resideo PCVF-ECM2020 AquaPump Variable Speed Circulating Pumps Installation Guide
- June 6, 2024
- resideo
Table of Contents
- AquaPUMP Variable Speed Circulating Pumps
- Table 1. Dimensions
- WARNING
- 1. SYMBOLS USED IN THIS DOCUMENT
- 2. GENERAL INSTALLATION
- Models
- 3. INSTALLATION
- Fig. 1. Mounting the AquaPUMP variable speed circulator
- Fig. 2. Control box position (The inverted pump will work, just reading
- 4. ELECTRICAL CONNECTION
- 4.2 ANALOG INPUT (OPTIONAL)
- Analog Input Setting
- 5. CONTROL PANEL
- 5.2 FIRST POWER-UP
- 5.3 DISPLAY
- 6. SETTING THE PUMP
- 7. SYSTEMS WITH BYPASS VALVE BETWEEN FLOW AND RETURN PIPES
- 8. START-UP
- 9. PUMP SETTINGS AND PUMP PERFORMANCE
- 10. TROUBLESHOOTING
- TECHNICAL DATA AND INSTALLATION DIMENSIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
AquaPUMP Variable Speed Circulating Pumps
INSTALLATION INSTRUCTIONS
Table 1. Dimensions
Product Number
|
Max. Flow
|
Max. Pressure Head
|
Connections
|
Weight
lbs. (kg)
|
Dimensions
---|---|---|---|---|---
GPM
|
LPM
|
Feet
|
Meters
|
Bolt Hole
Spacing
|
Bolt Hole
|
L1
in. (mm)
|
L2
in. (mm)
|
L3
in. (mm)
|
L4
in. (mm)
|
L5
in. (mm)
PCVF-ECM2020/U
|
20
|
75.7
|
20
|
6
|
3-5/32 in.
(80.2 mm)
|
1/2 in.
(12.7 mm)
|
8.0
(3.6)
|
6.50
(165)
|
7.08
(165)
|
5.75
(146)
|
5.31
(135)
|
3.25
(80)
PCVF-ECM2020-LF/U
|
20
|
75.7
|
20
|
6
|
3-5/32 in.
(80.2 mm)
|
1/2 in.
(12.7 mm)
|
8.0
(3.6)
|
6.50
(165)
|
7.08
(165)
|
5.75
(146)
|
5.31
(135)
|
3.25
(80)
Table 2. Accessories and Spare Parts
Product Number
|
Description
---|---
PCG100/U
|
1 in. and 1-1/4 in. Circulating Pump Flange Gaskets
PCV100/U
|
1 in. and 1-1/4 in. Circulating Pump Check Valve
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
WARNING
- Prior to installation, read these installation and operating instructions. Installation and operation must comply with local regulations and accepted codes of good practice.
- The use of this product requires experience with and knowledge of the product. Only licensed or trained installers should install this product.
- For supply connection, use wires acceptable for at least 90°C (194°F).
- Risk of shock: this pump is not rated for use in swimming pools or marine areas.
- instructions for proper installation, connect to a properly grounded circuit only.
- For indoor use only.
- Use copper conductors only.
- Do not install with motor above or below pump body.
- Do not submerge.
- Do not run pump dry.
1. SYMBOLS USED IN THIS DOCUMENT
WARNING
The safety instructions must be followed to prevent potential personal injury.
CAUTION
The safety instructions must be followed to prevent potential malfunction or
damage to the equipment.
2. GENERAL INSTALLATION
2.1 RESIDEO AQUAPUMP VARIABLE SPEED CIRCULATOR Resideo AquaPUMP auto zone
changes the pump speed according to the system demand without any requirement
of external controls or control wiring.
The Resideo AquaPUMP circulator is recommended for circulating water in closed
hydronic heating systems or potable water systems.
Models
- PCVF-ECM2020/U cast iron
- PCVF-ECM2020-LF/U stainless steel
The Resideo AquaPUMP includes operating modes suitable for systems with constant or variable flows, such as:
- Underfloor heating systems
- One-pipe (series) systems
- Two-pipe (parallel) systems
- Multi-zone heating systems
Resideo AquaPUMP circulators incorporate variable speed control technology
with an ECM motor, enabling optimum energy efficiency and occupant comfort,
with built-in control algorithms that can adapt to continuously changing
system requirements.
The Resideo AquaPUMP features a user-friendly frontmounted control panel (see
section 5) and wiring box for ease of installation.
2.2 ADVANTAGES OF INSTALLING A RESIDEO AQUAPUMP VARIABLE SPEED CIRCULATOR Nine different modes of operation to suit different system requirements:
- Easily selectable from the front mounted display.
- Modes include sensorless demand-based control, Auto and proportional pressure, fixed speed and constant pressure.
- Analog input for external variable speed control.
- Power consumption and flow rate clearly displayed.
- Broad operating range, producing 20 feet of head or 20 USgpm of flow, provides versatility to cover the performance of a wide range of fixed speed or variable speed circulators.
- Flange to flange compatibility with many competing models.
- Front mounted wiring box for ease of installation and service.
3. INSTALLATION
3.1 EXTRA ELECTRICAL CONNECTOR IN THE BOX For your convenience Resideo has supplied a PG7 electrical strain relief connector in the box. It can replace the signal port plug to secure an insulated signal cable with an outer diameter between 0.118 and 0.234 inches.
3.2 MOUNTING All servicing personnel should be equipped with proper personal protective equipment. Shut off the water supply, or isolate the pump area. If valves have been installed, on the suction and discharge sides of the pump, close them. If no valves have been installed it may be necessary to drain the system. It is best to leave the drain valve open while working on the system.
Install suction and discharge flanges on the pipe ends. The use of Teflon tape
sealer or a high quality thread sealant is recommended. Install the AquaPUMP
variable speed circulator with the flange gaskets. Flange bolts should be
tightened evenly to 60lb-inch of torque. To wire the AquaPUMP variable speed
circulator, follow section 4.0 in the Electrical Connection section below.
Install the circulator where there will be sufficient room for inspection and
service.
NOTE: For future servicing, isolation flanges can be used in place of
standard flanges.
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
correct installations
incorrect installations
Fig. 1. Mounting the AquaPUMP variable speed circulator
Arrows on the pump housing indicate the liquid flow direction through the pump.
- Fit the two gaskets supplied when the pump is mounted in the pipe.
- Install the pump with the motor shaft horizontal (see Fig. 1).
3.3 CONTROL BOX POSITIONS
The orientation of the display can be adjusted by removing four screws that
attach the motor to the pump housing (see Fig. 2). Pump must be isolated from
the system when making this adjustments as this will open the system to the
atmosphere.
Fig. 2. Control box position (The inverted pump will work, just reading
the panel upside down is not recommended)
Ensure the gasket is intact and seated before evenly retightening the mounting screw to 4.5-5.5 lb/ft (6-7.5 Nm).
WARNING
The pumped liquid may be scalding hot and under high pressure. Drain the
system or close the isolating valves on either side of the pump before the
screws are removed.
CAUTION
After the position of the control box has been rotated, refill the pump with
system liquid before startup.
4. ELECTRICAL CONNECTION
4.1 POWER SUPPLY
The electrical wiring must be installed strictly in accordance with national
electrical codes, local codes and regulations.
- Electrical installation should be conducted by a qualified electrician.
- Always make sure electric power is disconnected before wiring the circulator.
The motor is designed for 60 Hz, 1 phase, 115 volt power.
Wire shall be 14 to 16 gauge solid wire or 16 to 18 gauge stranded wire.
To connect, loosen the screw from the wiring box cover and remove the screw
and cover.
Install a 1/2″ NPT strain relief fitting (not included) for the power wiring
in the large access hole provided on the right side of the box.
Insert the power wires through the fitting and secure the wires.
Strip 3/16″ of insulation from the ends of the three wires to be connected.
To insert the wires into the terminal strip, press the terminal lever forward
firmly. Insert the stripped wire into the opening and release the lever (see
Fig. 3). Tug on the wire gently to ensure it is secured.
Fig. 3. Terminal strip
Connect the hot wire to terminal “L1”, the neutral wire to terminal “L2/N”,
and the ground wire to terminal (see Fig. 4). Replace the wiring box cover and
tighten screw, unless you plan to use analog input (see section 4.2). The pump
is thermally protected so overload protection is not necessary. All that is
required is a fused plug or circuit breaker in the power line. Electrical
information can be found on the side of the wiring box.
L1 L2/ N
Fig. 4. Power supply connection
The electrical connections and protection must be carried out in accordance with National Electric codes.
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
WARNING
The electrical supply must be disconnected when wiring the circulator.
4.2 ANALOG INPUT (OPTIONAL)
WARNING
Ensure circulator is disconnected. Wire must remain isolated from power.
Wire shall be 18 to 24 gauge solid wire or stranded wire.
To connect, loosen the screw from the wiring box cover and remove the screw
and cover.
Install some form of strain relief connector (included in the box) on the left
side of the wiring compartment and tighten enough so the wire does not slide
when pulled.
Insert wires through the connector(s).
Strip 3/16″ of insulation from the ends of the two wires to be connected.
To insert the wires into the analog input terminal strip, press the terminal
lever forward firmly. Insert the stripped wire into the opening and release
the lever (see Fig. 3). Tug on the wire gently to ensure it is secured.
Connect the positive wire to terminal “v” for voltage input control and the
neutral wire to terminal “c” (see Fig. 5).
Fig. 5. Analog input connection 0-10 VDC or 2-10 VDC
Replace the terminal box cover and tighten screw.
Analog Input Setting
The pump can be controlled by an external controller via 0-10 VDC. (See Fig. 5
for how to install analog input wiring) Ensure the analog input mode is
selected.
The pump will vary the performance as per the external analog signal. See Fig.
6.
Fig. 6. 0-10 V operation
At an input voltage lower than 2V, the pump will be off. The pump will start to operate at the min. curve at or above 2V. The pump will reach max. curve at 10V. See Fig. 7.
Resideo AquaPUMP variable speed circulator A1 Analog Input Performance Curve
Fig. 7. Pump performance at different Analog input
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
5. CONTROL PANEL
5.1 THE CONTROL PANEL
Fig. 8. Resideo AquaPUMP control panel
Position
|
Description
---|---
A
|
Display showing the actual pump power consumption in Watts and reference flow in USgpm. Display alternates between Watt and GPM every 5 seconds.
B
|
Pump setting LEDs
C
|
Mode select button for changing pump setting
NOTE: GPM value and flow indicator are uncalibrated.
5.2 FIRST POWER-UP
The display is on and in Auto mode (position 0 in Fig. 9) the first time the
panel is powered on.
NOTE: Display shows “E#” when the pump is not operating properly (see
section 10). (E1, E2, E3 or ER)
5.3 DISPLAY
The Resideo AquaPUMP variable speed circulator has nine pump settings which can be selected with the Mode button.
Every time the Mode button is pressed (see Fig. 8, C) the pump setting is
changed to the next mode.
A full cycle through the available modes requires nine button presses.
The selected pump setting is indicated by one of nine different light fields (see Fig. 9).
Fig. 9. Pump setting LEDs
See section 9, Pump settings and pump performance, for information about the function of each setting.
Position
|
Description
---|---
0
|
AUTO (factory setting)
1
|
PC1 Lowest proportional-pressure curve
2
|
PC2 Highest proportional-pressure curve
3
|
PC3 Lowest constant-pressure curve
4
|
PC4 Highest constant-pressure curve
5
|
Constant speed curve, speed I
6
|
Constant speed curve, speed II
7
|
Constant speed curve, speed III
8
|
Analog input
6. SETTING THE PUMP
6.1 PUMP SETTING FOR SYSTEM TYPE
NOTE: Optimum energy savings & comfort can be achieved by careful
selection of the correct operation mode (see Fig. 10).
Recommended and alternative pump settings are shown below:
Image
|
System Type
|
Recommended Setting
|
Alternative Setting
---|---|---|---
A
|
Under floor heating (Radiant single zone)
|
Auto
|
Highest constant pressure curve (pc4) or Lowest constant pressure curve (pc3)
B
|
Two-pipe (parallel) systems
|
Auto
|
Highest proportional pressure (pc2)*
C
|
One-pipe (series)
systems
|
Lowest proportional pressure curve (pc1)*
|
Highest proportional pressure (pc2)*
*See pump settings and pump performance (section 9)
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
Auto (underfloor heating and two-pipe (parallel systems) Auto function observes and adjusts the pump performance to satisfy the system requirement. The pump adapts to the system over time, it is recommended to leave the pump in the auto position at least one week before selecting other pump settings.
single zone – constant resistance
multiple zone – variable loads parallel
multiple zone – variable loads in series
Changing from recommended (auto) to alternative pump setting: Heating systems
are ‘slow’ systems that cannot be set to the optimum operation within minutes
or hours.
If the recommended pump setting does not give the desired comfort in some
areas of the building, change the pump setting to the shown alternative.
See pump settings and pump performance (section 9) for more details.
Fig. 10. Recommended pump setting for different system type
7. SYSTEMS WITH BYPASS VALVE BETWEEN FLOW AND RETURN PIPES
7.1 PURPOSE OF BYPASS VALVE
The purpose of a differential pressure bypass valve is to ensure that the heat
from the boiler can be distributed when all valves in the underfloor-heating
circuits and/or thermostatic radiator valves are closed. These valves were
commonly applied in multi zone systems with traditional fixed speed pumps.
An AquaPUMP variable speed circulator eliminates the need for a differential
bypass valve when used in Auto or proportional pressure modes, because the
circulator will reduce speed when the valves in the system close and the heat
demand is reduced.
If you are servicing an existing system with a bypass valve and you are
replacing a fixed speed circulator with an AquaPUMP variable speed circulator,
there is no need to remove or open/ close the bypass valve, if you intend to
set to a constant pressure mode (PC3 / PC4).
It is recommend to remove the bypass valve if you intend to use Auto or
proportional pressure modes, because the circulator will reduce speed when the
valves in the system close and increase the efficiency of the system
operation.
8. START-UP
8.1 BEFORE START-UP
Fill the system with liquid and properly vent the system before starting the
pump. The required minimum inlet pressure in relation to liquid temperature
must be available at the pump inlet (see section 11).
8.2 VENTING THE PUMP
Even with system vented, air may be still be present in the pump. The air in
the pump may cause noise but the noise should cease after a few minutes
running.
The venting process can be shortened by setting the pump to run at speed III
for a short period of time (20 seconds).
Once the pump is vented and (the noise has ceased), set the pump mode
according to the recommendations (see sections 6).
CAUTION
The pump must not run dry.
9. PUMP SETTINGS AND PUMP PERFORMANCE
9.1 RELATION BETWEEN PUMP SETTING AND PUMP PERFORMANCE
Fig. 11. Pump setting in relation to pump performance
Select the optimum setting:
The AquaPUMP variable speed circulator comes with 9 modes of operation.
There are three fixed speed curve options which will operate just like
traditional fixed speed circulators, except that AquaPUMP variable speed motor
technology is far more energy efficient than traditional fixed speed
circulators.
The proportional pressure curves operate as Sensorless differential pressure
circulators. These curves follow preselected performance curves and will
reduce flow and energy consumption when the valves in the system close or open
and the flow requirements are reduced.
The constant pressure curves and auto mode maintain preselected pressure
ratings at the circulator.
Auto mode operates on the sensorless differential pressure principle, but will
learn usage patterns and adjust circulator performance over time to optimize
energy efficiency. The operating point will be within the gray envelope seen
in Fig. 11.
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
Setting
|
Pump Curve
|
Function
---|---|---
Auto (factory setting)
|
|
Operating within the defined range The Auto function controls the pump
performance automatically within a defined performance range (see Fig. 11 –
within the grey envelope).
• Adapt to the size of the system.
• Adapt to system demand over time.
In Auto mode the AquaPUMP variable speed circulator is set to a proportional-
pressure curve control.
PC1
|
Lowest proportional pressure curve
|
The operation point of the pump will follow the lowest proportional pressure curve (see Fig. 11) depending on the load demand. The head (pressure) is reduced during low demand and increased during high demand until the maximum wattage is reached, then the pump will run on the speed III curve.
PC2
|
Highest proportional pressure curve
|
The operation point of the pump will follow the highest proportional pressure curve (see Fig. 11) depending on the load demand The head (pressure) is reduced during low demand and increased during high demand until the maximum wattage is reached, then the pump will run on the speed III curve.
PC3
|
Lowest constant pressure curve
|
The operation point of the pump will follow the lowest constant-pressure curve (see Fig. 11) depending on the load demand.
The head (pressure) is kept constant, regardless of the load demand until the maximum wattage is reached, then the pump will run on the speed III curve.
PC4
|
Highest constant pressure curve
|
The operation point of the pump will follow the highest constant pressure curve (see Fig. 12) depending on the load demand. The head (pressure) is kept constant, regardless of the load demand until the maximum wattage is reached, then the pump will run on the speed III curve.
III
|
Speed III
|
Speed III is the highest constant speed performance curve of AquaPUMP variable speed circulator and it also presents the max performance capability of the pump (see Fig. 11). Speed III can also be used to vent the pump (see section 8.2).
II
|
Speed II
|
Speed II is the medium constant speed performance curve of AquaPUMP variable speed circulator (see Fig. 11).
I
|
Speed I
|
Speed I is the lowest constant speed performance curve of AquaPUMP variable speed circulator (see Fig. 11).
|
Analog input
|
Analog input controls the operation of AquaPUMP variable speed circulator from off up to 100% performance (see Fig. 6).
10. TROUBLESHOOTING
WARNING
Before starting any work on the pump, make sure that the electrical supply has
been switched off and that it cannot be accidentally switched on.
Fault
|
Control Panel
|
Cause
|
Remedy
---|---|---|---
No Fault
|
Shows “E1”
|
Voltage too high or too low (than ±10%) of the rated voltage)
|
Check voltage level of the electricity supply.
The pump does not run
|
Light off
|
No power to the pump
|
Check power supply.
The pump is defective
|
Replace the pump.
Shows “E2”
|
Jammed rotor
|
Remove the casing and manually unlock the impeller/rotor.
Shows “E3”
|
No liquid in the system at start up.
|
Fill up the system.
Shows “ER”
|
Miscellaneous internal failure
|
Check voltage of the electricity supply.
Replace the pump.
Noise in the system
|
Shows watts and USgpm
|
Air in the system
|
See section 8.2 Venting of the pump system.
The flow is too high
|
Select a lower speed or pressure curve (see section 9). Pump settings and pump performance.
Noise in the pump
|
Shows watts and USgpm
|
Lock Rotor
|
Change to another operation mode. If the situation continues remove the casing and free the rotor.
Air in the pump
|
Let the pump run. It vents itself over time (see section 8.2) venting the pump.
The inlet pressure is too low
|
Increase the inlet pressure or check the air volume in the expansion tank, if installed.
Insufficient heat in space
|
Shows watts and USgpm
|
No Water in the pump
|
Fill the system.
The pump performance setting may be too low
|
Select a higher speed or pressure curve setting (see section 9). Pump settings and pump performance.
Confirm that the system requirement can be met by this pump capacity or larger pump may be required.
AQUAPUMP VARIABLE SPEED CIRCULATING PUMPS
TECHNICAL DATA AND INSTALLATION DIMENSIONS
11.1 TECHNICAL DATA
Supply voltage: 1x 115 V ± 10% 60 Hz
|
Minimum
|
Maximum
---|---|---
Amp
|
0.05
|
0.72
Watt
|
5
|
45
Analog input: DC voltage only
Single Type
|
Min. Voltage Limit
|
Max. Voltage Limit
|
Max. Current Limit
---|---|---|---
2-10V
|
0 VDC
|
10 VDC
|
32 mA
Motor protection: The pump requires no external motor protection.
Maximum fluid temperature: 230°F (110°C) maximum
Maximum working pressure: 150 psi (10 bar).
Maximum relative air humidity (rh): 95%
Enclosure class: Type 2
Insulation class: H
Certification: ETL listed for US and Canada (conforms to UL STD 778
certified to CSA STD C22.2 NO.108-01) NSF 372 (stainless steel models)
INLET PRESSURE
Minimum inlet pressure in relation to liquid temperature:
Sound pressure level: The sound pressure level of the pump is lower than 43 dB(A).
Ambient temperature: 0°C (32°F) – 40°C (104°F)
Pumped liquids: Water or water glycol mix.
Liquid Temperature
|
Minimum Inlet Pressure
---|---
150°F (65°C)
|
3.0 ft (0.91 m)
167°F (75°C)
|
4.4 ft (1.34 m)
194°F (90°C)
|
9.2 ft (2.8 m)
230°F (110°C)
|
36.1 ft (11.0 m)
WARNING
This pump is not rated to pump flammable liquids such as diesel oil,
gasoline or similar liquids
Liquid temperature: 2°C (36°F) – 110°C (230°F)
To avoid condensation in the control box and stator, the liquid temperature
must always be higher than the ambient temperature.
Ambient Temperature
|
Liquid Temperature
---|---
Min.
|
Max.
0°C (32°F)
|
2°C (35.6°F)
|
110°C (230°F)
10°C (50°F)
|
10°C (50°F)
|
110°C (230°F)
20°C (68°F)
|
20°C (68°F)
|
110°C (230°F)
30°C (86°F)
|
30°C (86°F)
|
110°C (230°F)
35°C (95°F)
|
35°C (95°F)
|
90°C (194°F)
40°C (104°F)
|
40°C (104°F)
|
70°C (158°F)
CAUTION
Since water conditions can vary with geographical location (i.e. amount and
type of dissolved solids) it is recommended that the operating temperature of
the liquid for open (potable) systems be kept as low as possible (i.e. below
150°F or 65°C) to avoid crystalization of calcium.
VOLUTE MATERIAL
Cast iron: For closed systems (boiler loops)
Stainless steel: Open or closed systems (potable hot water or boiler loops)
Certified <0.25 weighted average percent lead (NSF 372) and complies with
California Health and Safety code section 116875 (commonly known as AB1953).
www.resideo.com
Resideo Technologies, Inc. 1985 Douglas Drive North, Golden Valley, MN 55422 1-800-468-1502 33-00543EF–01 M.S. 12-20 | Printed in United States
© 2020 Resideo Technologies, Inc. All rights reserved. This product is manufactured by Resideo Technologies, Inc. and its affiliates.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>