Honeywell Heavy Duty Pressure Transducers PX3 Series Installation Guide
- June 7, 2024
- Honeywell
Table of Contents
Honeywell Heavy Duty Pressure Transducers PX3 Series
Installation Instructions
General Information
Honeywell’s PX3 Series Pressure Transducers use piezoresistive sensing
technology with ASIC (Application Specific Integrated Circuit) signal
conditioning. The PX3 Series is calibrated and temperature compensated from
-40°C to 125°C [-40°F to 257°F].
The PX3 Series is not recommended for use with media involving water, saturated air such as steam and vapor, and ammonia.
Table 1. Performance Specifications (At 25°C [77°F] and under unless otherwise noted.)
Characteristic | Parameter |
---|---|
Operating temperature range1 | -40°C to 125°C [-40°F to 257°F] |
Storage temperature range1 | -40°C to 125°C [-40°F to 257°F] |
Compensated temperature range | -40°C to 125°C [-40°F to 257°F] |
Total Error Band2:
-20°C to 85°C [-4°F to 185°F]
<-20°C, >85°C [<-4°F, >185°F]
| ±1.0 %FSS
±2.0 %FSS
Accuracy BFSL3| ±0.25 %FSS
Response time| <2 ms (10% to 90% step change in pressure)
Turn on time4| <7 ms
EMC rating5:
surge immunity (all leads) electrostatic discharge radiated immunity fast transient burst immunity to conducted disturbances radiated emissions radiated immunity: ratiometric (voltage) output 4 mA to 20 mA (current) output
| **** ±1000 V line to ground per IEC 61000-4-5
±4 kV contact, ±8 kV air per IEC 61000-4-2
10 V/m (80 MHz to 1000 MHz) per IEC 61000-4-3
±1 kV per IEC 61000-4-4
3 V per IEC 61000-4-6
40 dBmV (30 MHz to 230 MHz), 47 dBmV (230 MHz to 1000 MHz) per CISPR 11
**** 200 V/m per ISO 11452-2
140 V/m per ISO 11452-2
Insulation resistance6: ratiometric voltage output current output| >100 MOhm at 1500 Vdc
100 MOhm at 1000 Vdc
Dielectric strength| <1 mA at 1500 Vac (1 min) or 1800 Vac (1 s)
Load resistance6: ratiometric voltage output current output| >5 kOhm
(Vin – 8) x 50 Ohm
Life| >10 million full scale pressure cycles over the calibrated pressure range
- Dependent on seal material..
- Total Error Band: The maximum deviation from the ideal transfer function over the entire compensated temperature and pressure range. Includes all errors due to offset, full scale span, pressure non-linearity, pressure hysteresis, pressure non-repeatability, thermal effect on offset, thermal effect on span, and thermal hysteresis.
- Accuracy: The maximum deviation in output from a Best Fit Straight Line (BFSL) fitted to the output measured over the pressure range at 25°C [77°F]. Includes all errors due to pressure non-linearity, pressure hysteresis, and pressure non-repeatability.
- Turn on time: Duration from power applied until first valid output for voltage output. Typical value for 4 mA to 20 mA output.
- Tested using 1,5 m [59.1 in] long cable.
- Tested in dry, non-ionized air.
Table 2. Electrical Specifications
Characteristic | Parameter |
---|
Supply voltage:
ratiometric voltage output: 5 Vdc
3.3 Vdc current output:
-40°C to 100°C >100°C to 125°C
| 5 Vdc ±0.25 Vdc
3 Vdc ±0.25 Vdc
**** 8 Vdc to 30 Vdc
8 Vdc to 25 Vdc
Over voltage and reverse voltage: ratiometric voltage output current output| ±16 Vdc
±35 Vdc
Current consumption: 5 Vdc supply 3.3 Vdc supply| 3.0 mA max.
1.6 mA to 2.1 mA
Short circuit protection| yes
Nominal output transfer function: 5 Vdc supply 3.3 Vdc supply 8 Vdc to 30 Vdc
supply| 0.5 Vdc to 4.5 Vdc (ratiometric to supply)
0.33 Vdc to 2.97 Vdc (ratiometric to supply) 4 mA to 20 mA
Figure 1. TEB Definition and Temperature Performance
Table 3. Pressure Reference Definitions
Pressure Reference | Definition |
---|---|
Absolute | Output is calibrated to be proportional to the difference between |
applied pressure and a fixed reference to perfect vacuum (absolute zero
pressure).
Sealed gage1| Sensor construction is identical to the absolute version with a
built in reference at zero pressure in order to minimize measurement error
over temperature. The output is calibrated to be proportional to the
difference between applied pressure and a reference of 1 standard atmosphere
(1.013 barA | 14.7 psiA). Example: 100 psi sealed gage has a calibrated
pressure range from 14.7 psi absolute to 114.7 psi absolute. (See Figure 2.)
Sealed gage option only available in pressure ranges at or above 8 bar | 100 psi.
Figure 2. Ratiometric Output Option AA for 100 psi, Absolute vs Sealed Gage
Table 4. Pressure Ratings
bar | psi |
---|---|
Operating Pressure | O v er- pressure |
Pressure | Operating Pressure |
Burst Pressure
1| 5| 8| 15| 70| 115
1.6| 5| 8| 30| 150| 250
2| 10| 17| 50| 250| 400
2.5| 10| 17| 100| 450| 750
4| 17| 27| 150| 450| 750
6| 31| 51| 174| 450| 750
8| 31| 51| 200| 450| 1150
10| 31| 51| 250| 450| 1150
12| 31| 51| 300| 1000| 1500
16| 32| 80| 500| 1000| 1500
20| 69| 103| 600| 1000| 1500
25| 69| 103| 667| 1000| 1500
30| 69| 103| 700| 1000| 1500
35| 69| 103| –| –| –
40| 69| 103| –| –| –
46| 69| 103| –| –| –
50| 69| 103| –| –| –
Diagnostics Mode (For Ratiometric Voltage Output Only)
The PX3 Series diagnostics mode allows the device to indicate when internal or
external faults occur. If an internal fault occurs, the output will rail to
the preset lower or upper limit values shown in Figure 3 and Table 5.
External faults will result in the sensor’s output exceeding those preset
limits (lower or upper). (For example, if the external sensor ground (signal)
were lost, the sensor output would exceed the upper rail of 97.5%.)
Figure 3. Analog Output with Diagnostics
Table 5. Output Transfer Function Codes
Fault Condition | Analog Diagnostic Rail |
---|---|
EEPROM Corrupt | below lower rail |
Sensor Bridge Open (any element) | above upper rail |
Sensor Bridge Short (any element) | above upper rail |
Low supply voltage | below lower rail |
Loss of ground connection | above upper rail |
Table 6. Environmental and Mechanical Specifications
Characteristic | Parameter |
---|---|
Shock: threaded ports tube port | 100 G per MIL-STD-202G, Method 213B, Cond. F |
(at 25°C [77°F])
100 G per MIL-STD-202F, Method 213B, and Condition C
Vibration: threaded ports tube port| 20 G sweep, 10 Hz to 2000 Hz (at 25°C [77°F])
10 Hz to 55 Hz, 2 mm displacement, tested as per IEC 60068-2-6; Test FC. (at 25°C [77°F])
Ingress protection:
Metri-Pack 150 electrical connector cable harness electrical connector DIN electrical connector
| IP67
IP65, IP67, IP69K IP65
Ambient humidity| 0 %RH to 95 %RH, non-condensing
External freeze/thaw resistance| >6 cycles from -30°C to 50°C [-22°F to 122°F]
Wetted materials: threaded ports external seals for ports tube port braze
filler internal O-ring media seal sensing element and substrate adhesives|
brass C36000; lead (Pb) content: 3.7% max. nitrile copper UNS C12200; lead
(Pb) free silver and copper alloy seal material based on application (see seal
material media compatibility options below) alumina, glass, silicon epoxy
Internal O-ring material media compatibility1: HNBR (option H)
silicone (option S)| refrigerants, engine oil, petroleum-based hydraulic fluid
dry air
Electrical connector material| PBT 30% GF
Honeywell can assist with selecting suitable O-ring seal material for the media based on the seal manufacturer’s recommendation. The customer should test the compatibility with the media to ensure that it is correct for the application.
CAUTION: PRODUCT DAMAGE TO TUBE PRESSURE PORT TYPE DURING BRAZING
Ensure that the temperature of the brass port and plastic connector is
maintained below 125°C during flame brazing.
Exposure to temperatures higher than 125°C can cause permanent product damage
and can compromise ingress protection leading to short circuits.
Failure to comply with these instructions may result in product damage.
CAUTION: PRODUCT DAMAGE DUE TO MECHANICAL ISSUES
- Ensure torque specifications are determined for the specific application. Values provided are for reference only. (Mating materials and thread sealants can result in significantly different torque values from one application to the next.)
- When using mating parts made of stainless steel, use a thread sealant with anti-seize properties to prevent thread galling. Ensure the sealant is rated for the application.
- Use appropriate tools (such as an open ended wrench or deep well socket) to install transducers.
- Always hand-start transducers into the hole to prevent cross threading and damage.
- Ensure that torque is not applied to the electrical connector.
- Ensure that the proper mating electrical connector with a seal is used to connect the transducer. Improper or damaged seals can compromise ingress protection, leading to short circuits.
Failure to comply with these instructions may result in product damage.
CAUTION: PRODUCT DAMAGE DUE TO PARTICULATES AND SATURATED AIR
Ensure that filters and dehumidifiers are used upstream of the transducers to
keep media flow free of large particulates and condensed moisture. PX3 Series
transducers are dead-end devices. Particulate accumulation may clog the port
or damage the diaphragm. Condensing moisture may affect sensor output and
lower insulation resistance.
Failure to comply with these instructions may result in product damage.
CAUTION: PRODUCT DAMAGE DUE TO CONDUCTIVE MEDIA
Ensure sensor is not used with conductive or ionic media. These media can
affect sensor output and lower insulation resistance.
Failure to comply with these instructions may result in product damage.
Figure 4. Metri-Pack Mounting Dimensions (For reference only. mm/[in].) E
Figure 5. DIN Mounting Dimensions (For reference only. mm/[in].) E
Figure 6. Cable Harness Mounting Dimensions Shown by Pressure Port Type (For reference only. mm/[in].) E
WARNING: PERSONAL INJURY
DO NOT USE these products as safety or emergency stop devices or in any other
application where failure of the product could result in personal injury.
Failure to comply with these instructions could result in death or serious
injury.
Warranty/Remedy
Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship during the applicable warranty period. Honeywell’s standard product warranty applies unless agreed to otherwise by Honeywell in writing; please refer to your order acknowledgement or consult your local sales office for specific warranty details. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace, at its option, without charge those items that Honeywell, in its sole discretion, finds defective. The foregoing is buyer’s sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. In no event shall Honeywell be liable for consequential, special, or indirect damages.
While Honeywell may provide application assistance personally, through our
literature and the Honeywell web site, it is buyer’s sole responsibility to
determine the suitability of the product in the application.
Specifications may change without notice. The information we supply is
believed to be accurate and reliable as of this writing. However, Honeywell
assumes no responsibility for its use.
For more information
Honeywell Advanced Sensing Technologies services its customers through a
worldwide network of sales offices and distributors. For application
assistance, current specifications, pricing or the nearest Authorized
Distributor, visit our website or call:
Asia Pacific +65 6355-2828
Europe +44 (0) 1698 481481
USA/Canada +1-800-537-6945
Honeywell Advanced Sensing Technologies
830 East Arapaho Road
Richardson, TX 75081
sps.honeywell.com/ast