MSA Safety FS-ROUTER-BAC2 FieldServer BACnet Router Instructions
- June 4, 2024
 - MSA Safety
 
Table of Contents
MSA Safety FS-ROUTER-BAC2 FieldServer BACnet Router
Overview
The FieldServer BACnet Router offers a complete BACnet Internetworking solution for BACnet/IP, BACnet Ethernet, and BACnet MS/TP networks. This is the first standalone BACnet Router that has been certified by BTL to ensure the highest standard for BACnet integration. The FieldServer BACnet Router has two RS-485 ports enabling up to 64 BACnet MS/TP devices to be connected to it without the use of additional line drivers. Relative to a single port router, the dual port router halves device response time by distributing devices over the two RS-485 ports. The FieldServer BACnet Router has an easy one-page configuration, greatly simplifying the installation process. Included in the BACnet Router the BACnet Explorer, allows the integrator to push a button and discover all the BACnet devices connected to the router, greatly simplifying the commissioning process and troubleshooting the BACnet network.
BACnet Router Features and Benefits
Multiple BACnet Routing Connections
- BACnet/IP & BACnet MS/TP
 - BACnet/IP & BACnet/IP
 - BACnet MS/TP & BACnet Ethernet
 - BACnet/IP & BACnet Ethernet
 - BACnet MS/TP & BACnet MS/TP
 
Ease of Use
- BACnet Explorer: discovers devices connected to the FieldServer BACnet Router.
 - BACnet Broadcast Management Device (BBMD) for a connection between different subnets, up to 50 devices supported on the Broadcast Distribution Table (BDT).
 - Web Based configuration with no additional software needed for configuration.
 - NAT support with secondary BACnet/IP connection for routing between public and private IP networks.
 - Foreign Device Registration (FDR), exposing up to 147 devices details on different subnets.
 - MSA Grid registration connects your devices to the cloud, allowing secure remote access for diagnostics, monitoring, alarming and configuration.
 - On-board diagnostics allow easy troubleshooting for both serial and Ethernet communications.
 - FieldSafe adds a wealth of security options, including: web configuration page authentication (self-signed certificates), robust user and password management features.
 
Ease of Installation
- MDIX to use any Ethernet cable for commissioning and installation.
 - DHCP to automatically obtain the IP setting from the network.
 - Software “ToolBox” to find and diagnose all FieldServer BACnet routers on the network.
 - Wide range of input power requirements, AC or DC.
 
FieldServer Data Sheet – BACnet Router
Hardware Specifications
Communication
- Serial (Galvanic Isolation): 2 x RS-485
 - Baud: 9600, 19200, 38400, 57600, 76800, 11520o
 - Ethernet: 10/100BaseT, MDIX, DHCP
 
Environment
- Operating Temperature:-20 to 70°C (-4 to 158°F)
 - Relative Humidity:10-95% RH non-condensing
 - Construction
 - Dimensions: (HxWxD) 4 x 1.1 x2.7 in (10.16 x 2.8 x 6.8cm)
 - Weight:0.4 Ibs (0.2 Kg)
 
Other
- Web Configuration
 - On-board diagnostics
 - DIN rail mount included
 
Power Requirements
- Input:: 24VAC 0.125A
 - 9-30VDC 0.25A@12VDC
 - Max Power: 3W
 
Approvals
- CE and FCC/BTL Marked
 - IC Canada and UKCA compliant
 - UL 60950-1 and CAN/CSA C22.2
 - RoHS3 and WEEE compliant
 
Ordering Information
The FieldServer BACnet Router is available in the following hardware
configurations: l FS–Router–BAC2 (2 Serial Ports)
Options
The Accessory Kit consists of a power supply, Ethernet cable, screwdriver and
a USB flash drive that includes all manuals, data sheets, notes and the
discovery tool. l FS-8915-38-QS Accessory Kit, 110/220V
NEED HELP
Contact MSA sales for an easy proof of concept evaluation: SMC- insidesales@msasafety.com
MSA Safety
- 1991 Tarob Court, Milpitas, California 95035 USA
 - O. +1 408 262-6611 TF. +1 800 727-4377 E. SMC-insidesales@msasafety.com
 - www.MSAsafety.com
 
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>