GOODWE BH SERIES Hybrid Inverter User Manual

June 3, 2024
GOODWE

BH SERIES Hybrid Inverter

PV Master APP

SEMS Portal APP SEMS Portal website www.semsportal.com

LinkedIn

Company’s offical website

GoodWe Technologies Co.,Ltd. No. 90 Zijin Rd., New District, Suzhou, 215011, China www.goodwe.com service@goodwe.com

340-00310-01

BH SERIES USER MANUAL
HYBRID INVERTER Rev 1.2

TABLE OF CONTENTS
01 INTRODUCTION
1.1 Operation Modes Introduction ……………………………………………………………………………. 01 1.2 Safety & Warning …………………………………………………………………………………………………. 02 1.3 Product Overview ……………………………………………………………………………………………….. 04
02 INSTALLATION INSTRUCTIONS
2.1 Unacceptable Installations ………………………………………………………………………………….. 05 2.2 Packing List …………………………………………………………………………………………………………. 05 2.3 Mounting …………………………………………………………………………………………………………….. 06
2.3.1 Select Mounting Location …………………………………………………………………………… 06 2.3.2 Mounting …………………………………………………………………………………………………….. 07 2.4 Electrical Wiring Connection ……………………………………………………………………………….. 09 2.4.1 Battery Wiring Connection ………………………………………………………………………….. 09 2.4.2 On-Grid & Back-Up Connection ………………………………………………………………….. 10 2.4.3 Smart Meter & CT Connection …………………………………………………………………….. 13 2.5 DRED / Remote Shutdown Connection ……………………………………………………………….. 15 2.6 Earth Fault Alarm Connection ……………………………………………………………………………… 16
03 MANUAL OPERATION
3.1 Wi-Fi Configuration ………………………………………………………………………………………………. 19 3.2 PV Master App ………………………………………………………………………………………………………. 20 3.3 CEI Auto-Test Function …………………………………………………………………………………………. 20
04 OTHERS
4.1 Error Messages ……………………………………………………………………………………………………. 21 4.2 Troubleshootings ………………………………………………………………………………………………… 23 4.3 Disclaimer …………………………………………………………………………………………………………… 27 4.4 Technical Parameters ………………………………………………………………………………………….. 28 4.5 Other Test ……………………………………………………………………………………………………………. 29 4.6 Quick Check List To Avoid Danger ……………………………………………………………………….. 30

01 INTRODUCTION
GoodWe BH series bidirectional inverter is designed for both indoor and outdoor use, which could be used with or without existing grid-tied inverter systems to store energy using batteries. Energy produced from the grid-tied inverters will be used to optimize self-consumption, excess will be used to charge the battery, anymore could be exported to the grid. Loads will be supported in priority by grid-tied system, then battery power, if more power is needed, energy will be imported from the grid.

Note:

The introduction describes a general behavior of BH system.

The operation mode can be adjusted on PV Master App

depending on the system layout. Below are the general

01

operation modes for BH system:

1.1 Operation Modes Introduction
BH system normally has the following operation modes based on your configuration and layout conditions.

Mode
Energy from grid-tied inverters optimize loads, excess will be used to charge the battery, anymore will be exported to the grid.

Mode
When energy from grid-tied inverters is weak, battery will discharge to support the load in priority together with the grid.

Mode
When grid power fails, battery will discharge to support back-up loads.

Mode
Battery could be charged by grid, and charge time/power could be set flexibly on PV Master App.

1.2 Safety & Warning
The BH series inverter of Jiangsu GoodWe Power Supply Technology Co., Ltd. (hereinafter called as GoodWe) strictly complies with related safety rules for product design and testing. Please read and follow all the instructions and cautions on the inverter or user manual during installation, operation or maintenance, as any improper operation might cause personal or property damage. Symbols Explantion
Caution! Failure to observe a warning indicated in this manual may result in injury
Danger of high voltage and electric shock!
02
Danger of hot surface!
Components of the product can be recycled.
This side up! The package must always be transported, handled and stored in such a way as the arrows always point upwards.
No more than six (6) identical packages being stacked on each other.
Products should not be disposed as household waste.
Fragile – The package/product should be handled carefully and never be tipped over or slung.
Refer to the operating instructions.
Keep dry! The package/product must be protected from excessive humidity and must be stored under cover. Signals danger due to electric shock and indicates the time to wait (5 minutes) before it is safe to touch the internal parts of the inverter after it has been
5min
disconnected from it power source
CE Mark

HYBIRD LED INDICATORS

SYSTEM BACK-UP BATTERY GRID ENERGY COM

INDICATOR SYSTEM BACK-UP BATTERY GRID ENERGY COM
WiFi FAULT

Safety Warning
Any installation and operation on inverter must be performed by qualified electricians, in compliance with standards, wiring rules or requirements of local grid authorities or companies (like AS 4777 and AS/NZS 3000 in Australia).

1.3 PRODUCT OVERVIEW

STATUS

Prohibit to insert or pull the AC and DC terminals when the inverter is running.

EXPLANATION ON = SYSTEM IS READY BLINK = SYSTEM IS STARTING UP OFF = SYSTEM IS NOT OPERATING ON = BACK-UP IS READY / POWER AVAILABLE OFF = BACK-UP IS OFF / ON POWER AVAILABLE ON = BATTERY IS CHARGING BLINK1 = BATTERY IS DISCHARGING BLINK2 = BATTERY IS LOW / SOC IS LOW OFF = BATTERY IS DISCONNECTED / NOT ACTIVE ON = GRID IS ACTIVE AND CONNECTED BLINK 1 = BATTERY IS DISCHARGING BLINK 2 = BATTERY IS LOW / SOC IS LOW ON = CONSUMING ENERGY FROM GRID / BUYING BLINK 1 = SUPPLYING ENERGY TO GRID / ZEROING BLINK 2 = SUPPLYING ENERGY TO GRID / ZEROING OFF = GRID IS NOT CONNECTED OR SYSTEM NOT
OPERATING ON = BMS AND METER COMMUNICATION OK BLINK1 = METER COMMUNICATION OK, BMS
COMMUNICATION FAIL BLINK2 = METER COMMUNICATION OK, BMS
COMMUNICATION FAIL OFF = BMS AND METER COMMUNICATION FAIL ON = WiFi CONNECTED / ACTIVE BLINK 1 = WiFi SYSTEM RESETTING BLINK 2 = WiFi NOT CONNECT TO ROUTER BLINK4 = WIFI SERVER PROBLEM OFF = WIFI NOT ACTIVE ON = FAULT HAS OCCURRED BLINK1 = OVERLOAD OF BACK-UP
OUTPUT / REDUCE LOAD OFF = NO FAULT

Before any wiring connection or electrical operation on inverter, all battery and AC power must be disconnected from inverter for at least 5 minutes to make sure inverter is totally isolated to avoid electric shock.

WiFi FAULT

The temperature of inverter surface might exceed 60 during working, so please make sure it is cooled down before touching it, and make sure the inverter is untouchable for children

Do not open inverter cover or change any components without GoodWe’s authorization,

03

otherwise the warranty commitment for the inverter will be invalid.

04

Usage and operation of the inverter must follow instructions in this user manual, otherwise the protection design might be useless and warranty for the inverter will be invalid.

Wi-Fi reset

Appropriate methods must be adopted to protect inverter from static damage. Any damage caused by static is not warranted by GoodWe.

Wi-Fi box Battery terminals

The inverter, with built-in RCMU, will exclude possibility of DC residual current to 6mA, thus in the system an external RCD (type A) can be used(30mA).

In Australia, the inverter internal switching does not maintain neutral integrity, which must be addressed by external connection arrangements like in the system connection diagram for Australia on page 16.

LED label

DRED

To Smart Meter

Smart meter communication cable

To battery

In Australia, output of Back-Up side in switchbox should be labeled “Main switch UPS supply”, the output of normal load side in switch box should be labeled “main switch inverter supply”.

BMS communication cable

Meter On-Grid port Back-Up Port
Reserved RS485

02 INTALLATION INSTRUCTIONS 2.1 UNACCEPTABLE INSTALLATIONS

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Back-Up

On-Grid

Back-up cannot connect to grid

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Back-Up

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Back-Up

Load Back-up cannot connect in parallel

05

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

USB

SMART METER
Smart Meter
Reset

Back-Up

Back-Up

One meter cannot connect to multi inverters, and different CT cannot connect to a smart fier cable

Incompatible battery

Battery

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Battery

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Battery

One battery bank cannot be connected to multi inverters

Generator

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Back-Up

On-Grid

On-Grid or back-up side cannot connect to any ac generator.

Incompatible battery

Battery

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Battery

Inverter battery input cannot connect to incompatible batteries.

2.2 Packing List
On receiving the BH series inverter, please check to make sure all the components as below are not missing or broken.

USB

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Inverter×1 Inverter

Wall-mounted Bracket

Smart Meter

Positive BAT Plug

Negative BAT Plug

Back Up AC Plug

On Grid AC Plug

PE terminal

Expansion bolts

User manual

Quick Installation Guide

2.3 Mounting 2.3.1 Select Mounting Location
For inverter’s protection and convenient maintenance, mounting location for inverter should be selected carefully based on the following rules: Any part of this system shouldn’t block the switch and breaker to disconnected inverter from DC and AC power. Rule 1. Inverter should be installed on a solid surface, where is suitable for inverter’s dimensions
and weight. Rule 2. Inverter installation should stand vertically or lie on a slop by max 15°
Max 15°

REWSiE-FTi

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI FAULT

06
Rule 3. Ambient temperature should be lower than 45°C (High ambient temperature will cause power derating of inverter)
Rule 4. The installation of inverter should be protected under shelter from direct sunlight or bad Rule weather like snow, rain, lightning etc.

Keep away from sunlight

Keep dry

Keep it clear of snow

Sun

Rain

Accmulated snow

Rule 5. Inverter should be installed at eye level for convenient maintenance. Rule 6. Product label on inverter should be clearly visible after installation. Rule 7. Leave enough space around inverter following the values.

200mm

300mm 200mm 300mm

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Upward ———- 300mm Downward —— 500mm Front ————- 300mm Both sides——– 200mm

500mm

Inverter cannot be installed near flammable, explosive or strong electro- magnetic equipment.[1]

2.3.2 MOUNTING
Inverter cannot be installed near flammable, explosive or strong electro- magnetic equipment.[1] The inverter is suitable for mounting on concrete or other non-combustible surface only.

Step 1

· Please use the mounting bracket as a template to drill 4 holes on right positions (10mm in diameter,and 80mm in depth)
· Use expansion bolts in accessory box and fix the mounting bracket onto the wall tightly

Note: Bearing capacity of the wall must be higher than 25kg, otherwise may not be

able to keep inverter from dropping.

195mm

Wall bracket Expansion pipe

07

115mm

130mm

self-tapping screws

Step 2
Carry the inverter by holding the heating sink on two sides and place the inverter on the mounting bracket. Note: Make sure the heat sink on inverter is right joint with mounting bracket.

Wi-Fi

RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI FAULT

Wi-Fi

RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI FAULT

Step 3 Ground cable must be connected to ground plate on grid side.

Wi-Fi

RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI FAULT

Wi-Fi

RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY COM

WIFI FAULT

Step 4 A lock could be used for anti-theft if it is necessary for individual requirement.

08

Wi-Fi

RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY COM

WIFI FAULT

The lock is not involved in the package, It can be purchesed by user.

Wi-Fi

2.4 Electrical Wiring Connection RESET

SYSTEM

BACK-UP

BATTERY

GRID

2.4.1

Battery

Wiring

Connection ENERGY

COM

WIFI

FAULT

· Please be careful against any electric shock or chemical hazard.

· Make sure there is an external DC breaker (40A) connected for battery without build-in DC breaker.

Make sure battery breaker is off and battery nominal voltage meet BH specification before connecting battery to inverter and make sure inverter is totally isolated from AC power.

Please following the steps as bellow strictly. Use improper wire may cause bad contact and high impedance, which is dangerous to the system.
· Use the right BAT plugs in the accessory box.
· Use the tin-plated cables with a conductor cross section of 4 to 6 mm² (AWG 10) because the maximum battery current is 25A (for BH3.6-6kW) and 32A (for BH3kW). Battery cable requirements are shown as below.

A

Grade Description

Value

A C

A

Outside diameter insulation 5.5-8.0 mm

B

Conductor core section

4-6 mm2

C

Conductor core length

7 mm

Step 1
Prepare BAT cables and BAT plugs 7mm

Step 2 Connect BAT cables to BAT connectors

7mm

09

Note

· Please use BAT plugs and

connectors in the accessory box.

· BAT cable should be standard,

4-6mm2 BAT cable.

Note · BAT cable must be tightly crimped into
the connectors. · For Amphenol connector, the limit
buckle cannot be pressed. · There will be a click sound if connectors
are inset correctly into BAT plugs.

Step 3
Screw the cap on and plug onto inverter side Note: There will be a click sound if connectors are inset
correctly into BAT plugs.

Note: For the compatible lithium batteries (Pylon/BYD) connection, please refer to battery connection part in BH quick installation instructions.
2.4.2 On-Grid & Back-Up Connection
An external AC breaker is needed for On-Grid connection to be isolate from grid when necessary. Below are the requirements of On-Grid AC breaker.

Inverter Model GW3K-BH GW3600-BH GW5000-BH GW6000-BH

AC Breaker Specification 50A/230V AC breaker 50A/230V AC breaker 63A/230V AC breaker 63A/230V AC breaker

1. Use separated AC breaker for individual inverter

2. On AC side, the individual breaker should be connected before loads “between inverter and loads”.

AC breaker AC breaker
AC breaker Grid

AC breaker

Grid

Loads

Requirement of AC cable connected to On-Grid and Back-Up side

Make sure inverter is totally isolated from any DC or AC power before connecting AC cable.
10
Note:
· The choice of AC cable needs to meet both the outside diameter and conduct core section requirements. Please refer to the table for selecting the AC cable.
· Neutral cable shall be blue, line cable is black or brown (preferred) and protective earth cable yellow-green.
· For AC cables, PE cable shall be longer than N&L cables, so that if in any case AC cable slips or taken out, the protecting earth conductor will be the last to take the strain.

On-Grid wiring connection process is as below Step 1 Prepare the AC cable according to the table.

A

B

Grade Description

Value

A

Outside diameter

13-22 mm

D

B

Separated wire length 10-15 mm

D

C

Conductor wire length 12-14 mm

D

Conductor core section 8-10 mm2

Note: If you don’t use the Back-Up function or use on-grid power to charge the battery,the wiring conduct core section can use 4-6mm2.

Step 1 1. Prepare the terminals AC cables. 2. Put AC cable through terminal cover
and screw the three cables tightly on the connectors.
Note: · Please use the terminals in compo-
nents box; · Make sure cable jacket is not locked
with conductor.

Step 3

1. Connect the assambled AC terminals

11

onto inverter.

Note: Make sure it is connected to

“On-Grid” side (other side connected

to public grid).

Step 2 Lock terminal cover and screw up the terminal cap.
Note: · BAT cable must be tightly crimped
into the connectors · For Amphenol connector, the limit
buckle cannot be pressed · There will be a click sound if
connectors are inset correctly into BAT plugs

Back-Up wiring connection process is as below Step 1 Prepare the AC cable according to the table.

A

B

D

D

Grade A B C D

Description Outside diameter Separated wire length Conductor wire length Conductor core section

Value 10-14 mm 7-10 mm 7-9 mm 4-6 mm2

An external AC breaker (32A) is needed for Back-Up connection to be isolate when necessary.
Note: The absence of AC breaker on Back-Up side will lead to inverter damage if only electrical short-circuit happened on Back-Up side. And Back-Up function cannot turn off under On-Grid condition.

Step 2
1. Prepare the terminals AC cables.
2. Put AC cable through terminal cover and screw the three cables tightly on the connectors.

Torque 0.7~0.9N.m

Step 3

Lock terminal cover and screw up the terminal cap.

Unlock

lock

Make sure the terminal cover is locked up here.

Step 4
Connect the assambled AC terminals onto inverter.
Press the button and hold it to unlock when unplugging AC terminals.

Note: Make sure the terminal cover is rightly locked onto the terminal.

Note: Make sure it is connected to

“Back-Up” side (other side connected

to public grid.

12

Special Adjustable Setting
The inverter has filed adjustable setting like tripping point, tripping time, reconnect time, active and invalid of QU/PU curves etc. by special firmware. Please contact GoodWe after sales for the special firmware and adjust methods.
Declaration For Back-Up Function
The back-up output of BH hybrid inverters have over load ability.
For details please refer to the technical parameters of BH series inverter section (Page **).
And the inverter has self-protection derating at high ambient temperature.
The below statement lays out general policies governing the energy storage inverters of the series EH, EM, ES, ET, BH, BT and SBP.
1. For Hybrid inverters (Series ES, EM, EH and ET), the standard PV installation typically consists of the connection of the inverter with both panels and batteries. In case of systems not connected to the batteries, the Back-Up function is strongly not advised to use. GoodWe shall not cover the standard warranty and be liable for any consequences arising from users not following this instruction.
2. Under normal circumstances, the Back-Up switching time is less than 10 ms (the minimal condition to be considered as the UPS level). However, some external factors may cause the system to fail on Back-Up mode. As such, we recommend the users to be aware of conditions and follow the instructions as below: · Do not connect loads if they are dependent on a stable energy supply for a reliable operation

· Do not connect the loads which may in total exceed the maximum Back-Up capacity · Try to avoid those loads which may create very high start-up current surges such as Inverter
Air-conditioner, high-power pump etc. · Due to the condition of battery itself, battery current might be limited by some factors includ-
ing but not limited to the temperature, weather etc.
Accepted Loads As Below:
BH series hybrid inverters are able to supply over load output at it’s Back- Up. For details please refer to the technical parameters of BH series inverter (4.3 section). And the inverter has self-protection derating at high ambient temperature.
· Inductive Load: 1.5P non-frequency conversion air-conditioner can be connect to back-up side. Two or more non-frequency conversion air-conditioner connect to Back-Up side may cause UPS mode unstable.
· Capacitive Load: Total power <= 0.6 x nominal power of model. (Any load with high inrush current at start-up is not accepted.)
· For complicated application, please contact after-sales.
Note:
For a convenient maintenance, an DP3T support could be installed on Back-Up and On-Grid
13 side. Then it is adjustable to support load by Back-Up or by grid or just leave it there.

1. Back-up load is supplied from back-up

side.

Back-Up

2. Back-up load is isolated.

1 2

On-Grid

3

3. Back-up load is supplied from grid side.

Load

SP3T

Grid

Declaration For Back-Up Overload Protection Inverer will restart itself as overload protection happens. The preparation time for restarting will be longer and longer (max one hour) if overload protection repeats. Take following steps to restart inverter immediately. · Decrease Back-Up load power within max limitation. · On PV Master Adcanced Setting Click “Reset Back-Up Overload History”

2.4.3 Smart Meter & CT Connection
The single-phase Smart Meter with 2 CTs in product box is compulsory for BH system installation, used to detect grid voltage and current direction and magnitude, further to instruct the operation condition of BH inverter via RS485 communication.
Make sure BH and grid-tied inverters are totally isolated from AC and DC power before connecting Smart Meter and CT

Smart Meter Wiring connection diagram
Single-Phase Grid-Tied inverter

BH

Smart Meter USB

CT1 L

SMART METER

House Grid

N

Reset
Grid

PV

CT2

Load

Note:

House Grid

1. The Smart Meter and CT is well configured, please do not change any setting on smart meter.

2. CT must be connected on the same phase with smart meter power cable.

3. Please use the Smart Meter with CT in product box.

4. CT cable is 3m as default, could be extended to max 5m.

5. Smart Meter communication cable (RJ45) is attached on the inverter (“To Smart Meter”
cable), could be extended to max 100m, and must use standard RJ45 cable and plug, as the 14
diagram:

Detailed Pin Function Of Each Port On BH

BMSCAN communication is configured by default. If 485 communication is used, please contact after-sales to replace with the corresponding communication line.

Position 1 2 3 4 5 6 7 8

Color Orange&white
Orange Green&white
Blue Blue&white
Green Brown&white
Brown

BMS Function 485_A2 NC 485_B2 CAN_H CAN_L NC NC NC

Smart Meter Function NC NC
485_B1 NC NC
485_A1 485_B1 485_A1

EMS 485_A 485_B 485_A
NC NC 485_B NC NC

Smart Meter LED Indications

STATUS POWER ENERGY
COM

OFF

ON

Blinking

Not working

Working

/

/

Importing

Exporting

Blink one time when it transfer data to inverter

POWER ENERGY COM

Make sure AC cable is totally isolated from AC power before connecting Smart Meter & CT.

The Smart Meter with CT in product box is compulsory for BH system installation, used to detect grid voltage and current direction and magnitude, further to instruct the operation condition of BH inverter via RS485 communication.
Note: 1. The Smart Meter with CT is well configured, please do not change any setting on Smart
Meter. 2. One Smart Meter can only be used for one BH inverter. 3. CT must be connected on the same direction as the CT indicated.
Anti-Reverse Function Connection
If BH system (connected with grid-tied inverters) requires anti-reverse function, it is operable but please note:
1. This diagram is only for installation where has exporting power limit function requirement. 2. For anti-reverse function, will also need set on PV Master AppAdvanced SettingPower
Limit. 3. This diagram only be reasonable if grid-tied inverter has anti- reverse function itself. And the
power limitation value shall be set on grid-tied inverter. 4. When using anti- reverse function, it would buy about 100W from the grid.

15 Connection Diagram As Below:
Single-Phase Grid-Tied inverter
BH

Smart Meter USB

CT1 L

SMART METER

House Grid

N

Reset

Grid

[1]

CT2

PV

House Grid

Load

[1] This cable is a theoretical connection supporting anti-reverse function, which could be different for different grid-tied inverters.

2.5 DRED & Remote Shutdown Connection
DRED(demand response enabling device) is only for Australian and New Zealand installations, in compliance with Australian and New Zealand safety requirements. And DRED is not provided by manufacturer. Remote shutdown is only for Europe installations, in compliance with Europe safety requirements. And Remote shutdown device is not provided by GoodWe. Detailed operation is shown as below:

Step 1
Screw this plate off from inverter. Note: DRED device should be connected through “DRED port” as the figure shows.

Step 2

1. Plug out the 6-pin terminal and dismantle the resistor on it.
2. Plug the resistor out, leave the 6-pin terminal for next step.

Note: The 6-pin terminal in the inverter has the same

function of DRED device. Please leave it in the

inverter if no external device connected.

16

Step 3-1 For DRED

1. Put DRED cable through the plate. 2. Connect DRED cable on the 6-pin terminal. The function of each connection position

NO

1

2

3

4

5

6

Function DRM1/5 DRM2/6 DRM3/7 DRM4/8 REFGEN COM / DRMO

123456

Single hole seal ring

Screw

Nut

The Screw Cap

Insulator

RS485 communication board

Cable

Step 3-2 For Remote Shutdown

1. Put the cable through the plate. 2. Wiring from the No. 5 and 6 holes respectively. The function of each connection position

NO

5

6

Function REFGEN COM / DRMO

123456

Single hole seal ring

Screw

Nut

The Screw Cap

Insulator

RS485 communication board

Cable

Step 4
Connect the terminal to the right position onto the inverter.

2.6 Earth Fault Alarm Connection
BH series inverter complies with IEC 62109-2 13.9. Fault indicator LED on inverter cover will light up and the system will email the fault information to customer.
Inverter should be installed at eye level for convenient maintenance.
2.7 SEMS Portal
SEMS Portal is an online monitoring system. After completing the installation of communication connection, you can access www.semsportal.com or download the App by scanning the QR code to monitor your PV plant and device.
17 Please contact the after-sales for more operation of SEMS Protal.
SEMS Portal App

WIRING SYSTEM FOR BH SERIES HYBRID INVERTER

Please select Breaker according to the specification below

GW3K-BH GW3600-BH GW5000-BH GW6000-BH

40A/600V DC breaker

50A/230V AC breaker 50A/230V AC breaker 63A/230V AC breaker 63A/230V AC breaker

32A/230V AC breaker 32A/230V AC breaker 32A/230V AC breaker 40A/230V AC breaker

Depends on household
loads

[1] For batteries with attached switch, the external DC switch is not necessary.
[2] Only for lithium battery which has BMS communication.
[3] Direction of the CT cannot be connected in reverse, please follow “House Grid” direction to do the connection.
For Spain Grid code, the output max. apparent power of GW6000-BH is 6KVA and will be less than 5kVA exported to grid limited by CT controller and power meter.
If the generation facility to be connected to the supply network with more than 5 kVA power in single phase, connection of the facility to the network shall be three-phase with an imbalance between phases of less than 5kW.

Grid Power Meter
AC Breaker
To Smart Meter CT1 [2]

DC Breaker
40A [1]

To Battery Cable AC Breaker
USB

SMART METER Reset
AC Breaker

18
House Grid
AC Breaker
On-Grid Load

Battery

CT2 [2] Single-Phase Grid-Tied inverter
Back-Up Load

PV

NL

System Connection Diagrams
Note: According to australian safety country, the neutral cable of on-grid side and back-up side must be connected together, otherwise back-up function will not work.

This diagram is an example for application that Neutral connects together with PE in distribution box. Such as: Australia, New Zealand, South Africa, etc. (Please follow local wiring regulations!)

BMS Battery

L N

Hybrid Inverter

Back-Up Meter

Distribution box

RCD

Don’t connect this terminal for Australian and New Zealand grid system!!!

RS485

Smart Meter

L
N Back-Up PE Loads

Grounding screw hole at the lower right corner

L N PE
On-Grid

E-BAR

RCD

CT
N-BAR E-N Link
E-BAR

L
N Grid PE

L N PE Normal Loads

This diagram is an example for grid systems without special requirements on electrical

19

wiring connection.

Note: The back-up PE line and earthing bar must be grounded properly and effectively.

Otherwise the back-up function may be abnormal when the grid fails.

BMS Battery

L N

Hybrid Inverter

Back-Up Meter

Distribution box
RCD

RS485

Smart Meter

L
N Back-Up PE Loads

Grounding screw hole at the lower right corner

L N PE On-Grid

E-BAR

RCD

CT E-BAR

L
N Grid PE

L N PE Normal Loads

Note: After the inverter is installed and worked normal when the grid connected , please turn off the grid power to check whether the Back-Up function is normal, which can avoid the problems in subsequent uses.

03 MAMUAL OPERATION

3.1 Wi-Fi Configuration
This part shows configuration on web page. You can also complete the configuration with PV Master App. Wi-Fi configuration is absolutely necessary for online monitoring and maintenance.

Preparation: 1. Inverter must be powered up with battery or grid power. 2. Router with available internet access to the website www.semsportal.com is required.

Step 1
1. Connect Solar-WiFi to your PC or smart phone ( its named the last 8 character of the inverter’s serial No.).
2. Open browser and login 10.10.100.253 Admin (User): admin; Password: admin.
3. Then click “OK”.

10.10.100.253

Admin(U) : Password :

admin

***** Remember the password(R)

OK

Cancel

Step 2

1. Click “Start Setup” to choose your router. 2. Then click “Next”.

Device information Firmware version MAC address Wireless AP mode
SSID IP address Wireless STA mode Router SSID Encryption method Encryption algorithm Router Passowrd

1.6.9.3.38.2.1.38 60:C5:A8:60:33:E1
Enable Solar-WiFi 10.10.100.253
Disable WiFi_Bum-in WAP/WAP2-PSK
AES WiFi_Bum-in

Cannot join the network, may be caused by:

No router / weak WiFi signal / password is not correct

Help: Wizard will help you to complete setting with one

minute.

Start Setup

Please select you current wireless network

SSID WiFi_Burn-in WiFi_Burn-in WiFi_Burn-in WiFi_Burn-in2

AUTH/ENCRY WPAPSKWPA2PSK/TKIPAES WPAPSKWPA2PSK/TKIPAES WPAPSKWPA2PSK/TKIPAES WPAPSKWPA2PSK/TKIPAES

RSSI 66 100 70 72

Channel 1 1 1 1

Refresh

Help: When RSSI of the selected Wi-Fi network is lower than 15%, the connection may be unstable.Please select other available network or shorten the distance between the device and router. If you wireless router does not broadcast SSID, please click “Next” and add a wireless network manually.

Back

Next

Step 3

1. Fill in the password of ther router, then click “Next”.
2. Click “Complete”.

Add wireless network manually

Network name (SSID) Encryption method Encryption algorithm

WiFi-Test WPA/WPA2-PSK AES

Please enter the wireless network passwork:

Password (8-63 bytes)

Router password

show psk

Note: Case sensitive for SSID and password, Please make sure all parameters of wireless network are matched with router, including password.

Back

Next

Note: If the Wi-Fi module fail to connect to network after enter the right passwords. It’s possible that there is special characters not supported by module in the hotspot passwords.
Save success! Click “Complete”, the current configuration will take effect after restart.
If you still neet to configure the other pages of information, please go to complete your required configuration.
Configuration is completed, you can log on the Management page to restart device by Click on “OK” button.
Confirm to complete?
Back Complete

20

Note: 1. Please make sure the password, Encryption method / algorithm is the same as the router’s. 2. If everything is right well, the Wi-Fi LED on inverter will change from double blink to quartic
blink then to solid status, which means Wi-Fi has connected to the server successfully. 3. Wi-Fi configuration could also be done on PV Master App, details please check on PV Master
App.
Wi-Fi Communication Wi-Fi Reset means restarting Wi-Fi module, Wi-Fi setting will be reprocessed and saved automatically. Wi-Fi Reload means setting Wi-Fi module back to default factory setting.

Wi-Fi Reset Button

Wi-Fi RESET

SYSTEM

BACK-UP

BATTERY

GRID

ENERGY

COM

WIFI

FAULT

Wi-Fi Reset

Wi-Fi Reload

Short press reset the button.

Long press reset the button (over 3s).

Wi-Fi LED will blink for a few seconds.

Wi-Fi LED will double blink until Wi-Fi

configuration again.

Note:

Wi-Fi reset & reload function is only used when:

1. Wi-Fi loses connection to internet or cannot connect to PV Master App

successfully.

2. Cannot find “Solar-WiFi signal” or have other Wi-Fi configuration problems.

3. Please do not use this button if Wi-Fi monitoring works well.

3.2 PV Master App

PV Master is an external monitoring / configuration application for hybrid
21 inverters, used on smart phones or tablet for both Android and iOS system.
Main functions are as below:
1. Edit system configuration to make the system work as customer needs.
2. Monitor and check the performance of the hybrid system.
3. Wi-Fi configuration.
Please download PV Master App from Google Play Store or Apple App Store. You can also download the App by scanning the QR code on the back of this user manual.

VIRGIN

4:21 PM

100%

95048EHU12345678

Waiting

0.00(kW)

0.00(kW) 0.00(kW)

0.00(kW)

Safety Country

English

Battery Type

Battery

Operation Model

Normal

Meter Communication Status CT connection

BMS Communication Status Alarm warning ?

Back-Up Switch

On

Anti-Reverse Function Switch

Off

Please download “PV Master Operation Instructions” from www.goodwe.com

Overview

Param

Set

3.3 CEI Auto-Test Function
PV auto-test function of CEI is integrated in PV Master App for Italy’s safety country requirements. For detailed instruction of this function please refer to “PV Master Operation Instructions”.

04 OTHERS
4.1 Troubleshootings
Checking Before Turn On AC Power
· Battery Connection: Confirm the connection between BH and battery : polarities ( +/-) not reversed, refer to Pic 33.
· On-Grid & Back-Up Connection: Confirm ON-GRID connected to power grid and Back-Up to loads: polarity (+/-) not reversed, refer to Pic 34.
· Smart Meter & CT Connection: Make sure Smart Meter & CT are connected between house loads and grid, follow the Smart Meter direction sign on CT, refer to Pic 35.

4.2-1

4.2-2

4.2-3

Checking As Start BH Up And Turn On AC Power

Battery Settings, BMS Communication And Safety Country:

After connecting Solar-WiFi (The Wi-Fi signal is named the last 8 characters of the inverter’s

serial No.), check on PV Master App “Param” to make sure battery type is the same as what you

have installed, and “Safety Country ” Setting is right. Please set it right in “Set” if the setting is not

right.

22

Param

Power LED Energy consumption LED Communications LED Reset switch USB Port

Battery (Battery-Box H9.0)

Battery Status

SOC: 39%, Charging

Battery Data

373.1V / 2.8A / 1.04kW

BMS Status

Normal

SOH (From BMS)

100.0%

Charge Current Limit (From BMS)

20.0A

Discharge Current Limit (From BMS)

25.0A

Waring (From BMS)

Normal

Temperature (From BMS)

25.0

Inverter SN Firmware Version Safety country Work status Error

96000EHU191W0001 000108
Germany Normal(On-Grid)

Overview

Param

Set

Note: For compatible lithium batteries, BMS status will display “Normal” after selecting the right battery company.

Possible Problems During Operation
High Power Fluctuation on Battery Charge or Discharge: Solution: Check if there is a fluctuation on load power.

Battery Does Not Charge: Solution: 1. Make sure BMS communication is OK on PV Master. 2. Check if CT connected in the right position and to right direction as on the user manual page 15.

Questions & Answer (Q&A)

About Wi-Fi Configuration
Q: Why can’t I find the Solar-WiFi signal on mobile devices?
A: Normally Solar-WiFi
signal could be searched right after inverter has powered up. But Solar-WiFi signal will disappear when EM connects to internet. If changes to the setting are required, connect to the router for change. If you can’t find the WiFi signal or connect to the router, then please try to reload Wi-Fi (please refer to “3.1 Wi-Fi Configuration”).

Q: Why can’t I connect Solar-WiFi* signal on my phone?
A: The Wifi module can only connect to one device at a time. If the signal is already connected to another device at the time for some reason, you cannot connect to the signal.

Q: Why does the Wi-Fi module fail to connect to network after I choose the right router hotspot and enter the right passwords?

A: It’s possible that there are special characters not supported by module in the hotspot

23

passwords. Please modify the password to consist of only Arabic numerals or uppercase

/lowercase letters.

About Battery Operation Q: Why does the battery not discharge when grid is not available, while it discharges
normally when grid is available? A: On the App, off-grid output and back-up function should be turned on to make battery
discharge under off-grid mode.
Q: Why is there no output on back-up side? A: For back-up supply, the “Back-Up Supply” on PV Master App must be turned on. Under off-grid
mode or when grid power is disconnected, “Off-Grid Output Switch” function must be turned on as well.

Note: When turning “Off-Grid Output Switch” on, don’t restart inverter or battery, otherwise the function will be switched off automatically.
Q: On Portal, why battery SOC has a sudden jump up to 95%? A: This normally happens on when BMS communication fail on lithium. If battery enter float
charge, SOC will be reset to 95% compulsively.
Q: Why battery cannot be fully charged to 100%? A: Battery will stop charge when battery voltage reaches charge voltage set on PV Master APP.
Q: Why battery breaker always trip when starts it up (Lithium battery)? A: The breaker of lithium battery normally trips for following reasons:
1. BMS communication fails. 2. Battery SOC is too low, battery trips to protect itself. 3. An electrical short-cut happened on battery connection side. Or other reasons please con-
tact After-sales for details.
Q: Which battery should I use for BH? A: For BH series inverter, it could connect lithium batteries which have compatibility with BH series inverter with nominal voltage from 85V to 450V. Compatible lithium batteries can see on battery list in PV Master APP.
About PV Master Operation and Monitoring Q: Why can’t I save settings on PV Master App? A: It could be caused by losing connection to Solar-WiFi .
1. Make sure you have already connected Solar-WiFi
(make sure no other devices connected) or router (if connected Solar-WiFi* to router). APP’s homepage shows connection well.
24
2. Make sure you restart inverter 10mins after you change some settings because inverter will save settings every 10 mins under normal mode. We recommend to change setting parameters when inverter is in wait mode.
Q: Why are the data displayed on the homepage different from the param page, like charge/discharge, PV value, load value or grid value?
A: The data refresh frequency is different, so there will be a data inconformity between different pages on the App as well as between these on portal and App.
Q: Some columns show NA, like battery SOH, etc. Why does that happen? A: NA means App does not receive data from inverter or server because of communication
problem, such as battery communication, and communication between inverter and the App.

About Smart Meter And Power Limit Function Q: How to activate output power limit function? A: For BH system, the function could be realized by:
1. Make sure Smart Meter connection and communication well. 2. Turn on export power limit function and set the max output power to grid on App. Note: Even if output power limit is set to 0W, there might still be a deviation of a max of 100W
exporting to grid.
Q: Why is there still power exporting to grid after I set power limit as 0W? A: Export limit could be 0W theoretically, but there will be a deviation of around 50-100W for BH
system.
Q: Can I use other brand Meter to take over Smart Meter in BH system or change some settings on Smart Meter?
A: No, because the communication protocol is integrated into inverter and Smart Meter, other brand meters cannot communicate. Also any manual setting change could cause Meter communication failure.
Q: What is the maximum current allowed to go through CT on Smart Meter? A: The max current for CT is 120A.

Other Questions

Q: Is there a quick way to make the system work?

A: For the shortest way, please refer to “BH Quick Installation Instructions” and “PV Master App

25

Instruction”.

Q: What kind of load can I use to connect on Back-Up side?
A: Please refer to “2.4.2 On-Grid & Back-Up Connection: Declaration For Back- Up Overload Protection”.

Q: Will the warranty of the inverter still be valid if for some special conditions we cannot 100% follow the user manual instructions on the installation or operation?
A: Normally we still provide technical support to problems caused from disobeying the instructions on the user manual, however we cannot guarantee any replacements or returns. So if there is any special conditions where you cannot 100% follow the instructions, please contact after-sales for suggestions.

4.2 Disclaimer
The BH series inverters are transported, used and operated under environmental and electrical conditions. Manufacturer has the right not to provide after- sales services or assistance under following conditions:
· Inverter is damaged during transfer.
· Inverter is out of warranty year and extended warranty is not bought.
· Inverter is installed, refitted or operated in improper ways without authority from manufacturer.
· Inverter is installed or used under improper environment or technical condition mentioned in this user manual, without authority from manufacturer.
· Installation or configuration of the inverter does not follow requirements mentioned in this user manual.
· The inverter is installed or operated against the requirements or warnings that are mentioned in this user manual.
· Inverter is broken or damaged by any force majeure like lightening, earthquake, fire hazard, storm and volcanic eruption etc.
· Inverter is disassembled, changed or updated on software or hardware without authority from manufacturer.
· Inverter is installed, used or operated against any related items in international or local policies or regulations.
· Any non-compatible batteries, loads or other devices connected to BH system.

Note:

Manufacturer will keep the right to explain all the contents in this user manual. To insure IP65,

inverter must be sealed well, please install the inverters within one day after unpacking,

otherwise please seal all unused terminals / holes, unused terminals / holes are not allowed to

be kept open, confirm that there is no risk of water or dust entering the terminals / holes.

26

Maintenance The inverter requires periodical maintenance, details are shown below: · Make sure inverter is totally isolated from all DC and AC power for at least 5 mins before mainte-
nance. · Heat sink: Please use clean towel to clean up heat sink once a year. · Torque: Please use torque wrench to tighten AC and DC wiring connection once a year. · DC breaker: Check DC breaker regularly, active the DC breaker 10 times in a row once a year. · Operating DC breaker will clean contacts and extend lifespan of DC breaker. · Water-proof plate: Check if water-proof plate of RS485 and other part are replaced once a year.

4.2 Error Message
The error messages below will be displayed on PV Master App or report by Email if the error really happen.

ERROR MESSAGE Utility Loss

EXPLANATION
Not available of public grid power (power lost or on-grid connection fails)

REASON Inverter does not detect the connection of grid

VAC Failure

Grid voltage is not within permissible range

Inverter detects that AC voltage is beyond the normal range required by the safety country

FAC Failure

Grid Efficiency is not within permissible range

Inverter detects that Grid frequency is beyond the normal range required by the safety country

Relay Check Failure

Self checking of relay fails

Neutral & ground cable are not connected well on AC side or just occasional failure

Over Temperature
27
DC Injection High

Temperature inside of the inverter is too high
/

Inverter working environment leads to a high temperature condition
Inverter detects a higher DC component in AC output

EEPROM R/W Failure SPI Failure DC Bus High

/ Internal communication fails BUS voltage is over-high

Caused by a strong external magnetic field etc. Caused by a strong external magnetic field etc. /

Back-Up Over Load

Back-up side is over loaded

Total Back-Up load power is higher than the nominal backup output power

NOTE: All the errors about battery happen only on Lithium battery with BMS communication.

SOLUTIONS
1. Check (use multi-meter) if AC side has voltage . Make sure grid power is available. 2. Make sure AC cables are connected tightly and right well. 3. If all is well, please try to turn off AC breaker and turn on again after 5 mins.
1. Make sure safety country of the inverter is set right. 2. Check (use multi-meter) if AC voltage (Between L & N) is within a normal range (Also on AC breaker side)
a. if AC voltage is high, then make sure AC cable complies with that required on user manual and AC cable is not too long.
b. if voltage is low, make sure AC cable is connected well and the jacket of AC cable is not compressed into AC terminal. 3. Make sure the grid voltage of your area is stable and within normal range.
1. Make sure safety country of the inverter is set right. 2. If safety country is right, then please check on inverter display if AC frequency (Fac) is within a normal range. 3. If FAC failure only appear a few times and resolved soon, it should be caused by occasional grid frequency unstability.
Check use multi-meter if there if there is high voltage (normally should be lower than 10V) between N&PE cable on AC side. If the voltage higher than 10V, it means the Netural & ground cable are not connected well on AC side or restart inverter.
1. Try to decrease surrounding temperature. 2. Make sure the installation complies with the instruction on inverter user manual. 3. Try to close inverter for 15 mins, then start up again.
28
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Try to restart inverter, check if it still happens, if not, means it is just an occasional situation or contact GoodWe.
Decrease Back-Up loads to make sure the total load power is lower than Back-Up nominal output power (please refer to page 12).

4.4 TECHNICAL PARAMETERS AND CERTIFICATES

Technical Data

GW6000-BH GW5000-BH GW3600-BH GW3k-BH

Battery Input Data

Battery Type

Li-Ion

Battery Voltage Range(V)

85~460

85~400

Start-up Voltage (V)

90

Max. Charging/Discharging Current (A)

25/25

32/32

AC Output/Input Data (On-grid)

Nominal Apparent Power Output to Utility Grid (VA)*2

6000

5000

3600

3000

Max. Apparent Power Output to Utility Grid(VA)*2

6000/66001 5000/55001 3600/39601 3000/33001

Max. Apparent Power from Utility Grid (VA)

12000 Charging 6kwbackup output 6kw

10000 Charging 5kwbackup output 5kw

7200Charging 6000Charging 3.6kwbackup 3kwbackup output 3.6kw output 3kw

Nominal Output Voltage (V)

230

230

230

230

Nominal Output Freqency (Hz)

50/60

50/60

50/60

50/60

Max. AC Current Output to Utility Grid (A)*2

26.1/28.7*1

21.7/24*1

16/18*1

13.1/14.3*1

Max. AC Current From Utility Grid (A)

52.2

43.4

32

26.2

Output Power Factor

Adjustable from 0.8 leading to 0.8 lagging

Output THDi (@Nominal Output)

<3%

Back-up Output Data (Back-up)

Max. Output Apparent Power (VA)

6000

5000

3600

3000

Peak Output Apparent Power (VA) 720060sec 600060sec 432060sec 360060sec

Max. Output Current (A)

26.1

21.7

15.7

13.1

Automatic Switch Time (ms)

<10

Nominal Output Voltage (V)

230 (±2%)

Nominal Output Frequency (Hz)

50/60 (±0.2%)

29 Output THDv (@Linear Load)

<3%

Efficiency

Max. Efficiency

96.60%

Protection

Anti-islanding Protection

Integrated

Integrated

Integrated

Integrated

Battery Input Reverse Polarity Protection

Integrated

Integrated

Integrated

Integrated

Insulation Resistor Detection

Integrated

Integrated

Integrated

Integrated

Residual Current Monitoring Unit

Integrated

Integrated

Integrated

Integrated

Output Over Current Protection

Integrated

Integrated

Integrated

Integrated

Grid Output Short Protection

Integrated

Integrated

Integrated

Integrated

Output Over Voltage Protection

Integrated

Integrated

Integrated

Integrated

General Data

Operating Temperature Range ()

-35~60

Relative Humidity

0~95%

Operating Altitude (m

4000

Cooling

Nature Convection

Noise (dB)

<35

User Interface

LED & APP

Communication with BMS

CAN

Communication with Meter

RS485

Communication with Portal

WiFi/Ethernet(Optional)

Weight (kg)

15.5

15.5

15.5

15.5

Size (WidthHeightDepth mm

354433147

Mounting

Wall Bracket

Protection Degree

IP65

Standby Self Consumption (W)*3

<10

Topology Certifications & Standards*4

Battery Non-Isolation

Grid Regulation

G99,G100

AS/NZS4777.2

Safety Regulation

IEC 62477-1

EMC

EN61000-6-1

*1: For CEI 0-21.

*2: The grid feed in power for VDE-AR-N 4105 and NRS097-2-1 is limited 4600VA, for AS/NZS 4777.2 is

limited 4950 VA & 21.7A.

*3: No Back-up Output.

*4: Not all certifications & standards listed, check the official website for details.

4.5 Other Test

For Australian requirements, in the THDi test, Zref should be added between inverter and mains.

RA, XA for Line conduvtor

RN, XN for Neutral conductor

30

Zref:

RA=0, 24; XA=j0,15 at 50Hz;

RN=0, 16; XN=j0,10 at 50Hz

4.6 Quick Check List To Avoid Danger
1. Inverter cannot be installed near flammable, explosive or strong electro- magnetic equipment, please refer to “2.3.1 Select Mounting Location”.
2. Remember that this inverter is heavy! Please be careful when lifting out from the package, please refer to “2.3.2 Mounting”.
3. Make sure battery breaker is off and battery nominal voltage meets EM specification before connecting battery to inverter and make sure inverter is totally isolated from PV and AC power, please refer to “2.4 Electrical Wiring Connection”.
4. Make sure inverter is totally isolated from any DC or AC power before connecting AC cable, please refer to “2.4.2 On-Grid & Back-Up Connection”.
5. Make sure AC cable is totally isolated from AC power before connecting Smart Meter & CT, please refer to “2.4.3 Smart Meter & CT Connection”.
Appendix Protection Category Defintion Overvoltage Category Definition

Category I Category II

Applies to equipment connected to a circuit where measures have been taken to reduce transient overvoltage to a low level.
Applies to equipment not permanently connected to the installation. Examples are appliances, portables tools and other plug-connected equipment.

Category III

Applies to a fixed equipment downstream and including the main distribution board. Examples are switchgear and other euiquipment in an industrial installation.

31
Category IV

Applies to equipment permanently connected at the origin of an installation (uostream of the main distribution board). Examples are electricity meters, primary over-current protection equipment and other equipment connected directly to outdoor open lines.

Moisture Location Category Definition

Moisture Parameters
Temperature Range Moisture Parameters

3K3 0~+40 5%~85%

Level 4K3 -33~+40 15%~100%

Environment Category Definition Environment Condition Ambient Termperature Relative Humidity

Outdoor

-20~50

4%~100%

Indoor Unconditioned

-20~50

5%~95%

Indoor conditioned

0~40

5%~85%

4K4H ~20~+55 4%~100%
Applied to PD3 PD3 PD2

Pollution Degree Definition

Pollution Degree I

No pollution or only dry, non-conductive polllution occurs. The pollution has no influence.

Pollution Degree II

Normally only non-conductive pollution occurs. Occasionally,

however, a temporary conductivity caused by condensation must be expected.

32

Pollution Degree III Pollution Degree IV

Conductive pollution occurs, or dry. non-conductive pollution occurs, which becomes conductive due to condensation, which is expected.
Persistent conductive pollution occurs, for example, the pollution caused by conductive dust, rain and snow.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals