ReliaGear ™ Pro-Stock ™
Lighting Panels
User Manual
ReliaGear Pro-Stock Lighting Panels
A lighting panelboard for projects with short turnaround
Select interior
Select the interior by bus type, panel rating and number of circuits.
Identify the box/front height for use in steps 2 and 3.
Copper Bus
Voltage| Amp Rating| No. of Circuits| Feed-thru Cat. No.¹|
Box/Front Height| Non Feed-thru
Cat. No.¹| Box/Front Height| TGL2 Ground
Bars² ³
---|---|---|---|---|---|---|---
240 Vac, 1 Phase| 100-250| 18| AQU1182RCXAXT1B4| 37.5″| AQU1182RCXAXB4| 31.5″|
2
| 30| AQU13O2RCXAXT1B4| 43.5″| AQU13O2RCXAXB4| 37.5″| 3
| 42| AQU1422RCXAXT1B4| 49.5″| AQU1422RCXAXB4| 43.5″| 4
400| 18| AQU1184RCXAXT1B4| 64.5″| –| –| 2
| 42| AQU1424RCXAXT1B4| 1 76.5″| I AQU1424RCXAXB4| 64.5″| 4
600| 18| AQU1186RCXAXT1B4| 1 64.5″| –| –| 2
| 42| AQU1426RCXAXT1B4| 1 76.5″| AQU1426RCXAXB4| 64.5″| 4
208/120
Vac, 3 Phase| 100-250| 18| AQU3182RCXAXT1B4| 37.5″| AQU3182RCXAXB4| 31.5″| 2
| 30| AQU33O2RCXAXT1B4| 43.5″| AQU33O2RCXAXB4| 37.5″| 3
| 42| AQU3422RCXAXT1B4| 49.5″| AQU3422RCXAXB4| 43.5″| 4
400| 18| AQU3184RCXAXT1B4| I 64.5″| –| –| 2
| 42| AQU3424RCXAXT1B4| 76.5″| AQU3424RCXAXB4| 64.5″| 4
600| 18| AQU3186RCXAXT1B4| 64.5″| –| –| 2
| 42| AQU3426RCXAXTIB4| 76.5″| AQU3426RCXAXB4| 64.5″| 4
480/277
Vac, 3 Phase| 100-250| 18| AEU3182RCXAXTIB4| 37.5″| AEU3182RCXAXB4| 31.5″| 2
| 30| AEU33O2RCXAXT1B4| 43.5″| AEU33O2RCXAXB4| 37.5″| 3
| 42| AEU3422RCXAXT1B4| 49.5″| AEU3422RCXAXB4| 43.5″| 4
400| 18| AEU3184RCXAXT1B4| 64.5″| –| –| 2
| 42| AEU3424RCXAXT1B4| 76.5″| AEU3424RCXAXB4| 64.5″| 4
600| 18| AEU3186RCXAXT1B4| 64.5″| –| –| 2
| 42| AEU3426RCXAXT1B4| 76.5″| AEU3426RCXAXB4| 64.5″| 4
Aluminum Bus
Voltage| Amp Rating| No. of
Circuits| Feed-thru Cat. No.¹| Box/Front Height| TGL2
Ground
Bars
---|---|---|---|---|---
240 Vac, 1 Phase| 100-250| 18| AQU1182RCXAXT1| 37.5″| 2
30| AQU1302RCXAXT1| 43.5″| 3
42| AQU1422RCXAXT1| 49.5″| 4
208/120 Vac, 3 Phase| 100-250| 18| AQU3182RCXAXT1| 37.5″| 2
30| AQU3302RCXAXT1| 43.5″| 3
42| AQU3422RCXAXT1| 49.5″| 4
480/277 Vac, 3 Phase| 100-250| 18| AEU3182RCXAXT1| 37.5″| 2
30| AEU3302RCXAXT1| 43.5″| 3
42| AEU3422RCXAXT1| 49.5″| 4
TGL20 ground lug quantities
| No. of TGL20s Required by Panel Rating
---|---
Interior Type| 100-250A| 400A| 600A
Main Lug Only| 1| 1| 2
Main Lug & Feed-thru| 2| 2| 4
Main Breaker Only| 1| 1| –
Main Breaker & Sub-feed| 1| 1| –
Main Breaker & Feed-thru| 2| 2| –
- For TGL20 ground lug quantities, see TGL20 ground lug quantities table above.
- For isolated ground, use EGS12. When using the EGS12, 3, 5 and 7 ground lugs (TGL20s) are required for 18, 30 and 42 circuits respectively.
- Main bus rating of 250A for main breaker interiors and a bus rating of 225A for main lug interiors.
Choose box
Select a box of the correct height (see step 1). Boxes come with blank
endwalls.
If endwalls with knockouts are required, also order knockout endwall kit
AKEW2.
| NEMA 1| NEMA 3R| NEMA 4, 4X and 12 Painted Galvaneal|
NEMA 4, 4X and 12 Stainless Steel
---|---|---|---|---
Box Height| 20″ Wide| 20″ Wide| 20″ Wide| 20″ Wide
25.5″| –| –| –| AB254S
31.5″| AB31B| AB313| AB314| AB314S
37.5″| AB37B| AB373| AB374| AB374S
43.5″| AB43B| AB433| AB434| AB434S
49.5″| AB49B| AB493| AB494| AB494S
64.5″| AB64B| AB643| AB644| AB644S
76.5″| AB76B| AB763| AB764| AB764S
Add a front
Add a front of the correct height (available for NEMA 1 enclosures only)
Standard fronts are equipped with concealed hinges and trim adjusting screws
hinges, trim adjusting screws and quarter turn locks.
The door-in-door is convenient for contractors to gain easy access to
equipment from the front of the panel. Door-in-door allows a contractor access
to the gutters without removing the front.
Front hinged to box is similar to door-in-door for convenient access to
gutters, but a contractor must remove four screws to access the outer door.
Front| Standard (20″ Wide)| Door Within Door (20″ Wide)|
Front Hinged to Box (20” Wide)
---|---|---|---
**Height| Flush¹| Surface¹| Flush¹| Surface¹|
Flush¹| Surface¹**
31.5″| AF31F| AF31S| AF31FP| AF31SP| AF31FD| AF31SD
37.5″| AF37F| AF37S| AF37FP| AF37SP| AF37FD| AF37SD
43.5″| AF43F| AF43S| AF43FP| AF43SP| AF43FD| AF43SD
49.5″| AF49F| AF49S| AF49FP| AF49SP| AF49FD| AF49SD
64.5″| AF64F (T)| AF64S (T)| AF64FP (T)| AF64SP (T)| AF64FD (T)| AF64SD (T)
76.5″| AF76F (T)| AF76S (T)| AF76FP (T)| AF76SP (T)| AF76FD (T)| AF76SD (T)
1 (*T) Fronts with quarter turn lock for applications with XT5 circuit breakers
Select main and/or sub-feed breaker kit
Select the main breaker kit appropriate for your interior type (see step 1),
amp rating and kAIC rating. If a sub-feed breaker is required, repeat the
selection process. Some units come standard with a breaker.
Please see the list to the right.
Cat. No. | Breaker Description | Breaker Type |
---|---|---|
MBM124WB | XT5 TMA 400 AMPS 3P | XT5NU340ABFN000XXX |
MBB13WB | XT4 TMF 225 AMPS 3P | XT4NU3225AFJ000XXX |
MBB16WB | XT4 TMF 225 AMPS 3P | XT4NU3225AFJ000XXX (2) |
MBM134WB | XT5 TMA 400 AMPS 3P | XT5NU340ABFN000XXX |
MBC33WB | XT1 TMF 125 AMPS 3P | XT1HU3125AFD000XXX |
MBB33WB | XT4 TMF 225 AMPS 3P | XT4HU3225AFJ000XXX |
MBB36WB | XT4 TMF 225 AMPS 3P | XT4HU3200AFJ000XXX (2) |
MBM334WB | XT5 TMA 400 AMPS 3P | XT5HU340ABFN000XXX |
MBM324WB | XT5 TMA 400 AMPS 3P | XT5HU340ABFN000XXX |
Interior | ||
Type | Cat. No. 1 | Max. Amp |
Rating | No. of | |
Poles | 10 | 14 |
100 | 150 | 200 |
--- | --- | --- |
AQU1: 240 | ||
VAC, 1 Phase | MB612 | 100 |
MB614 | 100 | 4 |
MBA12 | 225 | 2 |
MBM324 | 400 | 2 |
MBM124WB | 400 | 2 |
AQU3: 208/120 | ||
VAC, 3 Phase | MB613 | 100 |
MB616 | 100 | 6 |
MBA13 | 225 | 3 |
MBA16 | 400 | 6 |
2 | (x2) A2A | |
MBB33 | 250 | 3 |
MBB13WB | 225 | 3 |
MBB36 5 | 400 | 6 5 |
MBB16WB
5| 400| 6 5| | | | | | | XT4N| | |
MBM334| 400| 3| | | | | | | XT5N| XT5S| XT5H| XT5L
MBM134WB| 400| 3| | | | | | | XT5N| | |
MBM124WB4| 400| 2
3| | | | | | | XT5N| | |
| AEU3: 480/277
Vac, 3 Phase| MB423| 100| 3| | TEY| | | | | | | |
MB426| 100| 6| | (x2) TEY| | | | | | | |
MBC33| 125| 3| | | | XT1N| XT1S| | XT1H| | |
MBC33WB| 125| 3| | | | | | | XT1H| | |
MBB33| 250| 3| | | | | | | XT4H| | |
MBB33WB| 225| 3| | | | | | | XT4H| | |
MBB365| 400| 6 5| | | | | | | (x2) XT4H| | |
MBB36WB5| 400| 6 5| | | | (x2) XT4N| (x2) XT4S| | (x2) XT4H| | |
MBM334| 400| 3| | | | | XT5N| XT5S| XT5H| | |
MBM334WB| 400| 3| | | | | | | XT5H| | |
MBM324WB4| 400| 23| | | | | | | XT5H| | |
-
Breaker not included except for “WB” kits (where product number ends in “WB”).
“WB” kits include a breaker, mounting kit and load-side lugs. -
Actual breaker short circuit rating is 25 kAIC.
-
Use 2 outer poles for 3 pole applications.
-
For sub-feed application only.
-
6 poles of sub-feed applies only to 400 A and 600 A interiors.
-
Can use (2) 3 pole devices only, no 2 pole allowed.
Select alternative main breakers
Skip step 5 if you selected a main breaker kit ending in “WB” — no breaker is
required.
To correlate breaker types with the kAIC rating in specific panelboards, see
the table for step 4.
For more rating details, see ReliaGear lighting panels rating series labels
(1TQC173100E0001).
Use 2 outer poles for 3 pole applications.
For TEY and THQB main breakers, see branch breakers tables in step 7.
Tmax XT breakers1 (3-pole) for use with appropriate main breaker kit (see step 4).
240V KAIC| 480V KAIC| Breaker Description| US Product
Number| Wire Range (Cu/Al)| Cables per Lug
---|---|---|---|---|---
65| 65| XT1H 125 TMF 30 AMPS 3P| XT1HU3030AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT1H 125 TMF 60 AMPS 3P| XT1HU3060AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT1H 125 TMF 100 AMPS 3P| XT1HU3100AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT1H 125 TMF 125 AMPS 3P| XT1HU3125AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 35| XT1S 125 TMF 100 AMPS 3P| XT1SU3100AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT4H 250 TMF 150 AMPS 3P| XT4HU3150AFJ000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 65| XT4H 250 TMF 200 AMPS 3P| XT4HU3200AFJ000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 65| XT4H 250 TMF 225 AMPS 3P| XT4HU3225AFJ000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 35| XT4S 250 TMF 175 AMPS 3P| XT4SU3175AFJ000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 35| XT4S 250 TMF 200 AMPS 3P| XT4SU3200AFJ000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 35| XT4S 250 TMF 225 AMPS 3P| XT4SU3225AFJ000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 35| XT4S 250 TMF 250 AMPS 3P| XT4SU3250AFL000XXX| Cu Al 1×4 AWG–300 kcmil|
1
65| 35| XT4N 250 ekip DIP 60-150 AMPS 3P| XT4NU3150FFL000XXX| Cu Al 1×4
AWG–300 kcmil| 1
65| 35| XT4S 250 ekip DIP 100-250 AMPS 3P| XT4SU3250FFL000XXX| Cu Al 1×4
AWG–300 kcmil| 1
65| 65| XT4H 250 ekip DIP 100-250 AMPS 3P| XT4HU3250FFL000XXX| Cu Al 1×4
AWG–300 kcmil| 1
65| 65| XT5H 400 TMA 400 AMPS 3P| XT5HU340ABFN000XXX| Cu Al 2×2/0 AWG–500
kcmi| 2
65| 50| XT5S 400 TMA 300 AMPS 3P| XT5SU330ABFN000XXX| Cu Al 2×2/0 AWG–500
kcmi| 2
65| 50| XT5S 400 TMA 400 AMPS 3P| XT5SU340ABFN000XXX| Cu Al 2×2/0 AWG–500
kcmi| 2
65| 35| XT5N 400 ekip DIP 16-400 AMPS 3P| XT5NU340AFFN000XXX| Cu Al 2×2/0
AWG–500 kcmi| 2
65| 65| XT5H 400 ekip DIP 16-400 AMPS 3P| XT5HU340AFFN000XXX| Cu Al 2×2/0
AWG–500 kcmi| 2
1 Thermal Magnetic Fixed (TMF) – no adjustments possible. Thermal Magnetic Adjustable (TMA) – adjustable thermal (L) and magnetic (I).
Main or sub-feed breakers for use with RQ panels (208/120 V AC 3-phase or 240 V AC single-phase). See step 4.
| | 2-pole| | 3-pole
---|---|---|---|---
| 10kAIC| 22kAIC| 10kAIC| 22kAIC
Amp Rating| Cat. No.| Cat. No.| Cat. No.| Cat. No.
125| A2A125TL-2| A2N125TL-2| A2A125TT| A2N125TT
150| A2A150TL-2| A2N150TL-2| A2A150TT| A2N150TT
175| A2A175TL-2| A2N175TL-2| A2A175TT| A2N175TT
200| A2A200TL-2| A2N200TL-2| A2A200TT| A2N200TT
225| A2A225TL-2| A2N225TL-2| A2A225TT| A2N225TT
Select main lug kit and accessories
Main lug kits
Lug Type | Amp | Standard | Oversized | 200%Neutral | |
---|---|---|---|---|---|
Rating Cat. No. | I Wire Range | Cat. No. | Wire Range |
Cat. No.
| 225 MLA1| I 6-350 kcmil| MLA2| 1-600 kcmil or (2)1/0-250 kcmil| NKA
400 MLA41| ?-600 MCM or (2)1/0-250 kcmil| MLA62| 3/0-800 kcmil| NKA42
600 MLA61| I (2) 2/0-500 kcmil| MLA62| 3/0-800 kcmil| —
Copper| 225 MLR1| 4-450 kcmil| MLR2| 1-600 kcmil| NKR
400 MLR41| 1-600 kcmil| MLR61| (2) 2/0-500 kcmil| NKR4
600 MLR61| (2) 2/0-500 kcmil| —| —| —
Compression| 225 MLT1| 2/0-300 kcmil| M LT2| 4/0-500 kcmil| NKT
400 M LT42| 250-600 kc mil| MLT41| 500-750 kcmil’| NKT4
Dual| 225 MLA2| 2-600 kcmil or (2)1/0-250 kcmil| —| —| —
Main| 400 MLA61| L (2) 2/0-500 kcmil| —| —| —
- 500 kcmil Cu, 750 kcmil Al.
- For 200% neutral feed-thru, order NKA4FT, (GO-101P). Wire range (2) 2/0–600 kcmil or (4) 4–250 kcmil.
Accessories
Service Entrance¹
Amp Rating | Cat. No. |
---|---|
225 | BNDKT |
400 | BNDKT6 |
600 | BNDKT6 |
- Service entrance kit includes a bonding strap with hardware and a service entrance label
Scan to find out more about ReliaGear™ Pro-Stock™
https://electrification.us.abb.com/products/panelboards/reliagear-pro-stock- panelboard
Select bolt-on branch breakers
The tables below show standard branch breakers.
Branch circuit breakers for use with RQ panels (208/120 V AC 3-phase or 240
V AC single-phase)
Amp
Rating| | | 10 kAIC| | | 22 kAIC
---|---|---|---|---|---|---
1-pole| 2-pole| 3-pole| 1-pole| 1 2-pole| 3-pole
Cat. No.| Cat. No.| Cat. No.| Cat. No.| Cat. No.| Cat. No.
15| THQB1115| THQB2115| THQB32015| THHQB1115| THHQB2115| THHQB32015
20| THQB1120| THQB2120| THQB32020| THHQB1120| THHQB2120| THHQB32020
25| THQB1125| THQB2125| THQB32025| THHQB1125| THHQB2125| THHQB32025
30| THQB1130| THQB2130| THQB32030| THHQB1130| THHQB2130| THHQB32030
35| THQB1135| THQB2135| THQB32035| THHQB1135| THHQB2135| THHQB32035
40| THQB1140| THQB2140| THQB32040| THHQB1140| THHQB2140| THHQB32040
45| THQB1145| THQB2145| THQB32045| THHQB1145| THHQB2145| THHQB32045
50| THQB1150| THQB2150| THQB32050| THHQB1150| THHQB2150| THHQB32050
60| THQB1160| THQB2160| THQB32060| THHQB1160| THHQB2160| THHQB32060
70| THQB1170| THQB2170| THQB32070| THHQB1170| THHQB2170| THHQB32070
80| –| THQB2180| THQB32080| –| THHQB2180| THHQB32080
90| –| THQB2190| THQB32090| –| THHQB2190| THHQB32090
100| –| THQB21100| THQB32100| –| THHQB21100| THHQB32100
Branch circuit breakers for use with RE panels (480/277 V AC 3-phase)
Amp Rating | 14 kAIC | ||
---|---|---|---|
1-pole | 2-pole | 3-pole | |
Cat. No. | Cat. No. | Cat. No. | |
15 | TEY115 | TEY215 | TEY315 |
20 | TEY120 | TEY220 | TEY320 |
30 | TEY130 | TEY230 | TEY330 |
40 | TEY140 | TEY240 | TEY340 |
50 | TEY150 | TEY250 | TEY350 |
60 | TEY160 | TEY260 | TEY360 |
70 | TEY170 | TEY270 | TEY370 |
80 | TEY180 | TEY280 | TEY380 |
90 | TEY190 | TEY290 | TEY390 |
100 | T EY1100 | TEY2100 | TEY3100 |
Interior product number structure
Interior Type| Phase| No. of Circuits| Max. Amp Rating|
Ti Feed-thru| Bus
---|---|---|---|---|---
AQU = 240 Vac| 1 = 1-Phase| 18 = 18 Circuits
1| 2 = 250A MB/ 225A MLO| Blank Non Feed-thru* (required copper bus [B4])| B4
= Copper
AEU = 480Y/277 Vac| 3 = 3-Phase| I 30 = 30 Circuits| 4 = 400A| | Blank =
aluminum
| | 42 = 42 Circuits| 6 = 600A| |
Customer Service:
EPIS.ASeries.Mebane@abb.com
Technical Support: 1-800-431-7867
4 or epis.component.support@abb.com
Warranty Support: 1-888-437-3765
ABB Inc
305 Gregson Drive
Cary, NC 27511
electrification.us.abb.com
© Copyright 2021 ABB. All rights reserved.
Information provided is subject to change without notice. Please verify all
details with ABB. All values are design or typical values when measured under
laboratory conditions, and ABB makes no warranty or guarantee, express or
implied that such performance will be obtained under end-use conditions.
GE is a trademark of GE. Manufactured under trademark license.
1TQC214100E0001 DEN455B 10.2021
Documents / Resources
| GE
APPLIANCES ReliaGear Pro-Stock Lighting
Panels
[pdf] User Manual
ReliaGear Pro-Stock Lighting Panels, Pro-Stock Lighting Panels, Lighting
Panels, Panels
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>