere to all national and local electrical codes.
- Wiring must be performed by a qualified electrician.
- Always connect the UPS to a grounded outlet.
Failure to follow these instructions could result in minor or moderate injury.
Note: The UPS will charge to 90% capacity in the first three hours of normal operation. Do not expect full battery runtime capability during this initial charge period.
-
Connect the equipment to the outlets on the rear panel of the UPS.
-
Connect the UPS to the building utility power.
Always connect the UPS to a two-pole, three-wire, grounded source. -
To use the UPS as a master ON/OFF switch, turn on all the equipment that is connected to the UPS.
-
Press the ON/OFF button on the front panel of the UPS to turn on the UPS and all connected equipment.
-
See “Controllable Outlet Groups” on page 9 for information on how to use the Controllable Outlet Groups.
Basic Connectors
| Serial port: Connect to a computer to use power management software.
---|---
| USB port: Connect to a computer to use power management software.
Note: Serial and USB communication can not be used simultaneously.
| External Battery Pack connector: Connect external battery packs to
provide extended runtime during
power outages. The UPS can support up to five external battery packs.
| Ground Screw: The UPS features a ground screw for connecting the ground
lead on surge suppression
devices such as telephone and network line protectors. When connecting a
ground cable, disconnect the
UPS from utility power.
Display Panel
Overview
- Online LED
- UPS Output ON/OFF butto
- On Battery LED
- Site Wiring Fault LED
- Replace Battery LED
- Display screen
- UP/DOWN arrow buttons
- ENTER button
- ESCAPE button
Using the display interface
Use the UP/DOWN arrow buttons to scroll through the main menu options. Press
ENTER to view the submenus under each main menu option. Press ESCAPE to exit a
submenu and return to the main menu.
Standard menus
The Standard menus are the most commonly used menus for the UPS.
Menu | General Functions |
---|---|
Status | View basic information about the UPS: |
•Operating mode
•Switched Outlet status, On or Off
•Efficiency of the UPS
•Information about the load
•Battery capacity
•Estimated runtime
•Input and output voltage and frequency
•Information about the last transfer to battery power
•Self-test results
•SmartSlot Card information
Configuration| Configure the settings for the UPS:
•Language
•Local power quality: Good, Fair, Poor
•Choose Standard or Advanced menus
•UPS Test settings
•Reset to Factory Defaults
Test & Diags| Use the Test & Diags menu to have the UPS perform a self-
test.
About| Display information about this unit:
•Unit model number
•Serial number
•Battery information
•Model number
•Installation date
•Suggested battery replacement date
•UPS firmware version
Advanced menus
The Advanced menus provide additional options for the UPS and are available
only if the display interface is configured to use the Advanced menus.
Menu | General Functions |
---|---|
Status | View detailed information about the UPS: |
•Energy meter
•Load current
•Status of the SWITCHED OUTLET GROUP(S)
•Battery voltage
•Efficiency
Configuration| Configure advanced settings for the UPS:
•MAIN AND SWITCHED OUTLET GROUPS—delays and settings
•High and lower transfer points
•Sensitivity settings
•Date of last battery replacement
•Output voltage
•Battery settings
•Number of battery packs (not available on all models)
•Reset energy meter
•UPS test settings
Control| Control the MAIN AND SWITCHED OUTLET GROUPS to turn on, turn
off, shutdown, or reboot.
Test & Dins| Perform UPS test and diagnostic functions such as user
interface testing, battery tests, and battery calibration.
Log| View the logs for information about any changes to the UPS and any
alerts.
About| View information about the unit:
•Hardware version
•Software version
•NMC information (if applicable)
•SmartSlot Card information (if applicable)
Configuration
UPS Settings
Startup settings
Configure these settings at initial start-up, using the display interface or
PowerChute™ software.
Note: During start-up, use the display interface to configure these
settings. If nothing is selected, the unit will use default settings.
Function | Factory Default | Options | Description |
---|---|---|---|
Language | English | •English |
•French
•German
•Spanish
•Italian
•Portuguese| The language for the display interface. Language options will
vary by model.
Local Power Quality| Good| •Good
•Fair
•Poor| Select the quality of input utility power.
•If Good is selected, the unit will go on battery power more often to provide
the cleanest power supply to the connected equipment.
•If Poor is selected, the UPS will tolerate more fluctuations in power and
will go on battery power less often.
If unsure of the local power quality, select Good.
Menu Type| Standard| Standard or Advanced| The Standard menus display a
limited set of menus and options. The Advanced menus include all parameters.
General Settings
Configure these settings at any time, using the display interface or
PowerChute software
Function | Factory Default | Options | Description |
---|---|---|---|
High Transfer point | 120 V: 140 Vac | 120 V: 140-150 Vac | To avoid unnecessary |
battery usage, set the transfer point higher if the utility voltage is
chronically high and the connected equipment is known to work under this
condition. The POWER QUALITY setting will automatically change this setting.
Note: Use the Advanced Menus to configure this setting.
230 V: 280 Vac| 230 V: 280-300 Vac
Low
Transfer Point| 120 V: 85 Vac| 120 V: 75-85 Vac| Set the transfer point lower
if the utility voltage is chronically low and the connected equipment can
tolerate this condition.This setting may also be adjusted using the power
quality setting.
Note: Use the Advanced Menus to configure this setting.
230 V: 170 Vac| 230 V: 150-170 Vac
Nominal Output Voltage| 230 V: 230 Vac 120 V: 120 Vac| 230 V: 220, 230, 240
Vac 120 Vac: N/A| Set the nominal output voltage of the UPS on battery. This
is available on 230 V models only.
Transfer Sensitivity| High| High, Low, Medium| Select the level of sensitivity
to power events that the UPS will tolerate.
•High: The UPS will go on battery power more often to provide the cleanest
power supply to the connected equipment.
•Low: The UPS will tolerate more fluctuations in power and will go on battery
power less often.
If the connected load is sensitive to power disturbances, set the sensitivity
to High.
---|---|---|---
Low Battery Alert| 150 sec| Set the value in seconds| The UPS will emit an
audible alarm when the remaining runtime has reached this level.
Date of Last Battery Replacement| Date set at the factory| Reset this date
when the battery module is replaced.
Audible Alarm| On| On/Off| The UPS will mute all audible alarms if this is set
to Off or when the display buttons are pressed.
Battery Self-Test Interval Setting| On start-up and every 14 days since the
last test| •Never
•Start up only
•Frequency of test (days)| The interval at which the UPS will execute a self-
test.
Reset to Factory Default| No| Yes/No| Restore the UPS factory default
settings.
Controllable Outlet Groups
Overview
The rear panel of the UPS has multiple outlets, some are grouped into
Controllable Outlet Groups, all of the other outlets are the UPS outlets,
which function as an outlet group. All of these groups can independently turn
off, turn on, shut down, and reboot connected equipment.
The Controllable Outlet Groups can be commanded to do the following:
-
Turn off: Disconnect from power immediately and restart only with a manual command
-
Turn on: Connect to power immediately
-
Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when utility power becomes available
-
Reboot: Shut down and restart
In addition, the Controllable Outlet Groups and the UPS outlets can be configured to do the following: -
Turn on or off in a specified sequence
-
Automatically turn off or shut down when various conditions occur
Note: If the Controllable Outlet Groups are not configured, all of the outlets on the unit will still provide battery backup power.
Model-specific controllable outlet groups
Using the controllable outlet groups and UPS outlets
Note: UPS outlets function as a master switch. They turn on first when
power is applied, shut off last when there is a power outage and battery
runtime has been exhausted.
The UPS outlets must be turned on for the Controllable Outlet Groups to turn
on.
-
Connect critical equipment to the UPS outlets (The 1500 VA units do not have UPS outlets. Connect all critical equipment to the same outlet group.)
-
Connect peripheral equipment to the Controllable Outlet Groups.
– Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery the runtime can be added to a short power-off delay
– If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups
– Equipment that needs to reboot independently from other equipment should be added to a separate group -
Use the Configuration menus to configure how the Controllable Outlet Groups will react in the event of a power outage.
Customize the controllable outlet groups and the UPS outlets
Use the Control menus to change the controllable outlet groups and the UPS
outlet settings.
Function | Factory Default | Options | Description |
---|---|---|---|
Name String Outlet Group | Outlet Group I | Edit these names using an external |
interface, such as the Network Management Card web interface.
UPS Name String| UPS Outlets
Turn On Delay| 0 sec| Set the value in seconds| The amount of time the UPS or
Controllable Outlet Group will wait between receiving the command to turn on
and the actual startup.
Turn Off Delay| 0 Net.| Set the value in seconds| The amount of time that the
UPS or Controllable Outlet Group will wait between receiving the command to
turn off and the actual shut down.
Reboot Duration| 4 sec| Set the value in seconds| The amount of time that the
UPS or Controllable Outlet Group must remain off before it will restart.
Minimum Return Time| 0 sec| Set the value in seconds| The amount of battery
runtime that must be available before the UPS or Controllable Outlet Group
will turn on.
Load Shed
On Batter)| Disabled| •Shutdown with Delay
•Shutdown immediately
•Turn off immediately
•Turn off with delay
•Disabled| When the unit switches to battery power, the UPS can disconnect
power to the Controllable Outlet Groups to save runtime.
Configure this delay time, use the LOAD SHED TIME WHEN ON BATTERY setting.
Load Shed Time when On Battery| Disabled| Set the value in seconds| The amount
of time the outlets will function on battery power before they will turn off.
Load Shed On Runtime| Disabled| •Shutdown with delay
•Shutdown immediately
•Turn off immediately
•Turn off with delay
•Disabled| When the battery runtime falls below the specified value, the
Controllable Outlet Group will turn off. Configure this time using the LOAD
SHED RUNTIME
R
REMAINING setting.
---|---|---|---
Load Shed On Runtime Remaining| Disabled| Set the value in seconds| When the
remaining runtime reaches this level, the Controllable Outlet Group will turn
off.
Load Shed on Overload| Disabled| •Disabled
•Enabled| In the event of an overload (greater than 100% output), the
Controllable Outlet Group will immediately turn off to conserve power for
critical loads. The Controllable Outlet Group will only turn on again with a
manual command.
Network Management Card Settings
These settings are available only on units that have a Network Management Card
(NMC) and are set in the factory.
These settings can only be modified using an external interface, like the NMC
web interface.
- NMC IP Address Mode
- NMC IP Address
- NMC Subnet Mask
- NMC Default Gateway
Emergency Power Off
Overview
The Emergency Power Off (EPO) option is a feature that will immediately
disconnect all connected equipment from mains power. The UPS will immediately
shut down and will not switch to battery power.
Connect each UPS to the EPO switch. If multiple units are to be controlled
with an EPO switch, each UPS must be connected separately to the EPO switch.
The UPS must be restarted for power to return to connected equipment. Press
the ON/OFF button on the front panel of the UPS.
CAUTION
RISK OF ELECTRIC SHOCK
- Adhere to all national and local electrical codes.
- Wiring must be performed by a qualified electrician.
- Always connect the UPS to a grounded outlet.
Failure to follow these instructions could result in minor or moderate injury.
Normally open contacts
- If the EPO switch or relay contacts are normally open, insert the wires from the switch or contacts at pins 1 and 2 of the EPO terminal block. Use 16-28 AWG wire.
- Secure the wires by tightening the screws.
If the contacts are closed, the UPS will turn OFF and power will be removed from the load.
Normally closed contacts
- If the EPO switch or relay contacts are normally closed, insert the wires from the switch or contacts at pins 2 and 3 of the EPO terminal block. Use 16-28 AWG wire.
- Insert a wire jumper between pins 1 and 2.
Secure the wires by tightening the three screws at positions 1, 2, and 3.
If the contacts are opened, the UPS will turn OFF and power will be removed from the load.
Note: Pin 1 is the power source for the EPO circuit, it provides a few
milliamperes of 24 V power.
If the normally closed (NC) EPO configuration is used, the EPO switch or relay
should be rated for dry circuit applications, the rating should be for low
voltage and low current applications. This normally implies the contacts is
gold-plated.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect the
EPO interface only to other SELVcircuits. The EPO interface monitors circuits
that have no determined voltage potential. SELV circuits are controlled by a
switch or relay properly isolated from utility power. To avoid damage to the
UPS, do not connect EPO interface to any circuit other than a SELV circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
- CL2: Class 2 cable for general use.
- CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
- CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
- CLEX: Limited use cable for use in dwellings and for use in raceways.
- Installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).
- Installation in countries other than Canada and the USA: Use standard low voltage cable in accordance with national and local regulations.
Troubleshooting
Problem and Possible Cause | Solution |
---|
The UPS will not turn on or there is no output
The unit has not been turned on.| Press the ON button once to turn on the UPS.
not connected to utility The UPS is ty power| Be sure that the power cable is
securely connected to the unit and to the utility power supply.
The input circuit breaker has tripped.| Reduce the load to the UPS, disconnect
nonessential equipment and reset the circuit breaker.
The unit shows very low or no input utility voltage.| Check the utility power
supply to the UPS by plugging in a table lamp. If the light is very dim, check
the utility voltage.
The battery connector plug is not securely connected.| Be sure that all
battery connections are secure.
UPS has detected an internal fault| Do not attempt to use the UPS. Unplug the
UPS and have it serviced immediately.
The UPS is operating on battery, while connected to utility power
The input circuit breaker has tripped.| Reduce the load to the UPS, disconnect
nonessential equipment and reset the circuit breaker.
There is very high, very low, or distorted input line voltage.| Move the UPS
to a different outlet on a different circuit. Test the input voltage with the
utility voltage display. If acceptable to the connected equipment, reduce the
UPS sensitivity.
UPS is emitted intermittent beeps
The UPS is in normal operation.| None. The UPS is protecting the connected
equipment.
I PS does not provide expected backup time
The UPS battery is weak due to a recent outage or is near the end of its
service life.| Charge the battery. Batteries require recharging after extended
outages and wear out faster when put into service often or when operated at
elevated temperatures. If the battery is near the end of its service life,
consider replacing the battery even if the replace battery indicator is not
yet illuminated.
The UPS is overloaded.| Check the UPS load display. Unplug unnecessary
equipment, such as printers.
Display interface LEDs flash sequentially
The UPS has been shut down remotely through software or an optional accessory
card.| None. The UPS will restart automatically when utility power is
restored.
The Site Wiring Fault LED illuminates
The UPS displays a message and emits a constant beeping sound
UPS has detected an internal fault.| Do not attempt to use the UPS. Tin the
UPS off and have it serviced immediately.
All LEDs are illuminated and the UPS is plugged into a wall outlet
The UPS has shut down and the battery has discharged from an extended outage.|
None. The UPS will retum to normal operation when the power is restored and
the battery has a sufficient charge.
The Replace Battery LED is illuminated
The battery has a weak charge.| Allow the battery to recharge for at least
four hours. Then, perform a self-test If the problem persists after
recharging. replace the battery.
The replacement battery is not properly connected.| Be sure that the battery
connector is securely connected.
The UPS displays a site wiring fault message
Wiring faults detected include missing ground, hot-neutral. polarity reversal,
and overloaded neutral circuit| If the UPS indicates a site wiring fault, have
a qualified electrician inspect the building wiring. (Applicable for 120 V
units only.)
Service
If the unit requires service, do not return it to the dealer. Follow these steps:
-
Review the Troubleshooting section of the manual to eliminate common problems.
-
If the problem persists, contact APC by Schneider Electric Customer Support through the Web site, www.apc.com.
a. Note the model number and serial number and date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
b. Call APC by Schneider Electric Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
c. If the unit is under warranty, the repairs are free.
d. Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric
Web site for country-specific instructions. -
Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.
a. Always DISCONNECT THE UPS BATTERIES before shipping. The United States
Department of Transportation (DOT), and the International Air Transport Association (IATA) regulations require that UPS batteries be disconnected before shipping. The internal batteries may remain in the UPS.
b. External Battery Pack products are de-energized when disconnected from the associated UPS product. It is not necessary to disconnect the internal batteries for shipping. Not all units utilize an external battery pack. -
Write the RMA# provided by Customer Support on the outside of the package.
-
Return the unit by the insured, prepaid carrier to the address provided by Customer Support.
Transport the unit
- Shut down and disconnect all connected equipment.
- Disconnect the unit from utility power.
- Disconnect all internal and external batteries (if applicable).
- Follow the shipping instructions outlined in the Service section of this manual.
Limited Factory Warranty
Schneider Electric IT Corporation (SEIT), warrants its products to be free
from defects in materials and workmanship for a period of two (2) years from
the date of purchase. The SEIT obligation under this warranty is limited to
repairing or replacing, at its own sole option, any such defective products.
Repair or replacement of a defective product or part thereof does not extend
the original warranty period.
This warranty applies only to the original purchaser who must have properly
registered the product within 10 days of purchase. Products may be registered
online at warranty.apc.com.
SEIT shall not be liable under the warranty if its testing and examination
disclose that the alleged defect in the product does not exist or was caused
by end user or any third person misuse, negligence, improper installation,
testing, operation or use of the product contrary to SEIT recommendations of
specifications. Further, SEIT shall not
be liable for defects resulting from: 1) unauthorized attempts to repair or
modify the product, 2) incorrect or inadequate electrical voltage or
connection, 3) inappropriate on site operation conditions, 4) Acts of God, 5)
exposure to the elements, or 6) theft. In no event shall SEIT have any
liability under this warranty for any product where the serial number has been
altered, defaced, or removed.
EXCEPT AS SET FORTH ABOVE, THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY
OPERATION OF LAW OR OTHERWISE, APPLICABLE TO PRODUCTS SOLD, SERVICED OR
FURNISHED UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH.
SEIT DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY, SATISFACTION AND
FITNESS FOR A PARTICULAR PURPOSE.
SEIT EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED, OR AFFECTED BY
AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF, SEIT RENDERING OF TECHNICAL
OR OTHER ADVICE OR SERVICE IN CONNECTION WITH THE PRODUCTS.
THE FOREGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL
OTHER WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE CONSTITUTE
SEIT’S SOLE LIABILITY AND PURCHASER EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH
WARRANTIES. SEIT WARRANTIES EXTEND ONLY TO THE ORIGINAL PURCHASER AND ARE NOT
EXTENDED TO ANY THIRD PARTIES.
IN NO EVENT SHALL SEIT, ITS OFFICERS, DIRECTORS, AFFILIATES OR EMPLOYEES BE
LIABLE FOR ANY FORM OF INDIRECT, SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES,
ARISING OUT OF THE USE, SERVICE OR INSTALLATION OF THE PRODUCTS, WHETHER
SUCH DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT, NEGLIGENCE
OR STRICT LIABILITY OR WHETHER SEIT HAS BEEN ADVISED IN ADVANCE OF THE
POSSIBILITY OF SUCH DAMAGES. SPECIFICALLY, SEIT IS NOT LIABLE FOR ANY COSTS,
SUCH AS LOST PROFITS OR REVENUE, WHETHER DIRECT OR INDIRECT, LOSS OF
EQUIPMENT, LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA, COSTS OF
SUBSTITUTES, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NOTHING IN THIS LIMITED WARRANTY SHALL SEEK TO EXCLUDE OR LIMIT SEIT
LIABILITY FOR DEATH OR PERSONAL INJURY RESULTING FROM ITS NEGLIGENCE OR ITS
FRAUDULENT MISREPRESENTATION OF TO THE EXTENT THAT IT CANNOT BE EXCLUDED OR
LIMITED BY APPLICABLE LAW.
To obtain service under warranty you must obtain a Returned Material
Authorization (RMA) number from customer support. Customers with warranty
claims issues may access the SEIT worldwide customer support network through
the APC by Schneider Electric Web site: www.apc.com.
Select your country from the country selection drop-down menu. Open the
Support tab at the top of the web page to obtain information for customer
support in your region. Products must be returned with transportation charges
prepaid and must be accompanied by a brief description of the problem
encountered and proof of date and place of purchase.
APC™ by Schneider Electric
Worldwide Customer Support
Customer support for this or any other APC by Schneider Electric product is available at no charge in any of the following ways:
-
Visit the APC by Schneider Electric Web site to access documents in the APC by Schneider Electric Knowledge Base and to submit customer support requests.
– www.apc.com (Corporate Headquarters)
Connect to localized APC by Schneider Electric Web sites for specific countries, each of which provides customer support information.
– www.apc.com/support/
Global support searching APC by Schneider Electric Knowledge Base and using e-support. -
Contact the APC by Schneider Electric Customer Support Center by telephone or e-mail.
– Local, country-specific centers: go to www.apc.com/support/contact for contact information.
– For information on how to obtain local customer support, contact the APC by Schneider Electric representative or other distributors from whom you purchased your APC by Schneider Electric product.
© 2021 APC by Schneider Electric. APC, the APC logo, Smart-UPS and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are property of their respective owners.
990-3458F
Documents / Resources
| APC
Smart-UPS X Uninterruptible Power
Supply
[pdf] User Manual
Smart-UPS X Uninterruptible Power Supply
---|---
References
- APC, a flagship brand of Schneider Electric - APC USA
- APC, a flagship brand of Schneider Electric - APC USA
- APC, a flagship brand of Schneider Electric - APC USA
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>