CIPer Model 30
CONTROLLER AND EXPANSION IO
CIPer Model 30 controllers are available in two models WEB-C3036EPUBNH and WEBC3036EPVBNH.
CONTROLLER
These are Internet Protocol (IP) based “EDGE” controllers that can be used for VAV, unitary, equipment, and plant applications. Each controller is programmable and configurable using the open Niagara 4 Framework. Each controller is equipped with a four-port Gigabit network switch, that can integrate with broader IP peripheral devices including cameras, variable frequency drives, utility meters, lighting systems, etc. The CIPer Model 30 controllers can communicate over TCP/ IP (FOXS), BACnet, and Modbus protocols. These controllers can be used to aggregate information (including real-time data, alarms, trends, and history) and integrate this data to maximize the efficiency and lifespan of expensive facility equipment (assets) while helping prevent unplanned downtown. Additional physical I/O points are available using Expansion IO modules WEB-O9056H and WEB-O3022H.
EXPANSION IO
Expansion IO can be directly connected to the CIPer Model 30 controller or remotely mounted up to 100 ft away. The CIPer Model 30 supports up to 8 Expansion IO modules (WEB-O9056H and WEB-O3022H). The WEB-O9056H module is a large Expansion module that adds 20 additional I/O points, and the WEB-O3022H module is a small Expansion module that adds 7 additional I/O points. You can mix the small WEB-O3022H and the large WEB-O9056H in any combination to meet specific project I/O requirements. The Expansion IO modules feature removable terminal blocks, Hand-Off-Auto switches, and indicator LEDs. They can be powered by the CIPer Model 30 controller.
ORDERING PART NUMBERS
MODEL | DESCRIPTION |
---|---|
WEB-C3036EPUBNH | CIPer IP Unitary Controller, Niagara N4 license for BACnet, |
150 Points, 3 Devices, SMA included
WEB-C3036EPVBNH| CIPer IP VAV Controller, Niagara N4 license for BACnet, 150
Points, 3 Devices, SMA included
FOC-EDGE-CONV| Software license conversion to BACnet, Modbus, 100 Points, 3
devices, SMAincluded
WEB-O9056H| CIPer IP Large Expansion Module, 20 I/O Points (9-UI, 6-BO, 5-UIO)
WEB-O3022H| CIPer IP Small Expansion Module, 7 I/O Points (3-UI, 2-BO, 2-UIO)
EXPANDABLE LICENSE UPGRADE
PIN-EDGE-UPG| Upgrade existing CIPer Model 30 to expandable license for 100
points and 5 devices. SMA is required and sold separately.
---|---
PIN-DEV-UP-1| 1 Device & 50 Point Upgrade. Only available with an expandable
license.
PIN-DEV-UP-2| 2 Device & 100 Point Upgrade. Only available with an expandable
license.
SMA-0002-xYR| Software Maintenance Agreement – available in 1,3, or 5-year
increments.
CONTROLLER PART NUMBERS DESCRIPTION
FEATURES AND HIGHLIGHTS
CONTROLLER
- Full Niagara 4 stack with 12 points of onboard I/O expandable up to 172 channels (including 9 monitored Hand-Off-Auto).
- 1Gbps 4-Port IP switch integrates demanding IP peripheral devices (like color cameras) 1000 times faster than serial MSTP.
- Full Niagara N4 license includes,
- 150 points (including data sharing points from the third-party BACnet devices) and 3 devices.
- The CIPer Model 30 supports up to 8 Expansion IO modules.
- Rapid Spanning Tree Protocol (IEEE 802.1w) supports 120 controllers on a daisy chain bus with fewer home runs for faster and lower cost wiring.
- Up to 40 controllers can be connected in a ring or loop, to provide high resilience to network failure.
EXPANSION IO
-
Plug-and-play functionality for each installation and maintenance.
-
All wiring connections are made to removable terminal blocks to simplify device installation and replacement.
-
Wide range of supported sensors such as 20 KNTC, PT1000, and other resistive sensors.
-
16-bit A/D conversion resolution for accurate measurement.
-
Supports Star network topology.
-
Spyder program and Venom conversion application standard.
-
BACnet B-BC listed product.
-
The CIPer Model 30 controller features a Sylk™ bus interface that facilitates the connection of room sensor, Sylk™ actuator, and display devices (e.g. the TR40 and TR42 series).
-
Direct supervisor connectivity (Cloud or on-premise); simplifying system architecture and reducing programming, commissioning & installation time.
-
Niagara 4 Framework eliminates the extra cost, proprietary software, and tools.
-
SSL encrypted communications (FOXS PKI Certificate) protect the facility’s expensive assets and infrastructure with
-
Indication LEDs for all Digital and Analog Outputs (DO & AO).
-
HOA (Hand-Off-Auto) switches on DOs and AOs. HOA is configurable and can be monitored.
-
Compact size for small installation housings.
-
Field configuration and programming for Expansion IO input and output functions can be performed using world-class cyber-security.
-
FIPS 140-2 Level 1 compliance for critical high-risk facilities.
-
Industry-standard TCP/IP connectivity, enabling the use of CAT5 or CAT6 Ethernet cables.
-
16-bit A/D conversion resolution for accurate measurement.
-
VAV model includes an onboard airflow sensor.
-
Live “real-time” programming; no time-consuming downloads.
-
Solid State Relay (SSR) outputs reduce the need for external relays.
-
Ready to use open-protocol Niagara 4 wire-sheet, alarming, history, schedules, web server, HTML graphics, standard tools and palettes, pre-configured common application macro library, analytic points, and Haystack Tagging.
CIPer Model 30 programming tool. -
The CIPer Model 30 supports up to 8 Expansion IO modules(WEB-O9056H and WEB-O3022H).
DIMENSIONS
Fig. 1 Different views of CIPer Model 30 controller
Fig. 2 WEB-O3022H
Fig. 3 WEB-O9056H
Fig. 4 Dimensional view of stacked Controller and Expansion IO modules
SYSTEM OVERVIEW
PRODUCT SPECIFICATION
HARDWARE SPECIFICATION
MRAM | 512 KB |
---|---|
RAM | 1 GB |
FLASH RAM | 4 GB |
CPU | Cortex A9 32-bit processor 1 GHz, Cortex-M4 227 MHz |
Operating system | QNX based |
Real-Time clock timekeeping accuracy | 24-hour, 365-day, multi-year calendar |
including the day of week and configuration for automatic daylight savings
time adjustment to occur at 2:00 am. local time on configured start and stop
dates. Minimum 48 hours backup.
Power failure memory backup| 24-hours at 32 °F to 100 °F (0°C to 38 °C),
22-hours at 100 °F to 122 °F (38 °C to 50 °C)
Time accuracy| ±1 minute per month at 77 °F (25 °C)
ELECTRICAL
Rated input voltage | 24 VAC (20 to 30 VAC) 50/60 Hz |
---|---|
Rated impulse voltage | 330 VAC for Category I (SELV) |
Rated output voltage | 20 to 30 VAC ® 50/60 Hz |
Rated output type | Solid-State Relay, 1.5 A Continuous, 3.5 A inrush for 100 |
ms.
Power consumption•| CIPer Model 30 Controller| 100 VA maximum for the
controller and all connected loads 50 VA maximum for controller only load
WEB-09056H| 207 VA maximum for I/O module with all connected loads 35 VA
maximum for I/O module without any load
WEB-03022H| 87 VA maximum for I/O module with all connected loads 15 VA
maximum for I/O module without any load
*Power consumption is based on the sum of the VA rating for each controller and should not exceed 100 VA. In case it exceeds 100 VA, use a separate transformer to power up the modules.
OPERATING ENVIRONMENT
Ambient temperature• | – 4 °F to 131 oF (-20°C to 55 °C) |
---|---|
Storage temperature | – 4 °F to 150°F (-20°C to 65 °C) |
Humidity | 5% to 95% RH non-condensing |
Protection | IP20 |
• When utilizing differential pressure transducer. operating temperature ambient rating:32°F to 122°F (0 °C to 50°C).
DIFFERENTIAL PRESSURE SENSOR (VAV MODEL)
Media type | Air, N2, O2 (non-condensing) |
---|---|
Media temperature | 32 °F to 122 °F (0 °C to 55 °C) |
Pressure range | WEB-C3036EPVBNH: ±2” WC (±500 Pa) |
Expansion IO: ±2” WC (±374 Pa)
SUPPORTED SYLK DEVICES
Wall modules sensors| TR40, TR40-H, TR40-CO2, TR40-H-CO2, TR42, TR42-H,
TR42-CO2, TR42-H-CO2, TR71, TR71-H, TR75, TR75-H,
TR120, TR120-H
---|---
Sensors| C7400S Sylk™ Sensor
Sylk Actuator| MS3103, MS3105, MS4103, MS4105, MS7403, MS7405, MS7503, MS7505,
MS8103, MS8105 spring return Direct
Coupled Actuators (DCA) are used within the heating, ventilating, and air-
conditioning (HVAC) systems. They can drive a
variety of quarter-turn; final control elements requiring spring return fail-
safe operation.
CONTROLLER AND EXPANSION IO UNIVERSAL INPUT/OUTPUT DETAILS
CONTROLLER | CONTROLLER TYPE | UI | UIO | UIO |
---|---|---|---|---|
WEB-C3036EPUBNH | Unitary | 3 | 3 | 6 |
WEB-C3036EPVBNH | VAV | 3 | 3 | 6 |
WEB-O3022H | IO module | 3 | 2 | 2 |
WEB-O9056H | IO module | 9 | 5 | 6 |
INPUT/OUTPUT SPECIFICATION
| UNIVERSAL INPUTS (UI)| UNIVERSAL INPUT/OUTPUT (UIO)| DIGITAL
OUTPUTS (DO)
---|---|---|---
Function| Voltage, current, resistive or digital input| Voltage, current,
resistive or digital input or analogue (voltage/current) output| Direct
(on/off); Slow PWM
Resolution| 16 bit (65536 steps)| NA
Pulse inputs| Frequency: 100 Hz max, minimum duty cycle: 5 mS ON / 5 mS OFF|
NA
Voltage Input| Input range: 0 to 10 VDC, Input resistance: 189 kQ,
Accuracy: 55% of full-scale (i.e. ±50 mV| As per supply voltage (20 – 30
VAC), Output Type solid-state relays.
Current Input| Input range: 0 to 20 mA, Current source: Internal (loop
power) or external PSU, Input resistance: 50012.w, Accuracy: 5±0.5% of
full-scale (i.e. 100 A)| 1.5 A continuous, 3 5 A (100 ms inrush)
Resistive Input| Resistance Input range: 0 to 300 Ica Accuracy. Not
specified, Bridge resistor 10 kit, Bridge supply. 3.3 V| NA
Digital Input| Voltage (open circuit): 3.3 V. Wetting current 330 A (3.3 V /
10 kit)
Analog Output| NA| Voltage mode
Range: 0 to 10 VDC (source 10 mA max, sink 1 mA max, load 21kW)
Accuracy. ±0.5% of full-scale (i.e. 50 mV) Current mode
Range: 0 to 20 mA (load 5550W) Accuracy. ±1% of full-scale
(i.e. ±200 A)
UNIVERSAL INPUTS SPECIFICATIONS FOR EXPANSION IO
INPUT TYPE | SENSOR TYPE | OPERATING RANGE |
---|
Room/Zone Discharge Air Outdoor Air
Temperature| 20K ohm NTC| -40 °F to 199 °F ( -40 °C to 97.77 °C)
Outdoor Air Temperature| C7031G| -40 °F to 120 °F (-40 °C to 49 °C)
C7041F| -40 °F to 250 °F (-40 °C to 121 °C)
PT1000 (IEC751 3850)| -40 °F to 199 °F (-40 °C to 93 °C)
TR23 Setpoint Potentiometer| 500 Ohm to 10,500 Ohm| 50 °F to 90 °F (10 °C to
32 °C)
Resistive Input| Generic| 100 Ohms to 100K Ohms
Voltage Input| Transducer, Controller| 0 – 10 VDC
Discrete Input| Dry Contact closure| OpenCircuit ≥ 3000 Ohms
ClosedCircuit < 3000 Ohms
STANDARDS AND APPROVALS
UL/CUL (E87741) listed under UL 60730-1 and CSA E60730-1, UL 60730-2-9:2010.
- Meets FCC Part 15, Subpart B:2017, Class B (radiated emissions) requirements.
- Meets Canada ICES-003:2016.
- EMC Directive: 2014/30/EU. Standards Applied:
- EN 61000-6:2005
- EN 61000-6-3:2007 + A1
- EN 60730-1: 2011, EN 60730-2-9: 2010
- RoHS Directive: 2011/65/EU. Standards Applied:
- EN 50581: 2012
CONFORMANCE STATEMENT
This digital apparatus complies with CAN ICES-3 (B)/ NMB-3 (B).
FCC NOTICE
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
APPLICABLE TECHNICAL LITERATURE
TITLE | REFERENCE |
---|---|
CIPer Model 30 Installation Instruction | 31- 00183 |
CIPer Model 30 System | 31- 00207 |
Engineering User Guide | NA |
CIPer Model 30 Software
Release Bulletin
SAFETY INFORMATION
AS PER EN60730-1
The Open System is intended for residential, commercial, and light-industrial
environments. The Open System is an independently mounted electronic control
system with fixed wiring.
The CIPer 30 controllers (WEB-C3036EPUBNH and WEB-C3036EPVBNH) and Expansion
IO (WEB-O9056H and WEB-O3022H) are suitable for mounting in the fuse boxes
conforming with standard DIN43880, and having a slot height of max. 1.77
inches (45 mm). It is suitable for panel rail mounting on 1.38 inches (35 mm)
standard panel rail (both horizontal and vertical rail mounting possible).
Safety information as per EN-60730-1
PARAMETER | DESCRIPTION |
---|---|
Electric Shock Protection | PELV |
Pollution Degree | Pollution Degree 2, suitable for use in industrial |
environments.
Installation| Class 3
Overvoltage Category| 24 V – powered controls: Category I
Rated Impulse Voltage| 330 VAC for Category I (SELV)
Automatic Action| Type 1
Software Class| Class A
Purpose of control| Operating Control, Open Energy Management Equipment.
Enclosure degree of protection| IP20
Ball pressure Test Temperature| > 167 °F (75 °C) for all housing and plastic
parts.
257 °F (125 °C) in the case of devices applied with voltage-carrying parts, connectors, and terminals.
Electromagnetic| Tested at 230 VAC, with the
Interference| Modules in normal condition.
System| Europe: safety isolating
Transformer| transformers according to I EC61558-2-6. U.S.A. and Canada: NEC
Class-2 transformers.
By using this Honeywell literature, you agree that Honeywell will have no
liability for any damages arising out of your use or modification to, the
literature. You will defend and indemnify.
Honeywell, its affiliates and subsidiaries, from and against any liability,
cost, or damages, including attorneys’ fees, arising out of, or resulting
from, any modification to the literature by you.
Honeywell Building Technologies
1985 Douglas Drive North
Golden VAlley, MN 55422
customer.honeywell.com
buildings.honeywell.com
@U.S. Registered Trademark
© 2021 Honeywell International Inc.
31-00236EFS-03 | Rev. 08-21
CIPer Model 30 and Expansion IO – Product Data Sheet | www.honeywell.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>