MSA FS-8700-137 Hochiki FireNET Driver Instruction Manual

June 6, 2024
MSA

MSA FS-8700-137 Hochiki FireNET--- LOGOJ **Driver Manual
FS-8700-137 Hochiki FireNET**

APPLICABILITY & EFFECTIVITY
Effective for all systems manufactured after March 2021.

Driver Revision: 1.00
Document Revision: 5.A
MSAsafety.com

Description

The Hochiki Serial driver allows the FieldServer to record data from Hochiki FireNET panels over RS-232 as per “Serial Port Spec Issue 2.37.pdf”. There is no active polling by this driver; the communications are one-way through the panel’s PC port (J5). The FieldServer acts as a Client; receives messages and records the status of a Panel. The panel MUST output messages in ASCII format in English.
This driver is not capable of emulating a Hochiki panel.
The Hochiki FireNET panel can be a standalone panel or can be part of network. Each Fire Alarm Panel on Network is considered as a Node. 64 Nodes can exist on one network.
Hochiki panel sends the events to the PC (J5) port. The FieldServer captures these events in text form, parses and stores them in Data Arrays. These Data Arrays can be monitored by third party tools. Since the FieldServer does not actively poll for data, the accuracy and timeliness of the stored data is limited to the frequency of update messages that the Hochiki Fire Panel issues.
Please note that the FieldServer can be configured with a large number of points. The point limits purchased with the FieldServer prevent the entire database from being accessed in any one application. It is therefore strongly advisable to ensure that only the point addresses of interest are configured, and that the FieldServer is purchased with the correct point count.
The types of Hochiki panel messages supported by this driver are summarized later in the manual. A detailed table shows each type of message the FieldServer recognizes and the effect that it has on the status of the points in the Data Array.

Max Nodes Supported

FieldServer Mode Nodes Comments
Client 1 Only one Hochiki PC Interface(J5) per port
Server N/A This driver cannot be configured as a Server

Driver Scope of Supply

Supplied by MSA Safety
Part # Description
FS-8915-10 UTP cable (7 foot) for Ethernet connection
FS-8915-10 UTP cable (7 foot) for RS-232 use
FS-8917-18 RJ45 to DB9F connector adapter (FS-B3510)
Provided by the Supplier of 3rd Party Equipment
Required 3rd Party Hardware
Part # Description
X187/S187 Programming cable to connect at communication port J5 of Hochiki

panel

Hardware Connections

The FieldServer is connected to the Hochiki panel as shown in the connection drawings below.
Configure the Hochiki panel according to manufacturer’s instructions. MSA
FS-8700-137 Hochiki FireNET--- Hardware

Connector Pinouts

RJ-45

Wire Color| Pin| Signal
Brown| 1| Rx
White/Orange| 8| Tx
Blue/White| 4| GND

Data Array Parameters

Data Arrays are “protocol neutral” data buffers for storage of data to be passed between protocols. It is necessary to declare the data format of each of the Data Arrays to facilitate correct storage of the relevant data.

Section Title|
---|---
Data_Arrays
Column Title| Function| Legal Values
Data_Array_Name| Provide name for Data Array.| Up to 15 alphanumeric characters
Data_Array_Format| Provide data format. Each Data Array can only take on one format.| Float, Bit, Byte, Uint16, Uint32, Sint16, Sint32
Data_Array_Length| Number of Data Objects. Must be larger than the data storage area required by the Map Descriptors for the data being placed in this array.| 1-10000

ExampleMSA FS-8700-137 Hochiki FireNET--- Hard

Client Side Configuration

For detailed information on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (see “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Hochiki FireNET panel.
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Hochiki FireNET communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

*NOTE: In the tables below, indicates an optional parameter, with the bold legal value as default.**

Client Side Connection Parameters

Section Title|
---|---
Connections
Column Title| Function| Legal Values
Port| Specify which port the device is connected to the FieldServer.| P1-P2, R1-R2 1
Protocol| Specify protocol used.| Hochiki
Baud| Specify baud rate.| 19200
Parity
| Specify parity.| None
Data_Bits| Specify data bits.| 8
Stop_Bits
| Specify stop bits.| 1
Timeout*| Specify heartbeat timeout (see Section 8.1.1).| 0-3600s, 20s

Example
MSA FS-8700-137 Hochiki FireNET--- Hardwa

Client Side Node Descriptors

Section Title|
---|---
Nodes
Column Title| Function| Legal Values
Node_Name| Provide name for node.| Up to 32 alphanumeric characters
Node_ID*| Provide the address of the Panel.| 1 – 64
Protocol| Specify Protocol used.| Hochiki
Port| Specify through which port the device is connected to the FieldServer.| P1-P2, R1-R2 1

Example
MSA FS-8700-137 Hochiki FireNET--- Ha

1 Not all ports shown may be supported by the hardware. Consult the appropriate Instruction manual for details of the hardware.

Client Side Map Descriptor Parameters
FieldServer Specific Map Descriptor Parameters
Column Title Function Legal Values
Map_Descriptor_Name Name of this Map Descriptor. Up to 32 alphanumeric

characters
Data_Array_Name| Name of Data Array where data is to
be stored in the FieldServer.| One of the Data Array names from
“Data Array” section above
Data_Array_Offset| Starting location in Data Array.| 0 to maximum specified in “Data
Array” section above
Function| Function of Client Map Descriptor.| Passive

Driver Related Map Descriptor Parameters
Column Title Function Legal Values
Node_Name Name of Node to fetch data from. One of the node names specified

in “Client Node Descriptor” above
Data_Type| Data type| Panel, Panel_Trouble,

Trouble, Alarm,
Panel_Device_Alarm,
Panel_Device_Trouble,
Heartbeat

Length| Length of Map Descriptor indicates the number of devices except in the case of panel related messages where it is the number of Data Array elements that will
be used to store data.| Any integer
Address| Device address – offset into the data array where data will be stored for a particular device. Specify 0 to store loop events or troubles unrelated to any specific device on the loop.| 0, any integer
Max_Sub_Address
| Maximum number of sub addresses of device. If there is no sub address or Data_Type is Trouble specify – .| -, any integer
Loop| Specify the SLC loop number.| 1-4

Map Descriptor Examples
Read Indications
Panel Map Descriptor Example

The following panel level Map Descriptors are used to process panel related messages:
HOC_HB Map Descriptor increments the value of DA_HB Data Array upon receiving heartbeat message from the panel. It will store a 0 value if there is a timeout and will also mark the Node offline.
HOC_1_PANEL Map Descriptor stores the panel state.
HOC_1_PANEL_TROUBLES Map Descriptor stores panel troubles.MSA FS-8700-137
Hochiki FireNET--- HarGJ

In the above example:

  • Data_Array_Name – Name of one of the Data Arrays defined in the Data_Array section. Indication statuses will be stored in this Data Array.
  • Node_Name – One of the Nodes declared in Node Section. Indications will be read from the station address belonging to this Node.
  • Data_Type – Specify: Heartbeat to store Heartbeat counts. Panel to store panel state. Panel_Troubles to store panel troubles (see Section 8.1).
  • Length – Length is the number of Data Array elements that are used to store data.
Loop Map Descriptor Example

The following Loop level Map Descriptors are used to process loop or loop device messages:
HOC_1L1_TROUBLES Map Descriptor is used to store troubles from Loop 1. The number of loop troubles is stored at offset 0. The number of troubles for each device is stored at the offset corresponding to the device address. Refer to Section 8.1.2 for more information.
HOC_1L1_EVENTS Map Descriptor is used to store all events other than troubles for loop1. Loop events unrelated to any specific device are stored at offset 0. The total number of events for each device is stored at the offset corresponding to the device address. For storage format details, see Section 8.1.4.
HOC_1L1_EVENTS2 is an example of the device address 14 and have 2 sub addresses. Driver will store events for first sub address at offset 14 and for 2nd address at offset 15.
MSA FS-8700-137 Hochiki FireNET--- HardJK

In the above example:

  • Data_Array_Name – Name of one of the Data Arrays defined in the Data_Array section. Indication statuses will be stored in this Data Array.
  • Data_Array_Offset – Offset into data array where data from a particular device is stored. Specify 0 to store loop events or troubles unrelated to any device on loop.
  • Node_Name – One of the Nodes declared in Node Section. Indications will be read from the station address belonging to this Node.
  • Data_Type – Trouble: to store number of troubles on device or on loop. Alarm: to store all events other than Troubles on Loop or device. See Section 8.1.4 for details.
  • Max_Sub_Address – Maximum number of sub addresses of device. If there is no sub address or Data_Type is Trouble specify -.
  • Length – Number of sequential devices. If Max_sub_address is non-zero then length should be the number of devices * max_sub_address. Any range of devices i.e. address to address + number of devices should have same max_sub_adress.
Communication Bus Map Descriptor Example

The following communication bus Map Descriptors are used to store events from devices connected directly to the panel:
HOC_1_PANEL_DEVTROUBLE Map Descriptor stores troubles from two devices with address 1 and 2. For storage format refer to Section 8.1.2.
HOC_1_PANEL_DEV Map Descriptor stores all events other than troubles from two devices with address 1 and 2 each with 16 sub addresses
Events from device 1, sub-addresses 1-16 will be stored in Data_Array 1PNL_DEV_EVENTS at offsets 0-15. Events from device 2, sub-address 1-16 will be stored at offsets 16-31. For storage format refer to Section 8.1.4.MSA
FS-8700-137 Hochiki FireNET--- HardGH

In the above example:

  • Data_Array_Name – Name of one of the Data Arrays defined in the Data_Array section. Indication statuses will be stored in this Data Array.
  • Data_Array_Offset – Offset into data array where data from a particular device is stored.
  • Node_Name – One of the Nodes declared in Node Section. Indications will be read from the station address belonging to this Node.
  • Data_Type – Specify: Panel_Device_Trouble to store number of troubles on device. Panel_Device_Alarm to store all events other than Troubles on device.
  • Max_Sub_Address – Specify maximum number of sub addresses of device. If there is no sub address or Data_Type is Panel_Device_Trouble specify -.
  •  Length – Specify number of sequential devices. If Max_sub_address is non-zero then length should be number of devices * max_sub_address. Any range of devices i.e.address to address + number of devices should have same max_sub_address.

Useful Features

Data Synchronization

The Fire Panel and the FieldServer can be synchronized as follows:

  • When in its normal state i.e. when no alarms or troubles are present, the panel can be connected to the FieldServer. The FieldServer will then reset its internal data.
  • Cycling power to the panel while connected to the FieldServer will cause the FieldServer to reset its internal data to synchronize with the panel.

NOTE:
Pressing “RESET” on the panel will not force the panel to resend all the alarms and troubles to FieldServer. Resetting the panel sends only latched alarms, such as Fire.

Troubleshooting

Heartbeat Data

If heartbeat data is frequently reset to 0 the timeout parameter value declared on the connection may be too short. The panel sends a heartbeat message after every 5 to 10 seconds – the timeout value should be set to 20 – 30s.

Using HyperTerminal to Address Communication Problems

If the heartbeat value is always 0 and the connection overview screen shows no increments to RX Char on the Hochiki connection, connect the panel to HyperTerminal and attempt to generate an event. If there is no message on the HyperTerminal, obtain the correct settings from the manufacturer to allow the panel to communicate with HyperTerminal. Retry connecting to the FieldServer using the same connection parameters as used in HyperTerminal.

Clear on Reset

The FieldServer needs to receive a CLEAR message before it will clear the active events in the Data Array. The Graphics System check box needs to be selected in order for the Panel to send a CLEAR message when a RESET is triggered. Refer to the screenshot below.

MSA FS-8700-137 Hochiki FireNET--- Clear on Reset

Reference

Data Types
Heartbeat

The Driver increments the value by 1 whenever it receives a heartbeat message from the panel. If the panel times out (no heartbeat message received in the time specified by the timeout parameter on the connection) the Driver stores a value of 0 indicating communication loss and will also mark the Node offline. The panel sends a heartbeat message after every 5-10 seconds – the timeout value should be set to 20-30s.

Panel

The Panel Data Type indicates whether the events listed in the table below are present globally on the panel.

Event Type Data Array Offset
FIRE 0
FIRE DRILL 1
PRE ALARM 2
SECURITY 3
DISABLEMENT 4
SUPERVISORY 5
STATUS 6
EMERGENCY 7
AUXILIARY 8
SILENCE ALARM 9
RESET 10
USER MESSAGE (Alarm Resound) 11
TEST MODE 12
Panel Troubles

Panel troubles are troubles that are not associated with any device or loop, e.g. Battery Disconnected or Low Battery Voltage.
The Driver stores each trouble at a different memory location as per the event number. Refer to Section

Alarms

The Driver stores different alarm types as 16bit integers as per the table below:

Event Type Decimal value Bit Offset
FIRE 1 0
FIRE DRILL 2 1
PRE ALARM 4 2
SECURITY 8 3
DISABLEMENT 16 4
SUPERVISORY 32 5
STATUS 64 6
EMERGENCY 128 7
AUXILIARY 256 8
SILENCE ALARM 512 9
RESET 1024 10
USER MESSAGE (Alarm Resound) 2048 11
TEST MODE 4096 12

If a device has more than one event, the value will be the sum of both events. For example, if the device is Supervisory and Pre-Alarm the driver will store a value of 32+4=36.
Individual alarms can be extracted from these integers by using the Bit_Extract function. Refer to the FieldServer Configuration manual for an example.

Troubles

The Driver stores the number of troubles currently existing on any loop, loop device or communication bus device. The Driver increments the value upon receiving a trouble message and decrements it when a trouble cleared message is received.

Event Number and Description Table
Event # Event Descriptor Event # Event Descriptor
0 Internal trouble 37 Unexpected I/O Module
1 Maintenance trouble 38 Unexpected network node
2 Detector removed 39 Unknown network type
3 Slave line open circuit 40 Network node missing
4 Slave line short circuit 41 Unexpected network card
5 Disconnected trouble 42 Network card not installed
6 Double address 43 Network card address incorrect
7 Monitored output trouble 44 Network open or short circuit
8 Unknown device 45 Network comms trouble
9 Unexpected device 46 Network comms timeout
10 Wrong device type 47 Network address invalid
11 Initializing Device 48 Fire Drill Active
12 System initializing 49 Unknown
13 Autolearn 50 Communicator Missing
14 New config downloaded from PC 51 Comms Fail
15 Ground trouble 52 Comms Phone Line 1 Trouble
16 Loop wiring trouble. Press ? for
details 53 Comms Phone Line 1 Restored
17 Loop short circuit 54 Comms Phone Line 2 Trouble
18 Loop open circuit 55 Comms Phone Line 2 Restored
19 AC Power Failure 56 Disabled device
20 Low battery voltage 57 Disabled zone
21 Battery disconnected 58 Disabled loop
22 Battery voltage too high 59 All sounders disabled
23 Aux 24V fuse trouble 60 Disabled panel input
24 Charger Trouble 61 Disabled panel output
25 Processor Watch Dog operated 62 CE disablement
26 Bad data trouble 63 Buzzer Disabled
27 Unknown event trouble 64 Printer Disabled
28 Pre alarm 65 Ground trouble Disabled
29 Calibration failed trouble 66 Disablement
30 Device initializing 67 Test mode
31 Input Activated 68 Unexpected IO Board
32 Cause & Effect Active 69 IO Board Missing
33 Loop Not Installed 70 Enunciator missing
34 Unexpected Loop 71 Unexpected IO Board
35 Sub address limit reached 72 Sensor Fire test pass
36 I/O Module not installed 73 Sensor Fire test fail

Additional Information

Message Types Recognized by the Driver

Message Type

Heartbeat
Fire
Fire drill
Pre alarm
Security
Disablement
Supervisory
Status
Emergency
Auxiliary
Silence alarm
Reset
User message (resound)
Test mode
Trouble

MSA FS-8700-137 Hochiki FireNET--- LOGOJMSA Safety
1991 Tarob Court
Milpitas, CA 95035
Website: www.MSAsafety.com
U.S. Support Information:
+1 408 964-4443
+1 800 727-4377
Email: smc-support@msasafety.com
EMEA Support Information:
+31 33 808 0590
Email: smc-support.emea@msasafety.com

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals