MSA Safety FS-ROUTER-BAC2 FieldServer BACnet Router Instructions

June 4, 2024
MSA Safety

MSA Safety FS-ROUTER-BAC2 FieldServer BACnet Router

Overview

The FieldServer BACnet Router offers a complete BACnet Internetworking solution for BACnet/IP, BACnet Ethernet, and BACnet MS/TP networks. This is the first standalone BACnet Router that has been certified by BTL to ensure the highest standard for BACnet integration. The FieldServer BACnet Router has two RS-485 ports enabling up to 64 BACnet MS/TP devices to be connected to it without the use of additional line drivers. Relative to a single port router, the dual port router halves device response time by distributing devices over the two RS-485 ports. The FieldServer BACnet Router has an easy one-page configuration, greatly simplifying the installation process. Included in the BACnet Router the BACnet Explorer, allows the integrator to push a button and discover all the BACnet devices connected to the router, greatly simplifying the commissioning process and troubleshooting the BACnet network.

BACnet Router Features and Benefits

Multiple BACnet Routing Connections

  • BACnet/IP & BACnet MS/TP
  • BACnet/IP & BACnet/IP
  • BACnet MS/TP & BACnet Ethernet
  • BACnet/IP & BACnet Ethernet
  • BACnet MS/TP & BACnet MS/TP

Ease of Use

  •  BACnet Explorer: discovers devices connected to the FieldServer BACnet Router.
  •  BACnet Broadcast Management Device (BBMD) for a connection between different subnets, up to 50 devices supported on the Broadcast Distribution Table (BDT).
  •  Web Based configuration with no additional software needed for configuration.
  •  NAT support with secondary BACnet/IP connection for routing between public and private IP networks.
  •  Foreign Device Registration (FDR), exposing up to 147 devices details on different subnets.
  •  MSA Grid registration connects your devices to the cloud, allowing secure remote access for diagnostics, monitoring, alarming and configuration.
  •  On-board diagnostics allow easy troubleshooting for both serial and Ethernet communications.
  •  FieldSafe adds a wealth of security options, including: web configuration page authentication (self-signed certificates), robust user and password management features.

Ease of Installation

  •  MDIX to use any Ethernet cable for commissioning and installation.
  •  DHCP to automatically obtain the IP setting from the network.
  •  Software “ToolBox” to find and diagnose all FieldServer BACnet routers on the network.
  •  Wide range of input power requirements, AC or DC.

FieldServer Data Sheet – BACnet RouterMSA Safety FS-ROUTER-BAC2
FieldServer BACnet Router 1

Hardware Specifications

Communication

  • Serial (Galvanic Isolation): 2 x RS-485
  • Baud: 9600, 19200, 38400, 57600, 76800, 11520o
  • Ethernet: 10/100BaseT, MDIX, DHCP

Environment

  • Operating Temperature:-20 to 70°C (-4 to 158°F)
  • Relative Humidity:10-95% RH non-condensing
  • Construction
  • Dimensions: (HxWxD) 4 x 1.1 x2.7 in (10.16 x 2.8 x 6.8cm)
  • Weight:0.4 Ibs (0.2 Kg)

Other

  • Web Configuration
  • On-board diagnostics
  • DIN rail mount included

Power Requirements

  • Input:: 24VAC 0.125A
  • 9-30VDC 0.25A@12VDC
  • Max Power: 3W

Approvals

  • CE and FCC/BTL Marked
  • IC Canada and UKCA compliant
  • UL 60950-1 and CAN/CSA C22.2
  • RoHS3 and WEEE compliant

Ordering Information
The FieldServer BACnet Router is available in the following hardware configurations: l FS–Router–BAC2 (2 Serial Ports)

Options
The Accessory Kit consists of a power supply, Ethernet cable, screwdriver and a USB flash drive that includes all manuals, data sheets, notes and the discovery tool. l FS-8915-38-QS Accessory Kit, 110/220V

NEED HELP

Contact MSA sales for an easy proof of concept evaluation: SMC- insidesales@msasafety.com

MSA Safety

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>