LG Electronics LG-UUA1 Air Conditioner Instruction Manual
- June 3, 2024
- LG Electronics
Table of Contents
LG-UUA1 Air Conditioner
ENGLISH ITALIANO ESPAÑOL FRANÇAIS DEUTSCH
INSTALLATION MANUAL
AIR CONDITIONER
ES TINA NEDERLANDS POLSKI LIMBA ROMÂN
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only. Please retain this installation manual
for future reference after reading it thoroughly.
Single Inverter Outdoor Unit Original instruction (R32)
[Representative] LG Electronics Inc. EU Representative : LG Electronics
European Shared Service Center B.V. Krijgsman 1, 1186 DM Amstelveen, The
Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro,
Seongsan-gu, Changwon-si, Gyeongsangnam-do, KOREA
MFL71675701 Rev.00_101520
www.lg.com
Copyright © 2019 – 2020 LG Electronics Inc. All Rights Reserved.
ENGLISH
2 MODEL DESIGNATION
MODEL DESIGNATION
Product information
– Product Name : Air conditioner – Model Name :
U U D 1 U3 0
Serial number Outdoor unit chassis name Electrical rating 1 : 1Ø, 220-240V,
50Hz 3 : 3Ø, 380-415V, 50Hz Module name & Nominal capacity range based on
`kBtu/h’ A : 9~18 B : 18~30 C : 24~36 D : 36~60 Type U : Outdoor unit Model
Type U : Universal model
– Additional Information : serial number is refer to the barcode on the
product.
– Max allowable pressure High side : 4.2 MPa / 4.32 MPa (it can be different
by model)
– Max allowable pressure Low side : 2.4 MPa – Refrigerant : R32
Airborne Noise Emission
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working
levels.
Whilst there is a correlation between the emission and exposure levels, this
cannot be used reliably to determine whether or not further precautions are
required.
Factor that influence the actual level of exposure of the workforce include
the characteristics of the work room and the other sources of noise, i.e. the
number of equipment and other adjacent processes and the length of time for
which an operator exposed to the noise. Also, the permissible exposure level
can vary from country to country.
This information, however, will enable the user of the equipment to make a
better evaluation of the hazard and risk.
ENGLISH
TIPS FOR SAVING ENERGY 3
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you
use the air conditioner. You can use your air conditioner more efficiently by
referring to the instructions below:
· Excessive cooling may be harmful to your health and may consume more
electricity. · Block sunlight with blinds or curtains while you are operating
the air conditioner. · Keep doors or windows closed while you are operating
the air conditioner. · Adjust the direction of the air flow vertically or
horizontally to circulate indoor air. · Speed up the fan to cool or warm
indoor air quickly, in a short period of time. · Open windows regularly for
ventilation as the indoor air quality may deteriorate if the air
conditioner is used for many hours. · Clean the air filter once every 2 weeks.
Dust and impurities collected in the air filter may
block the air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of
purchase or for warranty purposes. Write the model number and the serial
number here:
Model number : Serial number : You can find them labeled on the side of each
unit. Dealer’s name : Date of purchase :
ENGLISH
4 IMPORTANT SAFETY INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS
Read the precautions in this manual carefully before operating the unit.
This symbol indicates that the Operation Manual should be read carefully.
This appliance is filled with flammable refrigerant. (for R32)
This symbol indicates that a service person should be handling this equipment
with reference to the Installation Manual.
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and
ensure peak performance of your product.
! WARNING
Serious injury or death can result if directions are ignores.
! CAUTION
Minor injury or product damage can result if directions are ignored.
! WARNING
· Installation or repairs made by unqualified persons can result in hazards to
you and others. Refrigeration work must be performed by a qualified person who
is “F-Gas” registered.
· Installation work must be performed in accordance with the National Electric
Code by qualified and authorized personnel only.
· The information contained in the manual is intended for use by a qualified
service technician familiar with safety procedures and equipped with the
proper tools and test instruments.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS 5
· Failure to carefully read and follow all instructions in this manual can
result in equipment malfunction, property damage, personal injury and/or
death. (for R32)
· Compliance with national gas regulations shall be observed
Installation · Do not use a defective or underrated circuit breaker. Use the
correctly rated breaker and fuse. There is risk of fire or electric shock. ·
For electrical work, contact the dealer, seller, a qualified electrician, or
an Authorized Service Center. Do not disassemble or repair the product by
yourself. There is risk of fire or electric shock. · Always ground the product
as per the wiring diagram. Do not connect the ground wire to gas or water
pipes lightening rod or telephone ground wire. There is risk of fire or
electric shock. · Install the panel and the cover of control box securely.
There is risk of fire or electric shock due to dust , water etc. · Use the
correctly rated breaker or fuse. There is risk of fire or electric shock. · Do
not modify or extend the power cable. If power cable is damaged or has
deteriorated, then it must be replaced. There is risk of fire or electric
shock. · For installation, removal or reinstall , always contact the dealer or
an Authorized Service Center. There is risk of fire, electric shock,
explosion, or injury. · Do not install the product on a defective installation
stand. Be sure that the installation area does not deteriorate with age. It
may cause product to fall.
ENGLISH
6 IMPORTANT SAFETY INSTRUCTIONS
· Never install the outdoor unit on a moving base or a place from where it can
fall down. The falling outdoor unit can cause damage or injury or even death
of a person.
· In outdoor unit the step-up capacitor supplies high voltage electricity to
the electrical components. Be sure to discharge the capacitor completely
before conducting the repair work. A charged capacitor can cause electrical
shock.
· When installing the unit, use the installation kit provided with the
product. Otherwise the unit may fall and cause severe injury.
· Indoor/outdoor wiring connections must be secured tightly and the cable
should be routed properly so that there is no force pulling the cable from the
connection terminals. Improper or loose connections can cause heat generation
or fire.
· Safely dispose off the packing materials. Like screws, nails, batteries,
broken things etc after installation or svc and then tear away and throw away
the plastic packaging bags. Children may play with them and cause injury.
· Be sure to check the refrigerant to be used. Please read the label on the
product. Incorrect refrigerant used can prevent the normal operation of the
unit.
· Do not turn on the breaker or power under condition that front panel,
cabinet, top cover, control box cover are removed or opened. Otherwise, it may
cause fire, electric shock, explosion or death.
· Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air
purge. Do not compress air or Oxygen and do not use Flammable gases.
Otherwise, it may cause fire or explosion. – There is the risk of death,
injury, fire or explosion.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS 7
· The appliance shall be stored in a room without continuously operating
ignition sources (for example: open flames, an operating gas appliance or an
operating electric heater)
· Do not use means to accelerate the defrosting process or to clean, other
than those recommended by the manufacturer.
· Do not pierce or burn refrigerant cycle part. · Be aware that refrigerants
may not contain an odour. · Keep any required ventilation openings clear of
obstruction. · The appliance shall be stored in a well-ventilated area where
the room size corresponds to the room area as specified for operation. (for
R32) · The appliance should only be transported by two or more people holding
the appliance. · Mechanical connections shall be accessible for maintenance
purposes. · The appliance shall be disconnected from its power source during
service and when replacing parts. · The appliance shall be installed in
accordance with national wiring regulations.
Operation · When the product is soaked (flooded or submerged) in water,
contact an Authorized Service Center for repair before using it again. There
is risk of fire or electric shock. · Be sure to use only those parts which are
listed in the svc parts list. Never attempt to modify the equipment. The use
of inappropriate parts can cause an electrical shock, excessive heat
generation or fire. · Do not touch , operate, or repair the product with wet
hands. Hold the plug by hand when taking it out. There is risk of electric
shock or fire.
ENGLISH
8 IMPORTANT SAFETY INSTRUCTIONS
· Do not place a heater or other heating appliances near the power cable.
There is risk of fire and electric shock.
· Do not allow water to run into electric parts. Install the unit away from
water sources. There is risk of fire, failure of the product, or electric
shock.
· Do not store or use or even allow flammable gas or combustibles near the
product. There is risk of fire.
· Do not use the product in a tightly closed space for a long time. Perform
ventilation regularly. Oxygen deficiency could occur and hence harm your
health.
· Do not open the front grille of the product during operation. (Do not touch
the electrostatic filter, if the unit is so equipped.) There is risk of
physical injury, electric shock, or product failure.
· If strange sound, smell or smoke comes from product. Immediately turn the
breaker off or disconnect the power supply cable. There is risk of electric
shock or fire.
· Ventilate the product room from time to time when operating it together with
a stove, or heating element etc. Oxygen deficiency can occur and hence harm
your health.
· When the product is not to be used for a long time, disconnect the power
supply plug or turn off the breaker. There is risk of product damage or
failure, or unintended operation.
· Take care to ensure that nobody especially kids could step on or fall onto
the outdoor unit. This could result in personal injury and product damage.
· Take care to ensure that power cable could not be pulled out or damaged
during operation. There is risk of fire or electric shock.
· Do not place ANYTHING on the power cable. There is risk of fire or electric
shock.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS 9
· When flammable gas leaks, turn off the gas and open a window for ventilation
before turning on the product. Do not use the telephone or turn switches on or
off. There is risk of explosion or fire.
· Keep any required ventilation openings clear of obstruction · Turn off all
devices that cause fire when the refrigerant leaks.,
ventilate the room (example : opening the window or using the ventilation),
and contact with dealer who you purchased the unit.
! CAUTION
Installation · Two or more people must lift and transport the product. Avoid
personal injury. · Do not install the product where it will be exposed to sea
wind (salt spray) directly. It may cause corrosion on the product. · Install
the drain hose to ensure that the condensed water is drained away properly. A
bad connection may cause water leakage. · Keep level even when installing the
product. To avoid vibration or noise. · Do not install the product where the
noise or hot air from the outdoor unit could damage or disturb the
neighborhoods. It may cause a problem for your neighbors and hence dispute. ·
Always check for gas (refrigerant) leakage after installation or repair of
product. Low refrigerant levels may cause failure of product. · Please install
safely at a place that can sufficiently endure the weight of the product. If
the strength is not sufficient, the product may fall and cause injury.
ENGLISH
10 IMPORTANT SAFETY INSTRUCTIONS
· Any person who is involved with working on or breaking into a refrigerant
circuit should hold a current valid certificate from an industry-accredited
assessment authority, which authorizes their competence to handle refrigerants
safely in accordance with an industry recognized assessment specification.
(for R32)
· Wear adequate personal protection equipment (PPE) when installing,
maintaining or servicing the product.
· This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
· Pipe-work shall be protected from physical damage. · Do not install the unit
in potentially explosive atmospheres.
Operation · Do not use the product for special purposes, such as
preserving foods, works of art, etc. It is a consumer air conditioner, not a
precision refrigeration system. There is risk of damage or loss of property. ·
Do not block the inlet or outlet of air flow. It may cause product failure. ·
Use a soft cloth to clean. Do not use harsh detergents, solvents or splashing
water etc. There is risk of fire, electric shock, or damage to the plastic
parts of the product. · Do not touch the metal parts of the product when
removing the air filter. There is risk of personal injury. · Do not step on or
put anything on the product. (outdoor units) There is risk of personal injury
and failure of product.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS 11
· Always insert the filter securely after cleaning. Clean the filter every two
weeks or more often if necessary. A dirty filter reduces the efficiency.
· Do not insert hands or other objects through the air inlet or outlet while
the product is operating. There are sharp and moving parts that could cause
personal injury.
· Be cautious when unpacking and installing the product. Sharp edges could
cause injury.
· If the refrigerant gas leaks during repair, do not touch the leaking
refrigerant gas. The refrigerant gas can cause frostbite (cold burn).
· Do not tilt the unit when removing or uninstalling it. The condensed water
inside can spill.
· Do not mix air or gas other than the specified refrigerant used in the
system. If air enters the refrigerant system, an excessively high pressure
results, causing equipment damage or injury.
· If the refrigerant gas leaks during the installation, ventilate the area
immediately. Otherwise it can be harmful for your health.
· Dismantling the unit, treatment of the refrigerant oil and eventual parts
should be done in accordance with local and national standards.
· Replace all batteries in the remote control with new ones of the same type.
Do not mix old and new batteries or different types of batteries. There is
risk of fire or product failure.
· Do not recharge or disassemble the batteries. Do not dispose off batteries
in a fire. They may burn or explode.
· If the liquid from the batteries gets onto your skin or clothes, wash it
well with clean water. Do not use the remote if the batteries have leaked. The
chemicals in batteries could cause burns or other health hazards.
ENGLISH
12 IMPORTANT SAFETY INSTRUCTIONS
· If you eat the liquid from the batteries, brush your teeth and see doctor.
Do not use the remote if the batteries have leaked. The chemicals in batteries
could cause burns or other health hazards.
· Do not let the air conditioner run for a long time when the humidity is very
high and a door or a window is left open. Moisture may condense and wet or
damage furniture.
· Do not expose your skin or kids or plants to the cool or hot air draft. This
could harm to your health.
· Do not drink the water drained from the product. It is not sanitary and
could cause serious health issues.
· Use a firm stool or ladder when cleaning, maintaining or repairing the
product at height. Be careful and avoid personal injury.
· The appliance shall be stored so as to prevent mechanical damage from
occurring.
· Servicing shall only be performed as recommended by the equipment
manufacturer. Maintenance and repair requiring the assistance of other skilled
personnel shall be carried out under the supervision of the person competent
in the use of flammable refrigerants. (for R32)
· This appliance can be used by children aged from 8 years and above and
persons with reduced physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards
involved. Children shall not play with the appliance. Cleaning and user
maintenance shall not be made by children without supervision.
· Means for disconnection must be incorporated in the fixed wiring in
accordance with the wiring rules.
ENGLISH
TABLE OF CONTENTS 13
TABLE OF CONTENTS
2 MODEL DESIGNATION
3 TIPS FOR SAVING ENERGY
4 IMPORTANT SAFETY INSTRUCTIONS
14 INSTALLATION
15 INSTALLATION OF OUTDOOR UNIT
21 CONNECTING PIPES
21 Preparation of Piping 22 Connection of piping – Outdoor 23 Forming the
piping
24 WIRING CONNECTION
24 Electrical Wiring 24 Connecting Cables between Indoor Unit and Outdoor Unit
27 Connecting the cable to Outdoor Unit
28 LEAKAGE TEST AND EVACUATION
28 Preparation 28 Leakage test 29 Evacuation
30 TEST RUNNING
32 INSTALLATION PI485
33 FUNCTION
33 DIP S/W Setting 35 Pump Down 36 Saving Power Consumption 37 Night Quiet
Mode 38 Mode Lock
40 INSTALLATION GUIDE AT THE SEASIDE
41 SEASONAL WIND AND CAUTIONS IN WINTER
ENGLISH
14 INSTALLATION
INSTALLATION
Installation Tools
Figure
Name
Screw driver
Electric drill
Measuring tape, Knife Hole core drill Spanner Torque wrench
Figure
Name Multi-meter
Hexagonal wrench
Ammeter
Gas-leak detector Thermometer, Level Flaring tool set
ENGLISH
INSTALLATION OF OUTDOOR UNIT 15
INSTALLATION OF OUTDOOR UNIT
You need to select adequate installation location considering the following
conditions, and make sure to acquire the consent of the user.
Installation Places
– If an awning is built over the unit to prevent direct sunlight or rain
exposure, make sure that heat radiation from the condenser is not restricted.
– Ensure that the spaces indicated by arrows around front, back and side of
the unit are respected.
– Do not place animals and plants in the path of the warm air.
– Take the air conditioner weight into account and select a place where noise
and vibration are minimum.
– Select a place so that the warm air and noise from the air conditioner do
not disturb neighbors.
– Select a place that can sufficiently endure the weight and vibration of the
outdoor unit and where even installation is possible.
– Select a place that has no direct impact of snow or rain
– Select a place with no danger of snowfall or icicle drop
– Select a place without weak floor or base such as decrepit part of the
building or with a lot of snow accumulation
– Install at a place with fluent water draining to prevent damage from
localized heavy rain and avoid frequent flooded area.
Sunroof
More than 300
! CAUTION
Be very careful while carrying the product.
· Do not have only one person carry product if it is more than 20 kg.
· PP bands are used to pack some products. Do not use them as a mean for
transportation because they are dangerous.
· Do not touch heat exchanger fins with your bare hands. Otherwise you may get
a cut in your hands.
· Tear plastic packaging bag and scrap it so that children cannot play with
it. Otherwise plastic packaging bag may suffocate children to death.
· When carrying in Outdoor Unit, be sure to support it at four points.
Carrying in and lifting with 3-point support may make Outdoor Unit unstable,
resulting in a fall.
· Use 2 belts of at least 8 m long.
· Place extra cloth or boards in the locations where the casing comes in
contact with the sling to prevent damage.
· Hoist the unit making sure it is being lifted at its center of gravity.
oFbesntcaecloers
More than 300
More than 600
More than 700
[unit : mm]
A > 200 mm (7-7/8 inch)
ENGLISH
16 INSTALLATION OF OUTDOOR UNIT
Piping length and the elevation
· Single Operation
- Standard Inverter / High Inverter
ODU
Capacity (kBtu/h)
UUA1 UUB1 UUC1 UUD1/UUD3
9/12 18 24/30 36/42/48/60
Pipe Size mm(inch)
Gas
Ø 9.52 (3/8) Ø 12.7(1/2) Ø 15.88 (5/8) Ø 15.88 (5/8)
Liquid
Ø 6.35 (1/4) Ø 6.35 (1/4) Ø 9.52 (3/8) Ø 9.52 (3/8)
Length A(m)
Standard Max 7.5 20 7.5 30 7.5 50 7.5 85
Elevation B(m) Additona refrigerant
Standard Max (g/m)
5
15 20
5
30 20
5
30 40
5
30 40
- Compact Inverter
ODU
UUA1 UUB1 UUC1
Capacity (kBtu/h)
18 24/30
36
Pipe Size mm(inch)
Gas
Ø 12.7 (1/2) Ø 15.88 (5/8) Ø 15.88 (5/8)
Liquid
Ø 6.35 (1/4) Ø 9.52 (3/8) Ø 9.52 (3/8)
Length A(m)
Standard Max 7.5 30 7.5 35 7.5 50
Elevation B(m) Standard Max
Additona refrigerant
(g/m)
Connector Type
5
30 20
b
5
30 40
a, c
5
30 40
–
- Connector information
Connector
UUA1 UUB1
09F 12F 18F 18F 24F 30F
a Ø 6.35 Ø 9.52
X X X X O O
b Ø 9.52 Ø 12.7
X X O X X X
c Ø 12.7 Ø15.88
X X X X O O
ex.) UUA1 + CT18F
If installed tube is shorter than 7.5 m, additional charging is not necessary.
Additional Refrigerant = [A-7.5 (m)] x Additional refrigerant (g/m)
Indoor unit
Outdoor unit
A
A
B
Outdoor unit Indoor unit
B
ENGLISH
INSTALLATION OF OUTDOOR UNIT 17
Minimum floor area(for R32)
– The appliance shall be installed, operated and stored in a room with a floor
area larger than the minimum area.
– Use the graph of table to determine the minimum area.
Amin (m2) 600
Floor standing
500
400
300
200
100
Wall mounted
Ceiling mounted
0
m (kg)
0
1.224
2
3
4
5
6
7
8
– m : Total refrigerant amount in the system – Total refrigerant amount : factory refrigerant charge + additional refrigerant amount – Amin : minimum area for installation
Floor location
m (kg) Amin (m2)
< 1.224
–
1.224 12.9
1.4
16.82
1.6
21.97
1.8
27.80
2
34.32
2.2
41.53
2.4
49.42
2.6
58.00
2.8
67.27
3
77.22
3.2
87.86
3.4
99.19
3.6 111.20
3.8 123.90
4
137.29
4.2 151.36
4.4 166.12
Floor location
m (kg) Amin (m2)
4.6 181.56
4.8 197.70
5
214.51
5.2 232.02
5.4 250.21
5.6 269.09
5.8 288.65
6
308.90
6.2 329.84
6.4 351.46
6.6 373.77
6.8 396.76
7
420.45
7.2 444.81
7.4 469.87
7.6 495.61
7.8 522.04
Wall mounted
m (kg) Amin (m2)
< 1.224
–
1.224 1.43
1.4
1.87
1.6
2.44
1.8
3.09
2
3.81
2.2
4.61
2.4
5.49
2.6
6.44
2.8
7.47
3
8.58
3.2
9.76
3.4
11.02
3.6
12.36
3.8
13.77
4
15.25
4.2
16.82
4.4
18.46
Wall mounted
m (kg) Amin (m2)
4.6
20.17
4.8
21.97
5
23.83
5.2
25.78
5.4
27.80
5.6
29.90
5.8
32.07
6
34.32
6.2
36.65
6.4
39.05
6.6
41.53
6.8
44.08
7
46.72
7.2
49.42
7.4
52.21
7.6
55.07
7.8
58.00
Ceiling Mounted
m (kg) Amin (m2)
< 1.224
–
1.224 0.956
1.4
1.25
1.6
1.63
1.8
2.07
2
2.55
2.2
3.09
2.4
3.68
2.6
4.31
2.8
5.00
3
5.74
3.2
6.54
3.4
7.38
3.6
8.27
3.8
9.22
4
10.21
4.2
11.26
4.4
12.36
Ceiling Mounted
m (kg) Amin (m2)
4.6
13.50
4.8
14.70
5
15.96
5.2
17.26
5.4
18.61
5.6
20.01
5.8
21.47
6
22.98
6.2
24.53
6.4
26.14
6.6
27.80
6.8
29.51
7
31.27
7.2
33.09
7.4
34.95
7.6
36.86
7.8
38.83
ENGLISH
18 INSTALLATION OF OUTDOOR UNIT
· Synchro Operation
Install the branch pipe so that pipe length and difference between high and
low will not exceed below Spec.
[Unit : m]
L2 L3
L4
H1
L5
Remote Controller
L1
Branch A
A
Pipe Length & Height
Spec(MAX.)
Total(L1+L2+L3+L4+L5)
80
Main Pipe(L1)
45
H2
Branch Pipe (L2+L3+L4+L5)
40
Each
15
Indoor-Outdoor (H1)
30
Indoor-Indoor (H2)
1
(L1+L2),(L1+L3),(L1+L4),(L1+L5)
70
A
10
– When installing the branch pipe, direction and angle of installation is not
limited. – Take care so that burrs and foreign material may not enter into the
cutting surface when
connecting. – Connect remaining those by cutting or direct insertion to the
diameter of pipe.
· Refrigerant Additional Charging Method For additional charging method, see below table.
Indoor Unit
Refrigerant Additional charging (g)
Duo Refrigerant = (L1-b) x B + (L2 + L3) x C
Trio
Refrigerant = (L1-b) x B + (L2 + L3 + L4) x C
Quartet Refrigerant = (L1-b) x B + (L2 + L3 + L4 + L5) x C
Pipe Diameter. (mm) Ø 6.35
Ø 9.52
C (g/m) 35 40
Model UUD1 / UUD3
b(m)
B(g/m)
7.5
40
NOTE
b : Rated performance for refrigerant line length. C : Additional charging
Refrigerant of Branch Liquid Pipe. B : Additional charging Refrigerant of Main
Liquid Pipe.
! CAUTION
· Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
· Improper refrigerant charge may result in abnormal cycle.
INSTALLATION OF OUTDOOR UNIT 19
ENGLISH
Synchro Combination table
Applied Accessiries
IDU : INDOOR UNIT ODU : OUTDOOR UNIT BD : BRANACH
DISTRIBUTOR UNIT REMO : WIRED REMOTE
CONTROLLER MODEL
UUD1 / UUD3
BD unit Simple central controller**
Possible combination of indoor units
Synchro
Duo
Trio
Quartet
ODU
BD
IDU
IDU
REMO
ODU
ODU
BD
BD
IDU
IDU
IDU
IDU
IDU
IDU
IDU
REMO
REMO
Cassette
Duct
CT18F 2 CM18F 2
CT24F 2 CM24F 2
UT30F 2 UM30F 2
PMUB11A
Cassette CT12F 3 CT18F 3
Duct CL12F 3 CM18F 3
PMUB111A
PQCSZ250S0
Cassette CT12F * 4
Duct CL12F *4
PMUB1111A
NOTE
** When using synchro operation, · Do not use wireless remote controller. ·
Use only one wired remote controller in the indoor units. · Use central
controller and function controller “PQCSZ250S0” only.
ENGLISH
20 INSTALLATION OF OUTDOOR UNIT
Outdoor Unit PCB Setting Procedure For Simultaneous Operation System
1 DIP_SW Setting Set the DIP_SW as below Table ()
2 Auto Addressing Method Addressing work assigns address to each indoor unit.
When firstly installing product or replacing the indoor unit PCB. Auto
Addressing work should be done for simultaneous operation.
- Work procedure
- Set DIP_SW correctly. 2) Turn on main power. 3) Press the SW01M for about 3
seconds within 3 minutes After main power on.() 4) After step 3), the
LED01E(red LED) and LED02E(green LED) rapidly flickers. When Addressing
work is done, green LED is off, else LED (LED01E) stops flickering and lights continuously. Address of indoor unit is indicated on the wired remote control display window. (CH01, CH02, CH03, CH04)
] 5) Press button to turn on the indoor. - If you fail to perform the Addressing work, repeat step 2)~5).
DIP SW01D
1 23456
A
LED01E LED02E
B SW01M
Main PCB
DIP SW01D
1 23456 1 23456 1 23456 1 23456
Indoor Unit No. 1(Single) : Default
2(Duo) 3(Trio) 4(Quartet)
CONNECTING PIPES
Preparation of Piping
– Main cause of gas leakage is defect in flaring work. Carry out correct
flaring work in the following procedure.
– Use the de-oxidised copper as piping materials to install.
Cut the pipes and the cable. – Use the accessory piping kit or the pipes
purchased locally. – Measure the distance between the indoor and
the outdoor unit. – Cut the pipes a little longer than measured
distance. – Cut the cable 1.5 m longer than the pipe
length.
Burrs removal – Completely remove all burrs from the cut
cross section of pipe/tube. – Put the end of the copper tube/pipe to
downward direction as you remove burrs in order to avoid to let burrs drop in
the tubing.
Putting nut on – Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube having completed burr removal. (Not
possible to put them on after flaring work)
Flaring work – Carry out flaring work using dedicated flaring
tool for R32 as shown below.
Pipe diameter inch (mm)
A inch (mm) Wing nut type Clutch type
Ø 1/4 (Ø 6.35) 0.04~0.05 (1.1~1.3)
Ø 3/8 (Ø 9.52) 0.06~0.07 (1.5~1.7) Ø 1/2 (Ø 12.7) 0.06~0.07 (1.6~1.8) Ø 5/8 (Ø 15.88) 0.06~0.07 (1.6~1.8)
0~0.02 (0~0.5)
Ø 3/4 (Ø19.05) 0.07~0.08 (1.9~2.1)
Firmly hold copper tube in a bar(or clamp) as indicated dimension in the table
above.
Check – Compare the flared work with figure below. – If flare is noted to be
defective, cut off the
flared section and do flaring work again.
CONNECTING PIPES 21
Copper tube
90° Slanted Uneven Rough
Point down
Pipe Reamer
Flare nut Copper tube
Copper pipe
Smooth all round Inside is shining without scratches.
= Improper flaring =
Even length all round
Inclined Surface Cracked Uneven
damaged
thickness
ENGLISH
22 CONNECTING PIPES
ENGLISH
Connection of piping – Outdoor
– Align the center of the piping and sufficiently tighten the flare nut by
hand.
– Finally, tighten the flare nut with torque wrench until the wrench clicks.
When tightening the flare nut with torque wrench ensure the direction for
tightening follows the arrow on the wrench.
Outside diameter
mm
inch
Ø 6.35
1/4
Ø 9.52
3/8
Ø 12.7
1/2
Ø 15.88
5/8
Torque kg·m
1.8~2.5 3.4~4.2 5.5~6.6 6.6~8.2
- When tighten the pipe, hold the hexagonal body.
Preventing foreign objects from entering (Figure 2)
– Plug the pipe through-holes with putty or insulation material(procured
locally)to stop up all gaps, as shown in the figure 2.
<Figure 2>
Liquid side piping Gas side piping
Connecting wire Drain hose
Connection pipe
Resin, Clay, Putty or insulating material (produced locally)
Outdoor unit
Gas side piping (Bigger Dia.)
Liquid side piping (Smaller Dia.)
Torque wrench
Tubing Cover
Continuous
Torque wrench (250mmmm))
! CAUTION
Insects or small animals entering the outdoor unit may cause a short circuit
in the electrical box.
! CAUTION
· A brazed, welded, or mechanical connection shall be made before opening the
valves to permit refrigerant to flow between the refrigerating system parts.
· When flared joints are reused indoors, the flare part shall be re-
fabricated. (for R32)
· When mechanical connectors are reused indoors, sealing parts shall be
renewed. (for R32)
· Copper in contact with refrigerants shall be oxygen-free or deoxidized, for
example Cu-DHP as specified in EN 12735-1 and EN 12735-2.
CONNECTING PIPES 23
ENGLISH
Forming the piping
Form the piping by wrapping the connecting portion of the indoor unit with
insulation material and secure it with two kinds of vinyl tape.
– If you want to connect an additional drain hose, the end of the drain outlet
should be routed above the ground. Secure the drain hose appropriately.
In cases where the Outdoor unit is installed above the Indoor unit perform the
following.
1 Tape the piping and connecting cable from down to up.
2 Secure the taped piping along the exterior wall. Form a trap to prevent
water entering the room.
3 Fix the piping onto the wall by saddle or equivalent.
In cases where the outdoor unit is installed below the indoor unit perform the
following.
1 Tape the piping, drain hose and connecting cable from down to up.
2 Secure the tapped piping along the exterior wall using saddle or equivalent.
Seal a small opening around the pipings with gum type sealeanr.t.
Taping Drain hose
Plastic band
OUUTNDIOTOR
Pipings Connecting cable
Power supply cord
· Trap is required to prevent water from entering into electrical parts.
Seal a small opening around the pipings with gum type sealeanr.t. Trap
OUUTNDIOTOR
Trap
! CAUTION
· Refrigerant tubing shall be protected or enclosed to avoid damage.
· Flexible refrigerant connectors (such as connecting lines between the indoor
and outdoor unit) that may be displaced during normal operations shall be
protected against mechanical damage.
ENGLISH
24 WIRING CONNECTION
WIRING CONNECTION
Electrical Wiring
Perform the electrical wiring work according to the electrical wiring
connection. – All wiring must comply with local
requirements. – Select a power source that is capable of
supplying the current required by the air conditioner. – Use a recognized
ELCB(Electric Leakage Circuit Breaker) between the power source and the unit.
A disconnection device to adequately disconnect all supply lines must be
fitted. – Model of circuit breaker recommended by authorized personnel only
Main power source
Indoor
ELCB Switch box
Outdoor
Model Name UUA1 UUB1 UUC1 UUD1 UUD3
Phase(Ø) 1 1 1 1 3
ELCB (A) 15 20 25 40 20
Connecting Cables between Indoor Unit and Outdoor Unit
– Connect the wires to the terminals on the control board individually
according to the outdoor unit connection.
– Ensure that the color of the wires of outdoor unit and the terminal No. are
the same as those of indoor unit respectively
1(L) 2(N) POWER SUPPLY
1(L) 2(N) 3 TO INDOOR UNIT
1(L) 2(N) POWER SUPPLY
1(L) 2(N) 3 TO INDOOR UNIT
UUA1 / UUB1 / UUC1
1(L) 2(N) 3 TO INDOOR UNIT
UUD1
RS T N POWER SUPPLY
UUD3
WIRING CONNECTION 25
ENGLISH
Simultaneous Operation Unit 2,3,4
Main Unit1
S Terminals on the indoor unit 4 1(L) 2(N) 3 S Terminals on the indoor unit 3 1(L) 2(N) 3 S Terminals on the indoor unit 2 1(L) 2(N) 3 M Terminals on the indoor unit 1 1(L) 2(N) 3
Terminals on the Outdoor unit
(380V-415V3N) (220V-240V~)
RST N
LN
1(L) 2(N) 3
DUCT, CVT
POWER INPUT
POWER INPUT
1(L) 2(N) 3 4 5 1(L) 2(N) 3 4 5 1(L) 2(N) 3 4 5 1(L) 2(N) 3 4 5
CN-REMO CN-REMO CN-REMO CN-REMO
1(L) 2(N) 3 CST
Remote Controller
· When using simultaneous Operation System, use only one wired remote controller in the indoor units
! CAUTION
The power cord connected to the outdoor unit should comply to IEC 60245 or HD
22.4 S4 (This equipment shall be provided with a cord set complying with the
national regulation.)
1 Phase(Ø)
GN/YL 20 mm
3 Phase(Ø)
NORMAL CROSS-SECTIONAL AREA
Model Name UUA1 / UUB1 / UUC1
UUD1 UUD3
Phase(Ø) 1 1 3
Area(mm2) 2.5 6 2.5
GN/YL 20 mm
The connecting cable connected to the outdoor unit should comply to IEC 60245 or HD 22.4 S4 (This equipment shall be provided with a cord set complying with the national regulation.)
GN/YL
NORMAL CROSS-SECTIONAL AREA 0.75 mm2
20 mm
When the connection line between the indoor unit and outdoor unit is over 40
m, connect the telecommunication line and power line separately.
If the supply cord is damaged, it must be replaced by a special cord or
assembly available from the manufacturer of its service agent.
Pipes and wires should be purchased separately for installation of the
product.
ENGLISH
26 WIRING CONNECTION Precautions when laying power wiring Use round pressure
terminals for connections to the power terminal block.
Round pressure terminal Power wire
When none are available, follow the instructions below. – Do not connect
wiring of different thicknesses to the power terminal block.
(Slack in the power wiring may cause abnormal heat.) – When connecting wiring
which is the same thickness, do as shown in the figure below.
! WARNING
Make sure that the screws of the terminal are free from looseness.
ENGLISH
WIRING CONNECTION 27
Connecting the cable to Outdoor Unit
Remove the side panel for wiring connection. Use the cord clamp to fix the cord.
Earthing work – Case 1 : Terminal block of Outdoor Unit have mark.
Connect the cable of diameter 1.6 mm2 or more to the earthing terminal
provided in the control box and do earthing.
– Case 2 : Terminal block of Outdoor Unit don’t have mark. Connect the cable of diameter 1.6 mm2 or more, to the panel of control box, marked as and fasten with earth screw
Power cord
terminal
Connecting
cable terminal
Cord clamp Cord clamp
- Make sure the rubber bushes are Properly used in knock-out holes after connecting main Power cable
! CAUTION
· The circuit diagram is not subject to change without notice. · Be sure to connect wires according to the wiring diagram. · Connect the wires firmly, so that They won’t be pulled out easily. · Connect the wires according to color codes by referring the wiring diagram. · The Power cord connected to the unit should be selected according to the specifications
on 24 page.
ENGLISH
28 LEAKAGE TEST AND EVACUATION
LEAKAGE TEST AND EVACUATION
Air and moisture remaining in the refrigerant system have undesirable effects
as indicated below. – Pressure in the system rises. – Operating current rises.
– Cooling (or heating) efficiency drops. – Moisture in the refrigerant circuit
may freeze and block capillary tubing. – Water may lead to corrosion of parts
in the refrigeration system. Therefore, the indoor/outdoor unit and connecting
tube must be checked for leak tight, and vacuumed to remove incondensible gas
and moisture in the system.
Preparation
– Check that each tube (both liquid and gas side tubes) between the indoor and
outdoor units have been properly connected and all wiring for the test run
have been completed. Remove the service valve caps from both the gas and the
liquid side on the outdoor unit. Check that both the liquid and the gas side
service valves on the outdoor unit are kept closed at this stage.
Leakage test
– Connect the manifold valve (with pressure gauges) and dry nitrogen gas
cylinder to this service port with charge hoses.
! CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use
a stop valve for this purpose. The “Hi” knob of the manifold valve must always
be kept close.
– Pressurize the system to no more than 3.8 MPa with dry nitrogen gas and
close the cylinder valve when the gauge reading reached 3.8 MPa Next, test for
leaks using bubble test solution.
! CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top
of the cylinder must be higher than its bottom when you pressurize the system.
Usually, the cylinder is used in a vertical standing position.
LEAKAGE TEST AND EVACUATION 29
ENGLISH
1 Do a leakage test of all joints of the tubing (both Indoor unit and outdoor
unit) and both gas and liquid side service valves. Bubbles indicate a leak. Be
sure to wipe off the soap with a clean cloth.
2 After the system is found to be free of leaks, relieve the nitrogen pressure
by loosening the charge hose connector at the nitrogen cylinder. When the
system pressure is reduced to normal, disconnect the hose from the cylinder.
Evacuation
– Connect the charge hose end described in the preceding steps to the vacuum
pump to evacuate the tubing and indoor unit. Confirm the “Lo and Hi” knob of
the manifold valve is open. Then, run the vacuum pump. The operation time for
evacuation varies with tubing length and capacity of the pump. The following
table shows the time required for evacuation.
– When the desired vacuum is reached, close the “Lo and Hi” knob of the
manifold valve and stop the vacuum pump.
Finishing the job – With a service valve wrench, turn the valve
stem of liquid side valve counter-clockwise to fully open the valve. – Turn
the valve stem of gas side valve counter-clockwise to fully open the valve. –
Loosen the charge hose connected to the gas side service port slightly to
release the pressure, then remove the hose. – Replace the flare nut and its
bonnet on the gas side service port and fasten the flare nut securely with an
adjustable wrench. This process is very important to prevent leakage from the
system. – Replace the valve caps at both gas and liquid side service valves
and fasten them tight. This completes air purging with a vacuum pump. The air
conditioner is now ready to test run.
Outdoor unit
Indoor unit
Manifold valve
Pressure
Lo Hi
gauge
Charge hose
Nitrogen gas cylinder (in vertical standing position)
Required time for evacuation when 11.36 l/h vacuum pump is used
If tubing length is less If tubing length is than 10 m (33 ft) longer than 10 m (33 ft)
30 min. or more
60 min. or more
0.07 kPa or less
Indoor unit Outdoor unit
Manifold valve
Pressure
Lo Hi
gauge
Open
Open
Vacuum pump
ENGLISH
30 TEST RUNNING
TEST RUNNING
1 Precautions In Test Running – The initial power supply must provide at least
90 % of the rated voltage. Otherwise, the air conditioner should not be
operated.
! CAUTION
· For test run, carry out the cooling operation firstly even during heating
season. If heating operation is carried out firstly, it leads to the trouble
of compressor. Then attention must be paid.
· Carry out the test run more than 5 minutes without fail. (Test run will be
cancelled 18 minutes later automatically)
– The test run is started by pressing the room temperature checking button and
down timer button for 3 seconds at the same time.
– To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
– After completing work, be sure to measure and record trial run properties,
and store measured data, etc.
– Measuring items are room temperature, outside temperature, suction
temperature, blow out temperature, wind velocity, wind volume, voltage,
current, presence of abnormal vibration and noise, operating pressure, piping
temperature, compressive pressure.
– As to the structure and appearance, check following items.
Is the circulation of air adequate? Is the draining smooth? Is the heat
insulation complete
(refrigerant and drain piping)? Is there any leakage of refrigerant?
Is the remote controller switch operated? Is there any faulty wiring? Are not
terminal screws loosened?
M4……118 N.cm{12 kgf.cm} M5……196 N.cm{20 kgf.cm} M6……245 N.cm{25 kgf.cm}
M8……588 N.cm{60 kgf.cm}
2 Connection of power supply
– Connect the power supply cord to the independent power supply. Circuit
breaker is required.
– Operate the unit for fifteen minutes or more.
3 Evaluation of the performance
– Measure the temperature of the intake and discharge air.
– Ensure the difference between the intake temperature and the discharge one
is more than 8 °C (Cooling) or reversely (Heating).
Thermometer
ENGLISH
TEST RUNNING 31
! CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1 Never fail to have an individual power specialized for the air conditioner.
As for the
method of wiring, be guided by the circuit diagram pasted on the inside of
control box cover. 2 Provide a circuit breaker switch between power source and
the unit. 3 The screw which fasten the wiring in the casing of electrical
fittings are liable to come loose from vibrations to which the unit is
subjected during the course of transportation. Check them and make sure that
they are all tightly fastened. (If they are loose, it could give rise to burn-
out of the wires.) 4 Specification of power source 5 Confirm that electrical
capacity is sufficient. 6 Be sure that the starting voltage is maintained at
more than 90 percent of the rated voltage marked on the name plate. 7 Confirm
that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.) 8 Never
fail to equip a leakage breaker where it is wet or moist. 9 The following
troubles would be caused by voltage drop-down. – Vibration of a magnetic
switch, damage on the contact point there of fuse breaking,
disturbance to the normal function of a overload protection device. – Proper
starting power is not given to the compressor. 10 Use only 1 remote-controller
contained in indoor unit, when using simultaneous operation system as shown
below. After setting the ESP value in the Ceiling Concealed Duct Type Indoor
Unit, the main power turns off and then remove the remote controller. 11 It is
possible to connect (install) same type of indoor units only and also with in
a single room. 12 Connecting cable length is up to 90 m.
Connecting cable
HAND OVER Teach the customer the operation and maintenance procedures, using
the operation manual (air filter cleaning, temperature control, etc.).
ENGLISH
32 INSTALLATION PI485
INSTALLATION PI485
Fix the PI485 PCB as shown in below images. For detailed installation method
refer to PI485 Installation Manual. UUA1
UUB1
UUC1
UUD1 / UUD3
ENGLISH
FUNCTION 33
FUNCTION
DIP S/W Setting
If you set the DIP Switch when power is on, the change in setting is not
applicable. The changing setting is enabled only when Power is reset.
DIP Switch
1
2
Function
Normal Operation (No Function)
Pump Down
Saving Power Consumption (Step 1)
Saving Power Consumption (Step 2)
Mode Lock (Cooling)
Mode Lock (Heating)
Night Quiet Mode (Step 1)
Night Quiet Mode (Step 2)
Mode Lock (Cooling) + Night Quiet Mode (Step 1)
Mode Lock (Cooling) + Night Quiet Mode (Step 2)
Mode Lock (Cooling) + Saving Power Consumption (Step 1)
Mode Lock (Cooling) + Saving Power Consumption (Step 2)
Mode Lock (Heating) + Saving Power Consumption (Step 1)
1 : UUB1 / UUC1 2 : UUD1 / UUD3
Mode Lock (Heating) + Saving Power Consumption (Step 2)
34 FUNCTION
ENGLISH
DIP Switch 1 2 3 4 5 6
123456 123456 123456
Synchro_Duo Synchro_Trio Synchro_Quartet
Function
! WARNING
When you set the DIP switch, you should turn off the circuit breaker or shut
the power source of the product down.
! CAUTION
· Unless the applicable DIP switch is set properly, the product may not work.
· If you want to set a specific function, request that the installer sets the
DIP switch appropriately
during installation.
ENGLISH
Pump Down
Setting Procedure 1 Set the DIP Switch as follow after shutting the power
source down.
FUNCTION 35
5
UUB1 / UUC1
1 23 4 56
UUD1 / UUD3
2 Reset the power.
3 Red LED and Green LED of PCB lights during work. (The indoor unit is
operated by force.)
4 If operation is done, Red LED will be turned off. If operation is not done
normally, Red LED will blink.
5 Close the Liquid valve only after green LED turned off (7 minutes from the
start of the machine). Then close the gas valve after Green LED on.
! WARNING
· When the green LED of PCB is on, compressor is going to be off because of
low pressure. · You should return the DIP Switch to operate normally after
finishing the operation. · Improper Pump down will lead to product turn off
along with LED (green &red) off with in 20
minutes from the initial start.
Pump Down DIP S/W Setting
Power on (Red LED On, Green LED Off)
Comp on (Red LED On, Green LED On)
Pump Down Start (Red LED On, Green LED Off)
Liquid Valve Closed
Pump Down Complete (Red LED Off, Green LED On)
Gas Valve Closed
Power off (Red LED Off, Green LED On)
· The actual product can be different from above contents depending upon model type.
ENGLISH
36 FUNCTION
Saving Power Consumption
Saving Power Consumption operation is the function which enables efficient
operation by lowering the maximum power consumption value.
Power consumption
and current
Normal
Time
Setting Procedure 1 Set the DIP Switch as follow after shutting the power
source down.
UUB1 / UUC1
UUB1 / UUC1
UUD1 / UUD3 Step 1
2 Reset the power. Saving Power Consumption with Mode Lock.
UUB1 / UUC1
UUD1 / UUD3 Step 2
UUB1 / UUC1
UUD1 / UUD3
Saving Power Consumption (step 1) + Mode Lock (Cooling)
UUD1 / UUD3
Saving Power Consumption (step 1) + Mode Lock (Heating)
ENGLISH
UUB1 / UUC1
FUNCTION 37 UUB1 / UUC1
UUD1 / UUD3
Saving Power Consumption (step 2) + Mode Lock (Cooling)
UUD1 / UUD3
Saving Power Consumption (step 2) + Mode Lock (Heating)
Night Quiet Mode
Night Quiet Mode operation lowers the noise level of the outdoor unit by
changing the Compressor’s frequency and fan speed. This function is operated
all night long.
Setting Procedure 1 Set the DIP Switch as follow after shutting the power
source down.
h Noise level :Step 1 > Step 2
UUB1 / UUC1
UUB1 / UUC1
UUD1 / UUD3 Step 1
2 Reset the power.
UUD1 / UUD3 Step 2
ENGLISH
38 FUNCTION Night Quiet Mode with Mode Lock.
UUB1 / UUC1
UUB1 / UUC1
UUD1 / UUD3
Mode Lock (Cooling) + Night Quiet Mode (step 1)
UUD1 / UUD3
Mode Lock (Cooling) + Night Quiet Mode (step 2)
! CAUTION
· If compressor’s frequency and fan speed are down, the cooling capacity may
decrease accordingly.
· This function is only available for Cooling Mode. · If you want to stop the
Night Quiet Mode, Change the DIP Switch. · If operating indoor unit is set by
the fan speed “Power”, Night Quiet Mode will be stopped
until fan speed “Power” is changed.
Mode Lock
Setting Procedure 1 Set the DIP Switch as follow after shutting the power
source down.
UUB1 / UUC1
UUB1 / UUC1
UUD1 / UUD3 Only Cooling Mode
2 Reset the power.
UUD1 / UUD3 Only Heating Mode
ENGLISH
Mode Lock with Night Quiet Mode UUB1 / UUC1
FUNCTION 39 UUB1 / UUC1
UUD1 / UUD3 Mode Lock (Cooling) + Night Quiet Mode (step 1)
Saving Power Consumption with Mode Lock.
UUB1 / UUC1
UUD1 / UUD3 Mode Lock (Cooling) + Night Quiet Mode (step 2)
UUB1 / UUC1
UUD1 / UUD3
Mode Lock (Cooling) + Saving Power Consumption (step 1)
UUD1 / UUD3
Mode Lock (Heating) + Saving Power Consumption (step 1)
UUB1 / UUC1
UUB1 / UUC1
UUD1 / UUD3
Mode Lock (Cooling) + Saving Power Consumption (step 2)
UUD1 / UUD3
Mode Lock (Heating) + Saving Power Consumption (step 2)
ENGLISH
40 INSTALLATION GUIDE AT THE SEASIDE
INSTALLATION GUIDE AT THE SEASIDE
In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind
! CAUTION
· Air conditioners should not be installed in areas where corrosive gases,
such as acid or alkaline gas, are produced.
· Do not install the product where it could be exposed to sea wind (salty
wind) directly. It can result corrosion on the product. Corrosion,
particularly on the condenser and evaporator fins, could cause product
malfunction or inefficient performance.
· If outdoor unit is installed close to the seaside, it should avoid direct
exposure to the sea wind. Otherwise it needs additional anticorrosion
treatment on the heat exchanger.
Selecting the location (Outdoor Unit)
In case, to install the outdoor unit on the seaside, set If the outdoor unit
is to be installed close to the seaside, direct exposure to the sea wind
should be avoided. Install the outdoor unit on the opposite side of the sea
wind direction. a windbreak not to be exposed to the sea wind.
Windbreak
Sea wind
– It should be strong enough like concrete to prevent the sea wind from the
sea.
– The height and width should be more than 150 % of the outdoor unit.
– More than 70 cm of space should be kept between outdoor unit and the
windbreak for easy air flow.
Place with fluent water draining – Install at a place with fluent water
draining to
prevent damage from localized heavy rain and avoid frequent flooded area.
· Periodic ( more than once/year ) cleaning of the dust or salt particles
stuck on the heat exchanger by using water.
Sea wind
Sea wind
ENGLISH
SEASONAL WIND AND CAUTIONS IN WINTER 41
SEASONAL WIND AND CAUTIONS IN WINTER
– Sufficient measures are required in a snow area or severe cold area in
winter so that product can operate well.
– Get ready for seasonal wind or snow in winter even in other areas.
– Install a suction and discharge duct not to let in snow or rain.
– Install the outdoor unit not to come in contact with snow directly. If snow
piles up and freezes on the air suction hole, the system may malfunction. If
it is installed at snowy area, attach the hood to the system.
– Install the outdoor unit at the higher installation console by 50 cm than
the average snowfall (annual average snowfall) if it is installed at the area
with much snowfall.
– Where snow accumulated on the upper part of the Outdoor Unit by more than 10
cm, always remove snow for operation.
42
ENGLISH
· The information for Eco design is available on the following free access website. https://www.lg.com/global/support/cedoc/cedoc
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>