SAMLEX Inverter Installation Kit Owner’s Manual

June 6, 2024
SAMLEX

SAMLEX logo1 Inverter Installation Kit
DC-1000-KIT
DC-2000-KIT
DC-2500-KIT
DC-2500-KIT-XL
DC-3500-KIT
Owner’s Manual

Please read this manual BEFORE installing your DC Inverter Installation Kit
Disclaimer of Liability
UNLESS SPECIFICALLY AGREED TO IN WRITING, SAMLEX AMERICA INC.:

  1. MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY, OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
  2. ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS, OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL, OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK.

Samlex America reserves the right to revise this document and to periodically make changes to the content hereof without obligation or organization of such revisions or changes.
Copyright Notice/Notice of Copyright
Copyright © 2018 by Samlex America Inc. All rights reserved. Permission to copy, distribute and/or modify this document is prohibited without express written permission by Samlex America Inc.

Important Safety Precautions

SAMLEX Inverter Installation Kit - iconInstallation and wiring compliance
Installation and wiring must comply with the local and National Electrical Codes and must be done by a CERTIFIED ELECTRICIAN.
1.1 PREVENTING FIRE AND EXPLOSION HAZARDS
Working with the inverter may produce arcs or sparks. Thus, the inverter should not be used in areas where there are inflammable materials or gases requiring ignition-protected equipment.
These areas may include spaces containing gasoline-powered machinery, fuel tanks, battery compartments.
1.2 PRECAUTIONS WHEN WORKING WITH BATTERIES

  • Batteries contain very corrosive diluted Sulphuric Acid as an electrolyte.
    Precautions should be taken to prevent contact with skin, eyes, or clothing.

  • Batteries generate Hydrogen and Oxygen during charging resulting in the evolution of explosive gas mixture. Care should be taken to ventilate the battery area and follow the battery manufacturer’s recommendations.

  • Never smoke or allow a spark or flame near the batteries.

  • Use caution to reduce the risk of dropping a metal tool on the battery. It could spark or short circuit the battery or other electrical parts and could cause an explosion.

  • Remove metal items like rings, bracelets, and watches when working with batteries. Batteries can produce a short circuit current high enough to weld a ring or the like to metal causing a severe burn.

  • If you need to remove a battery, always remove the Negative terminal from the battery first.

Make sure that all the accessories are OFF so that you do not cause a spark.

General Information

2.1 DESCRIPTION
The Inverter Installation Kit consists of pair of 10 ft Red (Positive) and Black (Negative) cables and fuse arrangement for connecting the battery to the inverter in a safe manner.
2.2 CHARACTERISTICS OF THE CABLES PROVIDED WITH THE KITS
We have provided the highest quality, industrial/welding grade, flexible cable with the Kits. These cables are designed for use as motor and power lead where flexibility
and portability are required. The inherent nature of the design makes the cables suitable for battery cables for automotive and renewable energy applications.
Key features of the cables provided with the Kits are as follows:

  • 600V rating
  • Very wide operating temperature of -50oC to 105oC
  • High strand count, annealed, copper conductors for high flexibility.
  • Ethylene Propylene Rubber (EPR) jacket provides high 600V insulation and resistance to abrasion, oils, acids, and heat.

2.3 FUSE PROTECTION IN THE BATTERY CIRCUIT
A battery is an unlimited source of current. Under short circuit conditions, a battery can supply thousands of Amperes of current. If there is a short circuit along the length of the cables that connect the battery to the inverter, thousands of Amperes of current can flow from the battery to the point of shorting and that section of the cable will overheat, the insulation will melt and the cable will ultimately break. This interruption of very high current will generate a hazardous, high temperature, high energy arc with accompanying high-pressure waves that may cause fire, damage nearby objects, and cause injury. To prevent the occurrence of hazardous conditions under short circuit conditions, an appropriate fuse should be used in the battery circuit that has the required current interrupting capacity (Termed AIC – Ampere Interrupting Capacity).
For this purpose, a fuse with an AIC rating of 10000A at 14V / 5000A at 32V, or higher should be used.
The following types of fuses are included in the Kit:

  • 400A, 125 VDC, Model JLLN 400 manufactured by Littelfuse
    •   * AIC of 20,000A
    • UL Class “T” rated, UL listed as per UL Standard 248-15
  • Marine Rated Battery Fuse (MRBF Series) made by Cooper Bussmann
    •   * Voltage rating of max 58 VDC
    • Current ratings of 100A (MRBF-100), 200A (MRBF-200) and 300A (MRBF-300)
    • AIC of 10000A at 14VDC, 5000A at 32 VDC, and 2000A at 58 VDC
    • Ignition protected as per SAE J1171
    • Weather Proof (IP66)

SAMLEX Inverter Installation Kit - iconCAUTION
The fuse should be placed as close to the battery’s POSITIVE terminal as possible, preferably within 7” of the battery terminal.
2.4 CHARACTERISTICS OF FUSES AND FUSE HOLDERS PROVIDED WITH THE KITS
DC-1000-KIT, DC-2000-KIT, and DC-2500-KIT are provided with 100A, 200A, and 300A fuse respectively (Fig. 3.3). These fuses are Marine Rated Battery Fuses (MRBF-XXX Series) made by Cooper Bussmann. The MRBF Fuse provides easy, practical weatherproof, and economical circuit protection in tight space constraints. The fuse is installed between the Positive Battery Terminal Stud and the Positive Battery Cable with the help of a special Clamping Fixture. The Clamping Fixture consists of the following:

  • Clamping Fixture Bar (CFBAR), Fig. 3.4. Has a base plate for connecting to the battery stud (with a hole to accommodate battery stud of up to stud size 3/8” / M10) and a stud (size M-8) for connecting the MRBF fuse and the battery cable.
  • Stainless Steel nut (thread size M8, will require ½” or 13 mm wrench for tightening), Flat Washer, and Spring Washer, Fig. 3.5.
  • An Insulating Cap, Fig. 3.6. It slides over the base plate of CFBAR and is used to insulate the exposed stud and the nut of the CFBAR.

DC-3500-KIT is provided with 400A, Class-T Fuse Assembly.
2.5 SIZING OF CABLES TO REDUCE VOLTAGE DROP, HEATING, AND POWER LOSS
The flow of electric current in a conductor is opposed by the resistance of the conductor.
The resistance of the conductor increases linearly as the length of the conductor is increased and decreases as the cross-section (thickness) of the conductor are increased.
The flow of current through the resistance of the conductor produces voltage drop and power loss due to heating. Voltage drop due to resistance of the conductor increases linearly as the current increases.
Power loss because of heating due to resistance of the conductor increases by the square of the increase in the current – e.g. if the current increases 2 times, the heating/power loss increases 4 times. Thus, it is desirable that thicker and shorter conductors be used to reduce the undesirable effects of voltage drop, heating, and power loss.
The size (thickness/cross-section) of the conductors is designated by AWG (American Wire Gauge). Please note that a smaller AWG # denotes a thicker size of the conductor up to AWG #1. Wires thicker than AWG #1 are designated AWG

1/0, AWG #2/0, AWG #3/0, and so on. In this case, increasing AWG # X/0

denotes thicker wire.
The DC input circuit of an inverter is required to handle very large DC currents. Cables and connectors from the battery to the inverter should be properly sized to ensure minimum voltage drop, minimum heating, and minimum power loss between the battery and the inverter. Thinner cables and loose connections will result in larger voltage drop, increased loss of power and consequent reduction inefficiency, poor inverter performance, and will produce abnormal heating that may lead to the risk of insulation meltdown and fire.
For safety against overheating and consequent deterioration of the insulation and possibility of fire, various Standards specify the maximum current carrying capacity (Ampacity) of various types of cables for installation in free air/conduit. One such Standard is ISO 10133. Apart from the consideration of safety as explained above, reducing the voltage drop as a result of the long-distance cable between the battery and the inverter is also important for improving the efficiency of the DC input side of the inverter system. A longer distance between the battery and the cable will require a thicker cable. Normally, the thickness of the cable should be such that the voltage drop from the battery terminal to the inverter is as low as possible, preferably up to a maximum of around 5%.
The formula used for calculating the maximum % voltage drop on the DC input of the inverter:
Percentage Voltage Drop =
SAMLEX Inverter Installation Kit - math
NOTE:
For purposes of the calculation of % voltage drop in the formula above based on-resistance per unit length, the length of the cable has been taken as twice the cable routing length between the battery and the inverter to include the overall length of the Positive and Negative cables (e.g. if the distance between the battery and the inverter is taken as 3 ft, the length of the cable has been taken as 6 ft for calculation purposes.)
Inverters are designed to operate normally within a specified lower and upper input voltage range. The lower operating voltage limit of inverters is normally 10V, 20V, and 40V for 12V, 24V, and 48V battery systems respectively. When this limiting voltage is seen at the input terminal of the inverter, it will shut down due to low input voltage protection. Thus, if there is an excessive voltage drop in the input connection between the battery and the inverter due to thinner cable / longer distance / larger current, the inverter will shut down even if the battery is fully charged.
As the distance between the battery and the inverter may vary depending upon the user requirement, 10 ft or 15 ft length of cable is provided in the Inverter Installation Kits for convenience. Refer to specifications given in Tables 4.1 & 4.2 under Section 4.
Cut off the extra length of cable if the distance between the battery and the inverter is considerably less than the standard length of 10 ft/ 15 ft cable that has been provided.
2.6 HARDWARE SUPPLIED WITH EACH KIT
Each kit is supplied with a set of hardware as shown in Table 2.1

TABLE 2.1  HARDWARE SUPPLIED WITH EACH KIT

Description| Quantity
Cable Ties, 11.5” long| 6
Cable Clamps, ½”  diameter| 6
Pan Head Screws, #8 x 3/4”, Phillips Drive| 6

2.7 TOOLS REQUIRED

  • Wire Cutting Tool and Wire Stripper (for DC-3500-KIT)
  • ½” Wrench and 5/16” Allen Key (for Samlex DC-3500-KIT)
  • Appropriate screwdriver or wrench depending on the DC input terminal of your inverter.
  • Crimping tool and heat shrink tubing (if ring terminal for the inverter end is being changed to fit DC input terminals of the inverter).

Installation Instructions

3.1 INSTALLATION INSTRUCTIONS:
DC-1000-KIT, DC-2000-KIT, DC-2500-KIT AND DC-2500-KIT-XL
Preparing Cable Termination for Inverter End

  • The cables provided in the kits have copper ring terminals on both ends with holes to fit 3/8” stud
  • The ring terminal may not fit the DC input terminal on the inverter and may need to be reshaped/replaced with cable lugs provided with the inverter.
  • Some inverters require Pin Type of terminal lugs to fit DC input connectors with a cylindrical hole and set screw. As the terminal lug fitted on the cable is made of copper which is malleable, it can be beaten with a hammer to form a pin shape of the required diameter to fit the cylindrical hole.
  • It may be necessary to remove the cable lug and crimp the new lug provided with the inverter.

A. Identify the Positive & Negative cables

  • Positive cable: Red color with terminal lugs at each end as in Fig. 3.1.
  • Negative cable: Black color with terminal lugs at each end as in Fig. 3.2.

SAMLEX Inverter Installation Kit - kit| SAMLEX Inverter Installation Kit - kit2
---|---

B. Connect one end of the Positive cable to the Positive terminal of the inverter (usually Red in color). The terminal lug may need to be shaped/replaced to fit the inverter terminal (see details above).

SAMLEX Inverter Installation Kit - kit4

|

SAMLEX Inverter Installation Kit - kit6

---|---

C. Identify the components of the Fuse Assembly.
Refer to Figures 3.3 to 3.6.

SAMLEX Inverter Installation Kit - kit3| SAMLEX Inverter Installation Kit - kit7
---|---

D. Place the MRBF fuse onto the stud provided on the CFBAR. See Fig.3.7.
E. Next, place the cable lug (crimped to the free end of the Positive cable) onto the CFBAR stud so that it sits over the fuse MRBF. See Fig. 3.8.

SAMLEX Inverter Installation Kit - kit9| SAMLEX Inverter Installation Kit - kit10
---|---

F. Next, attach the flat washer, the spring washer, and the M-8 nut onto the CFBAR stud and tighten the nut with a ½” wrench. See Fig. 3.9.

SAMLEX Inverter Installation Kit - kit11 G. Slide the Insulating Cap onto the rectangular strip of the CFBAR and then place the hood portion over the exposed portion of the stud of the CFBAR. See Figures 3.10 and 3.11.

SAMLEX Inverter Installation Kit - kit12| SAMLEX Inverter Installation Kit - kit13
---|---

H. Bolt the CFBAR to the Positive terminal stud of the Battery usually denoted by the ‘+’ sign as shown in Fig. 3.12.

SAMLEX Inverter Installation Kit - kit14 I. Connect one end of the Negative cable to the Negative terminal of the inverter (usually Black in color). The terminal lug may need to be reshaped/replaced to fit the inverter terminal (see details above).
J. Connect the other end of the negative cable to the battery Negative terminal stud, usually denoted by the ‘-’ sign.
K. Please ensure that all the connections are tight.
3.2 INSTALLATION INSTRUCTIONS:
DC-3500-KIT
A. Identify the Positive & Negative Cables:

  • Positive cable: Red color with terminal lugs at each end as in Fig. 3.13.
  • Negative cable: Black color with terminal lugs at each end as in Fig. 3.14.

SAMLEX Inverter Installation Kit - kit15| SAMLEX Inverter Installation Kit - kit16
---|---

B. The Class T Fuse Assembly (Fig. 3.15) consists of the following components assembled as one unit:
Class T Fuse – Fig. 3.16: This is rated at 125V, 400A. It is UL Class “T” rated and UL listed as per UL Standard 248-15. It has an AIC (Ampere Interrupting Capacity) of 20,000A

SAMLEX Inverter Installation Kit - kit17| SAMLEX Inverter Installation Kit - kit18
---|---

Fuse Holder – Fig. 3.17: This consists of a fiberglass insulated base with studs/bolts (5/16” diameter, 18 Threads Per Inch) and nuts (requires ½” size wrench) for holding the fuse. The two terminals for cable entry are designed for #4/0 cable (Hole size is 0.6” / 15.5 mm). 5 /16”, hexagonal headed socket cap screws (requires Allen Key size 5 /16”) are used to clamp the cable ends.

SAMLEX Inverter Installation Kit - kit30

Snap-on cover: Made of clear polycarbonate and provides touch safety.
C. The fuse should normally be installed within 7 inches of the Positive Terminal of the battery. Cut the Positive cable based on the desired location of the Class “T” Fuse Assembly using an appropriate wire cutter. Strip 1.05” of the insulation at the cut ends using a suitable wire stripper. Please ensure that the innermost layer of the tape separator is completely removed. See Fig. 3.18.
D. Insert the bare ends of the cable into the hole for the cable entry and tighten the screw-down terminals firmly. Fix the clear polycarbonate snap- on cover for touch safety. See Fig. 3.19.

SAMLEX Inverter Installation Kit - kit31| SAMLEX Inverter Installation Kit - kit33
---|---

NOTES FOR FIG 3.17 and 3.19:
The diameter of the hole in the screw-down terminal for the cable entry is 0.6” and is just big enough for the diameter of the bare AWG #4/0 stranded cable. The ends of the strands towards the cut face of the cable may get bent, frayed, or spread outwards during cutting causing the diameter of the cable near the cut face to increase slightly.
The strands towards the cut face need to be pressed together closely to reduce the diameter near the cut face to less than 0.6”. To keep the strands towards the cut face pressed together for easier entry into the terminal for cable entry, tightly wrap insulation tape around 0.2” to 0.3” from the cut face. If required, straighten and compress the bent,  rayed, or spread-out ends to reduce the diameter to the minimum.
Insert the leading 0.2” to 0.3” bare portion into the hole and remove the insulating tape to insert the bare end of the cable fully.
Please ensure that all the strands get inserted into the hole and that no strand(s) is left forced out of the hole.
E. Connect the terminal lug of the shorter section of the cut Positive cable to the Positive terminal of the Battery, usually denoted by the ‘+’ sign (see Fig. 3.20).

SAMLEX Inverter Installation Kit - kit34 F. Connect the terminal lug of the longer section of the cut Positive cable to the Positive terminal of the inverter (usually Red in color). The terminal lug may need to be reshaped/replaced to fit the inverter terminal (see details above).
G. Connect one end of the Negative cable to the Negative terminal of the inverter (usually Black in color). The terminal lug may need to be reshaped/replaced to fit the inverter terminal (see details above).
H. Connect the other end of the negative cable to the battery Negative terminal, usually denoted by the ‘-’ sign. When the lug of the Negative cable first makes contact with the Negative terminal of the battery, a spark may be observed. This is normal. This spark occurs because of the initial charging current of the input side capacitors inside the inverter.
I. Ensure that all the connections are tight.

Specifications

4.1 SPECIFICATIONS

TABLE 4.1 SPECIFICATIONS FOR KITS WITH 10 FT CABLE LENGTH AND UP TO 3% VOLTAGE DROP


Model No. of Inverter Installation Kit (1)| Cable Size (Resistance
in Ohm/ft) 
(2)| Cable Lenght(s) (3)| Fuse Size (4)| The recommended size of Inverter for up to 3% Voltage Drop
Power range of 12VDC Inverter (5)| Power range of 24VDC Inverter (6)|

Power Range of 48VDC Inverter (7)

DC-1000-KIT| AWG #4 (0.00025 Ohm/ft)| 2 x 10ft| 100A| 600W to
800W| 600W to
1900W| Up to
4500W
DC-2000-KIT| AWG #2 (0.00016 Ohm/ft)| 2 x 10ft| 200A| 1000W to
1200W| 2000W to
3000W| Up to
8500W
DC-2500-KIT| AWG #2/0 (0.000077 Ohm/ft)| 2 x 10ft| 300A| 1500W to
2000W| 4000W to
6000W| Up to
13000W
DC-3500-KIT| AWG #4/0

(0.00005 Ohm/ft)

| 2 x 10ft| 400A| 2500W to
3000W| 6,500W to
8000W| Up to
16000W

TABLE 4.2 SPECIFICATIONS FOR KITS WITH 15 FT CABLE LENGTH AND UP TO 5% VOLTAGE DROP


Model No. of Inverter Installation Kit (1)

|

Cable Size (Resistance in Ohm/ft) (2)

|

Cable Lenght(s) (3)

|

Fuse Size (4)

|

The recommended size of Inverter for up to 5% voltage drop

Power range of 12VDC Inverter (5)| Power range of 24VDC Inverter (6)|

Power Range of
48VDC Inverter 
(7)

DC-2500-KIT-XL| AWG #2/0
(0.00007 Ohm/ft)| 2 x 15ft| 300A| 1500W to
000W| 4000W to
6000W| Up to
13000W

NOTES FOR TABLES 4.1 & 4.2:
a) Specifications are subject to change without notice
b) Cable sizes (Column 2) are indicated in AWG (American Wire Gauge).
Specifications:
(i) Red Positive, Black Negative, each 10 ft length, (ii) 600V, -50°C to 105°C, (iii) Stranded conductors with crimped Ring Terminals on either end: Hole diameter 0.41” for 3/8” stud
c) Ampacity of cable conductors (Column 2) has been based on: (i) ISO Standard 10133, (ii) Conductor temperature rating of 105°C / 221°F, (iii) Ambient temperature of 30°C / 86°F and (iv) Cable routed in free air (not in conduit)
d) Ampacity of the cable conductors (Column 2) is more than the Ampere rating of the associated fuse (Column 4)
e) Power ranges of Inverters/ (Columns 5, 6, 7) are based on the following % voltage drops:
(i) Table 4.1: Up to 3% voltage drop for cable routing length of 10 ft from the Inverter to the Battery at DC Input Current = the rated Ampere Capacity of the Fuse (Column 4)
(ii) Table 4.2: Up to 5% voltage drop for cable routing length of 15 ft from the Inverter to the Battery at DC Input Current = the rated Ampere
The capacity of the Fuse (Column 4)
f) Use the formula given under Section 2.5 to calculate the actual % voltage drop on the DC input side of the inverter at the desired DC input current of the Inverter

Warranty

2 YEAR LIMITED WARRANTY
Samlex Inverter Installation Kits manufactured by Samlex America Inc. (the “Warrantor“) are warranted to be free from defects in workmanship and materials under normal use
and service. The warranty period is 2 years for the United States and Canada and is in effect from the date of purchase by the user (the “Purchaser“).
Warranty outside of the United States and Canada is limited to 6 months. For a warranty claim, the Purchaser should contact the place of purchase to obtain a Return Authorization Number.
The defective part or unit should be returned at the Purchaser’s expense to the authorized location. A written statement describing the nature of the defect, the date of purchase, the place of purchase, and the Purchaser’s name, address, and telephone number should also be included.
If upon the Warrantor’s examination, the defect proves to be the result of defective material or workmanship, the equipment will be repaired or replaced at the Warrantor’s option without charge and returned to the Purchaser at the Warrantor’s expense.
(The contiguous US and Canada only)
No refund of the purchase price will be granted to the Purchaser unless the Warrantor is unable to remedy the defect after having a reasonable number of opportunities to do
so. Warranty service shall be performed only by the Warrantor. Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void. There
shall be no warranty for defects or damages caused by faulty installation or hook-up, abuse or misuse of the equipment including exposure to excessive heat, salt or fresh water spray, or water immersion.
No other express warranty is hereby given and there are no warranties which extend beyond those described herein. This warranty is expressly in lieu of any other expressed or implied warranties, including any implied warranty of merchantability, fitness for the ordinary purposes for which such goods are used, or fitness for a particular purpose, or any other obligations on the part of the Warrantor or its employees and representatives.
There shall be no responsibility or liability whatsoever on the part of the Warrantor or its employees and representatives for injury to any persons, or damage to person or persons, or damage to property, or loss of income or profit, or any other consequential or resulting damage which may be claimed to have been incurred through the use or sale of the equipment, including any possible failure of malfunction of the equipment, or part thereof. The Warrantor assumes no liability for incidental or consequential damages of any kind.
Samlex America Inc. (the “Warrantor”)
www.samlexamerica.com

Notes


Contact Information
Toll-Free Numbers
Ph: 1 800 561 5885
Fax: 1 888 814 5210
Local Numbers
Ph: 604 525 3836
Fax: 604 525 5221
Website
www.samlexamerica.com
USA Shipping Warehouses
Kent, WA
Plymouth, MI
Canadian Shipping Warehouse
Richmond, BC
Email purchase orders to
orders@samlexamerica.com

SAMLEX logo111013-DC-1000-2000-2500-2500XL-3500-KIT-1021

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals