GE APPLIANCES ReliaGear Pro-Stock Lighting Panels User Manual

June 3, 2024
GE Appliances

ReliaGear ™ Pro-Stock ™
Lighting Panels

User Manual

ReliaGear Pro-Stock Lighting Panels

A lighting panelboard for projects with short turnaround

Select interior

Select the interior by bus type, panel rating and number of circuits.
Identify the box/front height for use in steps 2 and 3.

Copper Bus

GE APPLIANCES ReliaGear Pro-Stock Lighting Panels

Voltage| Amp Rating| No. of Circuits| Feed-thru Cat. No.¹| Box/Front Height| Non Feed-thru
Cat. No.¹| Box/Front Height| TGL2 Ground
Bars² ³
---|---|---|---|---|---|---|---
240 Vac, 1 Phase| 100-250| 18| AQU1182RCXAXT1B4| 37.5″| AQU1182RCXAXB4| 31.5″| 2
| 30| AQU13O2RCXAXT1B4| 43.5″| AQU13O2RCXAXB4| 37.5″| 3
| 42| AQU1422RCXAXT1B4| 49.5″| AQU1422RCXAXB4| 43.5″| 4
400| 18| AQU1184RCXAXT1B4| 64.5″| –| –| 2
| 42| AQU1424RCXAXT1B4| 1 76.5″| I AQU1424RCXAXB4| 64.5″| 4
600| 18| AQU1186RCXAXT1B4| 1 64.5″| –| –| 2
| 42| AQU1426RCXAXT1B4| 1 76.5″| AQU1426RCXAXB4| 64.5″| 4
208/120
Vac, 3 Phase| 100-250| 18| AQU3182RCXAXT1B4| 37.5″| AQU3182RCXAXB4| 31.5″| 2
| 30| AQU33O2RCXAXT1B4| 43.5″| AQU33O2RCXAXB4| 37.5″| 3
| 42| AQU3422RCXAXT1B4| 49.5″| AQU3422RCXAXB4| 43.5″| 4
400| 18| AQU3184RCXAXT1B4| I 64.5″| –| –| 2
| 42| AQU3424RCXAXT1B4| 76.5″| AQU3424RCXAXB4| 64.5″| 4
600| 18| AQU3186RCXAXT1B4| 64.5″| –| –| 2
| 42| AQU3426RCXAXTIB4| 76.5″| AQU3426RCXAXB4| 64.5″| 4
480/277
Vac, 3 Phase| 100-250| 18| AEU3182RCXAXTIB4| 37.5″| AEU3182RCXAXB4| 31.5″| 2
| 30| AEU33O2RCXAXT1B4| 43.5″| AEU33O2RCXAXB4| 37.5″| 3
| 42| AEU3422RCXAXT1B4| 49.5″| AEU3422RCXAXB4| 43.5″| 4
400| 18| AEU3184RCXAXT1B4| 64.5″| –| –| 2
| 42| AEU3424RCXAXT1B4| 76.5″| AEU3424RCXAXB4| 64.5″| 4
600| 18| AEU3186RCXAXT1B4| 64.5″| –| –| 2
| 42| AEU3426RCXAXT1B4| 76.5″| AEU3426RCXAXB4| 64.5″| 4

Aluminum Bus

Voltage| Amp Rating| No. of
Circuits| Feed-thru Cat. No.¹| Box/Front Height| TGL2 Ground
Bars
---|---|---|---|---|---
240 Vac, 1 Phase| 100-250| 18| AQU1182RCXAXT1| 37.5″| 2
30| AQU1302RCXAXT1| 43.5″| 3
42| AQU1422RCXAXT1| 49.5″| 4
208/120 Vac, 3 Phase| 100-250| 18| AQU3182RCXAXT1| 37.5″| 2
30| AQU3302RCXAXT1| 43.5″| 3
42| AQU3422RCXAXT1| 49.5″| 4
480/277 Vac, 3 Phase| 100-250| 18| AEU3182RCXAXT1| 37.5″| 2
30| AEU3302RCXAXT1| 43.5″| 3
42| AEU3422RCXAXT1| 49.5″| 4

TGL20 ground lug quantities

| No. of TGL20s Required by Panel Rating
---|---
Interior Type| 100-250A| 400A| 600A
Main Lug Only| 1| 1| 2
Main Lug & Feed-thru| 2| 2| 4
Main Breaker Only| 1| 1| –
Main Breaker & Sub-feed| 1| 1| –
Main Breaker & Feed-thru| 2| 2| –

  1. For TGL20 ground lug quantities, see TGL20 ground lug quantities table above.
  2. For isolated ground, use EGS12. When using the EGS12, 3, 5 and 7 ground lugs (TGL20s) are required for 18, 30 and 42 circuits respectively.
  3. Main bus rating of 250A for main breaker interiors and a bus rating of 225A for main lug interiors.

Choose box

Select a box of the correct height (see step 1). Boxes come with blank endwalls.
If endwalls with knockouts are required, also order knockout endwall kit AKEW2.

| NEMA 1| NEMA 3R| NEMA 4, 4X and 12 Painted Galvaneal| NEMA 4, 4X and 12 Stainless Steel
---|---|---|---|---
Box Height| 20″ Wide| 20″ Wide| 20″ Wide| 20″ Wide
25.5″| –| –| –| AB254S
31.5″| AB31B| AB313| AB314| AB314S
37.5″| AB37B| AB373| AB374| AB374S
43.5″| AB43B| AB433| AB434| AB434S
49.5″| AB49B| AB493| AB494| AB494S
64.5″| AB64B| AB643| AB644| AB644S
76.5″| AB76B| AB763| AB764| AB764S

Add a front

Add a front of the correct height (available for NEMA 1 enclosures only) Standard fronts are equipped with concealed hinges and trim adjusting screws hinges, trim adjusting screws and quarter turn locks.
The door-in-door is convenient for contractors to gain easy access to equipment from the front of the panel. Door-in-door allows a contractor access to the gutters without removing the front.
Front hinged to box is similar to door-in-door for convenient access to gutters, but a contractor must remove four screws to access the outer door.

GE APPLIANCES ReliaGear Pro-Stock Lighting Panels - Add a
front

Front| Standard (20″ Wide)| Door Within Door (20″ Wide)| Front Hinged to Box (20” Wide)
---|---|---|---
**Height| Flush¹| Surface¹| Flush¹| Surface¹| Flush¹| Surface¹**
31.5″| AF31F| AF31S| AF31FP| AF31SP| AF31FD| AF31SD
37.5″| AF37F| AF37S| AF37FP| AF37SP| AF37FD| AF37SD
43.5″| AF43F| AF43S| AF43FP| AF43SP| AF43FD| AF43SD
49.5″| AF49F| AF49S| AF49FP| AF49SP| AF49FD| AF49SD
64.5″| AF64F (T)| AF64S (T)| AF64FP (T)| AF64SP (T)| AF64FD (T)| AF64SD (T)
76.5″| AF76F (T)| AF76S (T)| AF76FP (T)| AF76SP (T)| AF76FD (T)| AF76SD (T)

1 (*T) Fronts with quarter turn lock for applications with XT5 circuit breakers

Select main and/or sub-feed breaker kit

Select the main breaker kit appropriate for your interior type (see step 1), amp rating and kAIC rating. If a sub-feed breaker is required, repeat the selection process. Some units come standard with a breaker.
Please see the list to the right.

Cat. No. Breaker Description Breaker Type
MBM124WB XT5 TMA 400 AMPS 3P XT5NU340ABFN000XXX
MBB13WB XT4 TMF 225 AMPS 3P XT4NU3225AFJ000XXX
MBB16WB XT4 TMF 225 AMPS 3P XT4NU3225AFJ000XXX (2)
MBM134WB XT5 TMA 400 AMPS 3P XT5NU340ABFN000XXX
MBC33WB XT1 TMF 125 AMPS 3P XT1HU3125AFD000XXX
MBB33WB XT4 TMF 225 AMPS 3P XT4HU3225AFJ000XXX
MBB36WB XT4 TMF 225 AMPS 3P XT4HU3200AFJ000XXX (2)
MBM334WB XT5 TMA 400 AMPS 3P XT5HU340ABFN000XXX
MBM324WB XT5 TMA 400 AMPS 3P XT5HU340ABFN000XXX
Interior
Type Cat. No. 1 Max. Amp
Rating No. of
Poles 10 14
100 150 200
--- --- ---
AQU1: 240
VAC, 1 Phase MB612 100
MB614 100 4
MBA12 225 2
MBM324 400 2
MBM124WB 400 2
AQU3: 208/120
VAC, 3 Phase MB613 100
MB616 100 6
MBA13 225 3
MBA16 400 6
2 (x2) A2A
MBB33 250 3
MBB13WB 225 3
MBB36 5 400 6 5

MBB16WB
5| 400| 6 5| | | | | | | XT4N| | |
MBM334| 400| 3| | | | | | | XT5N| XT5S| XT5H| XT5L
MBM134WB| 400| 3| | | | | | | XT5N| | |
MBM124WB4| 400| 2
3| | | | | | | XT5N| | |
| AEU3: 480/277
Vac, 3 Phase| MB423| 100| 3| | TEY| | | | | | | |
MB426| 100| 6| | (x2) TEY| | | | | | | |
MBC33| 125| 3| | | | XT1N| XT1S| | XT1H| | |
MBC33WB| 125| 3| | | | | | | XT1H| | |
MBB33| 250| 3| | | | | | | XT4H| | |
MBB33WB| 225| 3| | | | | | | XT4H| | |
MBB365| 400| 6 5| | | | | | | (x2) XT4H| | |
MBB36WB5| 400| 6 5| | | | (x2) XT4N| (x2) XT4S| | (x2) XT4H| | |
MBM334| 400| 3| | | | | XT5N| XT5S| XT5H| | |
MBM334WB| 400| 3| | | | | | | XT5H| | |
MBM324WB4| 400| 23| | | | | | | XT5H| | |

  1. Breaker not included except for “WB” kits (where product number ends in “WB”).
    “WB” kits include a breaker, mounting kit and load-side lugs.

  2. Actual breaker short circuit rating is 25 kAIC.

  3. Use 2 outer poles for 3 pole applications.

  4. For sub-feed application only.

  5. 6 poles of sub-feed applies only to 400 A and 600 A interiors.

  6. Can use (2) 3 pole devices only, no 2 pole allowed.

Select alternative main breakers

Skip step 5 if you selected a main breaker kit ending in “WB” — no breaker is required.
To correlate breaker types with the kAIC rating in specific panelboards, see the table for step 4.
For more rating details, see ReliaGear lighting panels rating series labels (1TQC173100E0001).
Use 2 outer poles for 3 pole applications.
For TEY and THQB main breakers, see branch breakers tables in step 7.

Tmax XT breakers1 (3-pole) for use with appropriate main breaker kit (see step 4).

240V KAIC| 480V KAIC| Breaker Description| US Product Number| Wire Range (Cu/Al)| Cables per Lug
---|---|---|---|---|---
65| 65| XT1H 125 TMF 30 AMPS 3P| XT1HU3030AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT1H 125 TMF 60 AMPS 3P| XT1HU3060AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT1H 125 TMF 100 AMPS 3P| XT1HU3100AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT1H 125 TMF 125 AMPS 3P| XT1HU3125AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 35| XT1S 125 TMF 100 AMPS 3P| XT1SU3100AFD000XXX| Cu Al 1×14–2/0 AWG| 1
65| 65| XT4H 250 TMF 150 AMPS 3P| XT4HU3150AFJ000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 65| XT4H 250 TMF 200 AMPS 3P| XT4HU3200AFJ000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 65| XT4H 250 TMF 225 AMPS 3P| XT4HU3225AFJ000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 35| XT4S 250 TMF 175 AMPS 3P| XT4SU3175AFJ000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 35| XT4S 250 TMF 200 AMPS 3P| XT4SU3200AFJ000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 35| XT4S 250 TMF 225 AMPS 3P| XT4SU3225AFJ000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 35| XT4S 250 TMF 250 AMPS 3P| XT4SU3250AFL000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 35| XT4N 250 ekip DIP 60-150 AMPS 3P| XT4NU3150FFL000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 35| XT4S 250 ekip DIP 100-250 AMPS 3P| XT4SU3250FFL000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 65| XT4H 250 ekip DIP 100-250 AMPS 3P| XT4HU3250FFL000XXX| Cu Al 1×4 AWG–300 kcmil| 1
65| 65| XT5H 400 TMA 400 AMPS 3P| XT5HU340ABFN000XXX| Cu Al 2×2/0 AWG–500 kcmi| 2
65| 50| XT5S 400 TMA 300 AMPS 3P| XT5SU330ABFN000XXX| Cu Al 2×2/0 AWG–500 kcmi| 2
65| 50| XT5S 400 TMA 400 AMPS 3P| XT5SU340ABFN000XXX| Cu Al 2×2/0 AWG–500 kcmi| 2
65| 35| XT5N 400 ekip DIP 16-400 AMPS 3P| XT5NU340AFFN000XXX| Cu Al 2×2/0 AWG–500 kcmi| 2
65| 65| XT5H 400 ekip DIP 16-400 AMPS 3P| XT5HU340AFFN000XXX| Cu Al 2×2/0 AWG–500 kcmi| 2

1 Thermal Magnetic Fixed (TMF) – no adjustments possible. Thermal Magnetic Adjustable (TMA) – adjustable thermal (L) and magnetic (I).

Main or sub-feed breakers for use with RQ panels (208/120 V AC 3-phase or 240 V AC single-phase). See step 4.

| | 2-pole| | 3-pole
---|---|---|---|---
| 10kAIC| 22kAIC| 10kAIC| 22kAIC
Amp Rating| Cat. No.| Cat. No.| Cat. No.| Cat. No.
125| A2A125TL-2| A2N125TL-2| A2A125TT| A2N125TT
150| A2A150TL-2| A2N150TL-2| A2A150TT| A2N150TT
175| A2A175TL-2| A2N175TL-2| A2A175TT| A2N175TT
200| A2A200TL-2| A2N200TL-2| A2A200TT| A2N200TT
225| A2A225TL-2| A2N225TL-2| A2A225TT| A2N225TT

Select main lug kit and accessories

GE APPLIANCES ReliaGear Pro-Stock Lighting Panels - Main lug
kits

Main lug kits

Lug Type Amp Standard Oversized 200%Neutral
Rating Cat. No. I Wire Range Cat. No. Wire Range

Cat. No.
| 225 MLA1| I 6-350 kcmil| MLA2| 1-600 kcmil or (2)1/0-250 kcmil| NKA
400 MLA41| ?-600 MCM or (2)1/0-250 kcmil| MLA62| 3/0-800 kcmil| NKA42
600 MLA61| I (2) 2/0-500 kcmil| MLA62| 3/0-800 kcmil| —
Copper| 225 MLR1| 4-450 kcmil| MLR2| 1-600 kcmil| NKR
400 MLR41| 1-600 kcmil| MLR61| (2) 2/0-500 kcmil| NKR4
600 MLR61| (2) 2/0-500 kcmil| —| —| —
Compression| 225 MLT1| 2/0-300 kcmil| M LT2| 4/0-500 kcmil| NKT
400 M LT42| 250-600 kc mil| MLT41| 500-750 kcmil’| NKT4
Dual| 225 MLA2| 2-600 kcmil or (2)1/0-250 kcmil| —| —| —
Main| 400 MLA61| L (2) 2/0-500 kcmil| —| —| —

  1. 500 kcmil Cu, 750 kcmil Al.
  2. For 200% neutral feed-thru, order NKA4FT, (GO-101P). Wire range (2) 2/0–600 kcmil or (4) 4–250 kcmil.

Accessories

Service Entrance¹

Amp Rating Cat. No.
225 BNDKT
400 BNDKT6
600 BNDKT6
  1. Service entrance kit includes a bonding strap with hardware and a service entrance label

Scan to find out more about ReliaGear™ Pro-Stock™

GE APPLIANCES ReliaGear Pro-Stock Lighting Panels - qr
code

https://electrification.us.abb.com/products/panelboards/reliagear-pro-stock- panelboard

Select bolt-on branch breakers

The tables below show standard branch breakers.
Branch circuit breakers for use with RQ panels (208/120 V AC 3-phase or 240 V AC single-phase)

Amp
Rating| | | 10 kAIC| | | 22 kAIC
---|---|---|---|---|---|---
1-pole| 2-pole| 3-pole| 1-pole| 1 2-pole| 3-pole
Cat. No.| Cat. No.| Cat. No.| Cat. No.| Cat. No.| Cat. No.
15| THQB1115| THQB2115| THQB32015| THHQB1115| THHQB2115| THHQB32015
20| THQB1120| THQB2120| THQB32020| THHQB1120| THHQB2120| THHQB32020
25| THQB1125| THQB2125| THQB32025| THHQB1125| THHQB2125| THHQB32025
30| THQB1130| THQB2130| THQB32030| THHQB1130| THHQB2130| THHQB32030
35| THQB1135| THQB2135| THQB32035| THHQB1135| THHQB2135| THHQB32035
40| THQB1140| THQB2140| THQB32040| THHQB1140| THHQB2140| THHQB32040
45| THQB1145| THQB2145| THQB32045| THHQB1145| THHQB2145| THHQB32045
50| THQB1150| THQB2150| THQB32050| THHQB1150| THHQB2150| THHQB32050
60| THQB1160| THQB2160| THQB32060| THHQB1160| THHQB2160| THHQB32060
70| THQB1170| THQB2170| THQB32070| THHQB1170| THHQB2170| THHQB32070
80| –| THQB2180| THQB32080| –| THHQB2180| THHQB32080
90| –| THQB2190| THQB32090| –| THHQB2190| THHQB32090
100| –| THQB21100| THQB32100| –| THHQB21100| THHQB32100

Branch circuit breakers for use with RE panels (480/277 V AC 3-phase)

Amp Rating 14 kAIC
1-pole 2-pole 3-pole
Cat. No. Cat. No. Cat. No.
15 TEY115 TEY215 TEY315
20 TEY120 TEY220 TEY320
30 TEY130 TEY230 TEY330
40 TEY140 TEY240 TEY340
50 TEY150 TEY250 TEY350
60 TEY160 TEY260 TEY360
70 TEY170 TEY270 TEY370
80 TEY180 TEY280 TEY380
90 TEY190 TEY290 TEY390
100  T EY1100 TEY2100 TEY3100

Interior product number structure

GE APPLIANCES ReliaGear Pro-Stock Lighting Panels - Interior product number
structure

Interior Type| Phase| No. of Circuits| Max. Amp Rating| Ti Feed-thru| Bus
---|---|---|---|---|---
AQU = 240 Vac| 1 = 1-Phase| 18 = 18 Circuits
1| 2 = 250A MB/ 225A MLO| Blank Non Feed-thru* (required copper bus [B4])| B4 = Copper
AEU = 480Y/277 Vac| 3 = 3-Phase| I 30 = 30 Circuits| 4 = 400A| | Blank = aluminum
| | 42 = 42 Circuits| 6 = 600A| |

Customer Service: EPIS.ASeries.Mebane@abb.com
Technical Support: 1-800-431-7867

4 or epis.component.support@abb.com

Warranty Support: 1-888-437-3765

ABB Inc
305 Gregson Drive
Cary, NC 27511
electrification.us.abb.com

© Copyright 2021 ABB. All rights reserved.
Information provided is subject to change without notice. Please verify all details with ABB. All values are design or typical values when measured under laboratory conditions, and ABB makes no warranty or guarantee, express or implied that such performance will be obtained under end-use conditions.
GE is a trademark of GE. Manufactured under trademark license.
1TQC214100E0001 DEN455B 10.2021

Documents / Resources

| GE APPLIANCES ReliaGear Pro-Stock Lighting Panels [pdf] User Manual
ReliaGear Pro-Stock Lighting Panels, Pro-Stock Lighting Panels, Lighting Panels, Panels
---|---

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

GE Appliances User Manuals

Related Manuals