Introduction
The Bryant 3-Zone Control system brings the possibility of total comfort
control to the occupants by providing the right amount of heating or cooling
for up to 3 distinct spaces or zones within a home or business.
Each zone has independent temperature settings controlled by a conventional
thermostat or Wi-Fi® based thermostats and up to 5 dampers per zone.
The Quick Reference Guide will provide a simplified description on installing
the 3-Zone Control System. Please reference the Installation and Start-Up
Instructions included in the 3-Zone Controller packaging for the complete
design and installation information on the 3-Zone System.
Product Features and Benefits
- Duct Temperature Optimizer – Offers maximum equipment protection to help ensure long life.
- Wi-Fi® Thermostat compatibility – Matches the right thermostat to the homeowner’s comfort and lifestyle.
- Diagnostic LEDs – Intelligent system diagnostics to let homeowners know if there is a problem with their system.
- Emergency Heat Switch – Allows manual override for emergency heat strip operation when utilizing a heat pump.
- Max Cycle Rate – Allows 4 equipment cycles per hr (cph) providing maximum equipment protection.
- Selection Jumpers – Designed for easy configuration
- Additional Options
- Timeguard override
- Compressor protection
- Modulating damper control in emergency situations
- Damper fuse protection
- High and low temperature limits
- Auto changeover from any zone
- RH and RC for voltage isolation
- Bypass setup routine
- Staging time for energy savings
- Automatic checkout with installer mode
- Override zoning switch
- Timer override for serviceability
Components Needed
3-Zone Control Panel
- Separate transformer is not needed to provide power
- Designed so that wires can enter from behind, above, or below
- Each system controller also includes a duct temperature sensor 24v or Wi-Fi® Thermostats
- Advanced energy savings algorithms
- Remote access
TSTWHA01 Côr 7C Thermostat
T6-WEM01-A Côr Thermostat
Dampers (8-in. – 24-in.)
-
Up to five dampers may be used in each zone by electrically connecting them in parallel
-
By-pass damper available to prevent static pressure buildup
-
Fig. 1 – Damper Types
-
Rectangular Damper A05252
-
Round Damper A05251
-
By-Pass
-
Leaving Air Temperature (LAT) Sensor
-
Slip-In Damper
-
Component Location and Wiring Considerations
Locating Bryant 3-Zone System
All wiring is connected back to the Bryant 3-Zone System. Select a location
near the furnace or fan coil where wiring from each thermostat, each damper
actuator, and the equipment itself can come together easily.
The Bryant 3-Zone System is approved for indoor use only and should never be
installed with any of its components exposed to the elements. It may be
installed in any area where the temperature remains between 32° and 158°F, and
there is no condensation. The cover must be installed to prevent damage from
other sources. Do not locate where it will be accessible to children. Remember
that wiring access is likely the most important consideration.
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Turn off unit before routing control wiring or any service operation.
Remember, there may be more than one power supply to unit.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage.
To prevent possible damage to Bryant 3-Zone System, do not mount control on
plenum, duct work, or flush against furnace.
Wiring Considerations
-
All wiring in the Bryant 3-Zone system may be unshielded
-
Ordinary thermostat wire is ideal
-
Use 22 gage or larger for normal wiring
-
Lengths over 100 ft should use 20 gage or larger wire
-
Each damper actuator required 3 conductors
-
The connection to thermostat and equipment (furnace or fan coil) could require as many as 8 conductors for a multi-state installation
-
The Leaving Air Temperature (LAT) and Heat Pump Temperature
(HPT)-(used with heat pumps only) sensors require 2 conductors each -
Cables with excess conductors are acceptable
MOUNTING
Step 1 – Mounting the Bryant 3-Zone System
The Bryant 3-Zone System can be mounted in either vertical or horizontal
position near the HVAC system inside the home. It is designed so that wires
can enter it from behind, above, or below. Plan wire routing before mounting.
Fig. 2 – Mounting the System
- Remove the front cover from the base and use the base as a template to mark drilling locations on the wall, stud , or roof truss.
- Mount using 4 screws (and wall anchors) provided. (See Fig. 2.)
- Level for appearance and tighten screws.
INSTALLATION INSTRUCTIONS
Step 2 – Install Thermostats in each desired Zone
Location
- Install each thermostat according to the manufacturer’s instructions in their designated Zone location.
- Connect the thermostats wires to their respective Zone designation on the right side of the the 3-Zone Panels. (See Fig. 3).
Step 3 – Install Zone Dampers
Each damper has 3 connections: Close (CLS), Open (OPN), and
Common (COM). Find the connection points along the lower left side of the
3-Zone Control. Suggested colors are CLS = RED; OPN = GREEN, COM = WHITE.
Field label and make the connections at the dampers and at the 3-Zone Control.
Be careful not to cross zone numbers.
If duct work required multiple dampers for a single zone, up to 5 dampers may
be wired in parallel and may be installed in any position.
Fig. 3 – Wiring Diagram for Installation of Thermostats
Zone 1 Thermostate Wiring Example
Zone 2
Fig. 4 – Installing Dampers
Step 4 – Install Barometric Bypass Damper
The barometric bypass damper is a critical part of Bryant 3-Zone System for
controlling noise at minimum airflow. A barometric bypass should be installed
unless the duct work and indoor unit have been sized for use without a bypass.
When a direct bypass (outlet air fed back directly into the return) is used,
bypassing decreases entering air temperature in cooling and increases it in
heating. Excessive bypassing will lead to limit trips, either through the
LAT/HPT sensor or the equipment internal limits.
Step 5 – Install Leaving Air Temperature (LAT) Sensor / Heat Pump
Temperature (HPT) Sensor (optional)
The Leaving Air Temperature (LAT) sensor is used to detect a cooling overload
condition and is connected to the LAT and LATC terminals.
Polarity does not matter. Locate LAT sensor in main supply trunk after heating
and cooling coil and before bypass damper and first branch.
Cycling on internal equipment limits is to be avoided because it over stresses
and can shorten the life of the equipment. The LAT limit setting should be
selected to trip below the equipment limit.
**Fig. 5 – Leaving Air Temperature (LAT) Sensor / Heat Pump Temperature (TPT) Sensor optional
**
The HPT sensor is used with ZONEBB3ZHP01 to detect a cooling overload condition and is connected to the HPT and HPTC terminals. The HPT sensor will also be monitored in heating to detect a heating overload condition at the coil with a shutdown temperature of 115°F. It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet being careful that it does not interfere with the blower wheel. If the HPT sensor is not used, the 10K ohm resistor attached to the 2 HPT terminals on the board must be left in place.
NOTE: ZONEBB3ZAC01 model does not have HPT connector.
Fig. 6 – Leaving Air Temperature (LAT) Sensor
Please refer to Limit Temperature Levels and Actions Table in the
Installation and Start-Up Instructions for additional information on the
response of the system to LAT/HPT sensors.
Step 6 – Connect the Power Supply
Optional: Use a dedicated 24 VAC, 40 VA, 60 Hz isolated transformer (not
included).
Otherwise, if the cooling and heating systems have separate transformers,
twist off the Rc/Rh jumper using a pair of long nosed pliers. Then connect the
R of the cooling transformer to Rc, the R of the heating transformer to Rh and
the common of both transformers to C. Connect a jumper wire between Rz and Rc.
Rc powers G,Y, and O outputs. Rh power W outputs.
Dipswitch
Position| Operation Description| Default (OFF)| Optional
Settings
---|---|---|---
1| Auto changeover time between heating and cooling or vice versa| Auto
changeover time
ENABLED (OFF)| Auto changeover time DISABLED
2| Together with dipswitch 3, determines chanegover time| 20 minutes auto
changeover
time (OFF)| 30 minutes auto changeover time (ON)
3| Multiplier for the modified time set on dipswitch 2| 1.0 multiplier (OFF)|
0.5 multiplier (ON)
4| Installer Test Mode used to check system operation| Normal operation (OFF)|
Installer Test Mode ENABLED (ON)
5| Disables zoning operation with all dampers open and Zone 1 thermostat as
controller| Zoning Operation ENABLED
(OFF)| Zoning Operation DISABLED (ON)
6| Setting G (Fan) to energize with W| W NOT energized with G (OFF)| W
energized with G (ON)
7| Sets Leaving air Temperature (LAT) limit temperature (HP/2 Stage control
only)| 145°F
(OFF)| (OFF)| 160°F
(ON)| 175°F
(ON)
8| 130°F
(ON)| (OFF)
9| Designated Zoning Controller connection to heat pump (HP) or an air
conditioner (AC)| 1 or 2 Speed HP / 1 Stage Aux.
Heat (OFF)| 1 or 2 Speed
AC / 1 or 2
- Stage Heat
(ON)| 1 Speed HP / 1
Stage Aux
Heatt| (OFF)
10| Designates the type of thermostat used with the Zoning Controller (HP or AC)| (ON)
11| Disable over/under temperature protection for the equipment in emergency situations| LAT and HPT Safety Protection
ENABLED (OFF)| LAT and HPT Safety Protection DISABLED (ON)
12| Determine the Reversing Valve is energized for cooling (0 function) or heating (B function)| Reversing Valve energized on
COOLING (OFF)| Reversing Valve energized on HEATING (ON)
**Fig. 7 – Connecting the Power Supply
**
Step 7 – Wire the HVAC Equipment
The descriptions below and Table 1 will help you choose the connect wiring
diagram for your system. Table 1 also shows the proper setting of dipswitches
9 and 10 for each diagram.
There are 8 dipswitch settings on the AC zone control and an additional
4 dipswitch on the HP zone controls board. Table 1 summarizes their function
and available settings.
-
Fig. 9 – AC 3-Zone Control, AC Stat, 1-Stg. AC with 1-Stg. Heat
-
Fig. 10 – HP/2S 3-Zone Control, HP Stat, 1-Stg. HP with 1-Stg. Aux.
-
Fig. 11 – HP/2S 3-Zone Control, AC Stat, 2-Spd AC with 1-or 2-Stg. Heat
-
Fig. 12 – HP/2S 3-Zone Control, AC Stat, 1-Stg. AC with 1- or 2-Stg.
-
Fig. 13 – HP/2S 3-Zone Control, AC Stag, 1-Stg. HP with 1-Stg. Aux.
-
Fig. 14 – HP/2S 3-Zone Control, HP Stat, 2-Spd HP with 1-Stg. Aux Heat
Training
My Learning Center is your central location for professional residential HVAC
training resources that help strengthen careers and businesses. We believe in
providing high quality learning experiences both online and in the classroom.
Access My Learning Center with your HVACpartners credentials at
www.mlctraining.com. Please contact us a
mylearning@carrier.com with questions.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>