ADVANTAGE AIR RM2 Relay Module 2 Installation Guide
- June 7, 2024
- ADVANTAGE AIR
Table of Contents
RM2 (Relay Module 2)
Installation Manual
Advantage Air Pty Ltd
115 Vulcan Rd, Canning Vale WA 6155
Ph: 1300 850 191 or email:
techsupport@advantageair.com.au
Electrical Safety
General
The RM2 must be installed and/or used in accordance with your local wiring
rules, regulations and standards.
If you are unsure about any part of this installation then contact a licensed
electrician before proceeding.
Some steps of the installation process are required to be completed only by a licensed electrician; these steps are marked with this symbol
The RM2 (Relay Module 2) conforms to the following standards:
AS/NZS 60669.2.1:2013
IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC
61000-4-8,
IEC 61000-4-11
While the RM2 is primarily a Safety Extra Low Voltage (SELV) system (48V DC),
installations may have a mix of 240V and SELV wiring and switches
Always ensure the MAIN POWER breaker is OFF before opening, connecting,
configuring or modifying the RM2.
DO NOT MEGGER TEST
- Unplug PS48 and PSUACDC before megger testing
- Do not megger test ELV switches
The RM2 system runs at Safety Extra Low Voltage (SELV) (48V DC). Megger tests (aka Insulation Resistance Tests) do not apply, megger tests will damage the equipment.
Specifications
Input voltage | 48VDC ±5%, 0.2A |
---|---|
Output relay voltage | 220-240VAC |
Max output load | 2.5A (600VA) |
Environmental | IP20 |
TIP: See Load Guidelines section.
Installation
Mounting
The RM2 can be installed onto any flat surface using screws:
- use thread diameter 4 – 5mm
- use head size 9 – 11mm diameter.
- minimum thread length of 15mm.
Example for screwing into timber: 8Gx15mm button head screw.
Care must be taken to ensure that the internal PCB is totally free of any
foreign objects such as stray wire strands before applying power. Failure to
ensure this may result in permanent damage to the RM2 that is not covered
under warranty.
Note: It is highly recommended that the RM2 be mounted vertically as shown in
the photos below. In situations where the RM2 cannot be mounted vertically, it
should be securely fixed to a flat surface.
Mounting Example:
System
Size
A maximum of 72 switch inputs is allowed per the MyPlace system.
Up to 12 modules total. A mix of LM’s, RM’s, and RM2’s can be used, with a
maximum of 12 in total.
Load Guidelines
The max load is 600VA per channel.
What you can connect to each channel depends upon its VA rating and inrush
current.
For example, as a guideline, one RM2 channel can control:
- 300W of low voltage lighting – where electronic transformers are used. This includes all 240V powered LED lights and low voltage halogen lighting.
- 600W of 240V halogen or another filament lighting.
- Three typical interior blind motors.
- You can control over 600VA using a suitable external relay or contactor.
o For example Hager ESC125 contactor
PowerPoints
Install a PowerPoint for each PS48 and another for the PSUACDC power supply
unit (for the Control Box). (see Section 9 for power supply connection
options).
Installation of power circuits and power points must be completed by a licensed electrician.
Overviews
RM2 Overview
System Overview
Switch Wiring Options
48V Switching – Method 1
Low voltage wiring to the wall switch. Connects to “LOW VOLTAGE SWITCH INPUT”
on the RM2. Suitable for Roller Blinds, and 240V lights.
Note: Wall Switches should be fitted for each channel of blinds and
lights.
Recommended: use latching push-button type wall switches (for blinds and
lights).
Example: Use Clipsal 30PB (not bell press). Regular switches can also be used
for lights (Clipsal 30M).
240V Switching (using ADAP SW48) – Method 2
Leave the existing house wiring in place and use the ADAP SW48.
When using the ADAP SW48, ensure you use the ADAP SW48CABLE10 or ADAP
SW48CABLE20 to connect to the “LOW VOLTAGE SWITCH INPUT” on the RM2.
Polarity Sensitive ADAP 48SWCABLE10/20
Using the ADAP SW48 with Clipsal Saturn or similar LED lit switches
If you require Clipsal Saturn (and similar other types) light switches that
have a LED indicator light, then 240V will be required at the switches to
operate the LED. The 48V switch wire coming off the RM2 is unable to control
the LED.
Please refer to the wiring instructions provided by the switch manufacturer for recommended configurations.
Garage Doors
MyPlace allows you to open or close your garage door, and MyPlace will send a
notification alert to your mobile phone if your garage door is left open.
Compatibility
Some garage doors have multiple settings for accepting inputs from third-party
control systems. The garage door motorized opener must be able to accept
momentary “pulse” open/closed signals. A setting on the Garage Door controls
may be required to be changed.
For Garage Doors the RM2 “LOW VOLTAGE SWITCH INPUT” is used by the Garage Door
Sensor (MYG).
Brand | Model | Garage Door External Control Input |
---|---|---|
B&D | SDO-4V1 | AUX/OSC & OV |
Dynamic Openers | OL6P | PUSH BUTTON & COMMON/GROUND |
Merlin | prolift 230T | connect to each terminal labeled “manual control” |
Glidermatic / Gliderol | GTS2000 | GND + ST |
Jaytech | CK1200 | GND + PB |
For up to date compatibility info please see
https://www.advantageair.com.au/support/ or call us on
1300 850 191 or email
techsupport@advantageair.com.au for
assistance.
Garage Door Wiring Diagram
The switches use SELV-compliant voltages. DO NOT connect switches or cables which contain 240V mains, or other voltages.
Garage Door Sensor Wiring
The MYG consists of two parts; the sensor, and a junction box.
Garage door sensor parts:
- The part with wires should be mounted in a permanent position to detect the door when it is closed.
- The rectangular part (magnet) must be mounted to the door.
- The two parts must come very close to each other (10-20mm) when the garage door is closed.
- Angle bracket included for mounting
The Garage door sensor must detect when the door is closed.
Photo Electric Sensor Required
All garage doors and motorized openers should be installed in accordance to
AS/NZS60335.2.95. Advantage Air highly recommends that Photo-Electric safety
beams are installed when door openers are integrated with MyPlace. Please
consult further with your garage door and motorized opener supplier.
Garage Door Sensor – Location
The Garage Door Sensor (included in MYG) can be installed near the ground, or
along the side of the garage door, or near the top. This will be site-
specific.
The two parts of the sensor must come within 10-20mm of each other when the
garage door is closed.
RM2 Wiring for Garage Door
Channel Function | N/O Terminal | N/C Terminal | `C’ Terminal |
---|---|---|---|
Garage Door | WIRE 1 | Not Used | WIRE 2 |
Garage Door Sensor – Installation Example – up top
Garage Door Sensor – Installation Example – on the ground
Roller Blinds
MyPlace allows you to set your blind as open or closed.
Compatibility
SUITABLE MOTORS FOR MOTORISED ROLLER BLINDS USED WITH MYPLACE
MANUFACTURER | MODEL NUMBER |
---|---|
SOMFY | LS40 3/30 |
ACMEDA | ML S45 |
MOTOLUX | 802131000 |
MOTOLUX | MT35P-6-28- 240/50 |
ALPHA MOTORS | WSS40-5/28 |
IMPORTANT MOTOR REQUIREMENTS
- NEEDS 3 OR 4 WIRES
- HARDWIRED 240V
- Mechanical/Manual Limit Setting on Motor
- MUST NOT be controlled via any other remote control/ apps/wireless/radio
SUITABLE WALL SWITCHES FOR AUTOMATED ROLLER BLINDS
Please use latching push button switches for the blinds (not bell press).
MANUFACTURER| MODEL
NUMBER| IMPORTANT WALL SWITCH REQUIREMENTS
- LATCHING PUSH BUTTON SWITCH (not bell press)
---|---|---
CLIPSAL| 30PB
It is recommended to use a latching push button such as 30PB. Clipsal 30M can
also be used.
For up to date compatibility info please check our website:
www.advantageair.com.au/support
Note: Wall Switches should be fitted for each channel of blinds and lights.
Setting the Blind limits – top and bottom
Note: Be very careful when setting the blind top and bottom limits.
The incorrect procedure can cause the roller blind motor to damage the roller
blind and its mountings, and cause it to fall.
Set up as follows:
There are two settings to adjust on the motor shaft.
- One for up
- One for down
You can see small arrows that show you the direction or travel (rotation of the motor).
- Set the initial “up” position by rotating the “-” for 15-20 full turns
- Set the initial “down” position by rotating the “-” for 15-20 full turns
- Be prepared to cut the power to the blind if it keeps moving.
- Apply Power to the blind.
- Choose “Down” on the wall-mounted touch screen.
- Adjust the down direction “+” screw until the blind is lower to the correct position.
- Choose “Up” on the wall-mounted touch screen
- Adjust the up direction “+” screw until the blind raises to the correct position.
Roller Blind Motors Can Overheat
In some cases, when roller blinds are rolled up and down, repetitively, the
roller blind motor will overheat. This is a safety mechanism inside the roller
blind motor, and may vary from brand to brand. It will also vary depending
upon the ambient temperature and the fitted roller blinds width, height, and
weight.
If it overheats, then the roller blind motor stops.
Pressing buttons on the MyPlace Apps or wall switch will not make the motor
move again. The motor will stay stopped until it cools down.
When the roller blind motor does cool down, it will return to the last
position set via the MyPlace App or wall switch.
Roller Blind 240V Wiring
The wiring of the roller blind motor depends upon the side that the motor is mounted, and how the roller blind is mounted, as below.
Channel Function | N/O Terminal | N/C Terminal | ‘C’ Terminal |
---|---|---|---|
Motor Left, Back Roll Motor Right, Front Roll | The black wire of roller blind | ||
motor | Brown wire of roller blind motor | Active | |
Motor Left, Front Roll Motor Right, Back Roll | Brown wire of roller blind | ||
motor | The black wire of roller blind motor | Active |
Roller Blind Wiring – Method 1 (Using 48V switching on inputs)
Roller Blind Wiring – Method 2 (using 240V switching [using ADAP SW48] on inputs)
Lights 240V Wiring
Important introduction
Note: Do not use the RM2 as a junction box.
Only run wires into the RM2 for direct connection to N/O, N/C, and C for each
channel.
-
Ensure all power is turned off.
-
Remove the lid of the RM2.
-
Pass the wire through the cable gland.
Note: The outside diameter needs to be 5-10mm. -
Screw the cables to the channel terminals as shown in the table below.
Note: Strip length: 6mm.Channel Function| N/O Terminal| N/C Terminal| ‘C’ Terminal
---|---|---|---
Light| Load| Not used| Active
Other device| Load| Not used| Active -
Tighten the cable glands.
-
Set the DIP switches (in the next section).
-
Replace the lid with 6 screws.
The relay outputs must be wired and housed in accordance with the applicable
wiring rules, regulations, and standards.
All 240V mains wiring must be done by a licensed electrician.
240V Wiring – Method 1 (using 48V switching on inputs)
This method uses low voltage switching and controls 240V lights.
240V Wiring – Method 2 (using 240V switching [using ADAP SW48] on inputs)
Channel Setup
DIP Switch Setup
- Remove the RM2 lid
- Set the DIP switch for each channel according to what will be operated by the channel (see the table below for DIP settings)
- Close the lid
DIP SWITCH SELECTION (CH-1 to CH-6)
FUNCTION| SW1| SW2| SW3| SW4
Blind| ON| OFF| OFF| OFF
Garage Door| ON| ON| OFF| OFF
Light| OFF| OFF| ON| OFF
Other| OFF| OFF| OFF| ON
Ensure mains power is turned off before removing the lid.
Channel DIP Switches
Rename each channel / button
Rename each button on the Wall Mounted Touch Screen
Go to: MyPlace (purple tab) > Setup > Setup Buttons > choose the pencil to
rename
DIP Switch set to “other”
When you select “other” on Table 8, you can choose the button types that will display to the user. The choices are:
- Up/Down (arrows)
- On/Off
- Open/Closed
You can see the 3 button types below.
You can choose the button type on the Button Setup page, at the same time that
you change the name for that button. The selected button type has a purple
outline here. Example:
Purple Blue Yellow – which tabs will be shown
Please see the table of Tabs below that the end-user will see on their MyPlace
wall-mounted touch screen, based on what they have installed – and what
modules are used for the install.
Acronyms:
ELV Lights = 48V extra low voltage lights.
BOG = Blinds, Other, Garage Door.
Power Supply Options
The RM2 has two power supply connection options:
Single RM2
Connect the PS-48 directly into the RM2 module.
Multiple RM2s
An EXT-48 can be used to share power from each PSU48 to (up to) 4x RM2s.
More than 4x RM2s
11/05/2019
Documents / Resources
|
ADVANTAGE AIR RM2 Relay Module
2
[pdf] Installation Guide
RM2 Relay Module 2, RM2, Relay Module 2
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>